Operating and Installation Manual Shut-off damper Type AK-Ex with control components T0* and P50

Similar documents
Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

Air terminal devices

VFC. Operating manual TROX air terminal units Type VFC volume flow controllers. General information 2. VFC series volume flow controllers

Operating Instructions (Translation)

Fire damper. Type FKA-3.8. GB/en. Installation and operating manual. according to Declaration of Performance. DoP / FKA-3.

VAV terminal units VARYCONTROL. Installation and commissioning manual. GB/en. LVC TVR TVJ TVT TZ-/TA-Silenzio TVZ TVA TVM TVRK TVLK

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

Attachments. Explosion-proof actuators. For opening and closing multileaf dampers installed in potentially explosive atmospheres (ATEX) 09/2017 DE/en

Operating Instructions

Installation Instructions (Translation) Marking. Description. Danger, warning and note symbols. Technical data. ANTARES ExtSet.

Type AK FOR LOW-LEAKAGE SHUT-OFF. Homepage > Products > Control units > Shut-off and restriction > Shut-Off Devices > Type AK

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

Homepage > Products > External Louvres & Dampers > Multileaf dampers > Attachments > Type Explosion-proof actuators. Type Explosion-proof actuators

Operating Instructions

Operating Instructions

Installation manual wall-mounted distributor

Installation manual portable distributors

CO 3-WAY PNEUMATIC VALVE INSTRUCTION MANUAL 2080

Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex

PURE SINE WAVE DC TO AC POWER INVERTER

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Operating instructions Solenoid interlock TKM/TKF. 1. About this document. Content

Centrifugal fan with highly efficient EC drive motor

Operating Instructions

Operating Instructions

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU

Operating Instructions

Control units. Simple. Precise. Efficient. Control units LVC, TZ-/TA-Silenzio and VFL

AXIAL FANS Axis / Tubo OPERATION MANUAL

EVZ Series (Small body) Explosion protected luminaire Operating Instructions

Oil-free piston compressors KK and piston vacuum pumps KV

Assembly and Operating Instructions

These operating instructions apply for: NCX 380 NCZ 300 NCX 480 NCZ 370 NCX 580 L NCZ 480 NCX 660 K NCZ 560 NCZ 660 NCZ 800

Technical Documentation

Swing Piston Compressors and Vacuum Pumps

INSTRUCTION MANUAL. I/P Converter DSG BXXY3Z DSG BXXY4Z

Safety. Operating instructions Solenoid valve VGP DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 10.

User Manual Rittal PMC UPS 6kVA

Shut-off dampers. Type AKK. For contaminated air PD AKK 1

Operatingmanual. Mehrsprachige Anleitung unter Multilingual manuals at. pro BENNING TRITEST BENNING BENNING BENNING.

Control and Terminal Box Type A21-**-*****

ExBin-P Pressure switches 5 Pa Pa

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3

IQL Helios Area-/Streetlight. User Manual

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Operating instructions Solenoid interlock EX-AZM About this document. Content

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15

Adjustable Speaker Mount GRAVIS 8

Adjustable Speaker Mount GRAVIS 12

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur

SITRANS P measuring instruments for pressure

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

8.50 Kampmann Equestrian Solarium Perfect Enhances the Vital Functions and the Immune System Table of Contents.

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

Holtumsweg 13, D Weeze, Tel /9134-0, Fax /1444

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Wilo-Control SC-Fire Jockey

Bowl feeder WV401-1 / Translation of operating and installation instructions

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Appendix: Safety and application notes for... 15

Switching DC Power Supply

Capanivo Series CN 4000

Operating Instructions CYR52

Type Pneumatic Control Unit. Operating Instructions

Type Pneumatic Control Unit. Operating Instructions

Assembly instructions

Solenoid Operator 0516 / 1216

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

User Guide. Lubricus Lubrication System LUB-D1/LUB-D2/LUB-D3/LUB-D4 (24 VDC)

Quick-Disconnect Coupling one-hand operation Push Pull ND 5, connecting thread G 1/4,max. operating pressure 500 bar

Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600

Rotary feed-through DDF-S/-KS

Ex m Solenoid Operator Type 0519

Operating manual UPS - System

Type ISH FOR INDUSTRIAL ZONES WITHOUT AIR POLLUTING PROCESSES

Installation and Operating Instructions Electric Vibrators HV/VFL Series

RVP-R- VAV controller. In explosion-proof version

Solenoid Operator 0513 / 1213

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

Instruction Manual. Ex-Time 40 / 50

LV Capacitor CLMD03 Power Module Instruction manual

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

ZB0050 / ZB0051 ZB0070 / ZB0071

Operating instructions Solenoid interlock AZM 161../.. 1. About this document. Content

Mass Sine 24/10000 Mass Sine 24/15000

Instruction Manual. Sewage lifting station compli 300

Linear Luminaire for Fluorescent Lamps

Operating Instructions

HOYMILES MICRO-IVERTER MI-250

Technical Manual Electrical Power Supply System T4002

Catalyser Introduction. 3. Hazard Information. 2. Area of Application. 3.1 Symbology

EPS 16 ATEX 1072 X, IECEx EPS X. Operating Instructions. Solenoid coil Type AC19 Magnetspule Typ AC19 Bobine magnétique Type AC19

Pendant Light Fitting IEC

Linear Luminaire with LED

Operating instructions. METTLER TOLEDO MultiRange Floor scales/pit scales

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

Transcription:

Operating and Installation Manual Shut-off damper Type AK-Ex with control components T0* and P50 AK-Ex with electric actuator II 2G c II TX II 2D c II T 80 C AK-Ex with pneumatic actuator II 2G c IIB TX The art of handling air

Contents 1 General information 3 Other applicable documentation 3 Symbols used in this manual 3 2 Safety and correct use 4 General information regarding safety 4 Standards and guidelines 4 Repair and replacement parts 4 Environmental protection 4 Correct use 4 Incorrect use 4 Residual risks 4 3 Product description 5 Electric actuator 5 Schematic illustration of the AK-Ex with electronic control 5 Functional description 5 System diagram 5 Pneumatic control 6 Schematic illustration of the AK-Ex with pneumatic control 6 Functional description 6 System diagram 6 4 Operation 7 General 7 Opening the damper casing 7 Closing the damper casing 7 5 Technical data 8 Product overview and dimensions 8 6 Transport, storage and packaging 10 Delivery check 10 Transport on site 10 Storage 10 Packaging 10 7 Installation 11 Safety 11 8 Wiring 12 Installation information 12 Notes on installation according to ATEX 12 General 12 Connecting the actuator 12 Terminal box connection assignment with electric actuator, with or without spring return 13 9 Pneumatic connection 14 Installation information 14 Tubing diagram 14 10 Commissioning, operation 15 Testing before commissioning 15 Operation 15 Commissioning of a damper with electric actuator 15 Commissioning of a damper with pneumatic actuator 15 11 Maintenance 16 Repair 16 12 Troubleshooting 17 13 Removal and disposal 18 Removal 18 Disposal 18 TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn, Germany Phone +49 (0) 2845 2020 Fax +49 (0) 2845 202265 E-mail trox@trox.de www.troxtechnik.com A00000061711 Subject to change / All rights reserved TROX GmbH 2 AK-Ex operating manual (3/2017)

1 General information This operating manual describes Type AK-Ex shut-off dampers with the following control components: Electric actuator (T0*) Pneumatic actuator (P50) To ensure complete functioning of the unit it is essential to read the provided operating manual before starting any work, and to comply with it. This manual must be given to the system owner when handing over the system. The system owner must include the manual with the system documentation. The manufacturer does not accept any liability for any malfunction or damage resulting from non-compliance with this manual or non-compliance with relevant statutory regulations. This operating manual is intended for specialist consultants, developers, and system owners. This manual is also intended for people conducting the following work: Transport and storage Installation Electrical wiring Pneumatic tubing Commissioning Operation Maintenance and cleaning Troubleshooting Decommissioning, removal and disposal Other applicable documentation In addition to this operating manual, the following documents apply: Type examination certificate TÜV 05 7218 X for AK-Ex shut-off damper with electric or pneumatic actuator Instruction manuals for electric control components (manufacturer's instructions) Explosion-proof actuators ExMax-5.10Y and YF Terminal box ExBox-Y/S-SW Auxiliary switch ExSwitch (optional) Instruction manuals for pneumatic control components (manufacturer's instructions) Pneumatic actuator AK31 (up to nominal size 250) Pneumatic actuator AK41 (from nominal size 315) Project-specific wiring documents Symbols used in this manual Danger! Designates danger to life and limb due to electrical voltage. Warning! Designates danger to life and limb. Important! Designates danger that can cause minor personal injury or damage to property. Note! Designates important notes or information. AK-Ex operating manual (3/2017) 3

