COURSE # 343 UNIT 4: ADVANTEX WASTEWATER TREATMENT SYSTEM. What you will learn in this lesson
|
|
- Jasmine Lambert
- 6 years ago
- Views:
Transcription
1 What you will learn in this lesson IN THIS LESSON, YOU WILL LEARN... Installation steps for an AdvanTex Treatment System Important inspection points for installation inspection UNIT 4-1
2 Installation Steps 1. Determine tank and AdvanTex pod position 2. Excavate site and set tank 3. Install risers and water-test tank 4. Set the AdvanTex pod 5. Install filtrate return and discharge lines 6. Install recirculating splitter valve (RSV) and float 7. Install Biotube pump package 8. Connect transport line to pod 9. Install passive air vent 10. Install control panel 11. Perform system functional test 12. Perform functional test for VeriComm control panel 13. Backfill UNIT 4-2
3 Step 1: Determine Tank and Pod Position Is it a Fully-Assembled Package (FAP) or unassembled system? Decide how to orient the filter pod The filter pod often sits on, or immediately adjacent to the tank Consider the filtrate return line for the best orientation AdvanTex AX20N installed in a less than optimum location UNIT 4-3
4 Step 2: Excavate and Set the Tank Determine the required elevation and grade requirements of the tank and AdvanTex pod before excavation The tank must be set deep enough below the pod to allow for a minimum 1/4 inch per foot slope from the outlet of the filter to the inlet of the RSV on the riser. Also, keep in mind that the top of the AdvanTex pod needs to sit 1 1/2 inches above final grade. UNIT 4-4
5 Tank Specifications All processing tanks must be either: A two-compartment recirculation (processing) tank, or A septic tank followed by a recirculation (processing) tank No vertically-aligned circular tanks Must be an Orenco fiberglass reinforced plastic (FRP) tank or a concrete tank that conforms to an Orenco-approved tank design authorized by an Orenco Dealer Must meet the tank specifications of Chapter 73, Section 31 UNIT 4-5
6 Why only Orenco FRP or Approved Concrete Tanks can crush or break if they are not structurally sound Tanks can leak in or out if they are not watertight Septic tank failure - polyethylene tank Septic tank failure - concrete tank without adequate reinforcing steel UNIT 4-6
7 High-quality concrete tank and Orenco FRP tank Quality concrete tank Quality Orenco FRP tank UNIT 4-7
8 Step 3: Install Risers and Water-test the Tank External splice box (if used) and recirculating splitter valve bracket should be installed on the riser before the riser is mounted The Orenco Dealer typically installs these components External splice box Recirculating splitter valve UNIT 4-8
9 Step 4: Set the AdvanTex Pod USING A CONCRETE TANK Prepare bedding for the filter Compact fill if placing the fi lter on the tank Install anti-fl otation flanges onto predrilled fi berglass tabs on the bottom corners of the filter Installation of anti-flotation flanges UNIT 4-9
10 What happens when you don t put the anti-flotation flanges on? AdvanTex pod floated in a high seasonal water event due to lack of anti-flotation flanges UNIT 4-10
11 Step 5: Install Filtrate Return & Discharge Lines Slope the filtrate return line at least 1/4 per foot (minimum 2 drop if less than 4 ) Orient the split-fl ow tee to the slope of the discharge line Connect the return line to one end of the tee Connect the discharge pipe to the other end of the tee UNIT 4-11
12 Pipe Grades NO!!!!! Pipe is sloped in the wrong direction Filtrate return line sloped in the wrong direction UNIT 4-12
13 Step 6: Install Recirculating Splitter Valve (RSV) Understand how the RSV works When the RSV float is seated (tank liquid level seats the float) the filtered effluent discharges When the RSV float is not seated (tank liquid level drops) in a Mode 1 configuration, all filtered effluent returns to the recirculation/processing tank. In a Mode 3 configuration, all filtrate is returned to the primary compartment of the processing tank. In Combo Mode, there is a 50/50 split of the effluent between the primary and the recirculation compartments Determine if bracket requires installation Some systems are supplied with the bracket pre-installed Note quick disconnect The quick disconnect must slide easily for removal and replacement Ensure that the disconnect bracket is not installed in a way that prevents removal and replacement Recirculating splitter valve UNIT 4-13
14 Step 6: Install RSV & Floats, continued: Determine the handle pipe length and install in the top of the RSV body Determine Float Levels The top float is normally set equal with the tank s inlet invert. The bottom float should be approximately 4 in. below the normal low operating level. For further assistance, use the diagram in the Installation Manual, Orenco document NIM-ATX-AX-1 (Appendix 3, pages 24 & 25 of the manual) to calculate stinger length and float levels UNIT 4-14
15 Step 6: Install RSV, continued: Carefully lower RSV body into bracket Push down until it is fully seated Recirculating splitter valve seated in the bracket UNIT 4-15
