GAFIK Systems lp-1 12.8.03 are ideal for projects with many small loads. Each panel provides power and dimming for up to 32 dimming legs. Features Work directly with incandescent, magnetic low voltage, and neon/cold cathode lighting, as well as Lutron TuWireTM Fluorescent Ballasts. Work with electronic low voltage lighting via Power Interfaces. Work with 3-wire AC motors through motor modules. Panels are prewired - just bring in feed and load wiring. Surface or recess mount between 16 center to center studs. Models available with: 100-127V, 220-240V (non CE), or 230V (CE) input power. 1 to 8 Modules for 4 to 32 dimming legs. Different feed types and breakers. work with: GX-4000 Control Units. GAFIK 5000TM, GAFIK 6000, and GAFIK 7000 Systems. GP Panels and XP Switching Panels. DMX512 dimming systems via the 2LIKTM option. Standard-Size LP4/28 LP8/32 Mini LP1/4 LP3/12 Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Specifications lp-2 12.8.03 Standards UL Listed (eference: UL File 42071). Complies with CSA, OM, or CE (where appropriate). Power Input power: 100-127V, 220-240V (non CE), and 230V (CE). All voltages 50/60Hz, phaseto-neutral. Branch Circuit Breakers: UL-rated thermal magnetic. AIC ratings: 100-127V 10,000 220-240V 6,000 230V (CE) 6,000 Lighting strike protection: Meets ASI/IEEE standard 62.41-1980. Can withstand voltage surges of up to 6000V and current surges of up to 3000A. 10-year power failure memory: Automatically restores lighting to scene selected prior to power interruption. Sources/Load Types Operate these sources with a smooth continuous Square Law dimming curve or on a full-conduction non-dim basis: Incandescent (Tungsten)/Halogen Magnetic Low Voltage Transformer Lutron Tu-WireTM Electronic Fluorescent Ballasts eon/cold Cathode Operate these sources via Power Interfaces: Electronic Low Voltage Transformer via dedicated internal Modules or external Power Interfaces. Lutron Electronic Fluorescent Ballasts via external Power Interfaces. Operate HID sources on a full conduction non-dim basis. Modules Each Module can handle a fully loaded electrical circuit - up to four dimming legs per Module. Maximum atings: Voltage Capacity per Capacity per Module Leg 100-127 V 16 A 16 A 220-240 V 16 A 16 A (non-ce) 230 V (CE) 13 A 10 A TISSTM filter circuit technology compensates for incoming line voltage variations: o visible flicker with +/-2% change in MS voltage/cycle and +/-2% Hz change in frequency/second. Internal: Prewired by Lutron. System communications: Low-voltage Class 2 (PELV) wiring connects Panels to other components. Line (mains) voltage: and load wiring only. o other wiring or assembly required. Setup Circuit Selector electronically assigns dimming legs to zones and sources. Permits reassignment of zones and sources without rewiring. Physical Design Enclosure: EMA-Type 1, IP-20 protection; #16 U.S. Gauge Steel. Indoors only. Weight: 27lb (13kg) for Mini LP, 63lb (29kg) for Standard-Size LP. Mounting Surface mount or recess mount between 16" (40cm) studs. Allow space for ventilating. Environment 32-104 F (0-40 C). elative humidity less than 90% non-condensing. Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Anatomy of a LP Model umber lp-3 12.8.03 L P 7 / 2 8-2 3 0 4 I S - 1 3 - C G P _ Prefix umber of Modules Voltage Branch Circuit Breaker ating Panel Custom Panel Suffix Type Prefix: LP for LP Panel umber of Modules: Indicates number of dimming modules in the panel. Also indicates number of full load circuits. umber of Legs: Indicates number of dimming legs in the panel. Each module has four dimming legs. Voltage: 120 for 100-127 V 230 for CE 240 for non-ce Type: 2 for 1 phase 2 wire 3 for 1 phase 3 wire (split phase) 4 for 3 phase 4 wire Panel : umber of Legs ML for Main Lugs only Mxx for Main Breaker with xx = breaker size