2 Safety and correct use General information regarding safety Only specialist personnel are allowed to perform the described work. Only skilled qualified electricians are allowed to work on the electrical system. The installation location must be easily accessible and have sufficient clearance for electrical connection and maintenance. It is essential to comply with the applicable regulations and generally recognised engineering practices when working. This applies in particular to the following German country specific regulations or as appropriate in the country where the installation is taking place: ATEX directive 94/9/EG = Explosionsschutzverordnung (11. ProdSV) Machinery Directive 2006/42/EC = Machinery Ordinance (9th ProdSV) Industrial Health and Safety Regulations (BetrSichV) as well as the following accident prevention regulations: Principles of prevention (BGV A1) Electrical systems and operating equipment (BGV A3) Standards and guidelines The requirements in DIN VDE 0100 Part 610 apply to the initial test in all cases. Comply with the following rules when operating the system: EN 50110-1 (VDE0105 Part 1) EN 50110-2 (VDE0105 Part 2) VDE 0105-100 (VDE0105 Part 100) EN 60079-14 (VDE 0165 Part 1) EN 13463-1 (for pneumatic actuators) Industrial Health and Safety Regulations (BetrSichV) The system must meet the applicable lightning protection requirements. Compliance with all additional relevant national and international standards and regulations for potentially explosive atmospheres is required. Repair and replacement parts The AK-Ex shut-off damper has been specially developed for use in potentially explosive atmospheres. To maintain the protection function for explosive atmospheres, use only genuine TROX replacement parts for repair. The AK-Ex shut-off damper must only be repaired by the manufacturer or by specialist personnel authorised by the manufacturer. Environmental protection Dispose of packaging in an environmentally sound manner. Have used components or the used product only disposed of by an authorised company. Correct use AK-Ex shut-off dampers are intended to be used for shutting off volume flows in ventilation systems; they are suitable for use in areas with potentially explosive atmospheres. The dampers can be used in air, gases, mists and vapours according to the ATEX classification given on each damper. AK-Ex shut-off dampers with an electric actuator are also suitable for use in dust zones in areas with potentially explosive atmospheres. However, dust deposits on the shut-off damper casing must not exceed 5 mm. Incorrect use The shut-off damper must not be used In areas with potentially explosive atmospheres for which the damper has not been approved In dust-laden air if a pneumatic actuator is used with the damper In aggressive atmospheres Use in ventilation systems in which high levels of dust and pollution, extreme humidity, or chemical contamination may impair the function Use outdoors without sufficient protection against the effects of weather In wet areas Modifying the unit or using replacement parts that have not been approved by TROX is not permitted. Residual risks TROX products are subject to strict quality controls during manufacturing. They also undergo functional tests before shipping. Damage can, however, occur during transport or installation and impair the function of the fire damper. The system owner has to check the correct function of the tunnel damper as part of commissioning and ensure it through regular maintenance while the unit is in use. Under rare and unfavourable conditions and even when the mentioned regulations are complied with, the function of the shut-off damper with an electric actuator might be impaired by electromagnetic fields. This problem can usually be resolved by shielding or moving the electric actuator. Foreseeable damage that might be caused by the failure of the shut-off damper should be anticipated and prevented. 4 AK-Ex operating manual (3/2017)

