BVX SERIES VERTICAL DIRECT EXPANSION BLOWER COIL UNITS

Similar documents
FFW/FSW/FHW SERIES FLOOR EXPOSED VERTICAL FAN COIL UNITS

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

BHH Product Specifications

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

CEW SERIES CEILING EXPOSED HORIZONTAL FAN COIL UNITS

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

Complete HVAC Capability

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

Unitary Products. Magic Aire Specifications Manual. Producing Quality Heating & Cooling Equipment For Over 50 Years

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

DIRECT-DRIVE BLOWER FAN COIL AIR CONDITIONER ENGINEERING GUIDE

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons

WAC Air Curtains Technical Guide

SINGLE PACKAGE AIR CONDITIONING WATER COOLED

HORIZONTAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

Climas y Proyectos Leyco, S.A. de C.V.

F SERIES. Floor Exposed Vertical Fan Coil Units. Nominal Sizes 200 thru 1200 CFM

FS Fan-Coil Units Hi-Rise, Vertical

50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS

Product Data. 42D Ducted Fan Coil Air Conditioners cfm

ELITE SERIES R-410A Ready - Multi-Position

FCVC Series VERTICAL FAN COILS

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL

36CWA4-HW 4-Pipe Chilled & Hot Water Air Handler (120V) 4-Pipe Heat & Cool Fan Coil 36,000 BTUH

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS

24CWA4-HW 4-Pipe Chilled & Hot Water Air Handler (120V)

RBV Sales Guide FAN COIL UNITS FLOOR-MOUNTED, VERTICAL

ROOF TOP SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

TVS/R FAN COIL UNITS HI-RISE, VERTICAL

Typical Applications. Horizontal Installation

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

48CWA2-00 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 48,000 BTUH

42CET/ 42CED Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 300 to 1400 cfm Electric heater option

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

FN Fan-Coil Units High-Performance, Horizontal

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

RAH Engineering Guide

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

VAHU Vertical Air Handling Unit

CFFWA Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 12,000-60,000 BTUH

Submittal. Front View Side View

Precision Cooling For Business-Critical Continuity. Liebert CW. System Design Manual kW, 50 & 60Hz

1. Air Handler Features Page Physical data Page Available kits Page Model nomenclature Page 5

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

Chilled Water FCU. Horizontal Fan Coil 50hz CFM. A Series.

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

SDL Single-Duct, Low-Height, VAV Terminals

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A)

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application

TECHNICAL GUIDE R-410A, 13 SEER LATITUDE SERIES 60 Hertz

MERIT Series R-410A - Upflow / Horizontal - Variable Speed

R-22, 13 SEER 60 Hertz

Vertical Hi-Rise Fan Coil Unit (Model FS)

BAC / BHC Product Specifications

MAH. Modular Air Handling Unit

MHWW-24-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 24,000 BTUH. Rev. 1.3

TSS Single-Duct VAV Terminals

Nomenclature. Nomenclature Distributing coil types

Horizontal Fan Coils 200-1,200 CFM

Guide Specifications. General. Casing. Coil/Drain pan. Fan/Motor

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)

BC Series Multi-position Air Handler Engineering and Specification Guide (Electric and Water Heat)

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Product Data. FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 SLIM LINE DUCTED FAN COIL WITH PLENUM ON/OFF DISPLAY TEMP

TECHNICAL GUIDE R410a SPLIT SYSTEM 1.5 to 5.0 NOMINAL TONS

SPECIFICATIONS AND DESIGN ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE. EDITION 11

Concealed Ducted Split Series R22

DAVE LENNOX SIGNATURE COLLECTION Multi Position Variable Speed Blower

DESCRIPTION FEATURES

TECHNICAL GUIDE. Description PREDATOR SERIES R-410A SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS AND AIR HANDLERS

SECTION AIR TERMINAL UNITS

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK

Section 5 AIR - COOLED CONDENSING UNITS MODEL PC 05Z TO PC NOMINAL COOLING CAPACITY RANGE 56.6 TO 772 MBH

12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT

Direct Gas-Fired Heating

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VQBL

BAC, BAF, BAH Central Station Air Handlers

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

EMIP60 ISO. EM Series, Inch Pounds - 60 Hz EM (iso) Spec Guides Drawings Spec Sheets Extended Range Ratings Low Temp Heating.

