Sentinel Field Satellite Controller

Similar documents
Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

Installation and Operation

Installation Manual. Rev

DeSoto NEMA 4X EMERGENCY LIGHTING UNIT. U.S. Versions: 6V- DM90X618 / DM90X654 12V- DM90X1254 / DM90X12100 INSTALLATION INSTRUCTIONS

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

ANZI Transfer Switch and Generator Wiring Installation Addendum

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

Earthing UNIT. Learning Objectives. Introduction. To understand purpose of Earthing. To learn system of earthing.

SOIL-CLIK. Soil Moisture System. Owner s Manual and Installation Instructions

E.S.P. Embedded Sensing Probes for Motor Brushes

OBE-3-FT Outdoor Series

STAINLESS STEEL AUTOMATIC CONTROLLER ENCLOSURE ASSEMBLY. SEE IRRIGATION LEGEND FOR MAKE AND MODEL. 2

650 Series Cargo Van Lift Mounting Instructions Ford Transit (Standard Roof) 2015-Present

Eaton Battery Charger Module Models ASY-0652 and ASY-0675 User s Guide

Sunwize Power Ready Express Quick Start

DeSoto EMERGENCY LIGHTING UNIT. U.S. Versions: 12V- DM (P2 & P3) / DM / DM INSTALLATION INSTRUCTIONS

TC26-B Vehicle Sensor

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

650 Series Cargo Van Lift Mounting Instructions Fullsize Ford 1992-Present

Albeo TM LED Luminaire Heavy Industrial High Bay Lighting (ABR1-Series)

Lumination TM LED Luminaires LAL Series - Continuous Run Option

Use and Care Guide.

WeatherTRAK FlowLink Installation Instructions 04/23/2013 Revision 2 HydroPoint Customer Support

Asymmetrical Installation Instructions. Components: i2cove Asymmetrical LED Light Fixtures. 12 [305mm] [918mm] 48.

FieldSmart Fiber Active Cabinet (FAC) 3200 Installation Manual

UNDERGROUND SERVICES - SECONDARY

FLO Home TM X5 Model. Installation Manual FLO Services Inc. All rights reserved.

5000 SERIES POWER SUPPLY/CHARGERS INSTALLATION GUIDE

MODEL ELC-12/40-CVM-D BATTERY CHARGER

RAIN BIRD - AQUAGATOR AQUAGATOR INSTALLATION & TROUBLESHOOTING MANUAL

Powerware Vdc Extended Battery Cabinet User s Guide.

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Mid-Power Remote Unit (MRU) SISO Outdoor Enclosure Assembly Quick Installation Sheet

LED Recessed Troffer Retrofit Kit

DIG Corporation Irrigation product Specifications

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

IMPORTANT SAFEGUARDS

DayStar Quick Start Guide

FOR INDOOR/SEASONAL USE ONLY

WF-5110R True Sine Wave Inverter

WF-5100 Series True Sine Wave Inverters

Installing Power Components

FLO Home TM G5 Model. Installation guide

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

Instruction Manual for the. E-SL 450 Series

7.5 FT PRE-LIT ENGLEWOOD PINE TREE

12 STATION MANUAL CONTROLLER INSTALLATION AND OPERATING GUIDE MODEL HRM-12

Touchstone TB130 DC Output UPS

Sylvania 9 Color Changing One Plug Tree Tree ID # T5, Item # V

READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

SELF DRILL SCREWS FILLER STRIP

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS

Rated for use on 110/120VAC 60Hz and 220/240VAC 60Hz applications

BLACK BOX. Fully assembled, ready-to-use wallmount cabinets. Elite Wallmount Cabinet User s Manual. Customer Support Information

Section 6 Electric Metering: Residential

User s Guide Rain Dial Plus 6, 9 and 12 Station Indoor and Outdoor Models

MODEL ELC-12/60-D BATTERY CHARGER

INSTALLATION MANUAL. Melink Corporation (513) Revision

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.

