Technical Data Sheet. Hilti Firestop Collar CFS-C P. European Technical Approval ETA N o 10/0404. Issue 08 / Hilti Firestop Collar CFS-C P

Similar documents
TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

7/S5 FIRE DAMPER FD40. v 2.9 (en)

Report Number BTC 12261F

your and attach spreadsheet of 23 December 2003; and

Report Number BTC 12024F

Fire/combustion gas damper EKO-JBL

Fire/smoke damper EKO-JBG2

Table of Contents COOLMANT. 2.0 Table of Contents

Fire/combustion gas damper EKO-JBG

Combustion gas damper EKO-SRB

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

Bracket U Value at 1.5M Centres. 265mm 275mm 295mm 300mm 315mm 335mm 355mm mm.

Fire/smoke damper EKO-SRBG1

Table of Contents. EIGERFLEX -Clima. 2.0 Table of Contents

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

Combustion gas damper EKO-JB

Table of Contents 2.0 COOLFLEX CLX. 2.0 Table of Contents

K-FLEX NAME PRODUCT June 2016 K-FLEX. Rail Application. K-FLEX thermal and acoustic insulation solutions for rolling stock market

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS

Installation Instructions

Waste water drainage PRODUCT GUIDE. Wavin SiTech+ for low-noise soil & waste drainage

Heights up to 1000 mm Fire resistance period up to 120 minutes

INDOOR CLIMATE SOLUTIONS PRODUCT CATALOG Uponor Radiant Heating/Cooling

MÜPRO. One-piece pipe clamps. Sprinkler pipe clamps. Refrigerant pipe clamps. Two-piece pipe clamps. Heavy-duty pipe support/din pipe clamps

PIPE LOG BOOK. Project no:... Project:... Construction section:... On behalf of:... Commissioned by:... Order no:... Date:... Construction period:...

Heradesign fine Product Data & Certificates

Bevent Rasch BSK6. - Fire /04/2017

Table of contents. Chapter 1: Fusiotherm. Chapter 4: climasystem Produktgruppe 20. Chapter 5: aquatherm. Chapter 2: aquatherm SHT.

PSI CASING END SEALS FOR CASING PIPE CLOSURE FOR PROTECTION AGAINST MOISTURE AND DIRT ALSO FOR RETROFITTING INDIVIDUAL CUSTOMIZED SOLUTIONS

4 pole insulated conductor rails UNILIFT-ULA 35A, 50A, 80A, 100A

ToppTube PA11 (Polyamide) page 4. ToppTube PA12 (Polyamide) page 5. ToppTube PA12HIPHL (Polyamide) page 6. ToppTube PUR 98A (Polyurethane) page 7

PKI-C Cartridge Fire Dampers

FireFree ScandiBoard 850 Passive Fire Protection of Steel Constructions R30 - R180

FROTH-PAK INDEX. General. FROTH-PAK mini kit

Fire protection accessories for the glazing industry

Cordless Systems. Cordless Systems. Hilti. Outperform. Outlast. Cordless. Systems

Cordless Systems. Cordless Systems. Hilti. Outperform. Outlast.

Steel Spline Joint Bulkheads Junction: B-0 Class FIPRO MS 16 mm steel spline No x3 mm Construction: free-standing Sound reduction: 29 db (estima

Smoke damper EKO-SRB1

MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA

Bevent Rasch BSK Fire /04/2017

WGA Long throw nozzle grille

Round or Square Type Low-Profile Housing with Toroidal Transformer for Flangeless Trims E3_LF-HDSM-WR_ 1.0

CU-LT. Optimised rectangular fire damper up to C3-EN-J-06/2018

PRICE/ LISTE PRICELIST. My favorite: Curaflam Konfix pro. The sealing of flexible e pipes? No problem by using the Curaflex Nova Senso!

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance

Catalogue of Accessories

SECTION METAL LOCKERS

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of

PSI Compakt-Seals. Pipeline Accessories. Compakt-Standard Compakt-Special Compakt-Varia. General Information. Selection Guide. Order Submittal Sheet

Installation Trunking

VALSIR SUPPLY SYSTEMS MIXAL

GmbH Lufttechnik Dresden USER INFORMATION ROOF FANS SERIES VRV. vertical outlet. Issue 07/02

accqpulse Velocity Profiler Sensor Installation Guide

TECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES

U Thermo datasheets May Manufactured in Springs according to ISO 9001 : 2008 South Africa

Connecting ignition tool

Sound insulated doors

CATALOGUE SEWAGE MANHOLES

FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL

Plaster In Grilles 1/1.5/B/1. AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser

Channel without outlet box for concrete, in-situ or tiled floor

SEMI RIGID THE PROFESSIONALS CHOICE

piece of straight pipe with a minimum length of 25 cm. (see figure 13) For this purpose the 45 long bend is included in the Wavin AS program.

Contents Technical characteristics Han A Technical characteristics Han 3 A with HARAX Termination

10. Universal Clips. 254 Product overview 2013 We reserve the right to change designs and technical specifications of our products.

CR120. Optimised circular fire damper up to 120' C11-EN-L 06/2018

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

Aluminium Productive Fence System 40 PRODUCT CATALOGUE

INSTALLATION & OWNER S MANUAL

Technical and Dimensional Data. Double Wall One Inch Air Space AL 29-4C Stainless Steel Special Gas Vent

Fire damper BKA-EN. with general technical approval Z tested according to DIN EN

UNDERSTANDING FIREBLOCK

Shelving systems Stable construction, simple assembly

Test certificate General construction inspection test certificate Nr. 3666/4421 -a - Fe/Wi 1. Issue ( )

Contents Technical characteristics Han A Technical characteristics Han 3 A with HARAX Termination

Security steel door dw 62-1 Teckentrup

NEC 2011 Code Changes

Accessories and extra equipment fit for SCHRAMM-switchgear cabinets and SCHRAMM-protection boxes

M A D E L. FOK-EIS-180 Fire dampers CE

INDUSTRIAL HOSES 1

CR120. Optimized circular fire damper up to 120' C11-I 07/2015

DIVISION: METALS SECTION: COLD-FORMED METAL FRAMING REPORT HOLDER: WARE INDUSTRIES D/B/A MARINO\WARE

Type 567. Wafer Style Butterfly Valve

Fire damper ETPR. Specifications. Product code example Fire damper ETPR

Ventilation system Design and installation guide

Spaceloft Insulation TECHNICAL GUIDE

LK Shunt Cabinet VS2, Shunt Cabinet VS2 Prefab

PRODUCT INFORMATION

INSTALLATION & OWNER S MANUAL

Fire Dampers. Types FKA FRL FRK 4/1/EN/1

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

raugeo ground-source systems innovative heating & cooling solutions parts list /11 EN ENERGY EFFICIENCY Building Solutions Automotive Industry