WE MAKE INDOOR AIR BETTER

MH1WC4W-08-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

CHP

University of Delaware

TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS

MODEL FF/FFC CEILING AND INLINE/CABINET VENTILATORS

PACKAGED HEAT PUMP AIR HANDLER UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

BELT DRIVEN CENTRIFUGAL ROOFTOP FILTERED SUPPLY FAN

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

YEAR-ROUND AIR CONDITIONING Our Deluxe-Aire units are ideally suited to provide heating, cooling and air filtration for areas where it is not

catalog SDL Single-Duct, Low-Height, VAV Terminals

Transcription:

BVX SERIES VERTICAL DIRECT EXPANSION BLOWER COIL UNITS MAGIC AIRE BVX SERIES FAN COILS ARE ETLC LISTED IN ACCORDANCE WITH UL 1995 AND ARE ASSEMBLED TO ORDER FOR COMPETITIVE DELIVERY. UNITED ELECTRIC COMPANY, L.P. 501 Galveston St. Wichita Falls, Texas 76301 940397100 Fax 940397166 BVX 4.0 www. magicaire.com PI 06/03 3M Page 1 BVX 4.0

ENGINEERING SPECIFICATIONS Contractor shall furnish and install high quality air handling units as indicated on plans. Sizes and capacities shall be shown in the Unit Schedule included on the drawings. All units shall be the products of Magic Aire with the ETL safety listing. Cabinets shall be fabricated of LFQ (min) steel. External parts are to be made with polyurethane based powder coated A60 galvanealed, while internal parts are to be built from G90 galvanized steel. Units shall pass 500 hour salt spray test as described in ASTM B117. Large access panels shall be provided to permit full access to internal components. The structural integrity of the cabinets shall remain unaffected by the removal of any or all access panels. Insulation shall be 3/4 1.5 pound density providing effective acoustical and thermal control, fire safety, and resistance to air erosion. Coils shall be of the staggered tube type constructed with seamless copper tubes and headers, and deep corrugated aluminum fins with straight edges. Manufacturer shall supply full depth collars, drawn in the fin stock to provide accurate control of fin spacing and completely cover the copper tubes to lengthen coil life. The tubes are to be mechanically expanded into the fins for a permanent primary to secondary surface bond, assuring maximum heat transfer efficiency. The coils are to be tested at 500 PSI for operation at 400 PSI gauge. The coils provided shall be suitable for the application and comply with the required performance as described in the Unit Schedule. Model 4 to 60 cooling coils standard with a thermal expansion valve for mounted for use on R and includes a side port distributor. Model 90 and 10 cooling coils are stocked both single and dual circuited with thermal expansion valves mounted for use on R and include side port distributors. Drainpans. Polymer thermoset sloped drain pan in Model 4 to 60 with 3/4 FPT connections. Galvanized steel drain pan in Model 90 and 10 with 7/ connection. Fan Wheels shall be double width, double inlet, forward curved, centrifugal type. They shall be statically and dynamically balanced for smooth, quiet operation. The housing shall be constructed of heavy gauge steel with dieformed inlet cones. The bearings shall be self aligning, sealed cartridge, permanently lubricated ball bearings that are rubber mounted and shall provide dependable fan operation for an average life of 00,000 hours. The fan shaft shall be solid cold rolled steel designed such that its operating speed is below its first critical speed. Motors and Drives shall be belt drive, standard duty, 175 RPM, open, dripproof construction. Single phase motors shall be provided with resilient mount and automatic reset thermal protection. Drive shall be of the Vbelt type. Variable pitch motor sheaves are to be furnished for ease and accuracy in balancing the system and adjusting the required air volume. The motors are to be bolted to an adjustable platform to facilitate belt tension and alignment. The blower sheave shall be cast iron single groove with split tapered bushing that is keyed to the blower shaft. Filters are to be disposable type. They shall be center loading with an 5% arrestance efficiency. The filters shall be included in the units as an integral part of the cabinet with easy access provided by the manufacturer. Page BVX 4.0