16 Optional Step: Install Pump (dosing) Tank or Basin A pump basin or dosing tank is used when dispersal requires pumping or dosing Contains pump, flow inducer, splice box, and discharge assembly Refer to Pump Basin installation instructions for details. Appendix 4, pages 26 & 27 of the AdvanTex Installation Manual, Orenco document NIM-ATX-AX-1. AdvanTex Treatment System flowing to a pump basin Pump basin UNIT 4-16
17 Step 7: Install Biotube Pump Package Can use internal or external splice box Attach external spice box before installing riser Note: The conduit seal is used with the internal spice box. Internal splice box External splice box For further assistance use the diagram in the AdvanTex Installation Manual, Orenco document NIM-ATX-AX-1 (pages 13 & 14 of the manual) UNIT 4-17
18 Step 7: Install Biotube Pump Package, continued: Splice boxes are watertight when installed correctly External splice box with waterproof wire nuts Cords secured out of the water and away from the pump and floats For Proper installation guidelines, refer to the AdvanTex Installation Manual, Orenco document NIM-ATX-AX-1. (pages 13 & 14 of the manual) UNIT 4-18
19 Step 7: Install Biotube Pump Package, continued: Earless vault rests on the bottom of the tank Secure the lifting rope to the splice box Biotube pump package installed Biotube pump package UNIT 4-19
20 Step 8: Connect the Transport Line to the Pod Temporarily disassemble the manifold union so that, when the pump first comes on during start-up, debris in the transport line will not be pumped into the manifold and orifices. Manifold Union AdvanTex AX20N pod UNIT 4-20
21 Step 9: Install the Passive Air Vent Use a 2-inch diameter vent line if the vent is 20 feet or less from the pod Consider locating the vent near a protective wall or under shrubbery Do not allow low points in the vent piping where water can accumulate and block the air flow Passive air vent UNIT 4-21
22 Ventilation Note: This is a poor installation. The pipe is not really buried. The vent is sitting on an old cinder block. Improper ventilation installation UNIT 4-22
23 Step 10: Install the Control Panel Use a licensed electrician for wiring Float connections Incoming power to the panel Power from the panel to the recirculation pump Power to the discharge pump, if applicable Conduit seal outside riser Note: Do not install the control panel on the wall of a bedroom, living room, or other living space. Control panel installed on post UNIT 4-23
24 Step 11: Perform System Functional Test Verify: Pump operation Filter operation The Authorized AdvanTex Service Provider will be present at start-up Temporarily disconnect the manifold union to flush any debris such as PVC shavings from the transport line UNIT 4-24
25 Step 11: Perform System Functional Test, continued: Verify the pump operation First, verify that the pump is submerged in water before continuing Test the pump operation in manual Test the pump operation in automatic using test mode Note: To enable test mode, hold the push-to-silence button on the front of the panel until the audible alarm sounds (approximately 15 seconds). Automatic/Manual switch in the control panel UNIT 4-25
26 Step 11: Perform System Functional Test, Continued: Verify fi lter operation Reconnect and hand-tighten the manifold union Hold the spring-loaded switch in manual position Open each lateral individually to flush debris Remove several orifice shields Check squirt height: 3 ft. to 5 ft. typical Record the residual head (squirt height) measurement Squirt height check on AdvanTex AX20N pod UNIT 4-26
27 Step 11: Perform System Functional Test, continued: Release the spring-loaded switch to the automatic position Fill the processing tank to one inch above the RSV cage Switch the manual/automatic switch to manual Verify proper liquid flow and drainage to and from the filter pod Verify no leaks at all plumbing joints UNIT 4-27
28 Step 12: Perform Functional Test for VeriComm Panel 1. Verify system status 2. Enable test mode 3. Perform manual pump test 4. Perform float test 5. Perform communication test 6. Disable test mode (optional) RESOURCE: VeriComm control panel For detailed procedures specific to each VeriComm model, refer to the documentation that comes with the panel. Information at UNIT 4-28
29 Step 13: Backfill When backfilling, be careful not to alter the slope of pipes. Brace the pipes or place the pipes on a compacted bed and carefully fill around them. Backfill the fi lter in maximum 12 lifts Ensure the top of the filter is a minimum of 1 to 2 above grade Slope ground away from filter Note: Before backfilling, make sure all pod and riser lids are bolted down. Failure to bolt down lids may result in deforming the pod and risers. Backfilling of AdvanTex AX20N system UNIT 4-29
30 Sampling Protocol FILTRATE SAMPLING LOCATION: RESIDENTIAL SYSTEMS Sample the discharge filtrate at the RSV Pull the RSV out of its quick disconnect bracket; lay it on a flat surface Take the sample at the RSV inlet Note: Take care not to scrape the bottle on surfaces and pick up debris. Wait for a timed pump cycle. Do not force the pump to run. Removing the recirculating splitter valve Collecting a sample at the RSV inlet for testing UNIT 4-30
31 Video Resourses PLEASE REVIEW THE FOLLOWING VIDEOS AT: AdvanTex: How it works AdvanTex Install - Part 1 AdvanTex Install - Part 2 Control Panel Install External Splice Box Install RSV Install UNIT 4-31
32 Lesson Summary IN THIS LESSON, YOU LEARNED... The important installation inspection points: Watertight tanks, connections, penetrations Only Orenco FRP tanks or concrete tanks that conform to an Orenco-approved tank design authorized by an Orenco Dealer Anti-fl otation flanges in place and properly connected Filtrate sample locations (RSV) are accessible Check all piping Proper slope No bellies in pipes Good, watertight joints UNIT 4-32
33 The important installation inspection points, continued: Check the splice box for location and connections Check the slope of the filtrate return line Check the piping to be sure it has been flushed Run functional checks The Orenco Authorized Service Provider will confi rm the 4:1 recirculation ratio based upon factory settings Make sure all riser lids are bolted down prior to leaving the site UNIT 4-33
Installation Manual. AdvanTex AX20 Treatment Systems. Residential Applications
Installation Manual AdvanTex AX20 Treatment Systems Residential Applications 1-800-348-9843 +1-541-459-4449 www.orenco.com Orenco Installation Manual: AX20 Treatment Systems How To Use This Manual... Page
More informationInstallation Manual. AdvanTex AX100 Treatment Systems. Commercial Applications
Installation Manual AdvanTex AX100 Treatment Systems Commercial Applications 1-800-348-9843 +1-541-459-4449 www.orenco.com How To Use This Manual....Page 2 Before You Begin....Page 3 Standard System Components...Page
More informationInstallation Manual. AdvanTex -AX20-RT Treatment Systems. Residential Applications. An illustrated guide to installing an Orenco AdvanTex
Installation Manual AdvanTex -AX20-RT Treatment Systems Residential Applications An illustrated guide to installing an Orenco AdvanTex AX20-RT Treatment System. Rev. 1.0, 1/10 Orenco Systems, Inc. Orenco
More informationInstallation Manual. AdvanTex AX100 Treatment Systems. Commercial Applications. Commercial AdvanTex Treatment Systems Installation Manual Orenco
Commercial AdvanTex Treatment Systems Installation Manual Orenco Installation Manual AdvanTex AX100 Treatment Systems Commercial Applications 1-800-348-9843 +1-541-459-4449 www.orenco.com Page 1 Orenco
More informationInstallation Manual. AdvanTex AX-RT Treatment Systems. Residential Applications
Installation Manual AdvanTex AX-RT Treatment Systems Residential Applications 1-800-348-9843 +1-541-459-4449 www.orenco.com How To Use This Manual... Page 2 Before You Begin... Page 3 Septic Tanks Used
More informationAdvanTex Operation and Preventive Maintenance
AdvanTex Operation and Preventive Maintenance Commercial Application 2/1/2011 #1 O&M is Important Because... It refines/optimizes process It ensures system longevity It establishes accountability It protects
More informationSeptic Tanks. Effluent Screen Cleaning. Effluent Screens. Surveying Abbreviations. Installation Keys. Septic Tanks, Holding Tanks & Pump Tanks
Septic Tanks Gravity treatment Separation Sludge sinks Scum floats Storage Septic Tanks, Holding Tanks & Pump Tanks Bacteria SCUM breakdown CLEAR ZONE Chemical SLUDGE WW Strength= Organic Load Effluent
More informationPUMP TYPES. Pump Sizing. Dose to Gravity. Pumping to Gravity Distribution. Systems that need a Lift. Distribution Box and Tiered Trenches.
PUMP TYPES Sump Clean Water Only Systems that need a Lift Effluent Multi stage Single stage Sewage Grinder Pumping to Gravity Distribution When STA is at higher elevation than septic tank Pump Sizing TDH
More informationE-Z Treat Installation Guidelines
E-Z Treat Installation Guidelines E-Z Treat Company or its representative will conduct on-site training with each installer before they are certified to install E-Z Treat systems. The training will include
More informationWSB clean: Installation Manual
WSB clean: Installation Manual Models: WSB 400 WSB 1250 WSB 500 WSB 1500 WSB 600 WSB 1600 WSB 750 WSB 1800 WSB 1000 TABLE OF CONTENTS 1 INTRODUCTION...3 2 SAFETY INFORMATION...3 3 WSB CLEAN SYSTEM OPERATION...4
More informationResidential AdvanTex. Installation. using a steel tank. Anchorage Tank
Residential AdvanTex Installation using a steel tank Anchorage Tank Introduction It s a team effort As the installer, operator, service provider, or homeowner of an onsite wastewater treatment system,
More informationPressure Distribution Design
1 Pressure Distribution Design 2 Let s Start with Nonpressurized systems Historically the norm 3 Distribution Systems 4 Distribution Systems Non-pressurized Distribution Non-pressurized Distribution (cont.)
More informationInstallation Manual. ProSTEP Effluent Pump Packages. Residential Applications
Installation Manual ProSTEP Effluent Pump Packages Residential Applications An illustrated step-by-step guide for installing and maintaining a ProSTEP Effluent Pump Package Rev. 2.4, 02/13 Orenco Systems,
More informationSPECIFICATIONS EFFLUENT/SUMP SIMPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS
Product information presented here reflects conditions at time of publication. Consult factory regarding discrepancies or inconsistencies. MAIL TO: P.O. BOX 16347 Louisville, KY 40256-0347 SHIP TO: 3649
More informationGB-250. Submittal Specifications Installation Application Specific Details
GREASE INTERCEPTOR TECHNICAL DATA Submittal Specifications Installation Application Specific Details 68" (1,727 mm) 13½" (343 mm) 51½" (1,308 mm) 38" (965 mm) SUBMITTAL 33½" (851 mm) STANDARD: 4" plain
More information2460 / 2472 / Series Simplex Grinder Systems
Installation Manual 5651000I 2460 / 2472 / 2484 - Series Simplex Grinder Systems Features: LSG or LSGX Series 2HP Grinder Pump 24 dia. Basin available in 60, 72, or 84 depths Guide Rail System Preassembled
More informationPressure Distribution. Western Canada Onsite Wastewater Management Association
Pressure Distribution EFFLUENT DISTRIBUTION Get even distribution Space the doses Layout the distribution system Make choices for: piping, orifices, volumes Use worksheets for calculations Dose or flush
More informationInstallation Manual. D3600- Series Duplex Grinder Systems. Contents
Installation Manual 7353000E D3600- Series Duplex Grinder Systems Features: 36 Diameter Fiberglass Tank Available in 48, 60, 72, 84, and 96 heights LSG Single or LSGX 2 Stage 2HP Grinder Pumps Factory
More informationAqua Green Utility Inc.
Aqua Green Utility Inc. Individual septic tank and pump tank requirements. Only configurations and equipment approved by Aqua Green Utility Inc. may be used. Not following these configurations shall be
More informationOperation and Maintenance
E-Z Set Company requires regular inspection and maintenance of the E-Z Treat Re- Circulating Sand/Media Filter, as a condition of purchase and ongoing operation compliance. The mandatory service contract
More informationGB-35. Submittal Specifications Installation Application Specific Details. PART #: XX DWG BY: C. O'Boyle DATE: 10/08/2015 REV: 0 / /201_ ECO:
GREASE INTERCEPTOR TECHNICAL DATA Submittal Specifications Installation Application Specific Details 33" (83.8 cm) 10" (25.4 cm) (63.5 cm) 15" (38.1 cm) (63.5 cm) SUBMITTAL STANDARD: 3" plain end inlet/outlet
More informationInstallation Manual. Q Series Quadplex Grinder Systems. Contents
Installation Manual 7759000A Q4800 - Series Quadplex Grinder Systems Features: 48 Diameter Fiberglass Tank Available in 84, 96, and 120 heights LSG Single or LSGX 2 Stage 2 HP Grinder Pumps Factory Installed
More informationWashtenaw County DESIGN PROCEDURES AND ENGINEERING STANDARDS FOR PRESSURE DISTRIBUTION NETWORKS
Washtenaw County Department of Planning & Environment Development Services Division DESIGN PROCEDURES AND ENGINEERING STANDARDS FOR PRESSURE DISTRIBUTION NETWORKS 705 N. Zeeb Road Phone: (734) 222-3800
More informationAMERICAN RECIRCULATING SAND FILTER SYSTEMS
American Manufacturing Company, Inc. P.O. Box 549, Manassas, VA 20108 1-800-345-3132 AMERICAN RECIRCULATING SAND FILTER SYSTEMS ENGINEERING DESIGN GUIDELINES FOR COMMUNITY AND COMMERCIAL SIZED TREATMENT
More informationMODELS 108 and 138 CRAWL SPACE PUMPING SYSTEM PREINSTALLATION CHECKLIST
NOTICE TO INSTALLER: Instructions must remain with installation. Your Peace of Mind is Our Top Priority Product information presented here reflects conditions at time of publication. Consult factory regarding
More informationGL0098P Beta+ Septic Tanks Installation & Operation Guidelines
000535 GL0098P Beta+ Septic Tanks Installation & Operation Guidelines Kingspan Environmental Service Contact Numbers: UK: 0844 846 0500 NI: 028 3025 4077 IRL: 048 3025 4077 Enclosed Documents DS1151P Beta+
More information2 INLET / HIGH HEAD DRAIN PUMP SYSTEMS MODELS , INSTALLATION INSTRUCTIONS PREINSTALLATION CHECKLIST
Product information presented here reflects conditions at time of publication. Consult factory regarding discrepancies or inconsistencies. MAIL TO: P.O. BOX 1637 Louisville, KY 06-037 SHIP TO: 369 Cane
More informationSEPTIC TANK PUMP VAULT FILTER SYSTEM PUMP VAULT INSTALLATION AND SERVICE MANUAL
SEPTIC TANK PUMP VAULT FILTER SYSTEM PUMP VAULT INSTALLATION AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party
More informationDEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE
DEFENDER SERIES 5 Gallon, Double Walled, Field Replaceable Spill Container Model 705-550 Series INSTALLATION, OPERATION, & MAINTENANCE Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel:
More informationAQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual
AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual This Aquator Commercial Oil Water Separator (OWS) Operating and Maintenance Manual gives instructions for single-wall
More informationNanometrics Solar Power System
Nanometrics Solar Power System Installation Guide Nanometrics Inc. Kanata, Ontario Canada 2003 Nanometrics Inc. All Rights Reserved. Installation Guide The information in this document has been carefully
More informationPRE-PLUMBED SEWAGE SYSTEM
PRE-PLUMBED SEWAGE SYSTEM Zoeller is a registered trademark of Zoeller Co. All Rights Reserved. MODEL #1910-0009 Español p. 13 ATTACH YOUR RECEIPT HERE Serial Number Purchase Date Questions, problems,
More informationRecirculating Media Filters OWNER'S MANUAL
3649 Cane Run Road Louisville, KY 40211-1961, USA 1-800-928-7867 1-502-778-2731 Fax: 1-502-774-3624 clarusenvironmental.com SECTION: C3.20.140 CL0064 0515 Supersedes 1011 Recirculating Media Filters Register
More informationMIDLAND PRECAST COMPANY, L.C. Tel: Hwy 14 PO Box 63 Toll Free: Corydon, Iowa Fax:
Product Catalog Table of Contents Item Page # Septic Tanks 1 Septic System Accessories 2 Frost Free Stock Tank 3 Feed Bunks 4 Storm Shelter 5 Parking Blocks 6 Pads & Blocks 7 Tiles 8 Pump Pit 9 Steps 10
More informationINSTALLATION GUIDE. Model #GB2 35/50 GPM Grease Interceptor For Indoor Use. Contents
INSTALLATION GUIDE Model #GB2 35/50 GPM Grease For Indoor Use Contents Special Precautions............................................ 2 Getting to Know the GB2....................................... 3
More informationPUMP VAULT S.T.E.P. SYSTEM
Installation and Service Manual PUMP VAULT S.T.E.P. SYSTEM NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the
More informationON-SITE WASTEWATER PRODUCTS
NOTICE TO INSTALLER: Instructions must remain with installation. Product information presented here reflects conditions at time of publication. Consult factory regarding discrepancies or inconsistencies.
More informationTurbine STEP System SIMPLEX OR DUPLEX
3649 Cane Run Road Louisville, KY 211-1961, USA 1-800-928-7867 1-502-778-2731 Fax: 1-502-774-3624 www.clarusenvironmental.com SECTION: C1.20.120 CL0019 0816 Supersedes 1212 Turbine STEP System SIMPLEX
More informationInstallation Manual. Engineered Pump Systems (EPS) Common Components: Manual Contents:
Installation Manual 7298000B Engineered Pump Systems (EPS) By definition, an EPS system is a custom product and some differences in materials, pumps, and design are unavoidable. This manual is intended
More informationINSTALLATION GUIDE. Model #GB1 20/25 GPM Grease Interceptor For Indoor Use. Contents
INSTALLATION GUIDE Model #GB1 20/25 GPM Grease For Indoor Use Contents Special Precautions............................................ 2 Getting to Know the GB1........................................
More informationBioSTEP Screened Pumping System Installation & Service Manual
BioSTEP Screened Pumping System Installation & Service Manual FOR USE WITH BioSTEP 1618 BioSTEP Manual Bio-Microbics, Inc. Revised June 2013. BioSTEP is a registered trademark owned by Bio-Microbics, Inc.
More informationOWS OPERATIONS & MAINTENANCE
SUPPLEMENTAL INSTRUCTIONS 1. INTRODUCTION 1.1. Containment Solutions manufactures Oil/Water Separator (OWS) tanks with internal coalescing plates. These units are available in single or double-wall model
More informationGB2 35/50 GPM Grease Interceptor for Indoor Use
INSTALLATION GUIDE GB2 35/50 GPM Grease for Indoor Use Contents Special Precautions.........................................2 Getting to Know the GB2....................................3 On the Floor Installation..................................
More informationABCD BFDC BEDA AB CDEFCC
ABCD BFDC BEDA AB CDEFCC ABCD BFDC BEDA AB CDEFCC AFC Oil/ Water Separator Specifications and Operation & Maintenance Schedule 1) Model of AFC Oil/ Water Separator: a)
More informationInstallation & Operating Manual
Installation & Operating Manual VN Series Non-Clog Pumps Congratulations On Your Choice In Purchasing This Webtrol Pump 10/15 Edition Its Quality is unsurpassed in material and workmanship and has been
More informationINSTALLATION GUIDELINES
SUMP TANKS INSTALLATION GUIDELINES Thank you for purchasing a quality SumpTank. In order to gain the maximum benefit from your purchase, we have outlined the following instructions for the installation
More informationInstallation Instructions
E/One Sewers TM Installation Instructions for Flexible Hose & Horizontal Slideface Read all instructions before proceeding with installation. 1 AMGP INSTALLATION LAYOUT SHEET 3 After Market Grinder Pump
More information2010iP Simplex Typical Installation Instructions Simplex Station 700 L Capacity
2010iP Simplex Typical Installation Instructions Simplex Station 700 L Capacity Rev. 1 The 2010iP Simplex station is a well-engineered system designed to provide low-pressure sewer service to individual
More informationRAIN BIRD - AQUAGATOR AQUAGATOR INSTALLATION & TROUBLESHOOTING MANUAL
AQUAGATOR INSTALLATION & TROUBLESHOOTING MANUAL Cozz GT27069-A Revised July 2002 P/N 632360 AQUAGATOR TABLE of CONTENTS DESCRIPTION PAGE INTRODUCTION....... 1 SECTION 1 - PRE-INSTALLATION REQUIREMENTS.
More informationAQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual
AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual For Single-Wall and Double-Wall Fibreglass Underground Storage Tanks This Aquator Commercial Oil Water Separator (OWS)
More informationSeptic Tank. Installation Guidelines
Septic Tank Installation Guidelines INSTALLATION GUIDELINES FOR WPL SEPTIC TANKS These guidelines represent Best Practice for the installation of spherical SEPTIC tanks. It must be noted, however that
More informationSimplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, w/fiberglass Cover
www.cranepumps.com Simplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, w/fiberglass Cover Specifications: inches (mm) BASIN...Fiberglass w/ 3 (76)
More informationPetrol & Oil Interceptor
Petrol & Oil Interceptor VP10AG > above-ground installation. > usually associated with automotive workshops such as a garage, carwash, & etc. and also referred to as a Triple Interceptor. > this tank design
More informationCONTENTS. Foreword...iii. 1. Introduction...1
Installation of Aboveground Storage Systems for Motor-Vehicle Fueling CONTENTS Foreword...iii SECTIONS 1. Introduction...1 1.1 Background...1 1.2 Purpose...1 1.3 Scope...1 1.4 Source...1 1.5 Use of PEI/RP100...1
More informationProfessional Séries. Professional Séries. Model T03828 SUBMERSIBLE SUMP DUPLEX SYSTEM SUBMERSIBLE SUMP DUPLEX SYSTEM. 1/3HP 2400 GPH Head of 20 (6 m)
Model T0828 Primary pump 1/HP 200 GPH Head of 20 (6 m) SUBMERSIBLE SUMP DUPLEX SYSTEM Professional Séries Discharge: 1 1/2 ABS DWV pipe Electric cable: 9 piggyback type Oil cooled Cast iron construction
More information3. The working pressure shall be 145 psi and tested to 230 psi.
Revisions to Section 333313 (standards for ARI) D. Automatic Air Release Valves for Wastewater Systems All force mains shall have automatic air release valves installed as they are indicated on the plans.
More informationDRAIN PUMP SYSTEM MODEL 105 (Korean) INSTALLATION INSTRUCTIONS PREINSTALLATION CHECKLIST
Notice to Installer: Instructions must remain with installation. Your Peace of Mind is Our Top Priority Product information presented here reflects conditions at time of publication. Consult factory regarding
More informationWater Storage Tanks Price List
Water Storage Tanks ist February 2016 ist ZWWP- 020116 February 1, 2016 Supercedes ist ZWWP-020115 (February 1, 2015) www.zcl.com Single-Wall and Double-Wall Tanks Tank Nominal itres Single-Wall Base Tank
More informationSequencing Batch Reactor. Reference Manual. Only modules bearing the NSF logo and designated PS1-XX are certified to NSF/ANSI Standards 40 and 245
Sequencing Batch Reactor Reference Manual Only modules bearing the NSF logo and designated PS1-XX are certified to NSF/ANSI Standards 40 and 245 2017 Anua 12-2017 Table of Contents 1.0 What s in the Box?
More informationInstallation - Tank & Aerator
Installation - Tank & Aerator 1500 SERIES MEDIA PLANTS & ALL OTHER MODELS NSF LISTED & 1500 S SERIES PLANTS These instructions apply to J-1500 Series and 1500 S Series plants. Each series has a 500, 750,
More informationRELN Septic & Holding Tanks
RELN Septic & Holding Tanks New, Improved Tanks RELN s complete range of purpose designed black water tanks take quality and flexibility to the next level, with: Unique stepped ribs for greater strength
More informationFlood Dosed System Worksheet
Number of bedrooms Flood Dosed System Worksheet Septic tank size Minimum 1000 gallons Dosing tank size Minimum 800 gallons or 1 bedroom smaller than septic tank size whichever is larger Filter: gravity(in
More informationBRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP SERIES
BRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP 25503 SERIES TABLE OF CONTENTS A. PRODUCT OVERVIEW... 3 A.1 Specifications A.2 Packing List B. SYSTEM BLOCK DIAGRAM... 3 C.
More informationProduct Manual PS3900 / PS4600 / PS7000 / PS15000 / BF1600 / BF1900 / BF2600 / BF
WG Product Manual PS3900 / PS4600 / PS7000 / PS15000 / BF1600 / BF1900 / BF2600 / BF3800 1.330.274.8317 www.atlanticwatergardens.com Table of Contents Pond Volume... 2 Surface Area... 3 Streambed Construction...
More informationPRE-INSTALLATION GUIDE
Dry Vacuum System Part Numbers V3, V5, V7, 2V3, 2V3CT, 2V5, 2V5CT, 2V7, 3V5 and 4V5 PRE-INSTALLATION GUIDE All pumps comply with NFPA 99C level 3 requirements. All installations must conform to local codes.