3 Product description Electric actuator Schematic illustration of the AK-Ex with electronic control System diagram 1 2 3 4 230 VAC 4 5 5 7 6 3 2 1 1 Cover 2 Auxiliary switch 3 Electric actuator 4 Terminal box 5 Cable bushing 6 Equipotential bonding 7 Damper blade 1 Shut-off damper 2 Electric actuator 3 Terminal box 4 Switch (to be provided by others) 5 Safe area Functional description AK-Ex shut-off dampers are intended to be used for shutting off volume flows in ventilation systems; they are suitable for use in areas with potentially explosive atmospheres. The damper is used to isolate parts of the ventilation system. The damper consists of a casing with an electric actuator. The actuator is controlled by a switch (by others) and moves the damper blade into OPEN or CLOSED position. The damper is fitted with a plastic seal and provides minimal leakage shut-off according to EN 1751, Class 4 (Class 3 with nominal sizes 100 and 125). AK-Ex operating manual (3/2017) 5

13 1 Product PageHeaderToc description Pneumatic control Schematic illustration of the AK-Ex with pneumatic control System diagram 4 1 2 Save Area 3 3 5 1 4 2 1 Cover 2 Pneumatic actuator 3 Control signal connection 4 Equipotential bonding 5 Damper blade 1 Shut-off damper 2 Pneumatic actuator 3 Valve or control signal 0 1 bar (to be provided by others) 4 Safe area Functional description AK-Ex shut-off dampers are intended to be used for shutting off volume flows in ventilation systems; they are suitable for use in areas with potentially explosive atmospheres. The damper is used to isolate parts of the ventilation system. The damper consists of a casing with a pneumatic actuator. The actuator is controlled by a switch (by others) and moves the damper blade into OPEN or CLOSED position. The damper is fitted with a plastic seal and provides minimal leakage shut-off according to EN 1751, Class 4 (Class 3 with nominal sizes 100 and 125). 6 AK-Ex operating manual (3/2017)

24 1 Operation PageHeaderToc General Opening the damper casing Proceed as follows to open the casing: 1) Unscrew and remove screws (4x) using a Phillips screwdriver. Important! Be careful to not damage the protective earth conductor. The cover of shut-off damper casing is fitted with a protective earth conductor with a lockable blade receptacle connector. Be careful when you open the damper casing. When pulling off the protective earth conductor, release the fuse by pressing the latch mechanism. 2) Press both side parts of the cover slightly outwards using a screwdriver. 3) Lift the cover by hand such that you can pull off the protective earth conductor. 4) Remove the protective earth conductor from the cover. 5) Remove the cover and put it down. Closing the damper casing Proceed as follows to close the casing: 1) Attach the protective earth conductor to the cover (note which way the cover opens). 2) Put the cover back onto the damper casing. 3) Screw in and tighten screws (4x) using a Phillips screwdriver. AK-Ex operating manual (3/2017) 7

15 1 Technical PageHeaderToc data Product overview and dimensions Dimensions of AK-Ex 600 536 C B₃ ~ 300 1 ØD H₃ 1 Keep clear to provide access for operation Dimensions Nominal size ØD B 3 H 3 C mm mm mm mm 125 124 372 221 129 160 159 372 221 111 200 199 463 311 182 250 249 463 311 157 315 314 627 461 289 400 399 627 461 246 Weights Nominal size AK-Ex/.../T0* m kg AK-Ex/.../P.. m kg 125 16.5 15.0 160 16.5 15.0 200 18.0 16.5 250 18.0 16.5 315 22.0 20.5 400 22.0 20.5 8 AK-Ex operating manual (3/2017)

