The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Similar documents
New York Science Journal 2017;10(3)

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

Analysis of Grid Connected Solar Farm in ETAP Software

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

Performance Analysis of Transient Stability on a Power System Network

Simulation of Voltage Stability Analysis in Induction Machine

Targeted Application of STATCOM Technology in the Distribution Zone

Grid Stability Analysis for High Penetration Solar Photovoltaics

OPTIMUM ALLOCATION OF DISTRIBUTED GENERATION BY LOAD FLOW ANALYSIS METHOD: A CASE STUDY

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

DISTRIBUTED GENERATION FROM SMALL HYDRO PLANTS. A CASE STUDY OF THE IMPACTS ON THE POWER DISTRIBUTION NETWORK.

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Behaviour of battery energy storage system with PV

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Power Conditioning of Microgrids and Co-Generation Systems

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

Voltage Index Method for Optimal Allocation of DG Units in a Distribution system to improve the Voltage Stability Margin

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

PSNH INTERCONNECTION REQUEST

Induction Generator: Excitation & Voltage Regulation

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

Simulation Modeling and Control of Hybrid Ac/Dc Microgrid

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

PV Grid Integration Research in the U.S.

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Modeling and Comparison of Dynamics of AC and DC Coupled Remote Hybrid Power Systems

Generation Capacity Design for a Microgrid for Measurable Power Quality Indexes

Intelligent Control Algorithm for Distributed Battery Energy Storage Systems

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

Laboratory Tests, Modeling and the Study of a Small Doubly-Fed Induction Generator (DFIG) in Autonomous and Grid-Connected Scenarios

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

ABB POWER SYSTEMS CONSULTING

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

Network Reconfiguration for Loss Reduction and Voltage Profile Improvement of 110-Bus Radial Distribution System Using Exhaustive Search Techniques

Solar Photovoltaic Inverter Current Distribution during Fault on Distribution and Transmission System

Control Application of PV Solar Farm as PV- STATCOM for Reactive Power Compensation during Day and Night in a Transmission Network

Optimal Placement of Distributed Generation for Voltage Stability Improvement and Loss Reduction in Distribution Network

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

United Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Power Management with Solar PV in Grid-connected and Stand-alone Modes

Power Quality Improvement Using Statcom in Ieee 30 Bus System

Design and Simulation of Grid Connected PV System

INTELLIGENT DC MICROGRID WITH SMART GRID COMMUNICATIONS: CONTROL STRATEGY CONSIDERATION AND DESIGN

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

UNC-Charlotte's Power Engineering Teaching lab

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Renewable Grid Integration Research in the U.S.

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Control System and Performance of DC Micro grid under Various Loads

Available online at ScienceDirect. Procedia Technology 25 (2016 )

Review paper on Fault analysis and its Limiting Techniques.

Case No. 5 Sequential Motor Dynamic Acceleration Simulation ETAP TS V&V Case Number TCS-TS-181

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

SIMULTANEOUS CONTROL OF VOLTAGE AND POWER OF MICRO-TURBINE IN DISTRIBUTION NETWORK

COMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

Implementation of FC-TCR for Reactive Power Control

Comments on the Solar Alliance Proposal for Changes to New Jersey Interconnection Rules

Ancillary Services & Essential Reliability Services

ECEN 667 Power System Stability Lecture 19: Load Models

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Impact of Photovoltaic Power Plant on the Transient Stability Compared With Synchronous Generator.

By: Ibrahim Anwar Ibrahim Ihsan Abd Alfattah Omareya. The supervisor: Dr. Maher Khammash

Power Flow Study and Voltage Stability Analysis for Radial System with Distributed Generation

CASE STUDY OF POWER QUALITY IMPROVEMENT IN DISTRIBUTION NETWORK USING RENEWABLE ENERGY SYSTEM

Characterization of Voltage Rise Issue due to Distributed Solar PV Penetration

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

Solar Development in New Jersey, and PV Impacts on the Distribution System Carnegie Mellon Conference on the Electricity Industry - March 9, 2011

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

Reactive Power Sharing Droop Control Strategy for DG Units in an Islanded Microgrid

Anupam *1, Prof. S.U Kulkarni 2 1 ABSTRACT I. INTRODUCTION II. MODELLING OF WIND SPEED

Building a Friendly Environment for Renewable Energy Resources by Upgrading Primary Feeders from Normally Closed Loop to Mesh Arrangement

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Implementation SVC and TCSC to Improvement the Efficacy of Diyala Electric Network (132 kv).