More informationMain Toll Free Range Road 73, Parkland County, Alberta T0E 0S0
Main 780-727-2702 Fax 780-727-2110 Toll Free 800-661-3047 Email info@pembinaconcrete.com 53231 Range Road 73, Parkland County, Alberta T0E 0S0 For over 25 years, Pembina Concrete Products has been manufacturing
More informationDuplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, with Steel Cover
www.cranepumps.com Duplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, with Steel Cover Pre-Packaged Fiberglass Systems Specifications: inches (mm)
More informationOrenco Automatic Distributing Valve Assemblies
This article may describe design criteria that was in effect at the time the article was written. FOR CURRENT DESIGN CRITERIA, call Orenco Systems, Inc. at 1-800-348-9843. Orenco Automatic Distributing
More informationINSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS
INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS CONTENTS Introduction Safety Operating Principle System Installation Initial Startup System Operations Troubleshooting Maintenance
More informationThe Pump Matic Range
The Below Ground packaged pumping Stations Ideal for - Sewage, Wastewater, Stormwater Pump Technology Ltd, manufactures its own pumping station tanks. We have complete control over the construction, quality
More informationGREASE INTERCEPTOR REQUIREMENTS Lakeway Municipal Utility District
Last Updated on October 27, 2011 Grease interceptors are required to separate out Fats, Oils and Greases (FOGs) and solids normally found in food preparation waste from the rest of the wastewater being
More informationInstallation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps
Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps EI-700-008 Rev -- Table of Contents Safety Guidelines 3 Caution 4 Wiring 4 Maintenance 4 Nameplate format 4 Prior to Operation
More information5220 SERIES Z-Cell OWNER'S MANUAL
3649 Cane Run Road Louisville, KY 40211-1961, USA 1-800-928-7867 1-502-778-2731 Fax: 1-502-774-3624 clarusenvironmental.com CL0180 0817 Supersedes New 5220 SERIES Z-Cell OWNER'S MANUAL Register your Clarus
More informationAccess Riser Fits PRO370 and PRO380 Series
Installation Manual 7171000D Access Riser Fits PRO370 and PRO380 Series Contents 1.) General Information 2.) Installation 3.) Optional 2 Installation Kits 4.) Typical Installation Diagram 5.) Junction
More informationEQUAL DISTRIBUTION OF WASTEWATER USING LOW-PRESSURE DISTRIBUTION Larry D. Stephens, P.E. *
EQUAL DISTRIBUTION OF WASTEWATER USING LOW-PRESSURE DISTRIBUTION Larry D. Stephens, P.E. * INTRODUCTION Experience with onsite systems has proven that equal application of wastewater over the entire soil
More informationLOWeFLOW -UV Treatment System O& M and Troubleshooting Manual January 2017
LOWeFLOW -UV Treatment System O& M and Troubleshooting Manual January 2017 US Patent 8,889,007 Manufactured by: Lowridge Onsite Technologies PO Box 1179 Lake Stevens, WA 98258 O: 877 476-8823, C: 425 750-4922
More information9.21 Tank Program Guide NYS Office of Mental Health Tank System Installation Guide
- Design Guides A. SITE PLANS: Provide existing condition, removal plan, and proposed installation site plans for all tanks. Plans must include the following: 1. Dimensions of tank and any structural pads.
More informationSPECIFICATIONS EFFLUENT/SUMP DUPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS
Product information presented here reflects conditions at time of publication. Consult factory regarding discrepancies or inconsistencies. MAIL TO: P.O. BOX 16347 Louisville, KY 40256-0347 SHIP TO: 3649
More informationINSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR
INSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR RED JACKET Extracta Remote Gasoline Pumps Models P75S17-3, P150S17-3 & X4P150S17 380 Volt, 3 Phase, 50 Hertz by 051-138 Rev. C ELECTRICAL SERVICE
More informationPRODUCT DESCRIPTION 1500 RECT 2/C Gallon 2 Compartment Septic Tank TOP VIEW. Rectangular lid has optional
1500 Gallon 2 Compartment Septic Tank 52.0 1.0 Taper Outlet and Inlet 24 O.D. with manhole cover. 4500psi @ 28 days Our septic tanks have 3 optional inlets and 1 outlet 55 from bottom of tank to bottom
More informationInst all a ti o n and Oper a tin g Instru c ti o n s
Inst all a ti o n and Oper a tin g Instru c ti o n s Congratulations, you are now the proud owner of an Aqua2use GWDD! INSTALLATION OF PUMP OPERATED AQUA2USE GWDD The Matala Aqua2use GWDD is specifically
More informationElite Skimmer Installation Manual. Manufacturers of Quality Pond Equipment & Supplies Item #PBESIM
Elite Skimmer Installation Manual Manufacturers of Quality Pond Equipment & Supplies Item #PBESIM A C G B F E D H I A B C D Biological Waterfall Box Filters harmful waste and toxins from water, keeping
More informationSOLAR WORLD, INC. INSTALLATION MANUAL
SOLAR WORLD, INC. INSTALLATION MANUAL Read this manual before beginning installation of solar system INSIDE THIS MANUAL Section 1 illustrates the kits and components used for installation of the solar
More informationDRAIN PUMP SYSTEMS MODELS 104*, 105, 110, 115, 120, 131
Notice to Installer: Instructions must remain with installation. Product information presented here reflects conditions at time of publication. Consult factory regarding discrepancies or inconsistencies.
