Safety 0 50 Please read and keep in a safe place Operating instructions Solenoid valve for gas VAS 1, double solenoid valve VCS 1

Similar documents
Safety. Operating instructions Bypass/pilot gas valve VBY 8 DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 12.

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15

Safety. Operating instructions Solenoid valve VGP DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 10.

Checking the usage. Slow opening/slow closing damping unit:

Solenoid valves for gas VAS, Double solenoid valves VCS

Solenoid valves for gas VAS, Double solenoid valves VCS

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

3 Edition Product brochure GB AGA

Solenoid valves for gas VAS, Double solenoid valves VCS

Tightness control TC. Product brochure GB Edition 12.10

Solenoid valves for gas VAS Double solenoid valves VCS

Solenoid valves for gas VAS, Double solenoid valves VCS AGA

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Solenoid actuator MB 7 and butterfly valves BVHM

WARNING Warnings are indicated when mishandling this product might result in death or serious injury to the user.

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

Old documentation - Only for your information! Product is not available any more!

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Combination controls CG 10

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Mounting and Operating Instructions EB 5868/5869 EN

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

Type 5411, Operating Instructions. Bedienungsanleitung Manuel d utilisation

Butterfly valves BVG, BVA, BV..F, BVH, BVHR, BVHS, BVHM Butterfly valves with actuator IBG, IBA, IB..F, IBH, IBHR, IBHS

Angle seat valve with diaphragm actuator VZXA-...-M

Type 6213 EV, 6281 EV

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Butterfly valves BVG, BVA, BV..F, BVH, BVHR, BVHS, BVHM Butterfly valves with actuator IBG, IBA, IB..F, IBH, IBHR, IBHS For gas, air, hot air and

GV-A Manufactured by Germany s Elster GmbH High-Performance Gas Solenoid Valve for Industrial Applications

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

Solenoid Valves Type 3963

SERIES 2000 GAS SAFETY SHUT OFF VALVE

WARNING CAUTION WARNING CAUTION. User s Manual for GV-A High-Performance Gas Solenoid Valve for Industrial Applications, NOTICE SAFETY PRECAUTIONS

Type 2000, Operating Instructions. Bedienungsanleitung Manuel d utilisation

Safety. Operating instructions Protective system control FCU 500 Furnace zone control FCU 505 DANGER. Contents WARNING CAUTION

Mounting and Operating Instructions EB 8227 EN. Pneumatic Control Valve Type 3331/BR 31a Special version Type 3331/3278. Type 3331 Butterfly Valve

Pressure Reducing Valve Type 2114/2415

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

Double solenoid valve Rp 3/8 - Rp 2 nominal diameters DMV-D/11 DMV-DLE/11

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Type 0283, Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

Angle seat valve with piston actuator VZXA-...-K

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 057 D01

Safety. Operating instructions Protective system control FCU 500 DANGER. Contents WARNING CAUTION. Changes to edition 08.12

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

Valve monitoring system VDK 200 A S02

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

VGD20... VGD40... Double Gas Valves. Siemens Building Technologies Landis & Staefa Division

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

North American 1599 Electro-Hydraulic Gas Shutoff Valve Bulletin 1599

BGD278 Series BASOTROL CE Approved Gas Valve

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

VE4000 & VE5000 SERIES

Pneumatic Controller for Temperature. Type Pneumatic Controller for Temperature. Type Mounting and Operating Instructions EB 7065 EN

Manually operated safety shut-off valve HSAV HSAV/5

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

V5197A Firing Rate Gas Valve

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

BGD258 Series BASOTROL CE Approved Class A Gas Valve

VMH. www. delta-elektrogas.com. Safety shut off valves for gas with hydraulic actuator DN65 DN200 EE

VLF45... Hot Air Valves. Building Technologies Division

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Globe Valve Type Fig. 1 Type 3241 Globe Valve. Mounting and Operating Instructions EB EN

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

VML. elektrogas.com. Safety solenoid valves for gas Slow opening and fast closing type DN10 DN80 EE

VE Series. Class "A" Gas Valves. Product handbook APPLICATION CONTENTS. General. Technical. Installation and operation. Various

The installation and maintenance of this product must be done under the supervision of an experienced

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

Electro- Hydraulic Actuator Gas Valves GH-5000

Type /2-way globe valve 2/2-Wege-Geradsitzventil Vanne à siège droit 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Type 3360, Service Manual. Serviceanleitung Service Manuel

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Oil-free piston compressors KK and piston vacuum pumps KV

Type 3320, Service Manual. Serviceanleitung Service Manuel

Declaration of Conformity as per Directive 97/23/EC

Single-stage safety solenoid valves MV/4 MVD, MVD/5, MVDLE/5

B21 Series BASOTROL Gas Valve

Flow. group *2) G1/4 1, , B G1/ , B /4 NPT , B N/en

Operating pressure (bar) kv factor (m 3 /h) *3)

Type 2000, 2002, 2012

Operating instructions Safety sensor BNS About this document. Content. 6 Disassembly and disposal 6.1 Disassembly Disposal...

