Overvoltage Suppression F7 Drive Software Technical Manual

Similar documents
YASKAWA AC Drive - A1000 Overvoltage Suppression Custom Software Supplement

Technical Information

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C

TRIPS AND FAULT FINDING

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide

Application Note: SyMAX Permanent Magnet Motor Simple Startup Procedure

Description 1/8-7.5HP

List of Tables: Page # Table 1: Emerson Commander SK VFD parameter settings 2. Table 2: Allen Bradly Power Flex 4M VFD parameter settings 3

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V

VFD E Series. Features

Addendum to Instruction Manual GP10 and VG10

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Troubleshooting. YASKAWA ELECTRIC SIEP C D YASKAWA AC Drive A1000 Technical Manual 301

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED

RVS-DN Digital Reduced Voltage Motor Starter

J1000 D E F I 1000 J1000 J1000 J1000 J1000

Quick Reference Guide. For NFX9000 Adjustable Frequency Drives. February 2006 NQ00. MN E February 2006

Standard Drives A & D SD Application Note

MCW Application Notes 24 th August 2017

Quick Start Guide of CV50- ControlVIT Series

Technical Explanation for Inverters

CRANE FUNCTION MANUAL. FR-A (0.4K) to 04750(90K)-CRN FR-A (0.4K) to 06830(280K)-CRN FR-A (315K) to 12120(500K)-CRN

SMS PRODUCT CATALOGUE

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.

ADJUSTABLE FREQUENCY CRANE CONTROLS

Motor parameters setting. Motor Control Parameters. These motor parameters below are needed to set:

RM B. Features. Drive Model Number Scheme. A RM6 Product Series

YASKAWA AC Drive A1000

CPW Current Programmed Winder for the 890. Application Handbook. Copyright 2005 by Parker SSD Drives, Inc.

YASKAWA AC Drive High Performance Vector Control A1000

V1000. Inverter Series.

V1000 Inverter Series

AC drive has detected too high a Check loading

Experience & Innovation

YASKAWA AC Drive High Performance Vector Control A1000

YASKAWA AC Drive High Performance Vector Control A1000

YASKAWA AC Drive High Performance Vector Control A1000

DYNEO Synchronous motors with permanent magnets-drive Commissioning

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

BLDPN30001 Series. 30A Brushless DC Controller. User s Guide E. Landon Drive Anaheim, CA

MAGPOWR Spyder-Plus-S1 Tension Control

V1000. YASKAWA AC Drive Compact Vector Control Drive

USERS MANUAL MCD REMOTE OPERATOR

Application Note CTAN #234

V1000. YASKAWA AC Drive. Compact Vector Control Drive

USER INSTRUCTION FOR PROGRAMMING INVERTER FUJI FRENIC LIFT

LIFT INVERTER SERIES L1000A

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

SDC,Inc. SCR-Regenerative Ac Drive

Vission 20/20 micro-controller. Operation and service manual

Kelly HPM High Power Full Bridge Permanent Magnet DC Motor Controller User s Manual

RVS-DX Digital Reduced Voltage Motor Starter

DE ES A A. For Modernisation and New Installation L1000A L1000A L1000A

MX1S Matrix Converter

J1000. Compact Inverter Series.

VFD - Mitsubishi. VFD Manuals. Mitsubishi D700 VFD Installation. Mitsubishi FR-D700 VFD User Manual. Mitsubishi D700 Parallel Braking Resistors

5.1 Errors (Alarms) Error (alarm) definitions PROTECTIVE FUNCTIONS. (1) Major faults

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II

ALTIVAR 58 AC Drives

INSTRUCTION MANUAL DIGITRAC % 2 DIGITAL TENSION READOUT AND CONTROL

Mitsubishi. VFD Manuals

YASKAWA AC Drive A1000

Kelly KDHA High Voltage Series/PM Motor Controller User s Manual

Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB

Automatic control. of the doors. 99 VF Evolution

Setup Tabs. Basic Setup: Advanced Setup:

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

SYSDrive Frequency Inverter

Large Drive. Variable Speed Control is Just the Beginning. Franklin FastApp Firmware. Variable Speed Control NEMA. Standard Features (Enclosed Drives)

MDC Series

Sensorless Vector Drives

Vission 20/20 micro-controller. Operation and service manual Version 2.6

Super Calendar. Heated rolls

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

Kelly KDC Series/PM Motor Controller User s Manual

VLT AutomationDrive for marine winch applications

5001TCP SPEED CONTROLLER

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Small Full Bridge Permanent Magnet Motor DC Controller User Manual

A V Class: ½ to 175 HP 480V Class: ½ to 1000 HP 600V Class: ½ to 250 HP

SINAMICS GM150 IGCT version

YASKAWA AC Drive Compact V/f Control Drive J1000

YASKAWA AC Drive V1000. YASKAWA AC Drive V1000

CTi Automation - Phone: Fax: Web:

Full Bridge Permanent Magnet DC Motor Controller User's Manual

2006trans13_b.doc ACCEPTABLE OPERATING RANGE AND RATIONALITY SENSED PARAMETER FAULT CODE PRIMARY MALF DETECTION PARAMETERS

Standard VVMC-1000 or VFMC-1000 controls, dispatched by an M3 Group System, allow group configurations with 64 landings and as many as 12 cars.

REGAL-BELOIT SpinMaster AC Adjustable Speed Drives

5001TCP SPEED CONTROLLER

PowerFlex AC Drives Portfolio

VSD Series II Variable Speed Micro Drives

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

NEW! Complete IMPULSE Control Panels Available

INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00

The IMPULSE Series 2 Crane Controls are ideal for use with inexpensive, NEMA A or B single-speed, squirrel cage induction motors.

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

Transcription:

Overvoltage Suppression F7 Drive Software Technical Manual Software Number: VSF11015X, Drive Models: CIMR-F7UXXXXXX-062, CIMR-F7U40750F-145. Document Number: TM.F7SW.062, Date: 09/17/2010, Rev: 10-09

This document is intended to provide proper installation and use of the Yaskawa drive with custom software. This document is a supplement to the standard drive technical manual. It describes the effects on the drive parameters and functions with the software installed. Read and understand this document and the standard drive technical manuals before attempting to install, adjust, operate, inspect or maintain the drive. Observe all cautions and warnings in this document and the standard drive technical manuals. Custom software is written to add functionality to a standard AC drive to enhance or enable use in a specific application. The software is loaded to the flash ROM area of the control board, and replaces the standard drive software. Custom software can add new functions, modify standard functions, or even inhibit standard functions. It can be used to modify display text or parameter names. Custom software is usually loaded to the drive before delivery. The control board and drive nameplate are assigned unique part numbers and the software is registered, archived, and retrievable. When seeking support for a drive with custom software, it is imperative to provide the unique part number shown on the drive nameplate. The software has been flashed to the control board memory and the operation of parameters, functions, and monitors are different than the standard drive software, as described herein. 1.0 Overview This Overvoltage Suppression software allows an F7 drive to control rotating machinery where part of the machine s cycle creates a cyclic regenerative (over-hauling) load. The Pump Jack Oil Well and Stamping/Punch Press are two applications that this software was specifically created for. The benefit of this software it that dynamic braking resistors are not required for normal operation. This software monitors the torque-producing current (Iq) in the motor, and regulates this against an Iq setpoint using a PI controller. If the torque producing current falls below the setpoint, the output frequency is increased to force a higher (positive) Iq and thus avoid a regenerative condition in the motor. Flywheel Motor / Gear Box Clutched Cam F7 Stamping Press Application 2.0 Changes from Standard Product a. The Ramp to Stop stopping method (B1-03 = 0) is deleted. b. Several parameter defaults have changed. See section 4.5. c. The Stationary auto-tuning method (T1-01 = 1) will not set E2-02 (Rated Slip) and E2-03 (No-load Current). Therefore, these parameters must be manually set using the motor s nameplate data. See Section 5.2. Date: 09/17/2010, Rev: 09-2010 Page 2 of 9 TM.F7SW.062

3.0 Limitations a. V/Hz and Open Loop Vector are the only control modes (A1-02 = 0 or 2) that support the Overvoltage Suppression function. Closed Loop V/F and Closed Loop Vector are available (A1-02 = 1 or 3) but the Overvoltage Suppression function is disabled. b. Bi-directional Speed Search. For some applications, when motor loading is extremely light at startup, it may be necessary to disable the bi-directional speed search feature by setting parameter B3-14 = 0. 4.0 Related Parameters and Functions 4.1 Overvoltage Suppression PI Controller Parameters Parameter Number Modbus Address Parameter Name Digital Operator Display Description Range Default Change During Run Access Level *1 P1-01 0600H P1-02 0601H P1-03 0602H P1-04 0603H P1-05 0604H P1-06 0605H OV Suppression PI Setpoint OV Reg Setpoint *2 OV Suppression Proportional Gain OV Reg Gain *2 OV Suppression Integral Time OV Reg I Time *2 OV Suppression Positive Integral Limit OV Reg I Limit OV Suppression Positive Overall Limit OV Reg Limit Motor Torque Producing Current (Iq) Feedback Filter Time Feedback Filter *2 This parameter sets the OV Suppression PI setpoint in percent of motor torqueproducing current (Iq). Note: 100 Iq = 100 motor rated torque. This parameter sets the gain of the OV Suppression PI controller. This determines the responsiveness of the Iq regulator. A larger setting equals more responsiveness. This parameter sets the integral time of the OV Suppression PI controller. This determines the responsiveness of the Iq regulator. A smaller setting equals more responsiveness. This parameter sets the positive limit of the integrator in the OV Suppression PI controller. Note: 100 = Fmax (E1-04). This parameter sets the positive limit of the OV Suppression PI controller (P+I). Note: 100 = Fmax (E1-04). Note: A setting of 0.0 disables the OV Suppression PI controller. This parameter sets the 1 st order filter time of the motor torque-producing current feedback. A larger setting equals a more filtered feedback but less responsiveness. -10 100.0 0.00 ~ 25.00 0.00 ~ 160.00 sec 100.0 100.0 5 ~ 10000 msec 12.0 Yes A 2.20 Yes A 0.10 Yes A 100.0 No A 100.0 No A 100 Yes A *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. V/F and Open Loop Vector only. Date: 09/17/2010, Rev: 09-2010 Page 3 of 9 TM.F7SW.062

4.2 Pumpjack Application Specific Parameters Parameter Number Modbus Address Parameter Name Digital Operator Display Description Range Default Change During Run Access Level *1 P1-07 0606H P1-08 0607H P2-01 060AH P2-02 060BH OV Regulator Gain Frequency Gain Frequency *2 OV Regulator Gain Multiplier Gain Multiplier *2 Heatsink Overheat Off -Delay Time OH Off Delay Heatsink Overheat Speed Reduction OH Spd Reduce This parameter sets the OV regulator gain change endpoint. See section 5.3 for details on this function. This parameter sets gain multiplier for the OV regulator gain (P1-02) based on output frequency. See section 5.3 for details on this function. This parameter sets the amount of time that the drive will revert to a reduced speed after an Overheat Pre-alarm occurs. See section 5.5 for details. This parameter sets the multiplier used to reduce the frequency reference after an Overheat Prealarm occurs. See section 5.5 for details. 0.00 ~ 400.00 Hz 1.000 ~ 10.000 30.0 min 100.0 90.0 0 1.30 0 Yes Yes A A 0.0 No A 100. 0 No A P2-03 060CH Belt Break Detection Belt Break Det. Note: 100 = Fmax (E1-04) This parameter configures the Belt Break Detection function. If the drive s soft starter is at maximum output frequency (E1-04) for more than 30 seconds, a belt-break fault (B-BRK) will occur. See section 5.4 for details. 0 ~ 1 1 No A 0: Disabled 1: Enabled This parameter determines the Torque Limit During forward and reverse motoring P3-01 0614H Start torque limits after a run command 0 ~ 300 200 is received, but before the torque No A Start Torque start timer (P3-02) expires. Overwrites L7-01 and L7-02. P3-02 0615H Torque Limit During This parameter sets the time that Start Timer parameter P3-01 will overwrite L7-01 and L7-02 after a run command 10.0 Start Torq Time is received. sec 0.0 No A This parameter sets the time required to ramp the torque limit Torque Limit During 100. This determines the rate at 0.1 ~ Start Ramp Time P3-03 0616H which the torque limits will return to 10.0 1.0 No A Torq Lim Ramp Tm the L7-01 and L7-02 values at the sec end of the starting torque time (P3-02). *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. V/F and Open Loop Vector only. *2: Making large changes in these settings while the drive is running can result in large and very rapid changes in the output frequency. Change these parameters in small increments only. Date: 09/17/2010, Rev: 09-2010 Page 4 of 9 TM.F7SW.062