SCION xb 2004 SATELLITE RADIO TUNER Section I Installation Preparation

MANUAL. Firescreen Temperature T1, T2, T3, T4

PSI Anti-Corrosion Tape

Transcription:

Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P European Technical Approval ETA N o 10/0404 Issue 08 / 2015 Hilti Firestop Collar CFS-C P Issue 02/2015 page 1

General information Pipe end configurations Page 03 Pipe end configurations according to intended use Page 04 Insulation configurations Page 05 Hilti Firestop Collar CFS-C P Page 06 Installation instructions Page 07 Fire classification detail tables for walls Walls Construction and minimum distances Page 08 Flexible and rigid walls minimum wall thickness 100 mm Page 08 Pre-insulated pipes Page 10 Plastic pipes Page 11 Plastic pipes with foamed elastomeric insulation Page 14 Composite pipes with foamed elastomeric insulation Page 16 Rigid walls minimum wall thickness 150 mm Page 17 Plastic pipes Page 18 Fire classification detail tables for floors Floors Construction and minimum distances Page 19 Rigid floors minimum density of 2400 kg/m 3 Page 19 Pre-insulated pipes Page 21 Plastic pipes Page 22 Plastic pipes with foamed elastomeric insulation Page 26 Composite pipes Page 27 Composite pipes with foamed elastomeric insulation Page 28 Rigid floors minimum density of 550 kg/m 3 Page 29 Pre-insulated pipes Page 29 Plastic pipes Page 29 Plastic pipes with foamed elastomeric insulation Page 32 Composite pipes Page 33 Composite pipes with foamed elastomeric insulation Page 33 Hilti Firestop Acrylic Sealant CFS-S ACR Product data sheet Page 35 Installation instructions Page 36 Specification Additional attributes Page 37 page 2 Hilti Firestop Collar CFS-C P Issue 02/2015

Pipe end configurations All pipes tested according to EN 1366-3 have been tested with a specific pipe end configuration. In the fire classification, the first letter of the end configuration refers to the end conditions within the furnace (fire-side), the second letter to the end conditions outside the furnace (non-fire-side). EI 90 U / U Configuration outside furnace Configuration inside furnace Fire resistance classification in minutes, Test condition Pipe end configuration Inside furnace Outside furnace U / U Uncapped Uncapped C / U Capped Uncapped U / C Uncapped Capped C / C Capped Capped As the EN test standard EN 1366-3 states, it is important to ensure that sealing systems have been tested with appropriate pipe end conditions. The conditions the pipe and sealing system must endure in a fire situation depend on whether one or both ends of the pipe are sealed in practice, as pressures and the flow of hot gases will vary depending on whether the pipe is ventilated or not. There are rules that determine which tested end configurations are valid for additional pipe end situations. For metal pipes: Tested U / C C / U C / C Covered U / C Y N N C / U Y Y N C / C Y Y Y Y = acceptable, N = not acceptable For plastic pipes: Tested U / U C / U U / C C / C U / U Y N N N Covered C / U Y Y N N U / C Y Y Y N C / C Y Y Y Y Y = acceptable, N = not acceptable So, for example, a plastic pipe tested with the end configuration U / U will cover all possible end conditions. But a plastic pipe tested U / C will only cover the conditions U / C or C / C. Hilti Firestop Collar CFS-C P Issue 02/2015 page 3

Pipe end configurations according to intended use As previously stated, it is important to ensure that the tested pipe configuration corresponds to the intended use of the pipe. The table below outlines recommended end configurations for various intended pipe uses as per suggestions laid out in EN 1366-3 2009 H.4.2.2. In the event that a national regulation conflicts with this table, the national regulation takes precedence. Intended use of penetrations (list not exhaustive, other pipes uses possible) Application Penetration material Manufacturer, product (examples) Insulation Heating Al-Composite Geberit Mepla U / C CS Recommended pipe end classification KeKelit KELOX KM 110 CS Rehau Rautitan stabil PE-X Rehau Rautitan flex CS -R Aquatherm blue Aquatherm blue Faserverbundrohr Potable water Al-Composite Geberit Mepla U / C CS KeKelit KELOX KM 110 CS Rehau Rautitan stabil CS PE EN 12201-2 PE-HD 100 RC Wavin TS CS/LS PE-X Rehau Rautitan flex CS EN ISO 15874, DIN 8077/ 8078 (e.g. AquathermGreen, Aquatherm GreenFaserverbundrohr) CS/LS PCV-C Friatherm starr CS/LS Refrigeration ABS +GF+ COOL-FIT CS U/C Ventilated PE EN 1519, EN 12666-1 U / U Waste water Roof CI/CS Drainage PE-HD 1000 RC Wavin TS CS/LS PE-S2 Geberit Silent db20 EN 1451-1 Magnaplast Skolan db Pipelife Master 3 Poloplast Polo Kal NG Poloplast Polo Kal 3S Rehau Raupiano Plus Wavin AS/KeKelit Phonex AS Wavin SiTech PVC-C EN 1566-1 PVC-U EN ISO 1452, EN 1329-1, EN 1453-1 Pneumatic Al-composite Geberit Mepla C/C DIN 8077/8078 Sprinkler -R Aquatherm red U/C Industry Al-Composite Various Varies depending upon application, PE EN ISO 15494, DIN 8074/8075 i.e. consider whether pipe is pressurized (U/C), DIN 8077/8078 ventilated (U/U) or unventilated PVC-U EN ISO 15493, DIN 8061/8062 (U/C) CS page 4 Hilti Firestop Collar CFS-C P Issue 02/2015

Insulation configurations When sealing pipes, the insulation configuration must be considered. The following configurations are possible: Insulation over the entire length of the pipe (i.e. thermal insulation) Continued sustained Continued interrupted Insulation only required in the area of the penetration seal Local insulation, sustained Local insulation, sustained See page 35 for specification of suitable insulation products. Hilti Firestop Collar CFS-C P Issue 02/2015 page 5