in Amps (custom panel option) IS for Isolation Switch (CE/non-CE only) Branch Circuit Breaker ating: 20 for 20 A branch circuit breakers (120 V only) 15 for 15 A branch circuit breakers (120 V only) 13 for 13 A branch circuit breakers (230 V CE only) 16 for 16 A branch circuit breakers (240 V non-ce only) Custom Panel Suffix: Indicates panel with special options Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Mini LP Models 230V (CE) Power lp-5 12.8.03 umber Of Modules umber Of Legs Type Maximum Panel LP1 LP2 LP3 4 8 12 1Ø, 2W 1Ø, 2W 1Ø, 2W 3Ø, 4W 13A 26A 39A 13A 13A Branch Circuit Breakers Wire Sizes Power (Hot/Live) (connect directly to Branch Circuit Breakers): 230V (CE) #18 AWG (1.0mm 2 ) to #4 AWG (25mm 2 ) eutral (connects to eutral Lug): 230V (CE) #14 AWG (2.0mm 2 ) to #8 AWG (6.0mm 2 ) Load All Models #14 AWG (2.0mm 2 ) to Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Standard-Size LP Models 230V (CE) Power lp-7 12.8.03 umber Of Modules umber Of Legs Type Maximum Panel Branch Circuit Breakers LP4 16 3Ø,4W 125A LP5 LP6 20 24 3Ø,4W 3Ø,4W 125A 125A Isolation Switch Only 13A LP7 28 3Ø,4W 125A LP8 32 3Ø,4W 125A Wire Sizes to Isolation Switch (CE/non-CE only): Power (Hot/Live) (3) 2.5mm 2 to 35mm 2 eutral (1) 2.5mm 2 to 35mm 2 Load All Models #14 AWG (2.0mm 2 ) to Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems lp-8 12.8.03 Mini LP Dimensions Top View 14.38 (365.25) Left Side View 2.21 (56.05) Front View 15.875 (403.23) 8.00 (203.2) ight Side View 54.15 (105.36) 0.15 (3.81) 24.00 (609.6) 21.50 (546.1) 24.50 (622.3) 1.34 (33.94) Cover 2.21 (56.05) 10.75 (273.05) 15.13 (384.3) Bottom View 4.09 (103.84) All dimensions in inches (mm). Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Standard-Size LP Dimensions lp-9 12.8.03 14.375 (365.13) Top View Left Side View 2.43 (61.85) 15.875 (403.23) Front View 8.00 (203.2) ight Side View 4.21 (106.93) 0.150 (3.81) 2.69 (68.25) 41.75 (1060.45) 59.00 (1498.60) 59.50 (1511.30) Cover 2.43 (61.85) 11.00 (279.4) 15.125 (394.18) Bottom View All dimensions in inches (mm). 4.15 (105.41) Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Mini LP Mounting lp-10 12.8.03 Surface or recess mount indoors. Consult Dimensions page for dimensions and conduit knockout locations. Panel generates heat. Mount only where ambient temperature is 32-104 F (0-40 C). This equipment is air-cooled. Do not block vents or warranty will be void. Mount Panels where audible noise is acceptable (internal relays click). Mount Panels so line (mains) voltage wiring is at least 6 feet (1.8m) from sound or electronic equipment and wiring. Mount Panel within 7 of true vertical. Surface Mounting Surface mounting keyholes accept 1/4 (6 mm) mounting bolts. This size is recommended. Panel Maximum Weight BTUs/hour Without Packaging LP1 90 33lb (15kg) LP2 170 35lb (16kg) LP3 250 37lb (17kg) Maximum and Wire Sizes Consult Overview page. ecess Mounting Mount Panel flush to 1/8" (3mm) below finished wall surface. Allow room for top cover. Leave 1 1/2" (38mm) clearance to each side of Panel. Front View Side View Front View Side View Terminal Blocks for Legs to Loads and Legs to loads Terminal Blocks for Legs to Loads and Legs to loads Class 2 (PELV) Do ot Block Vents Class 2 (PELV) Do ot Block Vents and Legs to loads Branch Circuit Breakers and Legs to loads Branch Circuit Breakers Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Standard-Size LP Mounting lp-11 12.8.03 Surface or recess mount indoors. Consult Dimensions page for dimensions and conduit knockout locations. Panel generates heat. Mount only where ambient temperature is 32-104 F (0-40 C). This equipment is air-cooled. Do not block vents or warranty will be void. einforce wall structure for weight and local codes. Mount Panels where audible noise is acceptable. (Panels hum