G-170. r ve Pickup Lift Mounting Instructions Fullsize Chevy & GMC Trucks- 1500, 2500 & 3500: 2007-present

READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Mid-Power Remote Unit (MRU) Outdoor Enclosure MIMO Assembly Quick Installation Sheet

Operating Instructions

Instruction Manual. Blink HQ Charger. Charge on. a CarCharging Company

WARNING/AVERTISSEMENT. Coupez l alimentation électrique à la boîte de fusibles ou au disjoncteur avant servicing or installing product.

Australian Wiring Instructions:

A419ABG-3C Electronic Temperature Control

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

Installation Instructions: Read these instructions in its entirety before performing any installation work.

TRAC-Station BT Installation Instructions

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel

Alliant Energy - Gas Service Manual Chapter 4 Gas Meter Connections

SPECIAL SPECIFICATION 1788 Surveillance Cabinet

CurrentGuard. CurrentGuard. CurrentGuard. Plus. Surge Protective Devices. Installation,Operation and Maintenance Manual PN

Bulletin 1494C Cable Operated Disconnect Switch Kit (600A) Installation Instructions (Cat 1494C- _ Series 2 : 600A)

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

and Original Series Pickup Lift Mounting Instructions Fleetside Chevy & GMC Trucks Fleetside 4-door Chevy & GMC Trucks T-100

Digital/Analog Amplifiers Installation Instructions

Approved Contractor Construction e-guide Residential Commercial

MAPNET II Transceiver Installation Instructions

WVC. Wireless Valve Controller. Multiple Station Battery Powered Irrigation Controller. Owner s Manual and Installation Instructions

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

SAVE THESE INSTRUCTIONS

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

Electro-Mechanical Swing Operator. Table of Contents

Auto-Lift Operating System

LP-2500/2600. Installation and Setup Guide. Lighting Control Panels. Revision 3.1 July 1999

Lumination TM LED Luminaire LUR Series

MC2500. Installation and Operation Manual

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE

SPECIAL SPECIFICATION 6894 Communication Cabinet

Installation Instructions for VTU

Photoelectric. Sensors Invisible Light Beam Protection Area

Owner's/Installation Manual

GTX UNIT SUBSTATION Installation, Maintenance & Operation Manual

GPS AutoSteer System Installation Manual

Cabinet and Rack Installation

Transcription:

WARNING HIGH VOLTAGE 115V M AP Sentinel Field Satellite Controller Installation Instructions Important: For your protection and the safety of the product user, please comply with all Caution and Warning statements within this document. All installation practices must comply with all applicable national and/or local electrical and building codes and be performed by qualified personnel only. Introduction The metal or plastic pedestal-mount satellite controller unit is designed for installation on a substantial concrete pad with embedded conduit of various diameters to enable wiring connections for power, field, earth ground, sensor and optional external antenna. Pedestal anchor bolts and a steel bolt pattern template are supplied with the controller. The wall-mount satellite unit is designed for installation on a structurally-sound building wall. The stainless steel cabinet is moisture resistant and suitable for outdoor installation. The cabinet has upper and lower support attachments and is supplied with a mounting bracket which attaches directly to the wall. Refer to wall mount installation procedures on page 2. Additional materials required to complete the installation must be obtained separately. A material list can be compiled by reading through the instructions completely prior to starting the installation. Installation I. Metal Pedestal (PS1) 1. Prepare a hole for the pad and wiring conduit using the minimum recommended dimensions shown in Figure 1. This size pad requires approximately cu ft (122cu cm) of concrete. * Refer to local electrical codes for the required wire burial depth. 2. Position straight and sweep elbow conduit sections in foundation hole as shown. Placing the controller toward the back of the pad as shown protects the ground near the front of the controller from wear. 3. Tape the conduit ends to seal out dirt. Backfill soil to form a 6 (15cm) foundation depth. The conduit should not extend more than 2 (51mm) above the finished top surface of the foundation.. Form the perimeter of the pad area using 2 x 6 boards or 3/ (19mm) plywood. 5. Prepare the mounting bolt template with the provided L-shaped bolts and hex nuts as shown in Figure 1. 6. Pour concrete into the formed area and trowel smooth. Finish the concrete pad with a level flat area for the pedestal base approximately 8 x 17 (20cm x 3cm). 7. Aligning the mounting bolt template with the conduit, press the L-shaped bolts into the concrete until the template makes contact. To prevent pooling at the base of the pedestal, add a slight taper away from the template. Allow the concrete to sufficiently harden before continuing. 8. Remove the mounting bolt hex nuts. Remove and discard the mounting bolt template. Place the pedestal on the pad ensuring all bolts are inserted into the pedestal base. Install a flat washer and a hex nut on each bolt and tighten securely. Figure 1 6 (15.2mm) 1/2 (13mm) Conduit for Earth Ground 3/ (20mm) Conduit for Input Power Wiring 2 (50mm) Conduit for Field Wiring (12 2 Stations) 1 1/ (32mm) Conduit for External Antenna Cable (Optional) 2 (50mm) Conduit for Field Wiring (25 8 Stations) 1/2 (15mm) Conduit for Sensor Wires (Optional) Taper See * Wood Form Mounting Bolt Template - Cabinet Base Area 8 x 17 (20.3cm x 3.2cm) 29 (73.7cm) Mounting Bolt Template 36 (91cm) Mounting Bolts w/hex Nuts (Typical Four Places) 2 (51mm) 6 (15cm) 1 中文 Deutsch