Hilti Firestop collar CFS-C P Firestopping for flammable pipes up to 250 mm in diameter with European Technical Approval. Applications n Sealing flammable pipes from 50 mm to 250 mm in diameter in penetrations through fire compartment walls and floors n Pipe materials: PVC, PVC-U, PE, PE-HD, PE-X,, ABS, Al-composite n Suitable for use in openings in concrete, aerated concrete, masonry, drywall, shaft wall and coated board. n Different backfilling and sealing materials are covered Advantages n Quick and easy closure without use of a tool n Adjustable position tabs for simple fastening n Sound decoupling strip based on PE (foam) can be used n Low profile for tight installations Technical data Minimal wall thickness Minimal ceiling thickness Storage and transportation temperature - range Close aperture with CFS-C P 100mm 150mm -5 C - 50 C Gypsum plaster, cementitious mortar, Hilti Firestop Acrylic Sealant CFS-S ACR Expansion temperature 210 C The European Technical Approval (ETA) and the technical data sheet can be obtained via your local Hilti contact. Nominal pipe diameter Number of hooks and fasteners Order designation Sales Quantity Item Number 50 mm 2 Firestop collar CFS-C P 50/1.5 1 pc 00435406 63 mm 2 Firestop collar CFS-C P 63/2 1 pc 00435407 75 mm 3 Firestop collar CFS-C P 75/2.5 1 pc 00435408 90 mm 3 Firestop collar CFS-C P 90/3 1 pc 00435409 110 mm 4 Firestop collar CFS-C P 110/4 1 pc 00435410 125 mm 4 Firestop collar CFS-C P 125/5 1 pc 00435411 160 mm 6 Firestop collar CFS-C P 160/6 1 pc 00435412 180 mm 8 Firestop collar CFS-C P 180/7 1 pc 00435413 200 mm 8 Firestop collar CFS-C P 200/8 1 pc 00435414 225 mm 10 Firestop collar CFS-C P 225/9 1 pc 00435415 250 mm 12 Firestop collar CFS-C P 250/10 1 pc 00435416 page 6 Hilti Firestop Collar CFS-C P Issue 02/2015

Installation instructions Seal the opening: The aperture around the pipe is filled with gypsum plaster (flexible walls) or cementitious mortar (concrete walls/floors) over the full thickness of the wall/floor or alternatively sealed with minimum 25 mm thick Hilti Firestop Acrylic Sealant CFS-S ACR on both sides. Backfilling with stone wool may be omitted in case of small annular gaps and classifications EI 120. In case of missing sound decoupling means around the pipe it is recommended to use Hilti Firestop Acrylic Sealant CFS-S ACR as annular gap seal. If gypsum plaster or cementitious mortar is intended to be used it is recommended to install a PE foam strip around the pipe over the entire wall or floor thickness for sound de coupling of the pipe. Clean the plastic pipe. Remove all plaster/mortar or dust from the pipe in the area where the Firestop collar is to be installed. Close the Hilti Firestop Collar: Place the Hilti Firestop Collar around the plastic pipe and apply firm pressure by hand until it latches with a "click" sound. No tools, pins or screws are necessary. The Hilti Firestop Collar can be re-opened by pushing down the engaged "tongue" with a screwdriver while pulling the Hilti Firestop Collar apart. Attach fastening hooks/tabs: The fastening hooks can be attached to various points of the metal housing. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indicated below and on the packaging. Fasten the Hilti Firestop Collar: a) Attach fastening hooks/tabs on the metal housing. b) Mark the fastening points on the wall/floor. c) Fasten the Hilti Firestop Collar, using recommended metal anchors/fasteners, e.g. Hilti HUS for rigid walls and floors or threaded rod, nuts, washers in flexible walls. These are defined in the respective test reports and approvals. d) If required by national prescriptions mark the penetration seal with an identification plate containing the required information. In such a case fasten the identification plate in a visible position next to the seal. For wall applications: Repeat installation on the other side of the wall. Collar sizes and number of hooks for suitable pipe diameters FS Collar P 50/1,5" 2 FS Collar P 63/2" 2 FS Collar P 160/6" 6 FS Collar P 250/10" 12 FS Collar P 75/2,5" 3 FS Collar P 90/3" 3 FS Collar P 180/7" 8 FS Collar P 200/8" 8 FS Collar P 110/4" 4 FS Collar P 125/5" 4 FS Collar P 225/9" 10 Hilti Firestop Collar CFS-C P Issue 02/2015 page 7

1. Flexible and rigid walls, minimum wall thickness 100 mm The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Flexible walls / drywalls (E) with a minimum thickness of 100 mm (t E ), with timber or steel studs lined on both faces with a minimum of two layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and any stud, and the cavity must be filled with a minimum of 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) over the entire thickness of the wall or Hilti Firestop Acrylic CFS-S ACR Sealant (A2) on both sides with a depth of minimum 25 mm from the surface of the wall. Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 450 kg/m 3, minimum thickness 100 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire thickness of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on both sides with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool. Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum thickness see tables below. page 8 Hilti Firestop Collar CFS-C P Issue 02/2015

Annular gap seal (drawings show non-insulated pipes as example) Gypsum plaster (A 3 ) Gypsum plaster (A 3 ) together with sound decoupling (C 1 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Gypsum plaster or cementitious mortar (A 3 ) Gypsum plaster or cementitious mortar (A 3 ) together with sound decoupling (C 1 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Pipe insulation (drawings show mortar as an example for the annular gap seal) Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS) Hilti Firestop Collar CFS-C P Issue 02/2015 page 9

Flexible and rigid walls 100 mm 1.1. Pre-insulated pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 120-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 60-U/C page 10 Hilti Firestop Collar CFS-C P Issue 02/2015

Flexible and rigid walls 100 mm 1.2. Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification PVC-U EN ISO 1452-2, 50 mm 2.4 5.6 mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, 63 mm 3.0 4.7 mm CFS-C P 63/2 5 mm) EN 1329-1, 75 mm 2.2 3.6 mm CFS-C P 75/2.5 EN 1453-1 90 mm 2.7 4.3 mm CFS-C P 90/3 110 mm 2.2 8.1 mm CFS-C P 110/4 125 mm 3.7 6.0 mm CFS-C P 125/5 160 mm 2.5 11.8 mm CFS-C P 160/6 PE EN 1519, 50 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U EN 12201-2, EN 12666-1 63 mm 3.0 mm CFS-C P 63/2 5 mm) 75 mm 3.0 mm CFS-C P 75/2.5 90 mm 3.5 mm CFS-C P 90/3 110 mm 4.2 mm CFS-C P 110/4 125 mm 4.8 mm CFS-C P 125/5 160 mm 6.2 mm CFS-C P 160/6 EN ISO 15494, 50 mm 2.9 4.6 mm CFS-C P 50/1.5 EI 120-U/U DIN 8074/5 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 90-U/U 63 mm 3.6 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 2.7 10.0 mm CFS-C P 110/4 EI 120-U/U 125 mm 3.1 7.1 mm CFS-C P 125/5 EI 120-U/U 160 mm 4.0 9.1 mm CFS-C P 160/6 EI 120-U/U EN ISO 15874 50 mm 1.8 2.9 mm CFS-C P 50/1.5 EI 90-U/U DIN 8077/8078 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 60-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 60-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 15.0 mm CFS-C P 90/3 EI 120-U/U 110 mm 2.7 mm CFS-C P 110/4 EI 120-U/U EN 1451-1 32 mm 1,8 CFS-C P 50/1.5 EI 120-U/U DIN EN 12056 40 mm 1,8 CFS-C P 50/1.5 EI 120-U/U 50 mm 1,8 2,0 CFS-C P 50/1.5 EI 120-U/U 70 mm 4,5 CFS-C P 75/2.5 EI 120-U/U 75 mm 1.8 3.8 CFS-C P 75/2.5 EI 120-U/U 90 mm 2.8 4.5 CFS-C P 90/3 EI 120-U/U 110 mm 2.7 5.3 CFS-C P 110/4 EI 120 U/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 11

Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification EN ISO 15874 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 90-U/C DIN 8077/ 8078 63 mm 5.8 10.5 mm CFS-C P 63/2 EI 60-U/C 63 mm 10.5 mm CFS-C P 63/2 EI 120-U/C 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 60-U/C 75 mm 6.8 12.5 mm CFS-C P 75/2.5 EI 120-U/C Branded pipes Pipe end configuration U/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 Geberit 56 mm 3.2 mm CFS-C P 63/2 EI 120-U/U (PE-S2) 63 mm 3.2 mm CFS-C P 63/2 EI 120-U/U 75 mm 3.6 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 5.6 mm CFS-C P 90/3 EI 120-U/U 110 mm 6.0 mm CFS-C P 110/4 EI 120-U/U Wavin TS (PE-HD Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U 100 RC) 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Geberit Silent 32 mm 1,8 mm CFS-C P 50/1.5 EI 120-U/U Ostendorf Skolan-dB, Phonex AS, Pipelife 40 mm 1,8 mm CFS-C P 50/1.5 EI 120-U/U Master 3, POLO- 50 mm 1,8 2,0 mm CFS-C P 50/1.5 EI 120-U/U PLAST Polo Kal NG, 56 mm 4,0 mm CFS-C P 63/2 EI 90-U/C POLOPLAST Polo Kal 3S, Rehau Raupiano 70 mm 4,5 mm CFS-C P 75/2.5 EI 120-U/U Plus, Wavin AS / 75 mm 1,8 3,8 mm CFS-C P 75/2.5 EI 120-U/U KeKelit Phonex AS, Wavin SiTech, 90 mm 2,8 4,5 mm CFS-C P 90/3 EI 120-U/U Cloes Blue Power, 110 mm 2,7 5,3 mm CFS-C P 110/4 EI 120 U/U Cloes PhoNoFire, Valsire Triplus, Valsire Silere, Marley Silent Aquatherm blue, 50 mm 1,8 2,9 mm CFS-C P 50/1.5 EI 90-U/U Aquatherm blue Faserverbundrohr, 63 mm 1,8 5,8 mm CFS-C P 63/2 EI 60-U/U Aquatherm red, 75 mm 1,9 6,8 mm CFS-C P 75/2,5 EI 60-U/U 9 mm Aquatherm green, 75 mm 6,8 12,5 mm CFS-C P 75/2.5 EI 120 U/U Aquatherm green Faserverbundrohr, 90 mm 8,2 15,0 mm CFS-C P 90/3 EI 120 U/U +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe 110 mm 2,7 mm CFS-C P 110/4 EI 120 U/U page 12 Hilti Firestop Collar CFS-C P Issue 02/2015

Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Aquatherm blue, 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 90-U/C Aquatherm blue Faserverbundrohr, 63 mm 5.8 10.5 mm CFS-C P 63/2 EI 60-U/C Aquatherm red, 63 mm 10.5 mm CFS-C P 63/2 EI 120-U/C Aquatherm green, 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 60-U/C Aquatherm green Faserverbundrohr, 75 mm 6.8 12.5 mm CFS-C P 75/2.5 EI 120-U/C +GF+ PROGEF 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 90-U/C Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe Branded pipes Pipe end configuration C/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 Geberit 135 mm 6.0 mm CFS-C P 160/6 EI 120-C/U (PE-S2) 160 mm 7.0 mm CFS-C P 160/6 EI 120-C/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 13

Flexible and rigid walls 100 mm 1.3. Plastic pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe material Pipe norm Pipe diameter PE EN 1519, EN 12201-2, EN 12666-1 EN ISO 15874 DIN 8077/8078 Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 110 mm 4.2 mm 10 mm CFS-C P 125/5 EI 90-U/U Continued Interrupted 110 mm 4.2 mm 25 mm CFS-C P 160/6 EI 90-U/U Continued sustained 40 mm 3.7 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C page 14 Hilti Firestop Collar CFS-C P Issue 02/2015

Branded Pipes Pipe designation Wavin TS (PE-HD 100 RC) Friatherm starr (PVC-C) Rautitan flex (PE-Xa) Aquatherm Climatherm Faserverbundrohr () Aquatherm Firestop () PROGEF Standard pipe () Pipe manufacturer Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe Aquatherm green Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 40 mm 3.7 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 90 mm 10.0 15.1 mm 22.5 mm CFS-C P 125/5 EI 120-U/C 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 40 mm 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued green Faserverbundrohr 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C Continued 63 mm 5.8 mm 10 mm CFS-C P 75/2.5 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 90 mm 8.2 mm 10 mm CFS-C P 110/4 EI 120-U/C 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 40 mm 4.5 mm 9 mm CFS-C P 63/2 EI 120-U/C 50 mm 5.6 mm 9 mm CFS-C P 75/2.5 EI 120-U/C length 200 mm 63 mm 7.1 mm 10 mm CFS-C P 90/3 EI 120-U/C Rehau 40 mm 5.5 mm 9 mm CFS-C P 63/2 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 63 mm 8.6 mm 10 mm CFS-C P 75/2.5 EI 120-U/C length 250 mm Aquatherm 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 40 mm 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C +GF+ 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 15

Flexible and rigid walls 100 mm 1.4. Composite pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe designation and material Geberit Mepla (PE-Xb/Al/ PE-HD) Rautitan stabil (PE-Xa/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE) Pipe manufacturer Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration Geberit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 3.0 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 40 mm 3.5 mm 9 mm CFS-C P 63/2 EI 120-U/C 50 mm 4.0 mm 9 mm CFS-C P 63/2 EI 120-U/C 63 mm 4.5 mm 10 mm CFS-C P 75/2.5 EI 60-U/C 75 mm 4.7 mm 10 mm CFS-C P 90/3 EI 90-U/C Rehau 16 mm 2.6 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 4.7 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 120-U/C Ke Kelit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 3.0 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 32 mm 3.0 mm 9 mm CFS-C P 50/1.5 EI 90-U/C 40 mm 4.0 mm 9 mm CFS-C P 50/1.5 EI 90-U/C 50 mm 4.5 mm 9 mm CFS-C P 63/2 EI 90-U/C 63 mm 6.0 mm 10 mm CFS-C P 75/2.5 EI 90-U/C page 16 Hilti Firestop Collar CFS-C P Issue 02/2015

2. Rigid walls The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 650 kg/m 3, minimum thickness 150 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire thickness of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool. Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum thickness see tables below. Hilti Firestop Collar CFS-C P Issue 02/2015 page 17