25 1 Technical PageHeaderToc data Electric actuator: Pneumatic actuator Area of application and ATEX marking Operating temperature/humidity External casing protection level IP 42 ATEX marking Atmosphere: Gases (gases, mists and vapours) Atmosphere: Dusts Supply voltage ¹ Power rating ² +10 C to +40 C for T6 +1 C to +50 C for T5 Humidity according to EN60335-1 Zones 1 and 2 Ex II 2 G c II TX II 2 D c II T 80 C Zones 21 and 22 Actuator/spring return actuator Protection level IP 66 IEC protection class 24 230 VAC/DC 50/60Hz 120 VA max. I (earthed) ¹ The inrush current is 3 to 5 times higher than the nominal current, with a pulse of a few milliseconds. ² Power consumption incl. inrush current. Area of application and ATEX marking Operating temperature/humidity 0 C to +50 C External casing protection level IP 42 ATEX marking Atmosphere: Gases (gases, mists and vapours) Atmosphere: Dusts Operating pressure range Control pressure ¹ II 2 D c II B TX Zones 1 and 2 Not approved Pneumatic actuator 0.3...0.9 bar 0...1.2 bar Protection level IP 20 Max. pressure 1 Required for achieving the actuator forces. 1.5 bar Auxiliary switch Voltage 30 V 250 V Inductive load AC cos ϕ = 0.6 5 A 3 A Inductive load DC L/R = 3 μs 5 A 0.03 A Protection level IP 66 AK-Ex operating manual (3/2017) 9

16 1 Transport, PageHeaderToc storage and packaging Important! Danger of injury from edges and sheet metal parts. Always wear protective gloves when handling the product. Important! Risk of damage to the shut-off damper. Handle the unit with care. Do not lift the shut-off damper by the actuator or the damper blade. Lift the unit only by lifting the entire casing. Delivery check Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, contact the shipping company and your supplier immediately. A complete shipment includes: AK-Ex shut-off damper with electric or pneumatic actuator AK-Ex operating manual Transport on site If possible, take the AK-Ex shut-off damper in its transport packaging up to the installation location. Storage If the product has to be stored temporarily: Moisture and lack of ventilation can lead to oxidation, even on galvanised components. Remove any plastic wrapping in order to avoid oxidation. Protect the device from dust and contamination. Store the unit in a dry place and away from direct sunlight. Do not store the unit below -5 C or above 60 C. Packaging Properly dispose of packaging material. 10 AK-Ex operating manual (3/2017)

27 1 Installation PageHeaderToc Safety Only specialist personnel are allowed to perform the described work on the shut-off damper. Only skilled qualified electricians are allowed to work on the electrical system. The personnel must have been trained and be aware of the special conditions that apply to areas with potentially explosive atmospheres. Pipe clamp with acoustic insulation insert Suspension Important! Danger of injury from edges and sheet metal parts. Always wear protective gloves when handling the product. Important! Risk of damage to the shut-off damper. Handle the unit with care. Do not lift the unit by the actuator or the damper blade. Lift the unit only by lifting the entire casing. Duct Ground strap Screw or rivet connection AK-Ex Installation location Select the installation location for the shut-off damper such that the control components and inspection panels remain accessible. Provide at least 300 mm clear space for the cover to be opened. The installation orientation is not critical. Installation Install the shut-off damper professionally, with a suitable suspension system, secured with locknuts. Load suspension systems only with the weight of the unit. Adjacent components and connecting ducts must be supported separately. Check the shut-off damper for contamination; clean it if necessary. Push ducts (DIN 1506 or EN 13180) onto the spigots; spigots are fitted with lip seals. Fix the shut-off damper with screws or rivets to the spigots such that it cannot be moved. For equipotential bonding, make an electrical connection by connecting the shut-off damper with the ground straps on both sides to the ducting. The connection should be self-locking. Connect the ducting to the terminal point for equipotential bonding of the building. Note! It is also possible to connect the shut-off damper directly to the terminal point for equipotential bonding of the building. The casing is fitted with a blade receptacle connector for this purpose. AK-Ex operating manual (3/2017) 11