More informationFully Automatic Bilge Pump INSTRUCTION MANUAL
Fully Automatic Bilge Pump INSTRUCTION MANUAL Purpose of this manual The purpose of this manual is to provide necessary information for product installation, operation and maintenance. CAUTION: Read this
More informationHYDR-O-RAIL SYSTEM. Pump Installation and Service Manual
Installation and Service Manual HYDR-O-RAIL SYSTEM NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system.
More informationSaniTEE Wastewater Screens Installation & Service Manual FOR USE WITH SNT416, SNT418, SNT818, SNT 838, SNT1618, and SNT1638
SaniTEE Wastewater Screens Installation & Service Manual FOR USE WITH SNT416, SNT418, SNT818, SNT 838, SNT1618, and SNT1638 SaniTEE Manual Bio-Microbics, Inc. Revised December 2009. SaniTEE is a registered
More informationBEST MANAGEMENT PRODUCTS, INC. The SNOUT OIL-WATER-DEBRIS SEPARATOR SPECIFICATIONS U.S. Patent # Canadian Patent #
1. PRODUCT NAME The SNOUT Oil-Water-Debris Separator U. S. Patent # 6126817 Canadian Patent # 2285146 2. MANUFACTURER Best Management Products, Inc. 53 Mt. Archer Rd. Lyme CT 06371 Phone: (800) 504-8008
More informationSystem Startup Manual. SeptiTech Wastewater Pretreatment System Models:
System Startup Manual SeptiTech Wastewater Pretreatment System Models: M400 / M400D M550 / M550D M750 / M750D M1200 / M1200D M1500 / M1500D M3000 / M3000D SeptiTech, LLC. 69 Holland Street, Lewiston, ME
More informationA u t o matic Backw ater V alve
A u t o matic Backw ater V alve P R O TECT YOUR I N V E S TMENT S INDEX PAGE FLOOD-GATE FEATURES Flood-Gate Features and Applications 2 How Flood-Gate Works 3 Flood-Gate Operation & Approvals 4 Fully mechanical
More informationMethod. Remote solenoids. QuickInstall Guide
Remote solenoids Where remote solenoids are specified a single supply pipe is taken from the pump, or tap supply and connected to a single entry point on the remote solenoid manifold. From each solenoid
More informationDELPHIN cube. Reliable process Strong tanks Clever modules. Compact biological wastewater treatment plants with fixed-bed technology
DELPHIN cube Compact biological wastewater treatment plants with fixed-bed technology DELPHIN Water Systems GmbH & Co. KG The experts for fixed-bed technology Modular system for decentralized wastewater
More informationGAMMA Septic Tanks Installation & Operation Guidelines
017906 GAMMA Septic Tanks Installation & Operation Guidelines Kingspan Environmental Service Contact Numbers: UK: 0844 846 0500 NI: +44 283025 4077 IRL: +44 283025 4077 NOR : +47 22 021 920 Enclosed Documents
More informationHYDROCARBON SEPARATORS
HYDROCARBON SEPARATORS Hydrocarbon separators class I in PE Standard version (to install in consolidated sand) Reinforced version (to install in sand) Without and with mud trap Hydrocarbon separators class
More informationFuel Management Systems
UTILITIES MFG CORPORATION Fuel Management Systems Inside: Fuel Transfer Pump Sets Fuel Filtration Sets Pump and Day Tank Sets Fuel Oil Handling Systems Fuel Oil Additives and Treatments Fuel Oil Specialties
More informationModel Combustible Gas Sample Draw Detector Head Operator s Manual
Model 1017-06 Combustible Gas Sample Draw Detector Head Operator s Manual Part Number: 71-0356 Revision: P1 Released: 2/4/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before
More informationHow to build a Hydraulic Ram Pump By Seth Johnson Land To House Version 1.1
Seth Johnson How to build a Hydraulic Ram Pump By Seth Johnson Land To House Version 1.1 History: A man named John Whitehurst first created the Hydraulic Ram Pump in 1772. That means that this ingenious
More informationBreezair TBA 550 Installation Manual
Breezair TBA 550 Installation Manual Table of Contents ITEM Safety Instructions Specifications Exploded View of the Air Cooler Components of the Air Cooler Dismantling the Air Cooler Installing the Transition
More informationBhagawati International Limited
Bhagawati International Limited Septic Tank Advantages of FRP Septic tank: Advantage #1 You will not need to dig as large a hole for a fiberglass septic tank as you will for a concrete septic tank. A fiberglass
More informationNOTE! To the installer: Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system.
HYDR-O-RAIL SYSTEM INSTALLATION AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system. Item
More information