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

KLINGER Piston Valves KVN DN PN 16 I/III with valve ring KX-GT Modul

User Guide. Lubricus Lubrication System LUB-D1/LUB-D2/LUB-D3/LUB-D4 (24 VDC)

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

SKP Series SKP15 U.. Gas Valve Actuator with Safety Shutoff Function

Gas Pressure Governors

Mounting and Operating Instructions EB 8039 EN. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve. Type 3351 Pneumatic On/off Valve

Transcription:

0 Elster GmbH Edition 0. Translation from the German 00 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas VAS, double solenoid valve VCS Cert. version 0. Contents Solenoid valve for gas VAS, double solenoid valve VCS.... Contents... Safety.... Checking the usage... Installation... Wiring... M0 cable gland... Plug... Socket... Proof of closure switch.... Tightness test... Commissioning.... Replacing the actuator... Replacing the damping unit... Maintenance...8 Accessories...8 Pressure switch for gas DG..VC....8 Bypass/pilot gas valves...9 Checking the bypass/pilot gas valve for tightness...0 Cable gland set for double solenoid valves.... Attachment block.... Seal set for sizes... Technical data... Logistics... Certification... Contact... Safety Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the operator. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com. Explanation of symbols,,,... = Action = Instruction Liability We will not be held liable for damage resulting from non-observance of the instructions and non-compliant use. Safety instructions Information that is relevant for safety is indicated in the instructions as follows: DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. CAUTION Indicates possible material damage. All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians. Conversion, spare parts All technical changes are prohibited. Only use OEM spare parts. Changes to edition 0. The following chapters have been changed: Installation Accessories -

Checking the usage Intended use Gas solenoid valves VAS for safeguarding gas or air on various appliances. Double solenoid valves VCS are combinations of two gas solenoid valves VAS. This function is only guaranteed when used within the specified limits see page (Technical data). Any other use is considered as non-compliant. Type code Code Description VAS Gas solenoid valve Sizes T T-product 0 Inlet and outlet flange nominal size R Rp internal thread N NPT internal thread (ANSI/ASME) /N Quick opening, quick closing /L Slow opening, quick closing Mains voltage: W 0 V AC, 0/0 Hz Q 0 V AC, 0/0 Hz K V DC P 00 V AC, 0/0 Hz Y 00 V AC, 0/0 Hz S G R L Part designations VAS With visual position indicator and proof of closure switch and proof of closure switch for V Viewing side (in flow direction): from the right from the left Solenoid actuator Flow body Connection box Connection flange Proof of closure switch Connection parts Sealing plug Electrical connection: plug with socket plug without socket M0 cable gland VAS..S, VAS..G - Mains voltage, electrical power consumption, ambient temperature, enclosure, inlet pressure and installation position: see type label. www.kromschroeder.com Osnabrück, Germany VAS... Installation.XXXX CAUTION Please observe the following to ensure that the gas solenoid valve is not damaged during installation and operation: Important! The gas must be dry in all conditions and must not contain condensate. Sealing material and dirt, e.g. thread cuttings, must not be allowed to get into the valve housing. A filter must be installed upstream of every system. It is not permitted to install gas solenoid valve VAS downstream of flow rate regulator VAH/VRH and upstream of fine-adjusting valve VMV. The VAS would no longer be able to perform its function as a second safety valve if installed in the above-mentioned position. Do not store or install the unit in the open air. If more than three valvario controls are installed in line, the controls must be supported. Do not clamp the unit in a vice. Only secure the flange by holding the octagon with a suitable spanner. Risk of external leakage. Solenoid valves with valve stem overtravel switch and visual position indicator VAS..SR/SL: actuator cannot be rotated. In the case of double solenoid valves, the position of the connection box can only be changed by removing the actuator and reinstalling it rotated by 90 or 80. Cleaning work on the solenoid actuator may not be performed using high pressure and/or chemical cleaning agents. This can cause moisture to get into the solenoid actuator and may lead to a dangerous failure. When joining two valves, determine the position of the connection boxes, push through the knock-outs in the connection boxes and install a cable gland set before installation in the pipework, see page (Cable gland set for double solenoid valves). For retrofitting a second gas solenoid valve, use the double block seal instead of O-rings. The double block seal is supplied with the seal set, see page (Seal set for sizes ).