18 1 Wiring PageHeaderToc Electric actuator: Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. Installation information Connect the shut-off damper according to the following wiring diagrams. Comply with the following requirements and regulations: Guidelines of VDE (German association for electrical, electronic and information technologies) or appropriate national guidelines Local regulations and guidelines Wiring guidelines and project-specific circuit diagrams The standards and guidelines listed in chapter 2 Wiring diagram AK-Ex Notes on installation according to ATEX The cables to be used must comply with ATEX. The type of protection for the unit must not be impaired by connecting cables. Irrespective of the type of protection, all cables to be used must have been tested and approved according to EN 50014, Appendix B (VDE 0170/0171, Part 1). Further requirements on electrical installations in potentially explosive atmospheres can be found in EN 60079-14 (VDE 0165, Part 1). Section 9, for example, contains information on the connection of portable operating equipment. General All cables must be fed into the damper casing through the provided cable glands. The electrical connection is made in the explosion-proof terminal box, which has been approved for the relevant zones. No loose terminals must be used in the terminal box. Once you have connected the cables, tighten the cable glands firmly in order to ensure IP protection (IP 66). In areas with potentially explosive atmospheres unused openings for cable penetration must be sealed with certified dummy plugs. Connecting the actuator The connections for the supply voltage and signal lines of the actuator are made in the terminal box. The terminal box is inside the damper casing. Note We recommend that you use screened cables for the signal lines of the actuator. Use separate grounds for the supply and signal cables. Supply voltage 24... 230 V AC/DC (by others) Shut-off signal (by others) Actuator Auxiliary switch (optional) Terminal box Signal line Supply voltage 12 AK-Ex operating manual (3/2017)

8 Wiring Electric actuator: Terminal box connection assignment with electric actuator, with or without spring return Without auxiliary switch With auxiliary switch A M20 M20 A M25 duplex M20 M20 PE PE V: 1-5 Y/S: 1-6 SW1-6 V: 1-5 Y/S: 1-6 PA K PE M20 PA K PE M20 M20 M20 V: Terminals V (1-5) correspond to actuator cables A (1-5) Y/S: Terminals Y/S (1-6) correspond to actuator cables B (1-6) ExMax connections Modulating or 3-point without spring return SB 4.0 V: Terminals V (1-5) correspond to actuator cables A (1-5) Y/S: Terminals Y/S (1-6) correspond to actuator cables B (1-6) SW: Terminals SW (1-6) correspond to ExSwitch connections HS1 (1-3) and HS2 (1-3) 24... 230 V AC/DC - + ~ ~ YmA YvDC T VDC/mA UmA UVDC Modulating or 3-point with spring return SB 5.0 PE A 1 2 Heating a b 3 4 1 2 3 4 5 6 I B PA 24... 230 V AC/DC - + ~ ~ A PE a b YmA YvDC T VDC/mA I UmA UVDC B Self adjustment: Press push button T for 3 seconds such that the actuator moves into both end positions to be adjusted. Function and override control a closed, damper open (closed) depending on the left/ right mounting of the actuator b closed, damper closed (open) depending on the left/ right mounting of the actuator 1 2 Heating 3 4 5 1 2 3 4 5 6 Self adjustment: Press push button T for 3 seconds such that the actuator moves into both end positions to be adjusted. Spring return running time: Approx. 10 seconds with standard wiring Approx. 3 seconds with additional link to terminal 5 PA ExSwitch connections 0... 90 0... 90 black grey brown black grey brown Function and override control a closed, damper open (closed) depending on the left/ right mounting of the actuator b closed, damper closed (open) depending on the left/ right mounting of the actuator 1 2 3 1 2 3 HS 1 HS 2 AK-Ex operating manual (3/2017) 13

19 1 Pneumatic PageHeaderToc connection Pneumatic actuator Danger! Operation only with instrument air that is free from oil, water and dust. Do not use combustible gases, oxygen or oxygen-enriched gases. Installation information Connect the shut-off damper according to the project-specific tubing diagrams and in compliance with the following instructions: Feed all the tubes into the damper casing through the bulkhead fittings on the outside of the damper casing. Only use pneumatic tubes that have an inside diameter of 4 mm and outer diameter of 6 mm. Tubing diagram Shut-off damper Pressure off: open Pressure off: closed Damper blade position S1 actuated CLOSED OPEN Operating S1 not actuated OPEN CLOSED pressure Important! The tubing diagrams shown are examples. The tubing documents supplied for the specific project apply. S1 AK-Ex 1 Input for the operating pressure (1.3 bar, ± 0.1 bar) S1 Pneumatic switch (by others) 14 AK-Ex operating manual (3/2017)