4.3 Monitors (U1-XX) Monitor Number Modbus Address Monitor Name Digital Operator Display Description Scaling for Multifunction Analog Output (H4-01/H4-04) Unit Access Level *1 U1-90 0720H U1-91 0721H U1-92 0722H Soft Start Frequency Reference Soft Start Freq Overvoltage Frequency Reference OV Reg Total Ref Overvoltage Suppression Regulator Error Signal OV Reg Error Overvoltage Suppression Regulator Output Displays the frequency reference after the soft starter, but before the OV Regulator PI controller output. Displays the frequency reference after the output of the OV Regulator PI controller. Displays the error (setpoint - feedback) of the OV Regulator PI controller. 100 = Fmax (E1-04) 100 = Fmax (E1-04) 100 = Motor Rated Torque (Iq) Displays the output of 100 = 0.1 U1-93 0723H the OV Regulator PI Fmax (E1-04) controller. OV Reg Output *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. V/F and Open Loop Vector only. 4.4 Faults Fault Display Description Cause Countermeasures 0.01 Hz 0.01 Hz 0.1 Q Q Q Q B-BRK Belt Break The drive s output frequency was at the maximum output frequency (E1-04) for more than 30 seconds. See section 6.3 for details. Fix belt / coupling. 4.5 Alarms Alarm Display Description Cause Countermeasures OTDLY Overtemp Delay Over-temperature Delay The drive s heat sink temperature exceeded parameter L8-02 (Overheat Pre-alarm Level) and then fell below the L8-02 level within the P2-01 time. This alarm will flash until the P2-01 timer has expired. See section 6.4 for details. Decrease the drive heat sink temperature. Check the drive s cooling fans. Check the sizing of the drive s enclosure. Date: 09/17/2010, Rev: 09-2010 Page 5 of 9 TM.F7SW.062

4.6 Parameter Default Changes Parameter Name Description Units Range Default A1-02 Control Method 0: V/F 1: V/F w/pg 2: Open Loop Vector 3: Flux Vector Note: The OV Suppression function is only available in V/F and Open Loop Vector (A1-02 = 0 or 2). - 0 ~ 3 0 B1-03 Stopping Method 0: Ramp to Stop 1: Coast to Stop 2: DC Injection to Stop 3: Coast to Stop With Timer - 1 ~ 3 1 E1-04 Maximum Output Frequency Maximum frequency that the drive will output. *3: The 90.0 Hz default setting only applies when E1-03 = F (Custom V/f Pattern). 0.1 Hz 5 400.0 90.0 *3 NOTE: The Overvoltage Suppression feature works best in Open Loop Vector (A1-02 = 2), only AFTER a full Rotational auto-tune is performed (T1-01 = 0). If a Rotational auto-tune cannot be performed, a Stationary auto-tune can be performed (T1-01 = 1). You must manually set E2-02 (Rated Slip) and E2-03 (No-load Current) from the motor s nameplate data before running the auto-tune as the Stationary autotuning method will not tune these parameters in this software. If performance is not achieved after the Stationary auto-tune, use the V/F control mode (A1-02 = 0) instead. See Section 5.2 for further details. CAUTION: The Overvoltage Suppression function is NOT active when the output frequency is at the maximum output frequency (E1-04). This is because the function needs frequency headroom to work. CAUTION: The motor / machinery connected to an F7 drive with this software needs to be mechanically capable of operation at the maximum output frequency (E1-04). CAUTION: Bi-directional Speed Search. If motor loading is extremely light at startup, it may be necessary to disable the bi-directional speed search feature by setting parameter B3-14 = 0. Not doing so may result in the motor accelerating in the wrong direction. 5.0 Function Description 5.1 Overvoltage Regulator The motor torque-producing current is detected and subtracted from the OV Regulator setpoint (P1-01). The result (error) is run through the OV Regulator PI controller. The PI controller will add frequency to the frequency reference in order to maintain a constant Iq setpoint. The PI controller will NOT subtract frequency from the frequency reference. This is done to keep the torque producing current positive (motoring) thus preventing regeneration and subsequent overvoltage faults (OV). This eliminates the need for a dynamic braking resistor package. Date: 09/17/2010, Rev: 09-2010 Page 6 of 9 TM.F7SW.062