BVX Series STANDARD FEATURES Controls (i.e. contactor, starter, or transformer/fan relay) not included in standard product. Only ODP, single and three phase motors on 5 Ton units are factorywired to Jbox. All other motors require field wiring to Jbox located on side of unit cabinet. Liquid and suction coil stubouts and drain connections are standard left hand looking at front of unit. 4 to 60 BVX are onepiece units. 90 to 10 BVX are threepiece units and each section is individually cartoned. Stocked Optional Accessories: Row Hot Water Heating Coil Specify preheat (std) or reheat (opt price add) for 5 Ton units Discharge Plenum (Grilles field supplied and installed) Return Plenum (Grille, if required, field supplied and installed) Pleated Filters Heat Pump Conversion Kit NonStock Options: Special Insulation Steam Coils (See Steam Brochure) Electric Heat 4 BVX with panels removed. 90 BVX with panels removed. 90 to 10 BVX are threepiece units and each section is individually cartoned. Page 3 BVX 4.0

460 BV PRODUCT DESCRIPTION MODEL NUMBER IDENTIFICATION SPECIFICATIONS MODEL NOMINAL RATING IN TONS COIL FACE AREA FILTER " LIQUID LINE SUCTION LINE COIL CONNECTION SHIPPING WT. ROW WATER CONNECTION SHIPPING WT.** 4 BVX. 0 0 0 x 0 5/16" 3/4" 163 7/" 14 36 BVX 0 0 0 x 0 5/16" 3/4" 170 7/" 14 4 BVX 4. 0 4. 0.5 x. 5 3/" 7/" 01 7/" 17 60 BVX 5. 0 5. 1 16 x 5 3/" 7/" 53 11/" 1 **Coil only. 460 BV UNIT CABINET DIMENSIONS MODEL UNIT BLOWER OUTLET A B C D E F G H I J 4 BVX 31/ 50 X X X X 3 1 3/ 4 36 BVX 31/ 50 X X X X 3 1 3/ 4 4 BVX 5 31/ 561/ X X X X 11/ 14 91/ 60 BVX 91/ 4 51/ 595/ X X X X 1 14 13 Page 4 BVX 4.0

9010 BV PRODUCT DESCRIPTION MODEL NUMBER IDENTIFICATION SPECIFICATIONS MODEL NOMINAL RATING IN TONS COIL FACE AREA FILTER " "A"COIL CONNECTION SHP WT ROW CONNECTION SHP WT 90 BVX 7. 5 7. 3 3 16 X 5 11/" 36 11/" 1 10 BVX 10 9. 4 4 0 X 5 13/" 456 11/" 10 9010 BV UNIT CABINET DIMENSIONS MODEL UNIT BLOWER OUTLET A B C D E F G H I J 90 BVX 39 7 X 34 9 191/ 151/ 1 163/ 4 131/ 4 10 BVX 511/ 7 X 34 9 191/ 01/ 1 163/ 4 131/ 4 Page 5 BVX 4.0

FAN PERFORMANCE MODEL INTER S.P. CFM.5" ESP.50" ESP.75" ESP 1.00" ESP 1.5" ESP 1.50" ESP 4 BVX.1.16.19.3.30 600 700 00 900 1000 644 695 747 74 36.0.11.13.1. 34 66 90 93 99.13.15.19.3.7 991 101 1054 1070 1114.1.0.4.9.34 113 1149 117 1194 16.4.6.30.34.41 146 159 13 1303 137.30.3.37.41.4 1354 1365 135 140 141.36.39.44.49.57 36 BVX.9.3.47.5.70 900 1050 1350 5 93 1019 1111 1195.19.6.3.44.59 1000 107 1144 117 1307.4.33.4.53.70 113 16 1333 1403.31.40.50.64.0 136 130 1363 1433 150.37.47.59.73.91 135 140 146 1513.43.54.65.1 1460 1503 1546 1603.50.60.71.9 4 BVX.44.57.71. 1.06 1400 1600 100 7 6 96 1066 114.9.4.54.7 1.00 9 1004 1061 114 11.36.5.64.90 1.14 1009 10 1154 131 19.43.60.75 1.0 1.30 1107 1169 136 1303 135.53.67.91 1.13 1.43 110 157 131 1375.6.1 1.00 1.7 177 1339 1391 144.73.90 1.1 1.37 60 BVX.41.5.65.0.96 1750 50 500 733 06 73 947 107.9.43.57.76.99 51 909 966 1036 1106.39.54.69.9 1.15 949 999 105 1117 115.46.6.77 1.04 1.6 1046 107 1134 1195 15.5.7.9 1.15 1.43 1140 1171 10 165.69.5 1.0 1.33 19 156 19 1340. 1.00 1.1 1.46 90 BVX.30.39.50.6.76 50 65 3375 3750 644 705 771 31 9.56.79 1.0 1.44 1.6 75 1 66 90 9.73.99 1.31 1.69.1 57 900 950 1001 1054.91 1.19 1.53 1.94.44 937 93 105 10 1130 1.07 1.39 1.74.1.73 101 1056 1100 1147 1.7 1.60 1.99.46 1094 115 1165 105 1.44 1.0.1.70 10 BVX.5.33.4.53.63 3500 4000 4500 5000 631 705 75 69 935.0 1.17 1.6.35 00 715 76 56 9.97 1.41 1.93.56 0 5 919 97 1.17 1.61.17.5 73 99 96 1.36 1.4.41 946 99 1049 1.55.05.66 1015 105 1107 1.75.7.94 FullLoad Currents in Amperes, Single Phase AlternatingCurrent Motors* HORSE POWER VOLTAGE/PHASE 1/4, 1/3 115/1 Split Phase Select appropriate motor horsepower from pages 67. When ordering, specify HP voltage/phase CFM@ESP. 1/4, 1/3, 1/, 3/4, 1, 1 1/, 115/030/ 1 1/4, 1/3, 1/, 3/4 115/1 SPD 1/4, 1/3, 1/, 3/4 30/1 SPD 1/4, 1/3, 1/, 3/4, 1, 1 1/ 77/ 1 1/3, 1/, 3/4, 1, 1 1/,, 3 030/460/ 3 Consult List Price Pages for motor installation and options. For motors not listed, contact factory. Only ODP, single and three phase motors on 5 Ton units are factorywired to Jbox. All others require field wiring to Jbox on side of unit cabinet. FullLoad Currents in Amperes, Single Phase AlternatingCurrent Motors* The following values of fullload currents are for motors running at usual speeds and motors with normal torque characteristics. Motors built for especially low speeds or high torques may have higher fullload currents, and multispeed motors will have fullload current varying with speed, in which case, the nameplate current rating shall be used. The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 10 and 0 to 40 volts. HORSEPOWER 115 volts 00 volts 0 volts 30 volts 1/4 5. 3. 9 1/3 7. 4. 1 4. 0 6 1/ 9. 5. 6 5. 4 4. 9 3/4 1 7. 9 7. 6 6. 9 1 16 9. 1.5 0 11. 5 1 4 1 *Values from NEC. Handbook 1999 Edition, 1 10 actual motor nameplate 1 1 amps may vary. Page 6 BVX 4.0

FAN PERFORMANCE MODEL INTER S.P. CFM.5" ESP.50" ESP.75" ESP 1.00" ESP 1.5" ESP 1.50" ESP 4 BVX w/4 VH.19.4.30.3.44 600 700 00 900 1000 76 76 1 9 951.09.1.14.0.6 913 946 979 1037 109.14.16.1.5.33 1057 100 110 1155 117.19.3.7.31.39 115 135 174 1311.3.7.33.3.45 1309 134 1349 1373 1406.9.34.3.45.5 1437 145 1463 143 1506.36.39.44.5.60 36 BVX w/36 VH.41.53.67.3 1.00 900 1050 1350 905 994 1091 19.1.9.3.54.70 1043 110 1 1319 1403.7.35.46.63.0 1165 141 1330 1413 1496.3.43.57.7.91 177 1345 144 1507 15.3.5.63.1 1.00 137 1440 1515 1576.46.57.7. 146 1519 159 1659.54.63.7.95 4 BVX w/4 VH.57.74.94 1.15 1.37 1400 1600 100 1 96 1056 1159 167.31.46.61.7 1.16 94 1066 114 136 1344.40.56.73.96 1. 1071 1154 11 134 1411.46.64.3 1.09 1.41 1159 136 131 1391.56.74.96 1. 157 131 1391 1463.64.3 1.0 1.35 1334 135 1457 1530.74.93 1.15 1.4 60 BVX w/60 VH.53.6.5 1.05 1.5 1750 50 500 775 51 930 1011 1091.34.4.66.7 1.1 91 950 1019 1097 1170.44.59.76 1.03 1.30 93 1041 1107 1173 143.53.69.9 1.15 1.46 10 11 11 146.64.7 1.0 1.9 1171 113 160 1316.74.95 1.17 1.4 157 196 1337 137.90 1.09 1.3 1.59 90 BVX w/90 VH.36.4.61.75.90 50 65 3375 3750 664 73 796 61 97.60.4 1.15 1.53 1.94 775 36 9 95 1010.76 1.07 1.3 1.1.5 71 9 979 1031 1090.96 1.6 1.63.05.55 959 100 1050 1101 1159 1.14 1.46 1.4.9.3 1043 107 11 1170 1.33 1.66.0.56 1115 1145 117 136 1.50 1.7.30.0 10 BVX w/10 VH.33.43.54.6.1 3500 4000 4500 5000 647 77 79 0.4 1.6 1.73.39 736 0 67 943 1.04 1.45.00.67 14 77 939 1006 1. 1.67.4.97 91 946 1003 1.43 1.90.50 960 1007 1067 1.6.11.7 104 1066 1119 1..3 00 FullLoad Currents in Amperes, Three Phase AlternatingCurrent Motors* The following values of fullload currents are typical for motors running at speeds usual for belted motors and motors with normal torque characteristics. Motors built for low speeds ( RPM or less) or high torques may require more running current, and multispeed motors will have fullload current varying with speed. In these cases, the nameplate current rating shall be used. The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 10, 0 to 40, 440 to 40, and 550 to 600 volts. HORSEPOWER 00 volts 0 volts 30 volts 460 volts 575 volts 1/. 5. 4. 1. 1 0. 9 3/4 7 5 1. 6 1. 3 1 4. 4. 6 4.. 1 1. 7 1.5 6. 9 6. 6 6 3. 4 7. 7. 5 6. 4. 7 3 11 10. 6 9. 6 4. 9 5 17. 5 16. 7 15. 7. 6 6. 1 7.5 5. 3 4. 11 9 10 30. 14 11 *Values from NEC Handbook 1999 Edition, actual motor nameplate amps may vary. Page 7 BVX 4.0

DIRECT EXPANSION COOLING CAPACITIES 4BVX 5 deg F / 71 deg F 0 deg F / 67 deg F 75 deg F / 63 deg F SUCT TEMP PD PSI CFM 40 6.5 600 00 1000 34 5 4.5 0.0 4.0 7. 54.0 57.3 59.9 57 56.4 5.4.6 6 36.0 1.5 1. 4. 51.5 54. 57.0 51.1 57 1. 6. 31.0 15.4 19.7 0 51. 5.3 5 50.5 51. 5. 45 4.47 600 00 1000 9.6 34 36. 1.6 1. 4. 56.4 59. 6.0 56.0 5.7 60.3 1.6 7.4 31. 15.5 19.7 56.1 57. 5.6 55.4 56.0 57.0 15.9 1.6 1. 11 16.0 1.7 54. 56.5 57.7 59 55.1 55. 50.7 600 00 1000.0.0 4 15.5 19.7 61.1 6. 65 60.3 60.9 61. 15. 1.6 1. 1 16.1 1. 59.6 61.4 6.6 5. 59.9 60.5 11.5 15 15.6 11.0 13 15.4 5.0 59.6 60. 56.6 57.4 57. 36BVX 5 deg F / 71 deg F 0 deg F / 67 deg F 75 deg F / 63 deg F SUCT TEMP PD PSI CFM 40 9.19 900 51.5 5.0 65 31.0 36. 41.5 5 56.7 59.4 5 56.3 5.5 44.0 49.5 54.0.6 36 0 50.6 54.1 56.4 50.6 55 55.4 36 41.5 47.0 4.4 30.6 35. 49.9 51.4 50 49.7 50. 5.1 45 6.46 900 46.0 51.0. 3 5 59.0 61.3 5.4 60. 34.6 4.5 4.5 4.6 30. 36.0 54. 56.3 57. 54.5 55.6 56. 5. 9.4 34. 0.6 5. 30. 5 55.6 56.4 53 54.6 55.1 50 4.35 900 35.4 45 49.5 4.6 31.0 36. 59.7 61.1 6.7 59.5 60.4 61.5 5.4 9.6 35.0 0.6 5.4 30.4 5.7 60.4 61.3 5. 59.4 59. 1.5.0 4.6 17.5 1.4 4. 57.0 5.5 60.1 56.1 56.9 57.6 4BVX 5 deg F / 71 deg F 0 deg F / 67 deg F 75 deg F / 63 deg F SUCT TEMP PD PSI CFM 40 10 1600 67.0 75.0.0 40.5 4.0 54.0 57 57. 59.9 57 56. 5.9 56.5 64.0 70.0 37. 44.0 50.5 51.3 54.4 56.7 51.3 59 55. 4.5 55 59.0 34. 40.0 46.0 4.6 51. 5 4.5 51. 5. 45 9.39 1600 5.5 66.0 7.0 37. 44.5 50.5 56.3 59.3 61.5 56. 5.7 60.5 47.5 55.0 60.5 34 40.0 46.0 54. 56.7 5.6 54.0 56.0 57.5 37.4 45.0 50.0 9. 36.6 4.5 5.5 59 55.4 5. 5 54.5 50 6.0 1600 49.0 56.0 61.5 36 40.5 46.5 59.1 61.5 64 5.9 60. 6.3 37.5 46.0 4.5 9.4 36. 41.5 57.4 5. 60. 57.1 5.0 59.5 5. 30. 37.0 4. 9.4 35. 56.4 5.0 5.5 55.7 56.6 56. Page BVX 4.0