II. Plastic Pedestal (PP1, PP2, PP3) 1. Prepare a hole for the foundation and wiring conduit using the minimum recommended dimensions shown in Figure 2. * Refer to local electrical codes for required wire burial depth. 2. Trench to the foundation site as required for each wiring run. 3. Position straight and sweep elbow conduit sections in foundation hole as shown. Tape the conduit ends to seal out dirt. Backfill soil to form a 6 (15.2cm) foundation depth. Conduit should not extend more than 2 (51mm) above the finished top surface of the foundation.. Prepare the sides of the foundation hole with wood forms. 5. Prepare the mounting bolt positioner with the 5/16 x -1/2 bolts and nuts (provided) as shown in Figure 2. The threads should extend 2 (51mm) from the top surface of the bolt positioner. 6. Pour concrete into the formed foundation hole. Press the mounting bolt positioner into the concrete until it is flush and level with the foundation surface and aligned with the conduit. 7. Finish the concrete with a level flat area of 16 x 16 (1cm x 1cm) for the pedestal base. To prevent pooling at the base of the pedestal, add a slight taper away from the cabinet base contact area. Allow concrete to sufficiently harden before continuing. 8. Remove the hex nuts from the mounting studs. Remove the cabinet cover and doors. Carefully position the controller onto the studs. Install a flat washer and a hex nut on each stud and tighten securely. III. Powder-coated Wall-Mount Cabinet (WS1) Cabinet installation for the WS1 cabinet is similar to the WS5 wall-mount cabinet (Section IV following). Refer to Figure 3 for electrical conduit and wiring connections. Figure 2 Wood Form Plastic Cabinet Base Area Conduit Recommendations (10cm) - Field Stations 1 1/2 (0mm) - External Antenna (Optional) 3/ (20mm) - Earth Ground 3/ (20mm) - Power Supply 2 (50mm) Maximum Mounting Bolt Positioner Figure 3 6 (15cm) 2 (50mm) MV/ PUMP 30 (76cm) VC/ 25 26 27 28 29 30 31 32 33 3 35 36 COM VC/ COM 37 38 39 0 1 2 3 5 6 7 8 1 2 3 5 6 7 8 9 10 11 12 COM COM 13 1 15 16 17 18 19 20 21 22 23 2 30 (76cm) Taper See *.88 (22 mm) Conduit for Power Wires 2.3 (62 mm) Conduit for Field Wiring 2

WARNING HIGH VOLTAGE 115V M AP ENTER Home/Back O SENTINEL Manual Watering Start A Scheduled Watering Help B Alarm Hold Irrigation Diagnostics Station Settings & Alarms Stop Satellite Settings IV. Stainless Wall-Mount Cabinet (WS5) 1. Position the upper support bracket on the wall with the joggle edge up to accept the mating upper cabinet bracket. The support bracket must be level and at a height approximately 2 (51mm) above eye level to enable the Sentinel control module display to be easily viewed. 2. Mark the two mounting screw hole locations and drill pilot holes for the screws or screw anchors. Use 3/8 (10mm) diameter fasteners to attach the cabinet support brackets. If installing the cabinet on dry wall or masonry, install the appropriate size and type screw anchors. 3. Secure the support bracket to the wall. Hang the cabinet on the wall by engaging the upper cabinet bracket and the support bracket.. Draw a pencil line the entire length of the lower support bracket. 5. Remove the cabinet from the wall and remove the lower support bracket from the cabinet. 6. Place the lower support bracket on the wall aligning it with the pencil mark. 7. Mark the two screw hole locations and drill pilot holes for the mounting screws or screw anchors. 8. Secure the bottom support bracket to the wall. * On early model cabinets, conduit access holes are only provided for power and one field wire conduit. Additional conduit access holes for earth ground, additional field wire conduit, optional sensor wires and optional external antenna must be cut or punched by the installer. All conduit access holes and knock-outs are provided on current production cabinets. 9. Remove optional conduit knock-outs as required for installation. See * above. 10. Hang the cabinet on the wall mount support bracket. The bottom edge of the cabinet should now rest squarely on the lower support bracket. 11. Secure the cabinet to the lower support bracket using the carriage bolts and nuts removed in Step 5 above. 12. Install electrical conduit for all wiring connections per local and national code. See Figure 5. Figure Figure 5 3/ (20mm) Conduit for Power Wires 2 (50mm) Conduit for Field Wiring (12 2 Stations) 1/2 (15mm) Conduit for Earth Ground Screw Anchors Upper Cabinet Bracket Upper Support Bracket Lower Support Bracket 1/2 (15mm) Conduit for Sensor Wires (Optional) 2 (50mm) Conduit for Field Wiring (25 8 Stations) 1 1/2 (0mm) Conduit for External Antenna (Optional) English 3

HIGH VOLTAGE 115V M A P V. Earth Ground Important: The satellite surge protection components cannot properly function unless an efficient pathway to earth ground is provided. The ground path must be as direct as possible, without sharp bends and must not exceed 30 ohms resistance (when measured with an earth ground resistance test device). A resistance reading of 0 10 ohms is considered excellent, 11 20 ohms is acceptable and 21 30 is considered marginal. All electrical components throughout the irrigation system should be grounded in a manner which provides the same ground potential. The following instructions depict one of several acceptable earth grounding methods. Due to variables in soil composition and terrain, the method shown may not be suitable for your installation site. Contact your local Toro distributor for assistance and availability of the required earth ground resistance test instrument. Recommended ground testers are: AEMC Instruments, model 3710 clamp-on tester, or Biddle Megger, model 250260 (or equivalent). Procedure 1. Drive a 5/8 by 8 (17mm x 2.m) copper-clad steel rod into well moistened soil not less than 8 (2.5m) or more than 12 (3.7m) from the satellite. The top of the ground rod should be 12 (30.5cm) below grade level. See Figure 6. 2. Using a 5/8 (17mm) clamp or Cad weld fastener, attach a 6 AWG (10mm2) solid copper wire near the top of the ground rod. Avoiding wire bends of less than 8 (20.3cm) radius and more than 90, route the wire through conduit into the controller cabinet. Secure the wire to the large copper ground lug. See Figure 6. Make sure the soil surrounding the ground rod(s) remains well moistened at all times. The addition of some form of irrigation may be required if the satellite is installed in a non-irrigated location. 3. Measure the ground resistance per the instructions provided with the ground test instrument. If the resistance exceeds the acceptable limit, additional ground rod(s) can be installed at a distance equal to twice the buried depth of the first rod; i.e., 16 (.9m). Interconnect the ground rods using 6 AWG (10mm2) solid copper wire and test again. If the measured ground resistance continues to read above the acceptable limit, contact your local Toro distributor for further assistance and recommendations. Installing a round valve box over the ground rod enables the ground rod to be easily located as well as providing access to the ground wire connection(s). Figure 6 Chassis Ground Lug WARNING Valve Box 6 AWG (10mm) Solid Copper Ground Wire 12 (30.5cm) 8 (20.3cm) Minimum Radius 8 12 (2.m 3.7m) 90 Ground Wire to Additional Rod(s) (Optional) Copper-Clad Ground Rod

VI. Input Power Caution: When installing multiple controllers, polarity of the Line and Neutral connections must be properly maintained throughout the irrigation system. Reversed polarity may cause damaging potentials to exist at one or more controller locations. An equipment ground wire from the power source must be connected to each satellite controller. WARNING AC power wiring must be installed and connected by qualified personnel only. All electrical components and installation procedures must comply with all applicable local and national electrical codes. Some codes may require a means of disconnection from the AC power source, installed in the fixed wiring, having a contact separation of at least 0.120 in the line and neutral poles. The wire used for connection to the controller must have insulation rated at 105 C minimum. Ensure the AC power source is prior to servicing or connecting to the controller. English Procedure 1. Place the controller s main power switch in the Off position. See Figure 7. 2. Position the input voltage select switch to the 115V or 230V position as required. 3. It is necessary to remove the transformer assembly from the bracket to access the power supply terminals located at the back of the assembly. Remove the two retaining screws indicated by the arrows in Figure 8. Disengage the transformer assembly from the bracket by lifting it upwards. Once disengaged, pull it outwards. Remove the power socket to free the power assembly from the Sentinel Unit.. Remove the terminal cover to access the transformer terminals block by removing the retaining screw. See Figure 8. 5. Route the appropriate size 3-conductor cable (10 AWG [2.5mm2] maximum) from the power source location to the terminal block. Leave at least 12 (30.5cm) of extra 3-conductor cable to allow maneuvering of the transformer assembly. Install a 3/ (19mm) clamp connector to retain the cable. 6. Secure the wires to the terminal block as indicated in Figure 8. 7. Reinstall the terminal cover, reinstall the power socket and reinstall transformer assembly to the bracket. 8. Apply power to the controller. Figure 7 WARNING HIGH VOLTAGE Figure 8 Line (Hot) Black Wire (115 VAC), VAC - Brown Wire (230 VAC) Equipment Ground - Green Wire (115 VAC), Green/Yellow (230 VAC) Neutral - White Wire (115 VAC), Blue Wire (230 VAC) 115V M A P.0A Circuit Breaker - Control Functions 3.2A Fuse - Station Output Input Voltage Select Switch Main Power Switch / 1.5A Circuit Breaker Power from Source 5

Wire Connections 1-12 Field Wire Installation 1. To provide a field common wire, attach one wire to either solenoid lead of all valves to be operated by the controller. Figure 9 13-2 2. Attach a separate power wire to each remaining solenoid lead. Label these wires for identification at the station output modules. 25-36 3. Using an approved waterproof splicing method, properly insulate all valve solenoid wire connections. 37-8 25 26 27 28 29 30. Route the field wires into the controller cabinet through 2 (50mm) conduit. Remove approximately 3/8 (10mm) insulation from the ends of each wire. 31 32 33 3 35 36 COM COM 37 38 39 0 1 2 25-36 MV/ PUMP 1 5. Connect the valve common wire(s) to terminal marked VC / COM. 2 3 6. Connect each valve power wire to the appropriate station number terminal. See Figure 9. 5 6 7 8 7 8 37-8 9 10 11 12 COM COM 13 1 15 16 17 18 19 20 21 22 23 2 13-2 1-12 Caution: Maximum current load per station must not exceed 0.5A. 3 5 6 Master Valve / Pump 2 VAC 7. If a 2 VAC pump start relay or master valve is used, connect the power wire to terminal MV/Pump in bottom left corner and the common wire to any VC/COM terminal. Caution: The pump start relay current load must not exceed 0.5A. Do not connect the pump starter directly to the controller damage to the controller will result. Output Switch Operation The 3-position switches provided on the station output module (Figure 10) enables local control of the station and master valve output. Figure 10 The switch positions are as follows: Manually activates the terminal. The terminal will remain on until the switch is moved to the or position. An indicator LED will illuminate when the switch is on the position. Shuts off the terminal. The terminal will be inoperative (for both automatic and manual operation while the switch is in the position. Enables the terminal to be automatically controlled during automatic or manual operation. Caution: To prevent controller damage, do not operate more than six stations concurrently (1.75A total load maximum) during either 25 26 27 28 29 manual or automatic operation. 6 MV/ PUMP 1 2 3 5 35 36 COM COM 37 38 39 0 1 2 3 10 11 12 COM COM 13 1 15 16 17 18 19 30 31 32 33 3 6 7 8 9 RELEASED Ver-D.0 Toro 2015

Alarm and Sensor Connections The Alarm Switch is designed to monitor a dry contact switch and the alarm functionality is programmable in the system software. The Alarm Switch input can be programmed to start or stop programs of your choice and even follow the contact status if desired. The Flow Signal is designed to read shorting pulse output from a Data Industrial flow meter (or equivalent). If a rain tipping bucket or evapotranspiration (ET) gauge is used, this would to be a normally open contact type. The controller measures the timing of the contact closures to determine if it is a flow pulse, rain pulse or ET pulse. 1. Connect a wire pair to the alarm switch and/or flow measuring device and route into the controller through 1/2 (15mm) conduit. 2. Connect the wire pair to the appropriate terminals as shown in Figure 11. Figure 11 ALRM1 ALRM2 ALM GND FLOW1 FLOW2 FL GND +12V -20-20 GND Refer to Sentinel Field Satellite Controller User s Guide for operating instructions. Alternate Communication Device Connection Optional The Sentinel Satellite is designed to work with various communication devices such as cellular modem. Refer to the recommended communication device listing at your local dealer for a list of approved devices. These devices may require the optional DC Power Supply unit. Electromagnetic Compatibility Radio complies with FCC Part 22 and Part 90 of the FCC Rules. This equipment has been tested and found to comply with the limits for a FCC Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. The equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to the radio communications. Operation in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. 7

Specifications Pedestal-Mount Plastic Cabinet (PP1, PP2, PP3) Key-actuated locking front, back and top covers 16 W x 16 D x 3 1/2 H (1cm W x 1cm D x 127cm H) Weight 70 lbs. (32.8kg) Pedestal-Mount Metal Cabinet (PS1) Stainless steel, type UL 3R Key-actuated locking front panel and top control panel cover 17 1/8 W x 8 5/8 D x 3 1/2 H (3.5cm W x 22cm D x 88cm H) Weight 55 lbs. (2.9kg) Stainless Wall-Mount Cabinet (WS5) Stainless steel, type UL 3R Key-actuated locking front panel 17 1/8 W x 8 5/8 D x 30 3/ H (3.5cm W x 22cm D x 78cm H) Weight 7 lbs. (21.3kg) Power: Input- 115 120 or 230 20 VAC, 50/60 Hz Output- 2 VAC, 2.0A (max. total) 0.5A (max. per station) 0.5A (max. master valve/pump start relay) Fuses: 250V, 2.0A Slow-Blow - 2 VAC 250V, 2.0A Slow-Blow - Common Sensor Input: Alarm Switch Dry contact switch Flow Signal Normally Open switch Radio: Radio Equipment used with the Sentinel controller must comply with all applicable national and/or local electrical codes. Powder-coated Wall Mount (WS1) Key-actuated locking front panel 10½ W x 5½ D x 30 15½ H (26.8 cm W x 1.1 cm D x 39.6 cm H) Weight 19.8 lbs. (9 kg) IP rating for enclosure: IP Temperature Range: Operating- 1 F to 10 F (-10 C to 60 C) Storage- -22 F to 158 F (-30 C to 70 C) 8 The Toro Company Irrigation Division www.toro.com Part Number 373-055 Rev. D