Installation position: black solenoid actuator in the vertical upright position or tilted up to the horizontal, not upside down. Retaining frame If two controls (regulators or valves) are assembled, a retaining frame with double block seal must be fitted, see page (Seal set for sizes ). The housing must not be in contact with masonry. Minimum clearance 0 mm (0,8"). The inlet pressure p u and the outlet pressure p d can be measured using the pressure test points on both sides. p u p d Strainer A strainer must be fitted in the unit on the inlet side. If two or more gas solenoid valves are installed in line, then a strainer only needs to be fitted on the inlet side of the first valve. The seals in some gas compression fittings are approved for temperatures of up to 0 C (8 F). This temperature limit will not be exceeded if the flow through the pipe is at least m /h (. SCFH) of gas and the maximum ambient temperature is 0 C ( F). Differential pressure orifice If pressure regulator VAD/VAG/VAV is retrofitted upstream of gas solenoid valve VAS, a DN differential pressure orifice with outlet opening d = 0 mm (.8") must be inserted at the outlet of the pressure regulator. In the case of pressure regulator VAx or VAx 0, the DN differential pressure orifice must be ordered separately and retrofitted, Order No. 90. The retaining frame must be fitted to secure the differential pressure orifice at the outlet of the regulator. VAS with flanges Note direction of flow. VAS without flanges Note direction of flow. O-ring and strainer (Fig. ) must be fitted. -

Wiring WARNING Attention! Please observe the following to ensure that no damage occurs: Electric shocks can be fatal! Before working on possible live components, ensure the unit is disconnected from the power The solenoid actuator heats up during operation. Surface temperature approx. 8 C (approx. 8 F) pursuant to EN 00-. M0 cable gland 8 9 Use temperature-resistant cable (> 80 C). Disconnect the system from the electrical power Shut off the gas Wiring to EN 00-. UL requirements for the NAFTA market. To maintain the UL environmental rating Type, the enclosure openings shall be closed with fittings rated UL Type ; ; R; RX; S; SX; X; X; ; ; P; ; K or. Gas solenoid valves shall be protected by a branch circuit protective device not exceeding A. When joining two valves, install a cable gland set, see page (Cable gland set for double solenoid valves), between the connection boxes. First push through the knock-out then unscrew the cover! If the M0 cable gland or plug is already fitted, it is not necessary to push through the knock-out. (+) N (-) N N Plug V (+) = black, V (+) = brown, N ( ) = blue 8 When installing two plugs on a VAS with proof of closure switch: label the sockets and plugs to avoid confusion. (+) N (-) N N -

Socket = N ( ), = V (+), = V (+) N 8 9 N N (-) blue (+) black N N (-) = blue (+) (+) = (-) N black Proof of closure switch VAS open: contacts and closed, VAS closed: contacts and closed. Visual indicator of proof of closure switch: red = VAS closed, white = VAS open. Double solenoid valve: if a plug with socket is fitted, only one proof of closure switch can be connected. CAUTION Please observe the following to ensure smooth operation: The proof of closure switch is not suitable for frequent cycling operation. Route valve and proof of closure switch cables separately through M0 cable glands or use two separate plugs. Otherwise, there is a risk of interference between valve voltage and proof of closure switch voltage. To make wiring easier, the connection terminal for the proof of closure switch can be removed. V (+) = black, N ( ) = blue rot red red schwarz black black weiß white white Label the plugs to avoid confusion. = N ( ), = V (+) Meldeschalter Proof of of closure switch N Ensure that the connection terminal for the proof of closure switch has been reconnected. Finishing the wiring -