Rigid walls 150 mm 2.1. Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO 1452-2, 180 mm 3.6 8.6 mm CFS-C P 180/7 EI 180-U/U EN ISO 15493, DIN 8061/2, 200 mm 4.0 9.6 mm CFS-C P 200/8 EI 180-U/U EN 1329-1, 225 mm 4.5 10.8 mm CFS-C P 225/9 EI 180-U/U EN 1453-1 250 mm 4.9 11.9 mm CFS-C P 250/10 EI 180-U/U PE EN 1519, EN 12201-2, 200 mm 6.2 mm CFS-C P 200/8 EI 120-U/U EN 12666-1 250 mm 7.8 mm CFS-C P 250/10 EI 120-U/U EN ISO 15494, 180 mm 4.4 16.4 mm CFS-C P 180/7 EI 120-U/U 5 mm) DIN 8074/5 200 mm 4.9 11.4 mm CFS-C P 200/8 EI 120-U/U 200 mm 11.4 mm CFS-C P 200/8 EI 180-U/U 225 mm 5.5 12.8 mm CFS-C P 225/9 EI 180-U/U 250 mm 6.2 14.2 mm CFS-C P 250/10 EI 180-U/U Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO 1452-2, 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/C EN ISO 15493, DIN 8061/2, 250 mm 4.9 11.9mm CFS-C P 250/10 EI 180-U/C EN 1329-1, EN 1453-1 PE EN ISO 15494, 50 mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C DIN 8074/5 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 250 mm 7.8 22.7 mm CFS-C P 250/10 EI 120-U/C 5 mm) Normed pipes Pipe end configuration C/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification EN 1451-1 200 mm 6.2 6.8 mm CFS-C P 200/8 EI 120-C/U DIN EN 12056 250 mm 8.6 mm CFS-C P 250/10 EI 120-C/U Branded pipes Pipe end configuration C/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent 200 mm 6.2 6.8 mm CFS-C P 200/8 EI 120-C/U Ostendorf Skolan-dB, Phonex AS, Pipelife 250 mm 8.6 mm CFS-C P 250/10 EI 120-C/U Master 3, POLO- PLAST Polo Kal NG, POLOPLAST Polo Kal 3S, Rehau Raupiano Plus, Wavin "AS / KeKelit Phonex AS, Wavin SiTech, Cloes Blue Power, Cloes PhoNoFire, Valsire Triplus, Valsire Silere,Marley Silent page 18 Hilti Firestop Collar CFS-C P Issue 02/2015

3. Rigid floors, minimum density of 2400 kg/m 3 The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Rigid floors (E) consisting of concrete with a minimum density of 2400 kg/m 3, minimum thickness 150 mm. Penetration seal consists of a single penetration in the floor with Hilti Firestop Collar CFS-C P (A1) on the underside of the floor. Annular gap filled either with gypsum plaster or cementitious mortar (A3) over the entire thickness of the floor or with mineral wool of minimum density 60 kg/m 3 covered by Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on top side (or on both sides) with a depth of minimum 10 mm. Classifications EI 120 and lower (opening diameter up to 300 mm), classification EI 180 (opening diameter up to 260 mm): The opening diameter should not be larger than the collar outside diameter to allow a safe fixing of the collar to the floor. Classification EI 180 (opening diameter > 260 mm): see in tables below. Minimum distance between collars/annular gap edge (s1): 0 mm. Firestop collar (A1) fastened by hooks (minimum number of hooks: see instructions for use) with metal anchors (e.g. Hilti HUS) on the underside of the floor (minimum 6 mm up to collar size 110/4" and 10 mm for higher collar sizes). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the floor. For maximum thickness see tables below. Hilti Firestop Collar CFS-C P Issue 02/2015 page 19

Annular gap seal (drawings show non-insulated pipes as example) Gypsum plaster or cementitious mortar (A 3 ) Cementitious mortar (A 3 ) together with sound decoupling (C 1 ) A3 C1 Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Pipe insulation (drawings show mortar as an example for the annular gap seal) Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Gypsum plaster or cementitious mortar (A 3 ) page 20 Hilti Firestop Collar CFS-C P Issue 02/2015

Rigid Floors 2400 kg/m 3 3.1. Pre-insulated Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded Pipes Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 60-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 21

Rigid Floors 2400 kg/m 3 3.2. Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO 1452-2, 20 mm 1.5 2.2 mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, 50 mm 2.4 5.6 mm CFS-C P 50/1.5 EN 1329-1, 63 mm 3.0 4.7 mm CFS-C P 63/2 5 mm) EN 1453-1 75 mm 2.2 3.6 mm CFS-C P 75/2.5 90 mm 2.7 4.3 mm CFS-C P 90/3 110 mm 1.8 8.1 mm CFS-C P 110/4 125 mm 3.7 6.0 mm CFS-C P 125/5 160 mm 2.5 11.8 mm CFS-C P 160/6 180 mm 3.6 8.6 mm CFS-C P 180/7 200 mm 4.0 9.6 mm CFS-C P 200/8 225 mm 4.5 10.8 mm CFS-C P 225/9 250 mm 4.9 11.9 mm CFS-C P 250/10 PVC-C EN 1566-1 20 mm 1.5 2.2 mm CFS-C P 50/1.5 EI 120-U/U 50 mm 2.4 5.6 mm CFS-C P 50/1.5 63 mm 3.0 4.7 mm CFS-C P 63/2 5 mm) 75 mm 2.2 3.6 mm CFS-C P 75/2.5 90 mm 2.7 4.3 mm CFS-C P 90/3 110 mm 1.8 8.1 mm CFS-C P 110/4 125 mm 3.7 6.0 mm CFS-C P 125/5 160 mm 2.5 11.8 mm CFS-C P 160/6 180 mm 3.6 8.6 mm CFS-C P 180/7 200 mm 4.0 9.6 mm CFS-C P 200/8 225 mm 4.5 10.8 mm CFS-C P 225/9 250 mm 4.9 11.9 mm CFS-C P 250/10 PE EN 1519, 50 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U EN 12201-2, EN 12666-1 63 mm 3.0 mm CFS-C P 63/2 75 mm 3.0 mm CFS-C P 75/2.5 5 mm) 90 mm 3.5 mm CFS-C P 90/3 110 mm 4.2 mm CFS-C P 110/4 125 mm 4.8 mm CFS-C P 125/5 160 mm 6.2 mm CFS-C P 160/6 200 mm 6.2 mm CFS-C P 200/8 250 mm 7.7 mm CFS-C P 250/10 EN ISO 15494, 20 mm 1.9 2.8 mm CFS-C P 50/1.5 EI 90-U/U DIN 8074/5 50 mm 2.9 4.6 mm CFS-C P 50/1.5 EI 120-U/U 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 2.7 10.0 mm CFS-C P 110/4 EI 120-U/U 125 mm 3.1 7.1 mm CFS-C P 125/5 EI 120-U/U 160 mm 4.0 9.1 mm CFS-C P 160/6 EI 120-U/U page 22 Hilti Firestop Collar CFS-C P Issue 02/2015

Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PE EN ISO 15494, 20 + 20 mm 1.9 mm CFS-C P 50/1.5 EI 90-U/U DIN 8074/5 2 Pipes in 1 Collar 20 + 20 mm 2.8 mm CFS-C P 50/1.5 EN ISO 15874 20 mm 1.9 3.4 mm CFS-C P 50/1.5 EI 120-U/U DIN 8077/8078 50 mm 1.8 2.9 mm CFS-C P 50/1.5 EI 120-U/U 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 180-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 180-U/U 110 mm 2.7 mm CFS-C P 110/4 EI 180-U/U 125 mm 3.1 mm CFS-C P 125/5 EI 180-U/U EN 1451-1 32 mm 1,2 1,8 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1,8 mm CFS-C P 50/1.5 50 mm 1,8 2,0 mm CFS-C P 50/1.5 58 mm 4,0 mm CFS-C P 63/2 75 mm 1,9 4,5 mm CFS-C P 75/2.5 78 mm 4,5 mm CFS-C P 75/2.5 90 mm 2,8 4,5 mm CFS-C P 90/3 110 mm 2,7 5,3 mm CFS-C P 110/4 125 mm 3,9 5,3 mm CFS-C P 125/5 135 mm 5,3 mm CFS-C P 160/6 160 mm 4,9 5,3 mm CFS-C P 160/6 Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO 1452-2, 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/C EN ISO 15493, DIN 8061/2, 250 mm 4.0 11.9 mm CFS-C P 250/10 5 mm) EN 1329-1, EN 1453-1 PE 5 mm) EN ISO 15494, DIN 8074/5 EN ISO 15874 DIN 8077/8078 50 mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C 180 mm 4.4 16.4 mm CFS-C P 180/7 EI 120-U/C 200 mm 4.9 11.4 mm CFS-C P 200/8 EI 120-U/C 225 m 5.5 12.8 mm CFS-C P 225/9 EI 120-U/C 250 mm 6.2 22.7 mm CFS-C P 250/10 EI 120-U/C 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 40 mm 3.7 5.5 mm CFS-C P 50/1.5 EI 120-U/C 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 180-U/C 63 mm 5.8 10.5 mm CFS-C P 63/2 EI 180-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C 75 mm 6.8 12.5 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C 90 mm 8.2 15.0 mm CFS-C P 90/3 EI 120-U/C 110 mm 10.0 15.1 mm CFS-C P 110/4 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 23

Branded pipes Pipe end configuration U/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 Geberit 75 mm 3.6 mm CFS-C P 75/2.5 EI 180-U/U (PE-S2) 90 mm 5.6 mm CFS-C P 90/3 EI 180-U/U 110 mm 6.0 mm CFS-C P 110/4 EI 180-U/U 135 mm 6.0 mm CFS-C P 160/6 EI 120-U/U 160 mm 7.0 mm CFS-C P 160/6 EI 180-U/U Wavin TS Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U (PE-HD 100 RC) 63 mm 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Geberit Silent 32 mm 1,2 1,8 mm CFS-C P 50/1.5 EI 180-U/U Ostendorf Skolan-dB, Phonex AS, Pipelife 40 mm 1,8 mm CFS-C P 50/1.5 EI 180-U/U Master 3, POLO- 50 mm 1,8 2,0 mm CFS-C P 50/1.5 EI 180-U/U PLAST Polo Kal NG, 58 mm 4,0 mm CFS-C P 63/2 EI 180-U/U POLOPLAST Polo Kal 3S, Rehau Raupiano 75 mm 1,9 4,5 mm CFS-C P 75/2.5 EI 180-U/U Plus, Wavin AS / 78 mm 4,5 mm CFS-C P 75/2.5 EI 180-U/U KeKelit Phonex AS, Wavin SiTech, 90 mm 2,8 4,5 mm CFS-C P 90/3 EI 90-U/U Cloes Blue Power, 110 mm 2,7 5,3 mm CFS-C P 110/4 EI 180-U/U Cloes PhoNoFire, Valsire Triplus, 125 mm 3,9 5,3 mm CFS-C P 125/5 EI 180-U/U Valsire Silere, Marley 135 mm 5,3 mm CFS-C P 160/6 EI 180-U/U Silent 160 mm 4,9 5,3 mm CFS-C P 160/6 EI 90-U/U Magnaplast Magnaplast 58 mm 4,0 mm CFS-C P 90/3 EI 180-U/U Skolan-dB pipes 78 mm 4,5 mm CFS-C P 75/2.5 90 mm 4,5 mm CFS-C P 90/3 110 mm 5,3 mm CFS-C P 110/4 135 mm 5,3 mm CFS-C P 160/6 160 mm 5,3 mm CFS-C P 160/6 Rehau Raupiano Rehau 50 mm 1,8 mm CFS-C P 50/1.5 EI 180-U/U Plus pipes (/-MV/) 75 mm 1,9 mm CFS-C P 75/2.5 EI 180-U/U 110 mm 2,7 mm CFS-C P 110/4 EI 180-U/U Wavin AS / KeKelit Wavin 70 mm 4,5 mm CFS-C P 75/2.5 EI 180-U/U Phonex AS pipes 90 mm 4,5 mm CFS-C P 90/3 EI 180-U/U 125 mm 5,3 mm CFS-C P 125/5 EI 180-U/U 160 mm 5,3 mm CFS-C P 160/6 EI 180-U/U Wavin SiTech pipes Wavin 75 mm 2,3 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 2,8 mm CFS-C P 90/3 EI 180-U/U 125 mm 3,9 mm CFS-C P 125/5 EI 180-U/U 160 mm 4,9mm CFS-C P 160/6 EI 180-U/U Aquatherm blue, Aquatherm 20 mm 1.9 3.4 mm CFS-C P 50/1.5 EI 120-U/U blue Faserver- bundrohr, Aquatherm 50 mm 1.8 2.9 mm CFS-C P 50/1.5 EI 180-U/U red, Aquatherm green, 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 180-U/U Aquatherm green 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 180-U/U Faser verbundrohr, +GF+ PROGEF 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 180-U/U Standard pipe, +GF+ 110 mm 2.7 mm CFS-C P 110/4 EI 180-U/U Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop 125 mm 3.1 mm CFS-C P 125/5 EI 180-U/U page 24 Industry pipe Hilti Firestop Collar CFS-C P Issue 02/2015

Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Aquatherm blue, 40 mm 3.7 5.5 mm CFS-C P 50/1.5 EI 120-U/C Aquatherm blue Faserverbundrohr, 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 180-U/C Aquatherm red, 63 mm 5.8 10.5 mm CFS-C P 63/2 EI 180-U/C Aquatherm green, 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C Aquatherm green Faserverbundrohr, 75 mm 6.8 12.5 mm CFS-C P 75/2.5 EI 120-U/C +GF+ PROGEF 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C Standard pipe, +GF+ Dekaprop Industry 90 mm 8.2 15.0 mm CFS-C P 90/3 EI 120-U/C pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe 110 mm 10.0 15.1 mm CFS-C P 110/4 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 25

