INSTALLATION, OPERATION & MAINTENANCE INSTRATIONS

Similar documents
Warning. Document ref: A October 2015

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils

Features: Concealed installation. Compact design. Available in electric, LPHW or ambient.

PRECISION UK Ltd DUPLEX AGSS PLANT

Operations & Maintenance Manual DFH-1000 DUCTLESS FUME HOOD

AIR FILTER MODEL NO: AF1000 OPERATION & MAINTENANCE INSTRUCTIONS PART NO:

564 Shadowbox Face (w Screen) Instructions

PIL0478 ISSUE 01/ 07/16

HR25 Solo. Installation and User Instructions. Through the Wall Heat Recovery Ventilators

(UK) Date : January 2014

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

Florham Park, NJ USA Call (ASCO) for sales or service

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

AIR CLEANERS. Model MX 6000 OWNER S MANUAL CAUTION. Read complete instructions before operating. Please file for future reference.

EWP 110 INSTALLATION INSTRUCTIONS

24V 3A EN54 Ancillary Power Supply

DAVIES, CRAIG PROPRIETARY LIMITED A.B.N A.C.N MELBOURNE AUSTRALIA

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Peristaltic Pump Operating Instructions

BOLT-ON AND WELD-ON FLUSH FLOOR SLIDEOUT SYSTEMS OPERATION AND SERVICE MANUAL

N-084M and N-069M-DV Series Heat Exchanger Replacement

Asymmetrical Installation Instructions. Components: i2cove Asymmetrical LED Light Fixtures. 12 [305mm] [918mm] 48.

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

Florham Park, NJ USA Call (ASCO) for sales or service

KLIMA Active Chilled Beams

LC I LIPPERT COMPONENTS HYDRAULIC FULL WALL SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL

SPH General Manual 400 Series

HAN-L62 MOUNTING PLATE

Revision THERMO TECHNOLOGIES. USDT 2001 Differential Controller. Installation and User s Guide

Installation, Operation & Maintenance Instructions 250 C Laboratory Fan Ovens Apex Range models AX30, AX60 & AX120

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

OPERATING SERVICE MAINTENANCE MANUAL

TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved.

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

Linea 28 Mark 1. Serial Number up to VOKERA SPARE PARTS BREAKDOWN

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

mygrid Installation Notes

Aerocourse Fan Assisted Trench Heating

SERVICE MANUAL (INTERNATIONAL)

The EFL 2000/1 & 2 User Guide Test Sieve Shaker. Contents

Hydro-Sync Slide-Out System

TO BE USED ONLY BY AUTHORISED PERSONNEL

3 FT CORD Models , , , FT CORD W/GFCI Models , , ,

Installation Instructions

Snapshot LX5 USER MANUAL. OK on Dimmer Outdoor OK Sound Activated DMX512 Master/Slave 115V/230V Switch Replaceable Fuse User Serviceable Duty Cycle

Controls and Accessories Part Number Controls and Accessories Part Number

Operating & Maintenance Manual Break Tank & Pump Set Model BTAB Arrow Valves

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c.

E.S.P. Embedded Sensing Probes for Motor Brushes

C RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

MANUAL CONTROL / SEMIAUTO TEMPERATURE CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

Solstice Electric Fryers SE Series Service Manual

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

Plaster In Grilles 1/1.5/B/1. AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser

Service & Maintenance

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

F L B Metal Halide Light Generator for Fiber Optic Lighting Systems

Electric Stone Hearth Oven

Halton Rex 600 RE6 - Adaptable active chilled beam

Embedded Rack Slide-out System

Electric Diesel Pump EDP/12, EDP/24

WhispAire Range Hood Quiet Hood

ELECTRIC WATER PUMP (EWP ) KIT INSTALLATION INSTRUCTIONS

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009

READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

CURVED CC5 CC5 RF6 CC5 RF9 CC5 RF12 CC5 RF15 CC5 HT6 CC5 HT9 CC5 HT12. Page 1. Download C.A.D models or contact us on COSSIGA.COM

AIR CLEANERS Model MC 3000 OWNER S MANUAL CAUTION Read complete instructions before operating. Please file for future reference.

USER INSTRUCTIONS STRIKER LED USER INSTRUCTIONS

Instruction Manual. E1M40, E1M80, E2M40 and E2M80 E2M40S and E2M80S Rotary Vacuum Pumps. Item Number

Driftsinstruks. Utopia kontroller feilkoder PCP-2HTE og PC-ART. Vi håper de får stor glede av et Novema kulde produkt!