Tightness test Close the gas solenoid valve. To be able to check the tightness, shut off the downstream pipeline close to the valve. N, p u max 0 8 0 0 Open the solenoid valve. Setting the start gas rate on VAS../L, VCS..L The start gas rate can be set by turning the damping unit a maximum of turns. There must be a period of 0 seconds between switching the valve off and on again so that the damping is fully effective. Loosen the M setscrew (. mm hexagon socket), but do not unscrew completely. - + Turn clockwise to the zero setting/as far as possible. Screw the M setscrew back in. N, p u max 9 Tightness OK: open the pipeline. Pipeline leaking: replace O-ring on flange, see page (Seal set for sizes ). Then check for tightness once again. Unit leaking: remove the unit and return it to the manufacturer. Commissioning Setting the flow rate At the factory, the gas solenoid valve is adjusted for maximum flow rate Q. The markings on the cover cap can be used for coarse adjustment of the flow rate. The cover cap can be rotated without changing the current flow rate. Allen key:. mm. Do not turn beyond the max. setting. Q [%] 00 - + max. Replacing the actuator The actuator adapter set is enclosed with new actuators. VAS VAS / The seals of the actuator adapter set are covered with a non-stick coating. No additional grease is required. VAS without damping Disconnect the system from the electrical power Shut off the gas Remove the M0 cable gland or other type of connection. 8 0 U min. max. min. The VAS remains tight even if the adjusting screw is overturned. 9 -

Depending on the construction stage of the unit, there are two different methods for replacing the actuator: If the unit concerned has no O-ring in this place (arrow), replace the actuator as described here. Otherwise, go to the next note. M M 0 VAS 0 VAS 8 Slide seal under the second groove. Insert seals. Position of the metal ring can be selected. If the unit concerned has an O-ring in this place (arrow), replace the actuator as described here: VAS : use all seals from the actuator adapter set. VAS /: use the small seal from the actuator adapter set and only one of the large seals. 0 VAS 9 For further disassembly and replacing the actuator, see page (Replacing the actuator). Once the new actuator has been wired, the damping unit can be fitted as described below and set to the desired start gas rate. 0 0 M Screw in the M setscrews. Slide seal under the second groove. Position new actuator. Follow the reverse procedure when reassembling. Fit the M0 cable gland or plug and socket. Connect the VAS to the electrical power supply, see page (Wiring). VAS../L with damping unit Disconnect the system from the electrical power Shut off the gas Loosen the setscrews, but do not unscrew completely (M =. mm hexagon socket, M =. mm hexagon socket). Gewindestifte Open the gas solenoid valve and 8M the gas fest Set the start gas rate, see page einschrauben. (Setting the start gas rate on VAS../L, M VCS..L). The connection between solenoid actuator and damping unit must then be checked for tightness. N <, x p u max 8 Replacing the damping unit Disconnect the system from the electrical power Shut off the gas Loosen the M setscrews (. mm hexagon socket), but do not unscrew completely. M 9 Screw the M setscrews back in 0 again. -

Open the solenoid valve and the gas 8 Set the start gas rate, see page (Setting the start gas rate on VAS../L, VCS..L). The connection between solenoid actuator and damping unit must then be checked for tightness. 9 0 Accessories Pressure switch for gas DG..VC The pressure switch for gas monitors the inlet pressure p u, the outlet pressure p d and the interspace pressure p z. p d p u N <, x p u max Maintenance CAUTION In order to ensure smooth operation, check the tightness and function of the VAS: Once per year, twice per year in the case of biogas; check for internal and external tightness, see page (Tightness test). Check electrical installations once a year in line with local regulations; pay particular attention to the PE wire, see page (Wiring). If the flow rate has dropped, clean the strainer. If more than one valvario control is installed in series: the controls may only be removed from the pipeline and reinstalled on the inlet and outlet flange all at once. We recommend replacing the seals, see page (Seal set for sizes ). Disconnect the system from the electrical power Shut off the gas Undo connection parts. 8 p d p u When using two pressure switches on the same side of the double solenoid valve, only the combination DG..C.. and DG..C..9 may be used for design reasons. DG..C..9 p z DG..C.. p u When retrofitting the pressure switch p for gas, see enclosed operating instructions Pressure z switches for gas DG..C, p u section entitled Mounting the DG..C.., DG..C..9 on valvario gas solenoid valves. The switching point is adjustable via hand wheel. Adjusting range (adjusting tolerance = ± % of the scale value) Mean switching differential at min. and max. setting [mbar] ["WC] [mbar] ["WC] DG VC 0.8.8 0.. 0. 0.8 DG 0VC 0 0. DG 0VC 0 0 8 0.8. DG 00VC 00 00 0 0. 8 Deviation from the switching point during testing pursuant to EN 8 Gas pressure switches: ± %. 9 Once the seals have been replaced, follow the reverse procedure to reassemble the unit. 0 Then check the unit for internal and external tightness, see page (Tightness test). -8

Bypass/pilot gas valves Disconnect the system from the electrical power Shut off the gas Prepare the installed main valve. Turn the actuator so that the side on which the bypass/pilot gas valve is to be installed is accessible. Setting the flow rate The flow rate can be set by turning the flow rate restrictor ( mm hexagon socket) ¼ of a turn. + - VBY for VAS Scope of delivery VAS VBY 8 A Bypass valve VBY..I A x bypass valve VBY..I B x retaining screws with x O-rings: both retaining screws have a bypass orifice C Grease for O-rings The screw plug at the outlet remains in place. Pilot gas valve VBY..R A x pilot gas valve VBY..R B x retaining screws with x O-rings: one retaining screw has a bypass orifice ( x O-rings), the other does not ( x O-rings) C Grease for O-rings Remove the screw plug at the outlet and connect the Rp ¼ pilot gas line. Mounting the VBY Grease O-rings B. VBY..I VBY..R C 8 9 0 B Only adjust the flow rate restrictor in the marked range, otherwise the required gas volume will not be reached. Wire the socket, see page (Wiring). Check for tightness, see page 0 (Checking the bypass/pilot gas valve for tightness). VAS for VAS, VAS, VAS Scope of delivery A VAS VAS / C C B D E A x bypass/pilot gas valve VAS B x O-rings C x double nuts for mounting to VAS or x spacer sleeves for mounting to VAS / D x connection parts E x mounting aid Bypass valve VAS F x connection pipes, if the bypass valve has a blind flange at the outlet side Pilot gas valve VAS F x connection pipe, x sealing plug, if the pilot gas valve has a threaded flange at the outlet side Mounting the bypass/pilot gas valve VAS Always use a connection pipe F at the inlet of the main valve. For a bypass valve: use connection pipe F Ø 0 mm (0.9") at the outlet of the main valve if the bypass valve s outlet flange is designed as a blind flange. For the pilot gas valve: insert sealing plug F at the outlet of the main valve if the pilot gas valve s outlet flange is designed as a threaded flange. F Tighten the retaining screws alternately so that VBY and VAS are flush. -9

B F B 8 9 E 0 Remove the sealing plugs on the mounting side of the bypass valve. VAS to VAS 8 9 Remove the nuts from the connection parts on the mounting side of the main valve. Remove the connection parts of the bypass/pilot gas valve. Use the new connection parts C and D from the scope of delivery for the bypass/pilot gas valve. D Check for tightness, see page 0 (Checking the bypass/pilot gas valve for tightness). Checking the bypass/pilot gas valve for tightness To be able to check the tightness, shut off the downstream pipeline as close as possible to the valve. Close the main valve. Close the bypass/pilot gas valve. CAUTION If the actuator of the VBY is rotated, the tightness can no longer be guaranteed. To ensure that there are no leaks, check the actuator of the VBY for tightness. C N, x p u max Check the bypass/pilot gas valve for tightness at the inlet and outlet. Wire the bypass/pilot gas valve VAS, see page (Wiring). 8 Check for tightness, see page 0 (Checking the bypass/pilot gas valve for tightness). VAS for VAS or VAS The connection parts of the main valve remain mounted. Remove the connection parts of the bypass/pilot gas valve. Use the new connection parts C and D from the scope of delivery for the bypass/pilot gas valve. For VAS and VAS, the connection parts consist of self-tapping screws. C D Self-tapping screws. N, x p u max N, x p u max N, x p u max 0 0 0 Bypass valve N, N x p u max, N x p u max, x p u max Pilot gas valve N, N x p u max, N x p u max, x p u max Open the bypass Open Abrir Откройте Ανοίξτε the or pilot bypass Aprire la τη gas or la байпасный Open Ouvrir Bypass-klep Otworzyć Åbn Abrir βαλβίδα Öppna Åpne Otevřít válvula by- a bypass- the la válvula obtokový tenn- zawór oder Zündgasventil или vanne of valve. pilot valvola aansteekgasklep valve. válvula bypass la пилот- di obejściowy pass-/tænd- gasventilen. de ή tändgasvengassventilen. de παράκαμψης bypass- eller ventil de or eller o lub ou la öffnen. ный pilot by-pass zawór nebo τη gás газовый βαλβίδα gazu piloto. ou de la valvola del клапан. valve. vanne openen. zapłonowego. αερίου gas de ανάφλεξης. tilen. zapalovací pilote. plynový encendido. gas pilota. ventil. Wire the bypass/pilot gas valve VAS, see page (Wiring). -0

Cable gland set for double solenoid valves When wiring a double solenoid valve, the connection boxes are to be connected using a cable gland set. VCx VCx VCx Order No. for size : 998, size : 998, size : 998. We recommend preparing the connection boxes before the double solenoid valve is installed in the pipework. Alternatively, one of the actuators must be dismantled as described below and reinstalled rotated by 90 in preparation for installation of the double solenoid valve. The cable gland set can only be used if the connection boxes are at the same height and on the same side. Disconnect the system from the electrical power Shut off the gas 8 Connect the valves to the electrical power supply, see section entitled Wiring. Attachment block For locked installation of pressure gauge or other accessories, the attachment block is mounted to the solenoid valve. Order No. 98 Disconnect the system from the electrical power Shut off the gas Use the enclosed self-tapping screws for installation. 9 8 In both connection boxes, push through the 9 knock-out for 0 the cable gland set then remove the covers. The covers must not be taken off before pushing through the knock-outs as it prevents damage to the connection boxes. 9 0 8 8 8 N, x p u max 9 Shut off the downstream gas pipeline close to N the, solenoid x p u max valve. 0 Open the solenoid valve. N, x p u max N, x p u max 8 9 -

Seal set for sizes When retrofitting accessories or a second valvario control or when servicing, we recommend replacing the seals. C D A B Order No. for size : Order No. 9988, size : Order No. 9989, size : Order No. 9990. Scope of delivery: A x double block seal, B x retaining frame, C x O-rings (flange), D x O-rings (pressure switch), for pressure test point/screw plug: E x sealing rings (flat sealing), x profiled sealing rings. Technical data Gas types: natural gas, LPG (gaseous), biogas (max. 0. %-by-vol. H S) or clean air; other types of gas on request. The gas must be clean and dry in all temperature conditions and must not contain condensate. Max. inlet pressure p u : max. 00 mbar (. psig). FM approved, non operational pressure: 00 mbar (0 psig). ANSI/CSA approved: 0 mbar ( psig). The flow adjustment facility limits the maximum flow rate: VAS: 0 to 00%, VBY: 0 to 00%. The setting can be monitored on an indicator. VAS../L: start gas rate adjustment: 0 to 0%. Opening times: VAS../N quick opening: s, VAS../L slow opening: up to 0 s. Closing time: quick closing: < s. E C Medium and ambient temperatures: VAS: -0 to +0 C (- to +0 F), VBY: 0 to +0 C ( to 0 F). No condensation permitted. Storage temperature: -0 to +0 C (- to +0 F). Enclosure: VAS: IP, VBY: IP. Valve housing: aluminium, valve seal: NBR. Connection flanges with internal thread: Rp to ISO -, NPT to ANSI/ASME. Class A, Group safety valve pursuant to EN and EN, 0 V AC, 0 V AC, V DC: Factory Mutual (FM) Research Class: 00 and, ANSI Z. and CSA.. Mains voltage: 0 V AC, +0/-%, 0/0 Hz; 00 V AC, +0/-%, 0/0 Hz; 0 V AC, +0/-%, 0/0 Hz; 00 V AC, +0/-%, 0/0 Hz; V DC, ±0%. Cable gland: M0 x.. Electrical connection: electrical cable with max.. mm (AWG ) or plug with socket to EN 0-80. Power consumption: Type Voltage Power V DC W 00 V AC W ( VA) VAS 0 V AC W ( VA) 00 V AC W ( VA) 0 V AC W ( VA) V DC W 00 V AC W (0 VA) VAS, VAS 0 V AC 0 W ( VA) 00 V AC 0 W ( VA) 0 V AC 0 W ( VA) V DC 8 W VBY 0 V AC 8 W 0 V AC 9. W Switching frequency: VAS../N: max. 0 x per minute, VAS../L: there must be a period of 0 seconds between switching off and on again so that the damping is fully effective. Duty cycle: 00%. Power factor of the solenoid coil: cos φ = 0.9. Contact rating of proof of closure switch: Type Voltage Min. current (resistive load) Max. current (resistive load) VAS..S 0 V AC, 0/0 Hz 00 ma A VAS..G 0 V DC ma 0. A -

