V5422L / V5422E ACTUATED BUTTERFLY VALVES. SPECIFICATIONS Valves

Similar documents
V5422L / V5422E ACTUATED BUTTERFLY VALVES. SPECIFICATIONS Valves

V5422L / V5422E ACTUATED BUTTERFLY VALVES. FEATURES With factory-mounted electric actuator. SPECIFICATIONS Valves

V5422L / V5422E ACTUATED BUTTERFLY VALVES. FEATURES With factory-mounted electric actuator

M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

S1024-2POS / S POS S2024-2POS / S POS

M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

MT4-024/MT4-230 MT8-024/MT8-230

V5832A/5833A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATIONS

MVN Rotary Valve Actuators FOR CONTROL BALL VALVES VBG (DN15 TO DN32)

V5822A / 5823A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATIONS GENERAL

MT4-024/MT4-230 MT8-024/MT8-230

VBGx-xx-xx Externally Threaded Control Ball Valves PN25 (DN40 TO DN50)

S10010 / S SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS 10/20 Nm (88/177 lb-in) FOR MODULATING AND FLOATING CONTROL SPECIFICATIONS GENERAL

M4410C/L SMALL LINEAR THERMOELECTRIC ACTUATORS

Motorized Butterfly Valve

Motorized Butterfly Valve

Motorized Butterfly Valve Actuated Wafer type butterfly valves

Motorized Butterfly Valve

V4(V7)-ABFW-EPN16 Actuated Wafer type butterfly valves

V5049A FLANGED LINEAR VALVE PN25/40

ML6420A/ML6425A,B. Electric Linear Valve Actuators

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

TRF.. series spring return rotary actuators for CCV

Concentric butterfly valves

STEVI 440 / 441. Straight through control valve DN

ML7420A/ML7425A,B. Honeywell. Electric Linear Valve Actuator FEATURES SPECIFICATIONS GENERAL SPECIFICATION DATA

EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS

Pneumatic Butterfly Valve Type 3335 / AT

with electric and pneumatic actuators Control valve in 3-way-form (3-way mixing valve) DN 300 ARI-STEVI 423 Electric actuator ARI-PREMIO

Butterfly valve with electrical actuator VFY-WA

Butterfly valve with electrical actuator VFY-WA

Greater Cairo Foundries. Concentric Rubber Lined Butterfly Valves

STEVI 450 / way control valve in mixing and diverting design DN

V5825B. Small Linear Valve / PN25 DH Compact Valve. FEATURES Pressure-balanced k vs m 3 /hr Normally-closed valve

Page 6. Page 6. Page 6. Page 7. Page 8. Page 9. Page 10 / 11

Butterfly valves for high temperature series GD(H) - LDK

ELECTRIC ACTUATORS 400 N

KEYSTONE SERIES GR RESILIENT SEATED BUTTERFLY VALVES GRW/GRL

Motor Valve GS 1 series, DN 15 up to DN 150

Saddle valves KH210GR - KH230GR

BUTTERFLY VALVE VF-7 Series

ARI-ZESA / ARI-GESA / THEA Butterfly valves

Electric Actuated Butterfly Valves Ductile Iron Wafer Body ASME 150# 2 to 6 Pipe

BUTTERFLY VALVES + NA ELECTRIC ACTUATOR

CV-SFS4-PN16 SERIES SLIENT CHECK VALVE, GLOBE TYPE FEATURES SPECIFICATIONS PRODUCT IDENTIFICATION SYSTEM PRODUCT DATA

Electro Controls. Valves / Linkages WattsIndustries.co.uk

Butterfly valves. ARI-ZIVA -Z - Fig Free of maintenance wafer pattern butterfly valve - soft sealed - industrial range

Butterfly valves ARI-ZIVA -Z / ARI-ZIVA -G. with notch lever. with worm gear. with electric rotary actuator rotork

BUTTERFLY VALVE 17 SERIES Gearbox

Control shut-off butterfly valves DN 25 DN 200 PN

VE-x Plug & Seat Valve Assemblies

VALVES WITH NA ELECTRIC ACTUATOR

Leakage rate. Valve body. U.S. Registered Trademark EN0B-0308GE51 R1002 Copyright 2002 Honeywell Inc. All rights reserved

STEVI 440 / 441. Straight through control valve DN

ARI-STEVI 470 / 471 (DN15-150)

gunric product selector gunric product selector

Installation Operation Maintenance

BUTTERFLY VALVE - WAFER FAF 3500

VALVES WITH SA ELECTRIC ACTUATOR

The ParaSeal range features a proven disc shaft and seat arrangement, to be used in high pressure and high velocity applications.

Operating manual Keula gate valves DN PN10/16

V5050A,B FLANGED LINEAR VALVE PN16 AND PN25/40

Pneumatic Shut-off Butterfly Valve Type 3335/BR 31a

Type / Material code Body* Disc Stem Lining**

Electric Actuated Butterfly Valves Ductile Iron Wafer Body ANSI/ASME 150 lb 2 to 6 inch Pipe

Tilting-disc Check Valves Short Body

Butterfly valves PN 16

The Belimo Butterfly Valves

SINGLE-ECCENTRIC BUTTERFLY VALVES TYPE L32.6

SINGLE-ECCENTRIC BUTTERFLY VALVES TYPE L32.6

KEYSTONE SERIES GR RESILIENT SEATED BUTTERFLY VALVES GRW/GRL (ISO)

V5050A,B FLANGED LINEAR VALVE PN16 AND PN25/40

Series A Electric Linear Actuators

ERHARD is a company of. Datasheet ERHARD ERK tilting-disc check valve

KEYSTONE SERIES GR RESILIENT SEATED BUTTERFLY VALVES GRW/GRL (ISO)

Valve Series V2001 Three-way Valve Type 3323

1 DESCRIPTION 2 WORKING PRINCIPLE 2.1 REGULATION ST

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

OPTIMAL VALVE SOLUTIONS PRODUCT PROGRAM

Operating Instructions ROCO Butterfly Valve with SKG Slider-crank Mechanism, with Electric Multi-turn Actuator

Butterfly valves PN6, PN10, PN16

ARI-STEVI 450 / 451 Pneumatic actuator ARI-DP 32-34T. Electric actuator ARI-PREMIO 2,2-25 kn ARI-PREMIO-Plus 2G 2,2-25 kn

20 to 150 mm 2-Way Automatic Flow Balancing Control Ball Valves

VALVE WITH SA ELECTRIC ACTUATOR

VG9000 Flanged Valves

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Two port valves. pneumatically actuated

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Butterfly valves PN 16

KEYSTONE SERIES GR RESILIENT SEATED BUTTERFLY VALVES GRW/GRL

Diaphragm Valve, Plastic

Butterfly valves Plastic and Metal

Gachot Ball Valve Type V16 carbon steel / reduced bore / DN 8 to DN 200

BUTTERFLY VALVE WAFER TYPE stainless steel 411 (41000) series PN40 For steam (fire safe versions) and 41001

Quarter turn actuators Index

MD15-C, MD15-HR, MD15-HE and MD15-DA Small Actuators for Rxx and RWxx Valves and Danfoss of the Series RA

ZONE CONTROLE / 2-WAY

ALC-3 BUTTERFLY VALVES NOMINAL PRESSURE NOMINAL SIZE MATERIALS CONNECTIONS DESIGN. ANSI Class PN DN

V Verafix Design Thera Design Edition - Lockshield Valve WITH HIGH QUALITY SURFACE FOR DESIGN RADIATORS

Transcription:

V5422L / V5422E CTUTED UTTERFLY VLVES SPECIFICTION DT FETURES With factory-mounted electric actuator Centric butterfly valve with elastomer liner Wide DN range (DN250 through DN400) For heating water containing up to 50% glycol Wafer body For modulating and floating control Maintenance-free control drive Mechanical setting indicator Manual adjustment wheel and declutch button mple reserve torque Sizable terminal compartment for cabling Long unit lifetime GENERL The V5422L and V5422E ctuated utterfly Valves are suitable for heating and cooling applications as well as in boiler management systems. They can also be employed for general services, water treatment, etc. The V5422L series is equipped with floating-control actuators (230 V, three-point). The V5422E series is equipped with modulating-control actuators with a standard control signal of 0...0 V (2...0 V, 0...20 m, and 4...20 m also possible). The actuators and valves are delivered factory-mounted. The position control and the end stops are completely justified. SPECIFICTIONS Valves Sizes Nominal pressure rating Shut-off pressure Tightness Temperature of medium ody DN250...DN400 PN0 0 bar bubble-tight -0...+95 C (DN250-300) +20 +95 C (DN350-400) Wafer, ductile iron GG25 Rilsan/epoxy-coated EPDM EW (max. 30 C) GGG40, epoxy-coated Liner Disc Shaft Stainless steel.4028 (ISI 420) ctuators Motor voltage 230 Vac (±0%), 50 to 60 Hz Current, running time See Table ngle of rotation 90 Duty cycles max. 30% (class S4 IEC60034) Running noise 65 d mbient temperature -20...+0 C Motor insulation class F according to VDE 0530 Protection class IP6 as per DIN 40050 Cable gland M20, cable 9...6 mm Copyright 200 Honeywell Inc. ll rights reserved EN0-039GE5 R00

Table. Type list for different valve sizes and corresponding data floating version modulating version actuator current () nominal start run time (sec) actuator torque (Nm) valve size (DN) Kvs (m 3 /h) weight (kg) V5422L006 V5422E00.2. 30 600 250 4800 39.2 V5422L04 V5422E09.2. 30 600 300 000 48 V5422L022 V5422E02 2.0 3.0 30 800 350 8300 60 V5422L030 V5422E035.2. 60 200 400 000 8 GENERL CHRCTERISTICS Position Indication and Running Status The actuator's position is indicated by a mechanical pointer located behind a window on the actuator's cover. The actuator's running status is indicated by three LED's located on the main PC: The green LED (Op) is lit when the valve has been opened. The red LED (Cl) is lit when the valve has been closed. ngle Limitation Manually djusting Valve The angle at the drive shaft can be adjusted to between 0 and 90. The end position is limited both electrically and mechanically. The electrical limitation can be adjusted by pressing and turning (with a screwdriver) the adjustment screws situated on the white and black cams. The end position is factory-set to -2 and +92. s a rule, it is not necessary to alter this value. CUTION efore manually adjusting the valve, you must first disconnect the power supply! The valve can be manually adjusted using the manual adjustment wheel and declutch button (see Fig. ). declutch button Fig.. Manual adjustment wheel and declutch button The manual safety wheel is disengaged automatically when the motor is running. To use the manual safety wheel, it must therefore first be re-engaged using the declutch button. Motor and Gear Protection The actuator motor is protected against overheating by a bimetal temperature monitor. The motor and gear train are also protected against mechanical overload by a torque limiter switch. The yellow LED (Tq) is lit when the torque limiter has been activated. Maintenance The actuators are maintenance-free. They are lubricated for a minimum of 00,000 operations. If it becomes necessary to renew the grease completely, use a lubricant complying with the following specifications: temperature range: -30...+35 C penetration: STM 265/295 at 25 C drop point: 80 C E.g. ELF Expecta 250, TOTL Multis EP2, SHELL alvania EP2, MOIL Mobilux EP2, or ESSO eacon EP2. EN0-039GE5 R00 2

Flow Rate and Pressure Drop 0 0 20 30 90 0 60 50 40 V5422L (Floating Control) The V5422L series is equipped with a main PC (see Fig. 3) located (together with the angle indicator) under the cover (see Fig. 4). To access the main PC, remove the cover. pressure drop (bar) 0. 0.0 2 8 6 8 4 9 feedback jacks Dead Pand Cl Op Tq Tr red/green/yellow LEDs microswitches Tr2 6 5 4 3 2 5 2 4 0 0 2 3 3 32 L N PE input Tr R2 R 2 26 4 40 2 3 3 power supply Fig. 3. Main PC of the V5422L Ful 0.00 angle indicator main printed circuit board 0.000 50000 feedback terminals flow (cubic meters per h) 0000 5000 000 500 00 50 400 350 250 300 20 0. 0.5 5 0 50 velocity (m/s) Fig. 4. Explosion view Fig. 2. Flow rate and valve pressure drop 3 EN0-039GE5 R00

Input Terminals n external floating controller controls the actuator of the V5422L. This controller transmits the phase to input 3 (for closing the valve) or to input 32 (for opening the valve). See also Fig. 2. Feedback Terminals The V5422L is equipped with two change-over switches (see Fig. 5): terminals 20, 2, and 22 (provides a feedback signal that the valve is in the OPEN position) and terminals 23, 24, and 25 (provides a feedback signal that the valve is in the CLOSED position). Fig. 5. Feedback terminals 20 2 22 23 24 25 NOTE: These change-over switches must be supplied with power from an independent (external) power source (maximum permissible load: 230 Vac, 6 ). V5422E (Modulating Control) The V5422E series is equipped with a main PC (see Fig. ) located (together with a feedback potentiometer and the angle indicator) under the cover (see Fig. 4). To access the main PC, remove the cover. P P2 offset adjustment 2 8 6 8 4 9 feedback jacks Dead and Cl Op Tq Tr microswitches 6 5 4 3 2 red/green analog /yellow LEDs input/output Tr2 5 2 4 0 Tr R2 R 2 26 4 40 2 3 3 0 2 3 3 32 L N PE power supply Fig.. Main PC of the V5422E djusting the V5422E for Modulating Control 2 Ful djusting the V5422L for Floating Control 2 6 5 4 3 2 ON Fig. 6. Default microswitch settings of the V5422L To adjust the V5422L for floating control, microswitches 5 and 6 (located on the main PC; see Fig. 3) must both be set to position "" (see Fig. 6). NOTE: In the case of the V5422L, microswitches, 2, 3, and 4 have no function/effect. djusting the Direction of Rotation of the V5422L To adjust the direction of rotation so that the V5422L closes in the clockwise (right) direction, microswitch must be set to position "". To set the direction of rotation so that the V5422L closes in the counterclockwise (left) direction, microswitch must be set to position "". 6 5 4 3 2 ON Fig. 8. Default microswitch settings of the V5422E To adjust the V5422E for modulating control, microswitches 5 and 6 (located on the main PC; see Fig. ) must both be set to position "" (see Fig. 8). djusting the Direction of Rotation of the V5422E To adjust the direction of rotation so that the V5422E closes in the clockwise (right) direction, microswitch must be set to position "". To set the direction of rotation so that the V5422E closes in the counterclockwise (left) direction, microswitch must be set to position "". See also section "Reversing Direction of Rotation of the V5422E". djusting the Input Signal Range of the V5422E The input signal range (0/2...0 V or 0/4...20 m) and the corresponding output signal are set using microswitches, 2, 3, and 4 (see Table 2). EN0-039GE5 R00 4

Table 2. djusting the input signal range (V5422E) Input signal output microswitch positions signal 2 3 4 5 6 * 0 0 V 0 0 V / 2 0 V 2 0 V / 4 20 m 4 20 m / 0 20 m 0 20 m / 0 0 V 0 20 m / 2 0 V 4 20 m / 4 20 m 2 0 V / 0 20 m 0 0 V / *Depends upon desired direction of rotation. Terminals for Input/Output Signals n external modulating controller controls the actuator of the V5422E by means of an analog signal provided at terminal 0/. n analog output signal for position indication is provided at terminal /2. djusting the Input/Output Signal Offset The offset of modulating actuators is adjusted at the factory and should not be changed. If you wish to change the offset (using offset potentiometer P2; see Fig. ), note that an excessively small offset will result in oscillation of the actuator. Reversing Direction of Rotation of the V5422E In the case of the V5422E, it is possible to reverse the direction of rotation of the valve by adjusting the feedback signals. The feedback signals are adjusted by resetting the microswitches and replugging the feedback potentiometer's cables. To do this, proceed as follows:. Turn the power off. 2. Reset the microswitches as shown in Table 2, but with microswitch in position. 3. Replug the feedback potentiometer's cables as shown in Fig. 9. Valve Mounting Install the actuated valve in the pipe according the following steps (see also Fig. 0).. Spread the valve's flanges to facilitate installation. The valve's disc must be partially open. 2. Set all stay-bolts while keeping the valve's disc slightly open and without tightening the nuts. 3. Open the valve's disc completely. Ensure that the piping is aligned. Tighten diagonally opposite the nuts until the flanges are in contact with the body of the valve. Never use gaskets or grease. Never weld the flanges after the valve has been installed. Step Step 2 Step 3 Fig. 0. Installing the valve olting Table 3 lists the number of bolts and nuts required for mounting. The number is dependent upon the size (DN). Table 3. olts and nuts required for installation DN PN0 bolts (M x length) number 250 M20x50 2 300 M20x60 2 350 M20x60 6 400 M24x90 6 length Fig. 9. Replugging the feedback potentiometer's cables 4. pply the desired control signal (0 V or 20 m, as the case may be) for the closing position. 5. Turn the power back on. 6. Using a small screwdriver, adjust the potentiometer P (located on the main PC; see Fig. ) until the valve closes completely. Fig.. olting 5 EN0-039GE5 R00

WIRING DIGRMS V5422L PE N L power supply: single-phase 230 Vac position indicator 32 3 open (counterclockwise) close (clockwise) E Fig. 2. Floating Control (V5422L) M20 PE N L V5422E power supply: single-phase 230 Vac Fig. 4. ctuated butterfly valve (side view) 0 2 Y = 0...0 V (2...0 V, 0/4...20 m) POS = 0...0 V (2...0 V, 0/4...20 m) D Fig. 3. Modulating Control (V5422E) C DIMENSIONS ctuator Dimensions and Weight Table 4. ctuator dimensions and weight valve size actuator dimensions (mm) weight (DN) C D E (kg) 250 509 69 35 89 300 509 69 35 89 350 509 69 35 89 400 564 2 4 33 6 30 Fig. 5. ctuated butterfly valve (top view) 2x M20 Fig. 6. ctuated butterfly valve (cross-sectional view) EN0-039GE5 R00 6

Valve Dimensions and Weight Table 5. Valve dimensions and weight valve size valve dimensions (mm) (DN) C D H weight (kg) 250 280 96 68 324 243.5 22.2 300 35 232 8 38 292.5 30.8 350 330 25 8 425 329.5 4.5 400 365 292 02 45 35.5 5.2 E H D C Fig.. Valve dimensions EN0-039GE5 R00

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du ois 3, Switzerland by its uthorized Representative: utomation and Control Solutions Honeywell GmbH öblinger Straβe D-0 Schönaich Phone: (49) 03 630 Fax: (49) 03 63493 http://europe.hbc.honeywell.com Subject to change without notice. Printed in Germany EN0-039GE5 R00