Single Point Overfill Prevention Control Monitor Model: ST-15C Series Technical Manual

IMPORTANT SAFETY INSTRUCTIONS

3 FT CORD UL/NEC Models , , , FT CORD w/gfci UL Models , , ,

www. ElectricalPartManuals. com Operator s Manual

READ AND SAVE THESE INSTRUCTIONS

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

COMFORT AIR CURTAIN. SensAir

ROMpak Series. Keeping the World Flowing. Installation Manual. Valve Actuators

COMFORT AIR CURTAIN. SensAir

Troubleshooting PROBLEM LIKELY CAUSE(S) SOLUTION(S)

This chapter describes how to perform periodic inspection and maintenance to ensure the long operating life of the chamber.

Operating & Maintenance Manual Compact Domestic Booster Set Model BTAF Arrow Valves

Features: Available in horizontal and vertical units

5000TOC Sensor Service Manual

MODEL MC1500 Installation and Operation Manual Important:

GLM SERIES CONTROL Users Manual Rev:

ECONOPLATE BV SERIES HOT WATER SERVICE PACKAGED HEAT EXCHANGERS WITH THERMAL STORES

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

Service and Parts Guide: Matrx Central Scavenger Waste Anesthetic Gas Disposal System

Fan Powered Low Profile Variable Volume Terminal Units

MODEL GS1-100 Air Filtration System. Operations Manual

Sofa Slideout Assembly OWNER'S MANUAL. Rev: Page 1 Sofa Slideout Owners Manual

Advantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.

RIGID PENDANT. Phoenix Pipeline Products Limited. Installation, Operation and Maintenance Manual

Transcription:

INSTALLATION, OPERATION & MAINTENANCE INSTRATIONS (27/6/13)

Contents 1. GENERAL DESCRIPTION... 2 2. RECEIPT AND PREPARATION... 2 3. INSTALLATION... 2 3.1. REMOVAL OF ACCESS PANEL... 2 3.2. FIXING A PLINTH... 2 3.3. REMOVING MOTOR PLATE... 3 3.4. CHANGE OF HANDING... 3 3.5. CHANGE OF CONNECTION ORIENTATION... 4 3.6. FIXING THE UNIT... 4 3.7. BUILDER S WORK... 4 3.8. WIRING... 5 4. OPERATION & MAINTENANCE... 9 4.1. ELECTRIC MOTOR PROTECTION... 9 4.2. THERMOSTATIC OPERATION... 9 4.3. FILTER... 9 4.4. COIL... 9 4.5. FAN SET... 9 4.6. SPARES... 10 5. FAULT FINDING... 10 5.1. FAN OPERATION... 10 5.2. HEATING... 10 Page 1

1. GENERAL DESCRIPTION This manual covers the Copperad Fan Convector range. These are cabinet type units intended for either vertical or horizontal mounting. Controls can be contained within the casing to give a clean outline or installed remote (on-site by the contractor) for easy customer control. 2. RECEIPT AND PREPARATION The units are wrapped and display the serial number, model reference, site reference (where appropriate). Installation, operation and maintenance instructions, together with wiring and any special instructions are all supplied with the unit. On receipt, check that all details are correct to the Customer Schedules prior to opening packaging. Damage should be reported to the supplying B S S branch immediately. It is recommended that packaging is kept in place and the units stored in a safe area until the necessary services are completed, in order to avoid the possibility of damage on site. 3. INSTALLATION 3.1. REMOVAL OF ACCESS PANEL The panel should be affixed to the casing by means of the hook at the bottom of the front panel. Screw fixing through the top of the grille then ensures positive retention of the front panel to the case. Key locks may alternatively be provided where key locks are fitted, the screw fixing at the top of the grille may also be carried out for additional safety. SCREW FIXING THROUGH GRILLE KEY OPERATED LOCKS 3.2. FIXING A PLINTH Figure 1: Access panel To fix a plinth, which will be in a separate package, line it up to the casing with the long side flange to the front. Mark the hole positions on the bottom casing panels and drill no 30 holes for the self tapping screws. Page 2

3.3. REMOVING MOTOR PLATE IMPORTANT: Isolate unit electrically at mains controls! Remove front access panel. Disconnect the section of the terminal block marked LTC. Disconnect casing earthwire. Remove the front seal plate by loosening the two M5 bolts Slide out the motor-plate IMPORTANT TE On ceiling mounted units ensure that the motor plate and seal plate are adequately supported before releasing the transit bolts. 3.4. CHANGE OF HANDING Unless otherwise specified all units will be supplied with heat exchangers having 3/4 connections at the Right Hand end. If it is necessary to reverse this handing on site this is easily achieved by following these instructions: Ensure unit has been isolated from mains power supplies. Remove the front access panel and slide out the motor plate as 3.3 above. Unscrew the two M6.0 hex head screws securing the heat exchanger, plus the M5 screw holding the connection blanking plate, and lift clear, taking care that no damage occurs to the fins of the heat exchanger fin block Undo the M5 screw holding the LTC blanking plate in place, turn the coil around and switch the blanking plate positions. Swap the LTC location around. Reverse actions above to re-fit motor-plate. SEAL PLATE SEAL PLATE FASTENING TERMINAL BLOCK Figure 2: Seal plate & Terminal Box Page 3

3.5. CHANGE OF CONNECTION ORIENTATION Units are supplied, as standard with water connections pointing downwards. If required these can be reversed by turning the coil upside down. Remove the access panel, unscrew the M6 screws holding the heat exchanger and turn over. Replace the screws and access panel. LTC BLANKING PLATE CONNECTION BLANKING PLATE Figure 3: LTC & Connection blanking plate 3.6. FIXING THE UNIT All units have pilot holes in the back plate for attaching to a wall or ceiling. Mark as required from the casing, then drill and plug to suit No 10 wood screws for vertical applications. For suspended horizontal applications, bolts or hanger rods should be used through the strengthening strips attached to the inside back of the case. 3.7. BUILDER S WORK When using cased models for concealed applications, the builder s work surrounding the unit must have adequate provision for removing the front access panel of the unit, by providing a removable section of panelling. This is to provide access for filter cleaning etc. A similar provision must be made for Hideaway units, although in this case the removable panelling must be large enough to pull out the complete fan tray assembly and provide access to the valves and air vent, etc. If ducting is not fitted between the Hideaway s spigotted outlet and the air outlet grille, a suitable baffle must be provided around the spigot, to seal off the unit within the enclosure and prevent re-circulation of the discharged air. Page 4

3.8. WIRING Unit length (mm) Speed Power drawn (W) Current (A) SFP (W/l/s) Low 14 0.11 0.26 600 Medium 18 0.14 0.28 High 27 0.21 0.36 Low 21 0.16 0.18 900 Medium 29 0.19 0.21 High 40 0.25 0.25 Low 25 0.15 0.14 1200 Medium 35 0.21 0.16 High 46 0.28 0.19 Table 1: Electrical Data All electrical work should be carried out in accordance with current I.E.T regulations. The basic wiring diagram is as shown in Diagram no 1. Unless a switched fused spur box is to be fitted to the unit the mains lead is connected to the left hand side of the terminal block where marked mains. The casing rear or side panels should be drilled for the mains lead entry. When supplied, the switched fused spur box will be secured for transit within the unit together with it s cable gland entry bush. This box may be fixed to the outside of the casing with the entry bush, in a suitable position (drill casing to suit). The leads coming from the spur box should be connected into the terminal block section marked mains and the incoming mains supply connected into the spur box. If remote controls are to be used, wire into the lower left hand section of the terminal block as shown in diagram no 2. The remote thermostats should be mounted on the wall in accordance with the manufacturer s instructions (supplied with each thermostat). Connect the upper left hand section of the terminal block and replace the terminal block cover plate. If the handing has been changed on site, disconnect the casing earth lead at its casing end and reconnect at the non-pipe work end. Make sure the unit is protected by a 3 amp fuse. Two types of wire are used; solid coloured indicates 230Vac, twin coloured is 10Vdc control wiring. The basic wiring shown in Figure 4 is for a unit without optional control equipment fitted as such it is set to run continuously at the medium speed setting. Note that the wires in a single solid colour are subject to 230V ac while the twin colour cables and yellow links are the 10V dc control wires. The optional switch and thermostats which can be inbuilt are shown together with the arrows and numbers indicating the connecting wire and terminal block positions that they would occupy if fitted. If any of these options are inbuilt, then some of the dotted links shown numbered 1 to 5 are removed as follows. If on/off thermostat (T1) is required, then link 1 would not be fitted. Page 5

If speed change thermostat medium to low (T2) is required, then link 3 would not be fitted. If speed change thermostat high to medium (T3) is required, then link 4 would not be fitted and link 2 must be fitted between 5 and 6. If speed control switch is required, then link 2 would not be fitted. If summer/winter switch is required, then link 5 would not be fitted. If fan enable relay is required, then terminals 10 and 11 would be fitted. Notes 1. The LTC is factory fitted as shown in diagram no 1. If LTC is not required, link terminals 2 and 3. 2. T1, T2 and T3 cannot all be inbuilt and wired in together as indicated in the diagram. They must be fitted in combinations of T1 and T2, T1 and T3 or T2 and T3. If however, a control system involving all three is required, then it is recommended that the T1 thermostat is remotely mounted. 3. If summer/winter switch and fan enable relay are required, terminal 12 would be fitted. The fan enable relay will be linked between terminals 1 and 12 and the summer/winter switch linked between terminals 12 and 2. 4. 0-10v direct BMS control is possible using the incoming 0-10v on terminal 10 and incoming 0v on terminal 11. Link 5 should then be removed, terminal 10 wired to 0-10v on the board and terminal 11 wired to 0v on the board. 5. If a unit wired for single speed running is required to operate at low speed, then alter link 2 to connect between positions 5 and 7 on the terminal block. Similarly, for high speed re-connect link 2 between positions 5 and 9. Page 6

Figure 4 : Wiring Diagram 1 Page 7

Figure 5: Wiring Diagram 2 When required to operate with remotely mounted controls, units will be supplied wired for medium speed running as shown in Figure 5. Page 8

Remote options are wired using the same rules as internal options. For all units, we recommend a 3 amp fuse is fitted. IMPORTANT: Isolate unit electrically at mains controls before carrying out any work. The remote switch and thermostats required should be fitted to the removable sections of the terminal block as shown above. 4. OPERATION & MAINTENANCE 4.1. ELECTRIC MOTOR PROTECTION On ceiling mounted and reverse airflow applications where the fan motor is switched off for long periods, with hot water still circulating through the heat exchanger in excess of 82 C (180 F), it is recommended that a system be employed which automatically closes the hot water supply valve to prevent damage to the electric motor due to overheating. 4.2. THERMOSTATIC OPERATION The T1 and T2 thermostats both have graduated scales to cover their range of operation. Since the thermostatic bulb is frequently unit mounted, it may be offset by various amounts from the measured room temperature. Set the knob at mid-range and adjust to suit comfort conditions within the room. The range corresponds to a sensed temperature range of 10 o C to 30 o C. T1 and T2 are adjustable and determine the comfort room temperature range. Set T2 for the low and T1 for the high point. Example T2 16 o C and T1 20 o C. The standard LTC is not adjustable (45 o C) and provides a fan cut-off for the situation where the water temperature is not sufficiently high to provide warm blown air from the fan convector.. The LTC is mounted at the non-void end of the unit, and is clipped on to a return bend of the coil. To electrically test a unit to confirm operation before heat is available, short circuit terminal 2 and 3 on the terminal block. 4.3. FILTER Air filters will be fitted on either the air inlet grille or between the motor plate and coil (behind the seal plate). Filters should be gently tapped to remove most of the accumulated dust and either vacuumed clean or washed in lukewarm water with detergent. Rinse in clean water and allow to dry naturally before replacement. 4.4. COIL Remove the access panel and clean the coil with a brush or by vacuuming, taking care not to damage the coil surfaces. 4.5. FAN SET The motor has sealed for life sleeve bearings, which under normal circumstances require no Page 9

user maintenance. The motor deck is accessed by means of the access panel and is readily removed if required. Occasional vacuuming or cleaning of the motor plate is recommended. 4.6. SPARES For spare parts, quote the model reference and code given on the product label attached within the unit. Give a complete description, voltage and/or dimensions of the part(s) required. 5. FAULT FINDING 5.1. FAN OPERATION Check fuse on motor plate. Check power supply to unit. Check loose wiring and breaker plugs or damage to wiring. Check switches or bypass the switches. Check impellers run freely. 5.2. HEATING Check thermostat operation (change set point to maximum) where fitted. Check integrity of wiring. Check coil vented. Check hot water to unit. Check thermostat bulb in air stream. Check LTC contact on pipe-work or return bend. Page 10

FAN FAILS TO RUN YES CHECK POWER TO UNIT ADVISE CLIENT YES SWITCH OR THERMOSTAT FITTED (MAYBE INTERNAL) YES CHECK SWITCH IS ON AND THERMOSTAT CORRECTLY SET SWITCH ON/ADJUST THERMOSTAT YES CHECK WATER FLOW TEMPERATURE ABOVE 43 o C FAN RUNS RE-ATTACH LTC YES CHECK LTC FIRMLY FITTED ISOLATE UNIT, BYPASS LTC WITH LINK 2-3 THEN SWITCH ON FAN RUNS FAN RUNS ISOLATE UNIT AND CHECK WIRING IS TO WIRING DIAGRAM REWIRE YES FAN RUNS CHECK IMPELLER FOR FREE MOVEMENT, CONTACT LOCAL BSS OFFICE Figure 6 : Fault finding Page 11

The Copperad logo is a registered trademark of S & P Coil products Ltd, Evington Valley Road, Leicester. In accordance with our policy of continual product improvement, we reserve the right to amend the data contained in this document without prior notification. Page 12