A Novel Distribution System Power Flow Algorithm using Forward Backward Matrix Method

Analysis of Low Tension Agricultural Distribution Systems

Workshop on Grid Integration of Variable Renewable Energy: Part 1

Power Losses Estimation in Distribution Network (IEEE-69bus) with Distributed Generation Using Second Order Power Flow Sensitivity Method

LOAD SHARING WITH PARALLEL INVERTERS FOR INDUCTION MOTOR DRIVE APPLICATION

Computer Aided Transient Stability Analysis

Real-Time Simulation of A Modular Multilevel Converter Based Hybrid Energy Storage System

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Distribution System Analysis for Smart Grid

POWER FLOW SIMULATION AND ANALYSIS

Transcription:

International Journal of Engineering Works Kambohwell Publisher Enterprises Vol., Issue 1, PP. 99-103, Dec. 015 www.kwpublisher.com The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan Abstract Distributed Generation is gaining popularity with the recent advancements in the renewable energy sources. DGs are used as a source of energy as well as performance enhancers by utilities. Subject to the weather of a certain location different DG sources are used in which Wind Turbines, Small Hydro Plants, Photovoltaic and Fuel Cells are commonly used. In this research work, a detailed comparative analysis is made among Wind Turbine, Photovoltaic and Synchronous machine to suggest the most suitable source. The said comparison is made on the technical factors such as voltage and electrical power losses and on the basis of this comparison a suitable DG source is suggested. A radial distribution feeder is simulated in Electrical Transient Analyzer Program (ETAP) to study the effect of these sources on the test distribution network. Keywords Disributed generation, Voltage profile improvement, Electrical power losses, Synchronous and Induction Machines, Photovoltaic Nomenclature SG= Synchronous Generation WTG= Wind Turbine Generator PV= Photovoltaic DG= Distributed Generation RctPow= Reactive Power I. INTRODUCTION The power system is divided into three main categories; electrical generation, transmission and distribution. Each one of these is run by a different owner. Out of these three; distribution system is a more complex and costly, interms of providing electricity to the far ended rural areas. In a radial distributive system, voltage regulation is a difficult task to achieve as the voltage fluctuation can be of ± 10% [1]. DGs have many positive aspects on the system like decrease in line losses and voltage profile improvement []. DG can be classified into five major categories depending on the amount 1 Bahria University, Department of Electrical Engineering, Shangrila Road, Islamabad, Pakistan, mwaqas050@gmail.com, +9333935119 CECOS University, Department of Electrical Engineering, Hayatabad, Peshawar, Pakistan, zmarrakwali13@gmail.com, +93349186780 of contribution of active and reactive power to the system [3]. Category 1: power. Category : Category 3: Category 4: Injection of both the Real and Reactive Injection of Real and absorption of Reactive power. Only Real power injection. Only Reactive power absorption. DG units that are based on synchronous machine (cogeneration, gas turbine, etc.) falls in Category 1. Category mainly covers induction generators that are used in wind farms. Photovoltaic, micro turbines and fuel cells lies in category 3. Category 4 covers synchronous compensators and gas turbines [3]. As the impact of these sources is different from one another, so it is important to analyze each one separately. This research work concentrates on different results obtained from simulation performed on the DG interconnection scenarios and also on technical factors. The principal factors analyzed in this research work are voltage profile and electrical power losses of a network. These results will be useful for power distribution companies to select the most desirable type of a DG source to improve the voltage profile and to tackle electrical power loss, considering the main characteristics of the distribution network. This particular paper is organized in four sections. Section II addresses system configuration. The test system is discussed in Section III. Simulation results of voltage profile and electrical losses of the system are discussed in Section IV and V respectively. While conclusion of this research work is discussed in Section VI. II. SYSTEM CONFIGURATION Network components in this paper are represented by three phase models. For the analysis of voltage profile and power losses Newton-Raphson iteration is applied in ETAP. This iteration method uses (1) to calculate load flow [4]. Copyright 014 KWP Journals. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