Rigid Floors 2400 kg/m 3 3.3. Plastic pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe material Pipe norm Pipe diameter EN ISO 15874 DIN 8077/8078 Branded pipes Pipe designation Wavin TS (PE- HD-100 RC) Friatherm starr (PVC-C) Rautitan flex (PE-Xa) Pipe manufacturer Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 40 mm 3.7 5.5 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.6 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 75 mm 6.8 10.3 mm 10 mm CFS-C P 90/3 EI 180-U/C length 250 mm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 10.0 15.1 mm 10 mm CFS-C P 125/5 EI 180-U/C Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued Supllier 63 mm 5.8 mm 10 mm CFS-C P 75/2.5 75 mm 6.8 mm 10 mm CFS-C P 90/3 length 250 mm 90 mm 8.2 mm 9.5 mm CFS-C P 110/4 110 mm 10.0 mm 9.5 mm CFS-C P 125/5 Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Continued 40 mm 4.5 mm 9 mm CFS-C P 63/2 50 mm 5.6 mm 9 mm CFS-C P 75/2.5 length 200 mm 63 mm 7.1 mm 10 mm CFS-C P 90/3 Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 63 mm 8.6 mm 9 mm CFS-C P 90/3 EI 180-U/C length 250 mm 40 mm 6.0 mm 9 20.5 mm CFS-C P 63/2 EI 120-U/C 75/2.5 50 mm 6.9 mm 9 21 mm CFS-C P 75/2.5 EI 120-U/C 90/3 63 mm 8.6 mm 9 21.5 mm CFS-C P 90/3 EI 120-U/C 110/4 Aquatherm blue, 40 mm 3.7 5.5 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued Aquatherm 50 mm 4.6 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C blue Faserverbundrohr, 75 mm 6.8 10.3 mm 10 mm CFS-C P 90/3 EI 180-U/C length 250 mm Aquatherm red, 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C Aquatherm green, 110 10.0 15.1 mm 10 mm CFS-C P 125/5 EI 180-U/C Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe page 26 Hilti Firestop Collar CFS-C P Issue 02/2015

Rigid Floors 2400 kg/m 3 3.4. Composite pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Mepla Geberit 40 mm 3.5 mm CFS-C P 50/1.5 EI 90-U/C (PE-Xb/Al/PE-HD) 50 mm 4.0 mm CFS-C P 50/1.5 EI 120-U/C 63 mm 4.5 mm CFS-C P 63/2 EI 60-U/C 75 mm 4.7 mm CFS-C P 75/2.5 EI 30-U/C 110 mm 6.0 mm CFS-C P 110/4 EI 180-U/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 27

Rigid floors 2400 kg/m 3 3.5. Composite pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded Pipes Pipe designation Geberit Mepla (PE-Xb/Al/ PE-HD) Geberit Mepla (PE-Xb/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE-X) KELOX KM 110 (PE-X/Al/ PE-X) KELOX KM 110 (PE-X/Al/ PE-X) Rautitan stabil (PE-Xa//Al/ PE-HD) Pipe manufacturer Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration Geberit 40 mm 3.5 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.0 mm 9 mm CFS-C P 63/2 63 mm 4.5 mm 9 mm CFS-C P 75/2.5 length 250 mm 75 mm 4.7 mm 10 mm CFS-C P 90/3 Geberit 40 mm 3.5 mm 9 20.5 mm CFS-C P 63/2 EI 120-U/C 75/2.5 50 mm 4.0 mm 9 21 mm CFS-C P 63/2 90/3 63 mm 4.5 mm 9 21.5 mm CFS-C P 75/2.5 110/4 75 mm 4.7 mm 10 22 mm CFS-C P 90/3 125/5 KeKelit 32 mm 3.0 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Continuated 40 mm 4.0 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Sustained 50 mm 4.5 mm 9 mm CFS-C P 63/1.5 EI 180-U/C 63 mm 6.0 mm 10 mm CFS-C P 75/2.5 EI 120-U/C KeKelit 32 mm 3.0 mm 9 19.5 mm CFS-C P 50/1.5 EI 120-U/C Continuated 75/2.5 Sustained 40 mm 4.0 mm 9 20.5 mm CFS-C P 50/1.5 75/2.5 50 mm 4.5 mm 9 21 mm CFS-C P 63/2 90/3 63 mm 6.0 mm 10 21.5 mm CFS-C P 75/2.5 110/4 KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5 EI 120-U/C Continued 40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5 50 mm 4.5 mm 21 mm CFS-C P 90/3 length 250 mm 63 mm 6.0 mm 21.5 mm CFS-C P 110/4 Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 40 mm 6.0 mm 9-20.5 mm CFS-C P 63/2 EI 120-U/C 75/2.5 length 250 mm page 28 Hilti Firestop Collar CFS-C P Issue 02/2015

4. Rigid floors, minimum density of 550 kg/m 3 The floor must have a minimum thickness of 150 mm and comprise concrete or aerated concrete with a minimum density of 550 kg/m 3. For details of the penetration seal design see 3. Pipes shall be supported at maximum 250 mm away from the upper face of the floor construction. Rigid Floors 550 kg/m 3 4.1. Pre-insulated Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 60-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 120-U/C Rigid Floors 550 kg/m 3 4.2. Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO 1452-2, 20 mm 1.5 2.2 mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1 Pipe End Configuration U/U 50 mm 2.4 5.6 mm CFS-C P 50/1.5 EI 120-U/U PE EN ISO 15494, DIN 8074/5 Pipe End Configuration U/U EN ISO 15494, DIN 8074/5 2 Pipes in 1 Collar EN ISO 15874 DIN 8077/8078 20 mm 1.9 2.8 mm CFS-C P 50/1.5 EI 90-U/U 50 mm 2.9 4.6 mm CFS-C P 50/1.5 EI 90-U/U 20+20 mm 1.9 mm CFS-C P 50/1.5 EI 90-U/U 20+20 mm 2.8 mm CFS-C P 50/1.5 EI 90-U/U 20 mm 1.9 3.4 mm CFS-C P 50/1.5 EI 120-U/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 29

Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification EN ISO 15874 40 mm 3.7 5.5 mm CFS-C P 50/1.5 EI 120-U/C DIN 8077/8078 50 mm 4.6 6.9 mm CFS-C P 50/1.5 75 mm 6.8 mm CFS-C P 75/2.5 90 mm 12.3 mm CFS-C P 90/3 110 mm 10.0 15.1 mm CFS-C P 110/4 Branded pipes Pipe end configuration U/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 (PE-S2) 56 3.2 CFS-C P 63/2 75/2.5 EI 180-U/U Wavin TS (PE-HD-100 RC) Master 3 (-CO/-MV/- CO) Polo Kal 3S (/-MV/) Polo Kal NG (-CO/-MV/- CO) 63 3.2 CFS-C P 63/2 75/2.5 110 6.0 CFS-C P 110/4 Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U 63 mm 5.8 mm CFS-C P 63/2 EI 120-U/U 75/2.5 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Pipelife 32 mm 1.2 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 1.8 mm CFS-C P 50/1.5 75 mm 1.8 mm CFS-C P 75/2.5 110 mm 1.8 mm CFS-C P 110/4 POLOPLAST 75 mm 3.8 mm CFS-C P 75/2.5 EI 90-U/U 90 mm 4.5 mm CFS-C P 90/3 110 mm 4.8 mm CFS-C P 110/4 POLOPLAST 32 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 2.0 mm CFS-C P 50/1.5 75 mm 2.6 mm CFS-C P 75/2.5 90 mm 3.0 mm CFS-C P 90/3 110 mm 3.6 mm CFS-C P 110/4 Aquatherm blue, 20 mm 1.9 3.4 mm CFS-C P 50/1.5 EI 120-U/U Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe page 30 Hilti Firestop Collar CFS-C P Issue 02/2015

Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Aquatherm blue, 40 mm 3.7 5.5 mm CFS-C P 50/1.5 EI 120-U/C Aquatherm blue Faserverbundrohr, 50 mm 4.6 6.9 mm CFS-C P 50/1.5 Aquatherm red, 75 mm 6.8 mm CFS-C P 75/2.5 9 mm Aquatherm green, 90 mm 12.3 mm CFS-C P 90/3 Aquatherm green Faserverbundrohr, 110 mm 10.0 15.1 mm CFS-C P 110/4 +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Polo Kal NG (-CO/ -MV/-CO) POLOPLAST 200 mm 6.8 mm CFS-C P 200/8 EI 180-U/C 250 mm 8.6 mm CFS-C P 250/10 EI 180-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 31

Rigid Floors 550 kg/m 3 4.3. Plastic Pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter EN ISO 15874 DIN 8077/8078 Branded pipes Pipe end configuration U/C Pipe designation Rautitan flex (PE-Xa) Aquatherm Climatherm Faserverbundrohr Aquatherm Fusiotherm Faserverbundrohr Aquatherm Firestop Pipe manufacturer Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 90 mm 110 mm 12.3 mm 15.1 mm 22.5 mm 10 mm CFS-C P 160/6 CFS-C P 125/5 EI 120-U/C EI 120-U/C Continued length 250 mm Pipe diameter Pipe wall thickness Insulation thickness Collar size Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2 75/2.5 50 mm 6.9 mm 21 mm CFS-C P 75/2.5 90/3 Classification EI 120-U/C EI 120-U/C 63 mm 8.6 mm 21.5 mm CFS-C P 110/4 EI 120-U/C Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Insulation configuration Continued length 250 mm page 32 Hilti Firestop Collar CFS-C P Issue 02/2015

Rigid Floors 550 kg/m 3 4.4. Composite pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Mepla Geberit 40 mm 3.5 mm CFS-C P 50/1.5 EI 90-U/C (PE-Xb/Al/PE-HD) 50 mm 4.0 mm CFS-C P 50/1.5 EI 120-U/C 63 mm 4.5 mm CFS-C P 63/2 EI 60-U/C 75 mm 4.7 mm CFS-C P 75/2.5 EI 30-U/C Rigid Floors 550 kg/m 3 4.5. Composite pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe end configuration U/C Pipe designation Geberit Mepla (PE-Xb/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE-X) Rautitan stabil (PE-Xa/Al/ PE-HD) Pipe manufacturer Pipe diameter Pipe wall thickness Insulation thickness Collar size Geberit 40 mm 3.5 mm 20.5 mm CFS-C P 63/2 75/2.5 50 mm 4.0 mm 21 mm CFS-C P 63/2 90/3 63 mm 4.5 mm 21.5 mm CFS-C P 75/2.5 110/4 75 mm 4.7 mm 22 mm CFS-C P 90/3 125/5 Classification EI 120-U/C EI 120-U/C EI 120-U/C EI 120-U/C Insulation configuration Continued length 250 mm KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5 EI 120-U/C Continued 40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5 EI 120-U/C 50 mm 4.5 mm 21 mm CFS-C P 90/3 EI 120-U/C length 250 mm 63 mm 6.0 mm 21.5 mm CFS-C P 110/4 EI 120-U/C Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2 EI 120-U/C Continued 75/2.5 length 250 mm Hilti Firestop Collar CFS-C P Issue 02/2015 page 33

Loose mineral wool products suitable for being used as backfilling material of CFS-S ACR Firestop Acrylic Sealant: Product Heralan LS Isover loose wool SL Isover Universal-Stopfwolle Rockwool RL Paroc Pro Loose Wool Manufacturer Knauf Insulation Saint-Gobain Isover Saint-Gobain Isover Rockwool Paroc OY AB Suitable insulation products; Combustible insulation (closed cell flexible elastomeric foam, e.g. AF/Armaflex). Reaction to fire minimum B-s3, d0 (acc. to EN 13501-1) Combustible insulation for sound decoupling ( elastomeric foam, e.g. PE). Reaction to fire minimum E (acc. to EN 13501-1) page 34 Hilti Firestop Collar CFS-C P Issue 02/2015

Hilti Firestop acrylic sealant CFS-S ACR An acrylic based firestop sealant that provides movement capability in fire rated linear joint seals and penetration seals Applications n Within or between flexible wall constructions n Vertical joints in / between wall constructions n Horizontal joints in a wall abutting a floor, ceiling or roof n Joints in floor construction n Penetration seals (steel and copper pipes) Advantages n Easy to dispense, apply and tool n Strong adhesion to various base materials n Low shrinkage after curing n Excellent airborne sound insulation property n Broad application temperature range Technical data CFS-S ACR Chemical basis Water-based acrylic dispersion Volume shrinkage < 20 % Movement 12.5 % (ISO 11600) Cure Time (at 23 C / 50 % r.h.) ~ 3 mm / 72 h Application temperature range 5 C 40 C Storage and transportation 5 C 25 C temperature - range Shelf life (@73 F / 23 C and 24 month(s) 50 % relative humidity) Reaction to fire class D-s1d0 (EN13501-1) Approvals* ETA 10 / 0292, ETA 10 / 0389 * The European Technical Approval (ETA) can be obtained via your local Hilti contact or www.hilti.com Packaging Volume Color Order designation Sales Quantity Item Number Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc 00435859 Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc 00435860 Cartridge 310 ml Grey Firestop acrylic sealant CFS-S ACR 1 pc 00435862 Foil pack 580 ml White Firestop acrylic sealant CFS-S ACR 20 pc 00435863 Pail 5 l White Firestop acrylic sealant CFS-S ACR 1 pc 00435864 Pail 10 l White Firestop acrylic sealant CFS-S ACR 1 pc 02046766 Hilti Firestop Collar CFS-C P Issue 02/2015 page 35