DIRECT EXPANSION COOLING CAPACITIES 60BVX 5 deg F / 71 deg F 0 deg F / 67 deg F 75 deg F / 63 deg F SUCT TEMP PD PSI CFM 40 10.41 500.0 100.0 110.0 5.5 6.5 71.0 5.6 56.1 5.7 5.6 55.7 57.9 74.0 5.0 90 4.0 57.5 65.0 50.5 55 55. 50.5 50 54.9 6.5 70.0 77.0 45 51.5 59.0 4.0 51.1 51 47.9 50.6 5. 45 7.39 500 76.0.0 96.0 4.0 57.5 65.0 5.4 60.7 5.0 59.7 64.0 7.0 79.0 45 51.5 59.5 50 56.1 5.0 5. 57.0 47.0 5.5 60 36.6 46.0 5.5 5.4 56 5.1 5.9 54.4 50 4.7 500 65 70 1.0 4.5 5.0 59.5 5.6 61.0 6.9 5.5 60.4 61. 47.5 59.0 65 36. 46.5 50 57.3 5.5 60.4 57.0 57.7 59. 39.0 46.5 30.4 37. 44.5 56.3 57. 5.5 55.6 56.4 56. 90BVX 5 deg F / 71 deg F 0 deg F / 67 deg F 75 deg F / 63 deg F SUCT TEMP PD PSI CFM 40 9. 50 3750 130.0 147.0 161.0 7.0 9.0 104.0 50 56.5 59. 50 56.1 5.3 10.0 15.0 137.0 71.0 4.0 96.0 50.9 59 56. 50. 54 55. 9.0 100 114.0 64.0 76.0 7.0 4.4 51.5 55 4. 50.9 5.4 45 6.99 50 3750 11.0 19.0 141.0 71.0 5.0 97.0 55.9 5. 61.1 55.9 5.3 60.0 95.0 106.0 116.0 65.0 76.0 7.0 53 56.4 5.4 51 55.7 57. 6.0 5.0 97.0 55 6.0 0.0 5.9 54.0 55.3 5.5 5 54.1 50 4.49 50 3750 97.0 10.0 11.0 65.0 77.0.0 5.3 61.3 6 5.1 60.6 6.0 6.0 6.0 9.0 54.0 6.0 0.0 57. 5.9 60.1 57.4 5.1 5.9 4.0 57.0 67.0 44.5 55.0 65.0 56.6 5.1 5.9 55. 56.6 57.0 10BVX 5 deg F / 71 deg F 0 deg F / 67 deg F 75 deg F / 63 deg F SUCT TEMP PD PSI CFM 40 9.1 4000 5000 177.0 0.0.0 105.0 16.0 140 5.5 55.9 5.6 5.5 55.6 57. 14.0 171.0 19.0 96.0 115.0 131.0 50.4 54 55. 50.4 5.9 54. 15.0 141.0 156.0 7.0 100 11.0 4.0 51.1 51 47.9 50.5 5.1 45 6.45 4000 5000 150 176.0 194.0 96.0 115.0 131.0 5.4 60.7 57.9 59.7 19.0 144.0 160.0 7.0 100 119.0 50 56.1 5.0 5. 55.4 56.9 90 117.0 16.0 70 9.0 105.0 5.5 56 55.6 5.1 5.9 54.4 50 4.1 4000 5000 130 147.0 16.0.0 104.0 119.0 57.9 61.0 6.9 57. 60.3 61.7 94.0 11.0 17.0 70 90 106.0 57.5 5.5 60.4 57.1 57. 59. 65.0 77.0 9.0 60.5 74.0.0 56.4 57.9 5.6 55.7 56.5 56. Page 9 BVX 4.0

HOT WATER HEATING CAPACITIES CAPACITIES BASED ON 60 O EAT AND 10 O EWT. Units not recommended for heating applications when the leaving air exceeds 130 degrees. As with any hydronic system, proper freeze protections should be used. (Glycol or freeze stat.) HOT WATER HEATING CORRECTION FACTORS ENTERING AIR TEMP (F) ENTERING WATER TEMP (F) 100 110 10 130 140 150 160 170 10 50. 419. 500. 579. 665. 74. 3. 917 1.000 1.090 55. 376. 460. 544. 69. 70. 791. 73. 963 1.04 60. 335. 419. 500. 579. 665. 74. 3. 917 1.000 65. 90. 376. 460. 544. 69. 70. 791. 73.963 70. 51. 335. 419. 500. 579. 665. 74. 3.917 75. 05. 90. 376. 460. 544. 69. 70. 791.73 0. 167. 51. 335. 419. 500. 579. 665. 74.3 When correction factors are used for various entering air and entering water temperatures, multiply the correction factor times the above listed capacity. The correction factors may be used with all Magic Aire published 10 0 E.W.T. heating capacities. Page 10 BVX 4.0