5.2 Open Loop Vector Control In order to obtain optimal performance when using the Open Loop Vector control method (A1-02 = 2), a motor auto-tune should be performed. Ideally, the motor should be uncoupled from the load, and a Rotational auto-tune (T1-01 = 0) should be performed. If the motor cannot be uncoupled from the load, then a Stationary auto-tune (T1-01 = 1) should be performed. In the this software, Motor Rated Slip and Motor No-Load Current are not calculated in the Stationary auto-tuning method. Therefore, these need to be calculated and manually entered prior to running the Stationary auto-tune. After entering the E2-02 and E2-03 values, perform the auto-tune. Motor Rated Slip (E2-02) should be calculated as follows: Example: 4-pole, 60 Hz motor, Motor Rated Speed = 1730 RPM E2-02 = (Motor Synchronous Speed - Motor Rated Speed) * Motor Poles / 120 E2-02 = (1800RPM - 1730RPM) * 4 / 120 E2-02 = 2.33 Hz Motor No-Load Current (E2-03) can sometimes be read directly off of the motor nameplate; it is often listed as NLA (no-load amps). If there is no listing on the nameplate, motor no-load current can be estimated as follows: Motor full load current (FLA) * 35. Example: 4-pole, 60 Hz motor, Motor FLA = 60 Amps. E2-03 = 60 Amps * 35 E2-03 = 21 Amps. 5.3 OV Regulator Gain Increase Parameters P1-07 (OV Regulator Gain Frequency) and P1-08 (OV Regulator Gain Multiplier) automatically increase the overvoltage suppression regulator gain (P1-02) when the drive s output is above the motor base frequency (E1-06). This is sometimes necessary to compensate for the motor s reduced torque characteristics above its base speed (otherwise known as the constant horsepower or field weakening area). Shown below is an example when E1-04 = 150Hz, E1-06 = 60Hz, P1-02 = 1.00, P1-07 = 90.00 Hz, and P1-08 = 2.000. Figure 2: OV Regulator Gain Multiplier Above Motor Base Speed Date: 09/17/2010, Rev: 09-2010 Page 7 of 9 TM.F7SW.062

5.4 Belt Break Detection If the drive s output frequency is at maximum frequency for more than 30 continuous seconds, the drive will assume that the belt or coupling between the motor and the machinery has become disconnected. The drive will fault on a belt-break fault (B-BRK), energize the fault contacts (MA, MB, and MC), and coast to stop. 5.5 Heatsink Over-temperature Speed Reduction If the heatsink temperature exceeds L8-02 (Overheat Pre-alarm Level), the drive s frequency reference will automatically be reduced by the percentage set in parameter P2-02. This is done to prevent an Overheat Fault (OH) by reducing the machine speed and thus it s loading on the drive. The drive will remain at this frequency for the time set in parameter P2-01. While the heatsink temperature is above L8-02, an OH - Heatsnk Overtemp alarm will flash. If the temperature drops below the L8-02 level and before the P2-01 timer expires, OTDLY - Overtemp Delay will flash on the keypad. When the P2-01 timer expires, the drive will accelerate back to its normal frequency reference. If the temperature increases back above the L8-02 setting before P2-01 has expired, the timer will be reset. 5.6 Motoring Torque Limits at Start When a run command is first issued, the drive will internally use parameter P3-01 as both the forward and the reverse motoring torque limit, for the time specified in parameter P3-02. When the P3-02 time expires, the torque limit ramps back to the L7-01 & L7-02 values, at a rate determined by parameter P3-03. The time set into parameter P3-03 represents a torque limit change of 100. P3-02 can be more than, less than, or the same as L7-01 or L7-02. Example: If P3-01 = 200, L7-01 = 50, and P3-03 = 2.0 seconds, the torque limit ramp time would be calculated as follows: Torque Limit = P3-01 L7-01 = 200-50 = 150 Ramp Time = Torque Limit * P3-03 / 100 = (150 * 2.0) / 100 = 3.0 seconds Ramp Time = 3.0 seconds. Figure 3: Motoring Torque Limit at Start Date: 09/17/2010, Rev: 09-2010 Page 8 of 9 TM.F7SW.062

6.0 Block Diagram Date: 09/17/2010, Rev: 09-2010 Page 9 of 9 TM.F7SW.062