Switching frequency of proof of closure switch: max. x per minute. Switching Switching cycles* current [A] cos φ = cos φ = 0. 0. 00,000 00,000 0. 00,000 0,000 00,000 00,000 00,000 * Limited to max. 00,000 cycles for heating systems. Air flow rate Q Air flow rate Q for a pressure loss of p = mbar (0. "WC) p mbar (0, "WC) Designed lifetime This information on the designed lifetime is based on using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced. Designed lifetime (based on date of manufacture) in accordance with EN, EN for VAS: Designed lifetime Type Switching cycles Time [years] VAS 0 VAS 00,000 0 VAS VAS 00,000 0 You can find further explanations in the applicable rules and regulations and on the afecor website (www.afecor.org). This procedure applies to heating systems. For thermoprocessing equipment, observe local regulations. x VAS Type Air flow rate Q [m /h] Q [SCFH] VAS 0.. VAS. 9. VAS 0 8. 9. VAS 9.. VAS. 89. VAS. VAS 0. 89. VAS 0. 8.8 VAS 0. 8. VAS 0. 8. VAS.9 8. Air flow rate Q for a pressure loss of p = 0 mbar "WC) p 0 mbar ( "WC) x VBY/ x VAS Type Air flow rate Q [m /h] Q [SCFH] Bypass valve VBY 0.8 0.0 Pilot gas valve VBY 0.89. Type Bypass valve VAS Pilot gas valve VAS Air flow rate Ø [mm] Q Q [m Ø ["] /h] [SCFH] 0. 0.0.8 0. 0.08. 0.8 0. 8.. 0... 0.0 8.. 0. 09..9 0.8. 8. 0. 80. 9. 0. 8.9 0. 0.9. 0 8. 0.9 9. Logistics Transport Protect the unit from external forces (blows, shocks, vibration). On receipt of the product, check that the delivery is complete, see page (Part designations). Report any transport damage immediately. Storage Store the product in a dry and clean place. Storage temperature: see page (Technical data). Storage time: months before using for the first time. If stored for longer than this, the overall service life will be reduced by the corresponding amount of extra storage time. Packaging The packaging material is to be disposed of in accordance with local regulations. Disposal Components are to be disposed of separately in accordance with local regulations. -

Certification Declaration of conformity FM approved* We, the manufacturer, hereby declare that the products VAS, marked with product ID No. CE-00BO80, comply with the essential requirements of the following Directives: 009//EC in conjunction with EN, EN, EN 88-, EN and EN 8, 00/9/EC, 00/08/EC. The relevant product corresponds to the type tested by the notified body 00. The production is subject to the surveillance procedure pursuant to Directive 009//EC Annex II, paragraph. Elster GmbH Scan of the Declaration of conformity (D, ) see www.docuthek.com SIL, PL The solenoid valves VAS are suitable for singlechannel systems (HFT = 0) up to SIL /PL d, and up to SIL /PL e when two redundant solenoid valves are installed in a double-channel architecture (HFT = ), provided that the complete system complies with the requirements of EN 08/ISO 89. The safety function value which is actually achieved is derived by taking all components into account (sensor logic actuator). For this, the demand rate and structural measures to avoid/detect nonconformity are to be observed (e.g. redundancy, diversity, monitoring). Characteristic values for SIL/PL: HFT = 0 ( device), HFT = ( devices), SFF > 90, DC = 0, type A/category B,,,,, high demand mode, CCF >, β. PFH D = λ D = = 0. x n MTTFd B op 0d VAS B0d value Size,8,898 Sizes,,0 Factory Mutual (FM) Research Class: 00 and Safety overpressure slam shut valves. Designed for applications pursuant to NFPA 8 and NFPA 8. ANSI/CSA approved* Canadian Standards Association ANSI Z. and CSA. UL listed* Underwriters Laboratories UL 9 Electrically operated valves. AGA approved* AGA Australian Gas Association Eurasian Customs Union The product VAS, VCS meets the technical specifications of the Eurasian Customs Union. * Approval does not apply for 00 V AC or 00 V AC. Contact If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from Elster GmbH. We reserve the right to make technical modifications in the interests of progress. - Elster GmbH Postfach 8 09, D-908 Osnabrück Strotheweg, D-90 Lotte (Büren) T +9-0 F +9-0 info@kromschroeder.com, www.kromschroeder.com