= (1) Where P and Q are the real and reactive powers of the system buses, V and Z are the bus voltage magnitude and angle vectors respectively. While J 1, J, J 3 and J 4 are the elements of the Jacobin matrix. 11kV radially distributive feeder is selected which supplies power to five buses (from bus to bus 7) having a total of six distribution points. System under consideration is a balanced system. 3-phase 3-wire overhead cables are used to connect these distribution points. Size of the cables are selected per load requirement with a % drop in them. Real time data of electrical parameters is feed to the simulation software. This feeder powers seven distribution transformers of 11/0.4kV rating and lumped loads are connected to each of it. ETAP version 1.6 is used for simulation purposes. Transformer ratings at the test feeder buses is given in Table I. A. Synchronous Generator The synchronous generator installed as a DG source is a steam type generator with ratings of 1.5MW, 11kV, 1.765 MVA operating at 1500 rpm. It is a 4 pole machine with a power factor of 85% and a full load current (FLA) of 9.6A. The rotor type is Round-Rotor while the excitation method used is Thyristor Self- Excitation. It is used in voltage control mode and is solidly grounded. B. Induction Generator The induction generator installed as a DG source is a wind turbine. Ratings of induction generator are 1.5MW, 11kV, 1.765 MVA operating at 1500 rpm. It is a 4 pole machine with a power factor of 85% and a full load current (FLA) of 9.6A. Average wind speed is 15 m/s while the cut-in and cut-out speed of the turbine are 4 and 5 m/s respectively. It is openly grounded and the reactive power required for induction generator is absorbed from the system. C. Photovoltaic In this paper, the modeled PV array is manufactured by Moser Baer Solar. It is a Poly- Crystalline model with 0.9W rated power. Maximum peak voltage is 9.61V with 36.1V open circuit voltage. Maximum power of an individual panel is 7.46A while aximum peak power (MPP) of 1500.06 kw is obtained from a combination of 16 panels in series and 159 in parallel. The module efficiency is 13.4% while the calculated solar irradiance is 367W/m. outage durations. The test feeder is carefully designed on the basis of actual data collected from the grid station and from field surveys. number 7 is excluded from the simulation. Figure 1 shows the single line diagram of the test feeder. B. DG Interconnection Scenarios In order to verify the effects of PV, synchronous and induction machines on the test system, the following scenarios are modeled with three different combinations: 1. In this case no DG unit is connected and the results obtained from this will be used as a base for comparison of different DG sources.. 1.5MW synchronous generator is connected to the system in the following scenario. b) Then the DG unit connected at bus 6. 3. 1.5MW induction machine (Wind Turbine Generator) is connected to the system in the following scenario. b) Then the DG unit is connected at bus 6. 4. 1.5MW PV module is connected to the system in the following scenario. TABLE I. b) Then the DG unit is connected at bus 6. ID RATINGS OF TEST FEEDER TRANSFOMERS Transformer Ratings (kva) At bus 50 At bus 3 100 At bus 4 100 At bus 5 100 At bus 6 00 At bus 7 1000 III. PROPOSED SYSTEM STUDIES A. Description of the Test Feeder Careful consideration is required in the analysis of a certain DG source because each DG source has a certain unique impact on the performance of a Network. A feeder from Cant Grid Station located in Peshawar, Pakistan is selected for simulation because of the higher line losses and longer power

TABLE II. VOLTAGE PROFILE OF ALL ES WITH AND WITHOUT DG(S) IN KV No No DG SG at SG at 6 WTG at WTG at 6 PV at PV at 6 10.93 10.99 10.98 10.97 10.97 10.97 10.97 3 10.81 10.87 10.95 10.86 10.95 10.86 10.95 4 10.7 10.78 11.01 10.77 10.96 10.74 10.96 5 10.67 10.7 11.07 10.71 10.99 10.71 11.01 6 10.64 10.69 11.15 10.68 11.06 10.68 11.07 Figure 1. Test System IV. IMPACT OF DG ON VOLTAGE PROFILE Voltage stability analysis has been done using different techniques such as static and dynamic methods. The static technique can be analyzed by using the relation between the receiving power and the voltage at a certain point in a system [5]. The injection of a certain DG unit in a distribution system can enhance or decrease the voltage profile of the system depending on their operation at unity, leading or lagging power factors [6]. Voltage drop occurs due to the impedance of a certain component. The voltage drop varies with the injection of a certain DG unit. Table II shows the bus voltages for all the buses with and without the impact of DG; with DG units installed only on bus and 6 respectively. Figure. Voltage profile of all buses with Synchronous Machine. When no DG unit was connected in first case, voltage drops were increasing towards the final load point, because of the radial structure of the test system. This is shown in the figures, 3 and 4 respectively. The effects of SG, WT and PV on the voltage profile of the buses are also shown in the figures, 3 and 4 respectively. The source voltage of the test circuit is 11kV. With the injection of a DG unit, voltage levels of the system buses varies; subject to the type, size and location of the DG unit. 13 kv Power grid is considered as a source for the test system. All the DG units connected to the test feeders are synchronized with the system having same terminal voltage at point of common coupling. Figure 3. Voltage profile of all buses with Induction Machine