slightly and internal relays click.) Mount Panels so line (mains) voltage wiring is at least 6 feet (1.8m) from sound or electronic equipment and wiring. Mount Panel within 7 of true vertical. Surface Mounting Surface mounting keyholes accept 1/4 (6mm) mounting bolts. This size is recommended. Panel Maximum Weight BTUs/hour Without Packaging LP4 330 55lbs (25kg) LP5 410 57lbs (26kg) LP6 490 59lbs (27kg) LP7 570 61lbs (28kg) LP8 650 63lbs (29kg) Maximum and Wire Sizes Consult Overview page. ecess Mounting Mount Panel flush to 1/8" (3mm) below finished wall surface. Allow room for top cover. Leave 1 1/2" (38mm) clearance to each side of Panel. Front View Side View Front View Side View Terminal Blocks for Legs to Loads and Legs to Loads Terminal Blocks for Legs to Loads and Legs to Loads 2 4 6 1 3 5 Do not block vents 12" (31cm) minimum clearance 2 4 6 1 3 5 Do not block vents 12" (31cm) minimum clearance and Legs to Loads 8 7 Class 2 (PELV) 8 7 Class 2 (PELV) Main Lugs Main Lugs Preferred Class 2 (PELV) Preferred Class 2 (PELV) Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Mini LP Load Terminal Blocks Bypass Jumpers: Do not remove until load wiring is verified! H DH DH DH H Mini LP (Cover Off) lp-12 12.8.03 Tips Wire the Mini LP similar to wiring a lighting Distribution Panel: un feed and load wiring. o other wiring or assembly required. un separate neutrals for each module - no common neutrals across phases. The Mini LP can provide temporary lighting: Wire all loads. Do not remove the bypass jumpers that protect the Modules. Use Branch Circuit Breakers to switch lights on and off. Branch Circuit Breakers eutral Lug Power (Hot/Live) eutral Power (Hot/Live) 100-127V #14 AWG (2.0mm 2 ) to 220-240V #18 AWG (1.0mm 2 ) to 230V (CE) #4 AWG (25mm 2 ) eutral 100-127V #14 AWG (2.0mm 2 ) to #2/0 AWG (70mm 2 ) 220-240V #14 AWG (2.0mm 2 ) to 230V (CE) #8 AWG (6.0mm 2 ) Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Standard-Size LP Load Bypass Jumpers: Do not remove until load wiring is verified! DH DH DH DH H Standard LP (Cover Off) lp-13 12.8.03 Tips Wire the Mini LP similar to wiring a lighting Distribution Panel: un feed and load wiring. o other wiring or assembly required. un separate neutrals for each module - no common neutrals across phases. The LP can provide temporary lighting: Wire all loads. Do not remove the bypass jumpers that protect the Modules. Use Branch Circuit Breakers to switch lights on and off. Terminal Blocks Branch Circuit Breakers eutral Lug Power (Hot/Live) (3) #14 AWG (2.0mm 2 ) to #2/0 AWG (70mm 2 ) eutral #2/0 AWG (70mm 2 ) Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Typical Legs for 230V (CE) lp-16 12.8.03 All Load Types except Lutron Hi-lume or Eco-10TM (ECO-Series) Fluorescent Ballasts Electronic Low Voltage Load Dimmed Live eutral Bypass Jumpers: Do not remove! L Electronic Low Voltage Use Lutron ELVI Electronic Low Voltage Interface. Transformer ELVI Dimmed Live eutral Bypass Jumpers: Do not remove! L Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems lp-17 12.8.03 Low-Voltage Class 2 (PELV) (All Models) System communications use low-voltage Class 2 wiring. must be daisy-chained. must run separately from line (mains) voltage. GAFIK Eye 4000 System Class 2 (PELV) wiring link requires: Two #12 AWG (2.5mm 2 ) conductors for control power. One twisted, shielded pair of #18 AWG (1.0mm 2 ) for data link. One #18 AWG (1.0mm 2 ) conductor for Emergency (Essential) sense line, from panel to panel. Total length of Control Link may be no more than 2,000 ft. (610m). Approved low-voltage cable is available from Lutron, 1 Belden, and Liberty. These are approved with #22 AWG data link wires. LP Panels Control Interface Control Unit Wallstations GAFIK 5000TM/6000 /7000 System Class 2 (PELV) wiring link requires: Two #12 AWG (2.5mm 2 ) conductors for control power. One twisted, shielded pair of #18 AWG (1.0mm 2 ) for data link. One #18 AWG (1.0mm 2 ) conductor for emergency (essential) sense line, from panel to panel. Total length of Control Link may be no more than 2,000 ft. (600m). If -PT interface and GX-CBL-46L cable 1 is used, length may be up to 4,000 ft. (1200m). LP Panels 5000/6000/7000 Processor Control Interface Control Unit Wallstations efer to GAFIK 5000/6000/7000 Specification 1 GX-CBL-46L Class 2 (PELV) wiring cable is available from Lutron and contains: Two #12 AWG (2.5mm2) conductors for control power. One twisted, shielded pair of #22 AWG (0.625mm2) for data link. One #18 AWG (1.0mm2) conductor for emergency (essential) sense line. Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Class 2 (PELV) Panel-to-Panel (All Models) lp-18 12.8.03 To additional Power Panels 1 2 3,4 5 Control (2) #12 AWG (2.5 mm 2 ) 1: Common 2: 24VFW Data Link (1) shielded, twisted pair #18 AWG (1.0 mm 2 ) 3: 4: Shield/Drain (1) #18 AWG (1.0 mm 2 ) 5: Sense Line 1 2 3,4 Shield/Drain To Lighting Controls or Processors 1 2 3 4 D 5 1 2 3 4 D 5 Common +24VFW Drain Sense Data A OK Power Data B OK Link A B Link 1 2 3 4 D 5 C D SELECT CICUIT 1 Common Drain Common +24VFW Drain Sense Data A OK Power Data B OK Link A B Link 1 2 3 4 D 5 C D SELECT CICUIT 1 Common Drain 2 2 Circuit Circuit LP Panel 1 LP Panel 2 otes: Emergency Power: The additional #18 AWG (1.0mm 2 ) wire is a sense line from terminal 5 of another Panel. This sense line allows an Emergency (Essential) Lighting Panel to sense when ormal (on-essential) power is lost. If more than one Emergency Lighting Panel needs to sense from a specific ormal Panel, a dedicated wire between each pair of ormal (on- Essential) and Emergency (Essential) panels may be required. Shield/Drain: Connect shielding as shown. Do not connect to Ground (Earth) or circuit board of Circuit Selector. Connect the bare drain wires and cut off the outside shield. Class 2 (PELV) Terminal Connections Each low-voltage Class 2 (PELV) terminal can accept only two #18 AWG (1.0mm 2 ) wires. Two #12 AWG (2.5mm 2 ) conductors won't fit. Connect as shown using appropriate wire connectors. (4) #12 AWG (2.5mm 2 ) 1 2 3 4 D 5 Common 24VFW Data A OK Drain Sense 1 2 3 4 D 5 A Link Power Data B OK Link B Comm Drain C D Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber:
GAFIK Systems Options lp-19 12.8.03 Consult Lutron for ordering information and model numbers. Dimensions and wiring may change based on options chosen. Option Description Application Double Lug Sets Allows multiple Panels to be fed from the same feed. A single feed and multiple LP Panels are required. Branch Circuit Protection Lutron Ten Volt Module (TVM) 2LinkTM Branch Circuit Breakers with higher AIC ratings than those on standard Panels. Panels can also have Branch Circuit Breakers with special ratings such as: GFI (Ground Fault Interrupt) ELB (Earth Leakage Breaker) CD (esidual Circuit Device). Allows Panels to operate fluorescent ballasts that meet IEC 929 standards for 0-10V control including: Lutron s TVE ballasts 0-10V neon PWM fluorescent Tridonic DSI (Digital Serial Interface). The TVM can sink or source 50mA (typically 25-50 ballasts) on each circuit. Allows a DMX512 theatrical console to operate Panels load circuits. Allows a GAFIK Eye 4000 Series to handle 128 zone (two links of 64 zones). The two links are independent and do not communicate. Contact Lutron for further details. Jobs with fluorescent ballasts that require 0-10V, PWM, or DSI control. Control of architectural lighting from a DMX512 theatrical console is required. A mix of architectural and theatrical lighting exists on the job. Tridonic is a registered trademark of Zumtobel AG. Job ame: SPECIFICATIO SUBMITTAL Model umbers: Job umber: