Installation Instructions 300 A Current Sensor Kit for D1h/D3h/D5h/D6h Enclosure Sizes VLT Series FC 102, FC 103, FC 202, and FC 302

Similar documents
Installation Instructions 500 A Current Sensor Kit for D2h/D4h/D7h/D8h Enclosure Sizes VLT Series FC 102, FC 103, FC 202, and FC 302

Installation Instructions 500 A Current Sensor Kit for F1 F4/F8 F13 Enclosure Sizes VLT Series FC 102, FC 202, and FC 302

Control Card VLT FC Series

Installation Instructions Bus Bar Kit for 6-pulse, 4-drive System VLT Series FC 102, FC 202, and FC 302. Description. Kit Part Number.

Installation Instructions In-bottom/Out-back Cooling Kit for E4h Drives VLT FC Series FC 102, FC 103, FC 202, and FC 302

Installation Guide. VLT Real-time Clock MCB 117 VLT HVAC Drive FC 102, VLT Refrigeration Drive FC 103, VLT AQUA Drive FC 202, VLT AutomationDrive

Installation Instructions In-back/Out-back Cooling Kit for D5h/D6h and D7h/D8h Enclosures VLT Series FC 102, FC 202, and FC 302

INSTRUCTIONS INSTALLATION OF LOAD-SHARE TERMINALS FOR VLT DRIVES

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

Disassembling and assembling isave 21

Marine Annex covering all VLT Drives Note

Changing pistons APP and APP 16-22

Installation Guide VLT Parallel Drive Modules

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit

Installation Guide. Auxiliary Pressure Control Manifold on 6890 GC Accessory G1570A

Upgrading the Boxer LAD blower module

Installation Instructions. PowerFlex 700 Drive - Frame 8 Components Replacement

Changing pistons APP 21-43

Section 1.0 Warnings Section 2.0. Section 3.0. Section 4.0. MCD3000 Inside Delta Connection Kits. Contents

Thank you for purchasing a Borla Performance Stainless Steel Header.

INSTALLATION INSTRUCTIONS

INSTRUCTIONS 177R0076 INSTALLATION OF TOP AND BOTTOM COVERS FOR IP00 FRAMES D3, D4 & E2 INTO RITTAL ENCLOSURES

RANGER 900 POWER STEERING KIT

Installation Guide. DEVIreg 527. Electronic Time Regulator.

5. Installation on Pedestal - IP 21 / IP 54 Units 43

Altivar 61/71 Adjustable Speed Drives Spare Parts Kits

SURFACE/CEILING & SUSPENDED MOUNT INSTALLATION

Disassembling and assembling PAH , PAHT and PAHT G

3 Internal Frequency Converter Operation 43

CHROME ALLEY CAT L.E.D. FUEL & BATTERY GAUGE 7381

FOG LAMPS INSTALL KIT

Disposal declaration Frequency Converters Frame Size: D1, D2, D3, D4, D5, D6, D7 and D8 (New Generation) Production Place: USA and India

TYPE APPROVAL CERTIFICATE

Control Panel Interface Upgrade Installation Guide For Model 200i and 250i Motorcycle Dynamometers Serial Number 202xxxx.

MAKING MODERN LIVING POSSIBLE. Instruction Manual VLT AutomationDrive FC 300

TYPE APPROVAL CERTIFICATE

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions

Avoid damage to the motorcycle. Protect painted surfaces with a soft cloth or blanket.

(1) Remote Control with (2) AAA Batteries

TOYOTA Yaris Hatchback EC REARVIEW MIRROR Preparation

HVAC HOUSING - REMOVAL AND INSTALLATION

PowerFlex 7000 AC Drive with Direct-to-Drive Technology. Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions

SCION xa AUTO-DIMMING MIRROR Preparation

PowerFlex 700 Drive - Frame 8 Components Replacement

This kit may void factory warranty please check with manufacturer.

ATEX instruction for APP / PAH PAHT G 2-90 / PAH Tech

Turbo Upgrade Kit Installation for Ford F-150 PN s , ,

"Engineered to Ride, Built to Last "

Table of Contents. 1.0 INFORMATION 1.1 Introduction. 1.2 Product Information. 2.0 INSTALLATION 2.1 Pre-Installation. 2.2 Component Installation

Appendix: Safety and application notes for... 15

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only

Please call us at Mon-Fri 8am-5pm if you need any additional assistance.

Altivar 58 TRX Adjustable Speed Drive Controllers in Motor Control Centers hp, 480 V or 1 50 hp, 208/240 V Class 8998

NOVO LIGHTED MIRROR. Installation Instructions

ChangeOver6 and NovoCon ChangeOver6 - Motorized 6-port Ball Valves

Installation manual portable distributors

PROCEDURE STEPS: WARNING:

M-9603-FST FOCUS ST COLD AIR INTAKE KIT INSTALLATION INSTRUCTIONS

Starting Torque Limiter Type TCI (Soft Start)

Installation Instructions

- Wiring Brochure Universal Reset Module 422e

Superlift Leveling System / 6 Upgrade System for 2004 and Newer Ford F-150 4WD INSTALLATION INSTRUCTIONS

Installation Instructions For Motor Control Center (MCC) Units

INSTALLATION INSTRUCTIONS

Appendix: Safety and application notes for 19

Installation Instructions

INSTALLATION INSTRUCTIONS SEMI Hidden Kit Part Number: Application: Toyota Tacoma

SCION xb EC REARVIEW MIRROR Preparation

Butterfly valve with electrical actuator VFY-WA

Butterfly valve with electrical actuator VFY-WA

Floor heating system, heating circuit with FHV-A in flow.

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

Installing the Boxer fan upgrade kit

TOYOTA YARIS XM SATELLITE RADIO Preparation (Sedan & Hatchback)

The steering column is of a modular construction and features easy to service electrical switches.

"Engineered to Ride, Built to Last "

NANOTUNE. Installation Manual

Part Number: PT

SCION xb AUTO-DIMMING MIRROR Preparation

PowerFlex 700 Drive - Frame 9 Components Replacement

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

LVPS Replacement Instruction Sheet

HAZARDOUS LOCATION STREET LIGHT SLA SERIES INSTALLATION INSTRUCTIONS

SERVICE INSTRUCTIONS

TOYOTA PRIUS XM SATELLITE RADIO Preparation

LED Fog Light. Conflicts Note: 1832, 1852, 1856, 1872, General Applicability Fits Models

Installation Instructions

Installation Instructions

E.S.P. Embedded Sensing Probes for Motor Brushes

BOSTON TOWER MERCHANDISER ILLUMINATION KIT (P/N ) INSTALLATION INSTRUCTIONS

Agilent G1554A On-Column Capillary Inlet with EPC

ReadyLift (Part# ) Ford F-350 4WD Leveling Kit Installation Instructions

Premounted Midi Shunts

IMPORTANT SAFETY INSTRUCTIONS

MOUNT KIT Ford F-150 4X

INSTRUCTIONS Servicing PAH

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Assisted lift operated 2/2-way solenoid valves Type EV251B

Transcription:

1.1 Description The 300 A current sensor kit is designed for D1h/D3h/D5h/D6h enclosure sizes in the power ranges shown in Table 1.1. To identify the power rating, see Illustration 1.1. Product group and series Voltage rating Power rating VLT HVAC Drive FC 102, VLT Refrigeration Drive FC 103, VLT AQUA Drive FC 202 VLT AutomationDrive FC 302 (T4) 380 480 V 110 200 kw (150 300 hp) (T7) 525 690 V 75 315 kw (75 350 hp) (T5) 380 500 V 90 160 kw (125 200 hp) (T7) 525 690 V 55 250 kw (75 350 hp) 1 Product group and product series 2 Power rating 3 Voltage rating (phases and mains) Illustration 1.1 Nameplate for VLT AQUA Drive FC 202, 200 kw Table 1.1 Applicable Power Range for 300 A Current Sensor Kit This 300 A current sensor kit contains all components required to upgrade the current sensors in D1h, D3h, D5h, or D6h enclosure sizes. 1.1.1 Identifying the Power Rating To find the frequency converter power rating, use the following steps. 1. Obtain the following information from the nameplate, which is on the frequency converter. Refer to Illustration 1.1. 1.2 Kit Part Number Part number 176F6516 Kit description Current sensor kit for D1h/D3h/D5h/D6h Table 1.2 Part Number for 300 A Current Sensor Kit 1.2.1 Items Supplied For the complete parts list of the 300 A current sensor kit, see Illustration 1.4. 1a Product group and product series (characters 1 6) 1b Power rating (characters 7 10) 1c Voltage rating (phases and mains) (characters 11 12) 2. Determine if the power rating is in Table 1.1. Danfoss A/S 10/2016 All rights reserved. MI70Y102

1.3 Safety Instructions CAUTION TRAINING REQUIRED Only certified technicians trained by Danfoss are allowed to replace the parts described in these installation instructions. Installation work done by non-qualified personnel can result in personal injury or equipment damage. Make sure to read and save these instructions. WARNING ELECTRICAL SHOCK HAZARD VLT frequency converters contain dangerous voltages when connected to mains voltage. Improper installation, and installing or servicing with power connected, can cause death, serious injury, or equipment failure. To avoid death, serious injury, or equipment failure: Only use qualified electricians for the installation. Disconnect the frequency converter from all power sources before installation or service. Treat the frequency converter as live whenever the mains voltage is connected. Follow the guidelines in these instructions and local electrical safety codes. WARNING DISCHARGE TIME The frequency converter contains DC-link capacitors, which can remain charged even when the unit is off. High voltage can be present even when the warning indicator lights are off. Failure to wait a minimum of 20 minutes after power is removed before performing service work can result in death or serious injury. 1. Stop the motor. 2. Disconnect AC mains and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters. 3. Disconnect or lock PM motor. 4. Wait 20 minutes for the capacitors to discharge. 5. To verify full discharge, measure the voltage level. 1.4 Disassembly Guidelines NOTICE The current sensor kit includes an extra set of fasteners in case any fasteners are missing or unusable. To make the disassembly/reassembly process easier, use these general guidelines: 1. Follow the disassembly instructions for each component. 2. Place the component along with the removed fasteners together in one place. 3. Replace old component with the new component provided in the kit. 4. If any fasteners are stripped or lost, replace with similar fastener from the kit. 5. Follow the installation instructions for replacing and securing each component. 2 Danfoss A/S 10/2016 All rights reserved. MI70Y102

1.4.1 Removing AC Input Busbars Optional components mounted on the input terminal plate can result in differing configurations. These options include an RFI filter and AC fuses. See Illustration 1.2. Use the appropriate procedure based on the options present in the unit. No options 1. Remove the air baffle by removing 4 screws (T25), 1 from each corner. 2. Remove 3 nuts (13 mm) at the top of the input busbars, 1 per busbar. 3. Remove 6 nuts (13 mm) at the bottom of the input busbars, 2 per busbar. 4. Lift the input busbars from the unit. AC fuses only 1. Remove the air baffle by removing 4 screws (T25), 1 from each corner. 2. Remove the 3 AC fuses by removing 6 nuts (13 mm), 1 at each end of each fuse. 3. Remove 3 nuts (13 mm) at the top of the busbars, 1 per phase. 4. Lift the input busbars from the unit. RFI filter only 1. Remove the air baffle by removing 4 screws (T25), 1 from each corner. 2. Remove 3 nuts (13 mm) at the top of the RFI filter, 1 per bus phase. 3. Remove 6 nuts (13 mm) at the bottom of the RFI filter, 2 per phase. 4. Remove 4 mounting screws (T20) connecting the RFI filter to the side channels of the frequency converter. 5. Remove the RFI filter and unplug the RFI cable from the MK100 connector on the RFI card. AC fuses and RFI filter 1. Remove the air baffle by removing 4 screws (T25), 1 from each corner. 2. Remove AC fuses by removing 6 nuts (13 mm), 1 at each end of each fuse. 1 Input busbar 6 Power terminal mounting plate 2 RFI filter (optional) 7 Retaining nut 3 AC fuse (optional) 8 EMC shield 4 Terminal label 9 Output motor terminal 5 Mains input terminal 10 Mixing fan Illustration 1.2 AC Input Busbars with Optional RFI Filter and AC Fuses 3. Remove 3 nuts (13 mm) at the top of the RFI filter, 1 per phase. 4. Remove 4 screws (T20) connecting the RFI filter to the side channels of the frequency converter. 5. Remove the RFI filter and unplug the RFI cable from MK100 on the RFI card. 1.4.2 Removing Input Terminal Block 1. Disconnect the input power wiring. 2. Remove 2 screws (T25) at the bottom of the terminal block. 3. Remove 1 screw (T25) at the bottom of the EMC shield. 4. Release the current sensor wiring from retaining clips. 5. To remove the terminal, slide the terminal down to disengage it from the metal clips holding it in place. MI70Y102 Danfoss A/S 10/2016 All rights reserved. 3

1.4.3 Removing EMC Partition 1. Remove 1 screw (T25) at the top of the EMC shield. 2. Remove the EMC shield from the unit. 1.4.4 Removing Brake Terminal (optional) 1. Disconnect the brake wiring, if any. 2. To detach the R (+) terminal, remove 1 screw (T25) at the terminal block, and 1 additional screw (T40). 3. To detach the R (-) terminal, remove 1 screw (T25) at the terminal block, and 1 additional nut (13 mm). 4. To detach the brake terminal block, remove 2 nuts (13 mm). 1.4.6 Removing Power Terminal Mounting Plate 1. Remove the 4 retaining screws (T20) from the plate. 2. Remove the 3 nuts (M8) from the bottom edge of the plate. 3. Unplug the current sensor cables. 4. While pulling the plate up, unplug the mixing fan cable, located under the mounting plate. The mixing fan can remain in place in the mounting plate. 1.4.5 Removing Output Terminal Block 1. Disconnect motor wiring. 2. To detach the U output busbar, remove 1 screw (T25) from the busbar center and 1 bolt (T40) at the current sensor end. 3. To detach the V output busbar, remove 1 screw (T25) from the busbar center and 1 bolt (T40). 4. To detach the W output busbar, remove 1 screw (T25) from the busbar center and 1 bolt (T40). 5. Remove the 3 cylindrical busbars from the current sensors. 6. Remove the 2 screws (T25) at the bottom of the terminal block. 7. To remove the terminal, slide the terminal down to disengage it from the metal clips holding it in place. 1 Current sensor 5 Mixing fan 2 Retaining screw (T20) 6 Mixing fan slot 3 Power terminal mounting plate 7 Nut (8 mm) 4 Mixing fan cable Illustration 1.3 Power Terminal Mounting Plate 4 Danfoss A/S 10/2016 All rights reserved. MI70Y102

1.5 Reassembly Guidelines 1 M10x30 hex screw with captive washer (Qty 6) 12 M5x11 thread-cutting screw (Qty 4) 2 M10 hex nut (Qty 6) 13 M8 hex nut with captive washer (Qty 3) 3 Input label 14 Busbar insulation sleeve 4 Input/mains terminal block 15 Motor busbar, U 5 M5x12 machine screw with captive washer (Qty 11) 16 Motor busbar, V 6 Partition 17 Motor busbar, W 7 M5x16 Torx screw (Qty 3) 18 300 A current sensor 8 Output label 19 M4x8 Torx screw (Qty 6) 9 Output/motor terminal block M6x90 Torx screw (Qty 3) (not shown) 10 Input terminal mounting plate (Qty 2) IGBT busbars, U,V,W (not shown) 11 Mixing fan Wire harness (See Illustration 1.6.) Illustration 1.4 Exploded View and Parts List of 300 A Current Sensor Kit MI70Y102 Danfoss A/S 10/2016 All rights reserved. 5

1.5.1 Installing Current Sensors NOTICE TERMINAL MOUNTING PLATE There are 2 input terminal mounting plates included in the kit (1 for IP20 and 1 for IP21/IP54). Use the one that fits the enclosure size. 1. Align the current sensors so that the cable connectors face the back of the unit. 2. Attach each of the 3 new current sensors to the power terminal mounting plate using 2 screws (M4x8) per sensor. Torque to 2.8 Nm (24 in-lb). 3. Connect the wire harness to the current sensors. 4. Run the wire harness through the wire guides. 1.5.2 Installing Power Terminal Mounting Plate 1. Unplug the old wire harness from the power card and discard the harness. 2. Insert the power terminal mounting plate into the unit. To ease installation, insert the bottom of the plate near the bottom of the frequency converter. 3. Secure the plate with 4 thread-cutting screws (M5x11). Torque to 1.7 Nm (15 in-lb). 4. Connect the top of the wire harness to the power card. See Illustration 1.6. 5. Connect the bottom of the wire harness to the mixing fan. 6. Insert the mixing fan into the fan housing, with the label facing the open side of the housing. 7. With the fan label facing up, snap the mixing fan assembly into the plate opening. When properly seated, the fan assembly is level with the plate. 8. Install 3 hex nuts with captive washer (M8) onto the power terminal mounting plate. Torque to 19 Nm (169 in-lb). 1 Wire harness (current sensor) 2 Current sensor 3 Power terminal mounting plate 4 Wire harness (fan) Illustration 1.5 Wire Harness Attached to Current Sensors on Power Terminal Mounting Plate 6 Danfoss A/S 10/2016 All rights reserved. MI70Y102

1 Power card 5 Power terminal mounting plate 2 Power card connector to current sensor wire harness 6 Power card connector to RFI filter 3 Wire harness (current sensor) 7 Power card connector to fan wire harness 4 Current sensor 8 Wire harness (fan) Illustration 1.6 Power Terminal Mounting Plate with Current Sensors and Wire Harness MI70Y102 Danfoss A/S 10/2016 All rights reserved. 7

1.5.3 Installing Output Terminal Block 1. Place the output terminal label in its original position above the terminal connections U (T1), V (T2), W (T3). 2. Push the output terminal block up against the metal clips on the power terminal mounting plate until they engage. 3. Secure with 2 machine screws (M5x12) at the bottom of the terminal block. Torque to 2.3 Nm (20 in-lb). 4. Roll up the insulator sheet and insert it into the middle of each current sensor. 5. Insert the cylindrical busbar inside the insulator sheet. 6. Slide the insulation sleeve over the U-phase busbar. 7. Secure each motor busbar with 1 Torx screw (M5x16) near the current sensor and 1 thread-forming screw in the busbar center. Torque the Torx screw to 2.3 Nm (20 in-lb) and the thread-forming screw to 4.0 Nm (35 in-lb). 1.5.4 Installing Brake Terminal (optional) 1. Install the optional brake terminal block using 2 nuts (M8). Torque to 9.6 Nm (85 in-lb). 2. Install the R (-) terminal using 1 thread-forming screw (M4x8) at the terminal block, and 1 nut (M8). Torque the thread-forming screw to 2.8 Nm (24 in-lb) and the nut to 9.6 Nm (85 in-lb). 3. Install the R (+) terminal using 1 thread-forming screw (M4x8) at the terminal block, and 1 screw (T40). Torque the thread-forming screw to 2.8 Nm (24 in-lb) and the T40 screw to 9.6 Nm (85 in-lb). 4. Connect the brake wiring. 1.5.5 Installing Partition with EMC Shield 1. Install the partition to the left of the motor terminal block. 2. Secure with 2 machine screws (M5x12). Torque to 2.3 Nm (20 in-lb). 1.5.6 Installing Input Terminal Block 1. Place the input terminal label in its original position above the terminal connections R (L1), S (L2), T (L3). 2. Push the input terminal block up against the metal clips on the power terminal mounting plate until they engage. 3. Secure with 2 machine screws (M5x12) at the bottom of the terminal block. Torque to 2.3 Nm (20 in-lb). 1.5.7 Installing AC Input Busbars Optional components mounted on the input terminal plate can result in differing configurations. These options include an RFI filter and AC fuses. See Illustration 1.2. Use the appropriate procedure based on the options present in the unit. No options 1. Attach the busbars. 2. Secure each busbar with 1 nut (M8) at the top of the busbar and 2 nuts (M8) at the bottom of the busbar. Torque to 9.6 Nm (85 in-lb). AC fuses only 1. Secure each busbar at the top with 1 nut (M8). Torque to 9.6 Nm (85 in-lb). 2. Install the AC fuses using 6 nuts (M8), 1 at each end of each fuse. Torque to 9.6 Nm (85 in-lb). RFI filter only 1. Connect the RFI filter cable from MK100 on the RFI card to the RFI filter. 2. Attach the RFI filter to the side channels of the frequency converter with 4 thread-cutting screws (T20). Torque to 5.7 Nm (50 in-lb). 3. Secure the top of the RFI filter using 3 nuts (M8), 1 per phase. Torque to 9.6 Nm (85 in-lb). 4. Secure the bottom of the RFI filter using 6 nuts (M8), 2 per phase. Torque to 9.6 Nm (85 in-lb). AC fuses and RFI filter 1. Connect the RFI filter cable from MK100 on the RFI card to the RFI filter. 2. Attach the RFI filter to the side channels of the frequency converter with 4 thread-cutting screws (T20). Torque to 5.7 Nm (50 in-lb). 3. Secure the RFI filter using 3 nuts (M8) at the top of the RFI filter, 1 per phase. Torque to 9.6 Nm (85 inlb). 4. Install AC fuses using 6 nuts (M8), 1 at each end of each fuse. Torque to 9.6 Nm (85 in-lb). 1.5.8 Reconnecting the Mains and Motor Wiring 1. Reconnect the motor wiring to the U, V, and W terminals. 2. If a brake terminal is present, reconnect the brake wiring. 3. Reconnect the mains wiring to the R, S, and T terminals. 4. Install the air baffle using 4 screws (T25) and 2 nuts (M8). Torque to 2.3 Nm (20 in-lb). 8 Danfoss A/S 10/2016 All rights reserved. MI70Y102

MI70Y102 Danfoss A/S 10/2016 All rights reserved. 9

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com 130R0721 MI70Y102 10/2016 *MI70Y102*