STEAM CAPACITIES NONSTOCK CUSTOM STEAM COILS 700 Entering Air Dry Bulb 5# Steam Pressure MODEL NOMINAL CFM STANDARD CAPACITY HIGH CAPACITY 4BVSTM 00 3 6 36BVSTM 41000 77000 4BVSTM 1600 50000 9 60BVSTM 6 116000 90BVSTM 110000 04000 10BVSTM 4000 151000 79000 STEAM HEATING CORRECTION FACTORS ENTERING AIR TEMP (F) STEAM PRESSURE PSIG 0 5 10 15 0 5 40 60 0 1.46 1.50 1.55 1.63 1.70 1.70 1.0 1.93.05 0 1.33 1.37 1.41 1.46 1.55 1.63 1.6 1.79 1.9 0 1.1 1.6 1.31 1.36 1.45 1.50 1.56 1.67 1.79 40 1.09 1.15 1.19 1.5 1.33 1.3 1.44 1.55 1.67 60. 96 1.0 1.07 1.13 1.1 1.4 1.9 1.3 1.56 70. 9. 95 1.00 1.0 1.15 1.19 1.4 1.36 1.4 0... 9. 9 1.06 1.1 1.17 1.30 1.43 100. 71. 75. 1.. 95 1.00 1.05 1.1 1.31 Standard steam coils are not recommended for duty where entering air is less than 40 degrees. Units not recommended for heating applications when the leaving air exceeds 130 degrees. Page 11 BVX 4.0

BVX Series OPTIONAL PLENUM Optional Discharge Plenum Basic Unit Optional Discharge or Return Air Plenum K L M SHPG WT " 31/" 1" 3 " 31/" 1" 3 5" 31/" 14" 30 91/4" 51/" 16" 35 Optional Return Air Plenum 39" 7" 4" 41 511/" 7" 4" 41 Contact the factory for further information. Specifications subject to change without notice. Page 1 BVX 4.0

TYPICAL WIRING DIAGRAM FOR USE WITH BELT DRIVE UNITS Wiring, transformer, fan relay and terminal strips field provided. Transformer Primary must match Supply Voltage. REFER TO NAMEPLATE FOR PROPER VOLTAGE LOW VOLTAGE WIRING HIGH VOLTAGE WIRING GND L/N TRAN1 4V L1 R THERMOSTAT {C G FAN MOTOR SINGLE PHASE RELAY/CONTACTOR TRAN1 4V THERMOSTAT{ R C G L1 L FAN MOTOR THREE PHASE L3 GND CONTACTOR/STARTER Page 13 BVX 4.0

NOTES Page 14 BVX 4.0

Page 15 BVX 4.0

ENGINEERING SPECIFICATIONS Cabinets shall be fabricated of LFQ (min) steel. External parts are to be made with a polyurethane based powder coated A60 galvanealed, while internal parts are to be built from G90 galvanized steel. Units shall pass 500 hour salt spray test as described in ASTM B117. Coils are to be tested at 500 PSI for operation at 400 PSI guage. All water coils have air vents. Fan wheel bearings shall be self aligning, sealed cartridge, permanently lubricated ball bearings that provide dependable fan operation for an average life of 00,000 hours (belt drive only) Variable pitch motor sheaves. United Electric Company designs and builds its Magic Aire products to comply and perform to one or more of the following standards: COIL AIR FLOW CAPACITY General Belt Drive Equipment Direct Drive Equipment Hydronic Direct Expansion AMCA 10 ASHRAE 51 ARI 430 ARI 440 ARI 410 ARI 10 IN DUCT SOUND RATINGS Air Moving Equipment ASHRAE 6 AMCA 330 SAFETY MATERIAL AGENCY LISTINGS SPECIFICATIONS MAJOR COMPONENTS Coils UL Report # Equipment ETL Report # Sheet Metal Copper Tubing Aluminum Motors Wire Electrical Filters Fiberglass Paint UL 07 SA 343 CAN/CSA C. #36 ANSI/UL1995 49193 ASTM A55 ASTM A57 ASTM B6 ASTM B75 ASTM B ASTM B51 ASTM B09 UL/CSA NEMA UL/CSA UL/CSA UL ASHRAE 5 UL 11 UL 73 (5/50) ASTM E4 ASTM B117 UNITED ELECTRIC COMPANY, L.P. 501 Galveston St. Wichita Falls, Texas 76301 940397100 Fax 940397166 BVX 4.0 www. magicaire.com Page 16 PI 06/03 3M BVX 4.0