TABLE IV. EFFECT OF DGS ON LOSSES (REACTIVE) OF THE SYSTEM IN KVAR Number Before DG With SG With WTG With PV 54.4 41.5 53 45 Figure 4. Voltage profile of all buses with PV 6 54.4 5.5 90.3 8.6 V. IMPACT OF DG ON POWER LOSSES DG units may increase or decrease grid losses depending on their nature and the installed capacity [7]. The transmission of active and reactive power via overhead lines, underground cables and transformers gives rise to power losses. Insertion of a certain DG unit nearer to the consumers might have a positive or a negative effect on the system losses. In a purely loaded networks a DG unit of smaller size is likely to decrease the losses, provided both load and generation are located on the same feeder [8]. Different simulation results obtained from this research work reflects the impact of DG units on the system s active as well as the reactive power losses. Losses of all the lines in different scenarios are given in table III and IV respectively. Figure 5 shows that the active power losses are decreasing with all the DG sources installed at bus. However when they were placed at bus 6, losses of the system increased significantly with WT compared to the SG and PV; as both the sources are indicating a decrease in active power of the system. On the other hand, figure 6 shows that the reactive power losses are decreasing with all the DG units installed at bus. With the DG units at bus 6 reactive power losses have minimized in the case of SG as well as with PV in comparison with DG units at bus, however with WT at bus 6 the said losses have increased significantly. Figure 5. Effect of DGs on Active power TABLE III. EFFECT OF DGS ON LOSSES (ACTIVE) OF THE SYSTEM IN KW Number Before DG With SG With WTG With PV Figure 6. Effect of DG on Reactive Power 56 53. 55.6 54 6 56 49. 6.3 50 Some losses also occur in distribution transformers of rating 11/0.4 kv and cables which supplies power to 11kV loads directly. A % drop in cables is considered for simulation

purposes, which is also the default rating of ETAP though these losses remain constant for all the test scenarios. Results clearly show that the power losses can be altered with a certain DG source in a radial distribution system but that purely depends on the generating capacity and nature of DG unit as well as its location in the system. VI. CONCLUSION From the analysis of the test system, it can be concluded that integration of DG units significantly effects the traditional distributive network. It can be clearly seen from the results that all the sources improves voltage profile of the system. Among the sources synchronous machine shows significant improvement in the voltage profile. On the hand, power losses are greatly affected by the use of different sources. PV injects only real power in the system which in turn reduces the current flow in the lines and thus reduces active power losses. On the other hand synchronous machine injects both the active as well as reactive power into the system resulting a reduction in overall losses of the system, while induction machine (Wind Turbine Generator) injects only real power and absorbs reactive power from the system due to which current flowing in the lines increases thus enhancing the overall line losses of the system. REFERENCES [1] W. EL-Khattam, and M. M. A. Salama, Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System, Proceedings of the Power Systems 00 Conference, Impact of Distributed Generation, Clemson, SC, USA, pp. 13-14, March 00 [] P. Barker, and R. W. De Mello, " Detennining the Impact of Distributed Generation on Power Systems: Part 1 - Radial Distribution Systems," IEEE Trans. Power Delivery, vol. 15, no. 4, pp. -8, April 1999K. Elissa, Title of paper if known, unpublished. [3] D.Q. Hung, N. Mithulananthan, and R.c. Bansal, "Analytical expression for DG allocation in primary distribution network," IEEE Trans. on energy conservation, vol. 5, pp 814-80, Sept 010. [4] E. Bamdad, High Penetration Photovoltaic System Analysis, MSc. dissertation, Department of Electrical Engineering, California State University, Northridge, 014, Pg 37-38. [5] C.A.Canizaresand and F.L.Alvarado, Point of collapse and continuation methods for large AC/DC systems, IEEE Trans. Power Syst., vol. 8, no. 1, pp. 1 8, Feb. 1993. [6] R. A. Walling, R. Saint, R. C. Dugan, J. Burke, and L. A. Kojovic, Summary of distributed resources impact on power delivery systems, IEEE Trans.Power Del.,vol.3,no.3,pp.1636 1644,Jul.008. [7] M. Wolter and L. Hofmann, General estimation of the impact of additional DG sources on distribution grids, accepted for presentation at IEEE PES General Meeting 011, Detroit, United States 011. [8] I. Leiße, Efficient Integration of Distributed Generation in Electricity Distribution Networks, PhD. dissertation, Department of Measurement Technology and Industrial Electrical Engineering, Lund University, 013, Pg 174.