210 1 Commissioning, PageHeaderTocoperation Warning! Only authorised specialists are allowed to commission the shut-off damper. Testing before commissioning To comply with Industrial Health and Safety Regulations, a system requiring monitoring must be tested by an approved monitoring body before it is taken into operation for the first time and before it is taken into operation after a significant modification. Correct assembly, installation, installation conditions and functional safety with regard to the intended use are subject to testing. Operation Once commissioning has been completed, the shut-off damper will operate independently and require no intervention from the system owner. The statutory inspection intervals must be complied with. In case of a malfunction, take the shut-off damper out of operation and repair it before commissioning it again. Commissioning of a damper with electric actuator Commissioning of a damper with pneumatic actuator Check for correct installation Check the equipotential bonding Check the wiring Check for correct installation Check the equipotential bonding Check the tubing Switch on the voltage Switch on the air conditioning system Check and switch on the operating pressure Switch on the air conditioning system Check damper blade positions OPEN and CLO- SED; record. Check damper blade positions OPEN and CLOSED; record. AK-Ex operating manual (3/2017) 15

11 Maintenance Warning! Only authorised specialist personnel are allowed to perform the described maintenance measures. The shut-off damper, the actuator and the electric/pneumatic actuator are maintenance-free with regard to wear, but the damper must still be included in the regular cleaning of the ventilation system. Regular care and maintenance ensure operational readiness, functional reliability, and long service life of the shut-off damper. The statutory regulations for maintenance must be complied with. The system owner is responsible for maintenance. The system owner is responsible for creating a maintenance plan, for defining the maintenance goals, and for the functional reliability of the equipment. Units for installation in areas with potentially explosive atmospheres must only be opened by the manufacturer. However, the following components may be opened for maintenance work: Casing of the shut-off damper Actuator terminal box/auxiliary switch Inspection Inspection should be performed by a specialist and at least once a year in accordance with statutory regulations and guidelines (see chapter 2). The test of every single unit must be documented and evaluated. If the requirements are not fully met, suitable remedial action must be taken. Inspection work Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. Repair For safety reasons, repair work must only be carried out by expert qualified personnel or the manufacturer. Only genuine replacement parts must be used. Significant modifications may require a subsequent commissioning test. Maintenance service Regular maintenance by the TROX Technical Service is recommended in order to ensure operational readiness, functional reliability, and long service life of the unit. The TROX Technical Service can establish the actual condition of the unit, adapt or correct it if necessary, and ensure that the unit is in proper condition after maintenance. Necessary adjustments and parameter setting can be conducted as part of maintenance such that a high level of safety is always maintained. The following inspection work must be performed: Remove contamination from the shut-off damper that affects its function. Check all screws for firm seating and retighten them, if necessary. Check whether the damper blade moves to the OPEN and CLOSED positions Check special functions (override controls, alarm suppression on monitoring systems) and make corrections, if necessary. Check the optical and acoustic alarm emitters. Check sequence control loops (room balancing) and make corrections, if necessary. Document maintenance measures and measurement results. 16 AK-Ex operating manual (3/2017)

12 Troubleshooting Most malfunctions can be rectified with the help of the troubleshooting diagrams. If the malfunction cannot be rectified, please contact TROX Service. Troubleshooting with an electric actuator Troubleshooting with a pneumatic actuator Supply voltage correct? No Provide correct power supply Operating pressure correct? No Connect pressure supply Yes Yes Does the actuator open and close? Yes No Damper obstructed? Effect of actuator action correct? Is the actuator defective? Does the actuator open and close? Yes No Damper obstructed? Is the switch OK? No Check switch Is the pneumatic switch OK? No Check switch AK-Ex operating manual (3/2017) 17

13 Removal and disposal Removal 1. Switch off the ventilation system. 2. Switch off the power supply or operating pressure. Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. 3. Disconnect the connecting cable or remove the tubing 4. Remove the unit. Disposal Have the damper disposed of by an authorised company. 18 AK-Ex operating manual (3/2017)

AK-Ex operating manual (3/2017) 19

20 AK-Ex operating manual (3/2017)