MODEL 7710 INTELLIBOOST INSTRUCTION AND INSTALLATION MANUAL

Size: px
Start display at page:

Download "MODEL 7710 INTELLIBOOST INSTRUCTION AND INSTALLATION MANUAL"

Transcription

1 MODEL 7710 INTELLIBOOST INSTRUCTION AND INSTALLATION MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. Part # A Pentair Ltd. 12/03/12

2 SECTION 6 ITEM 7710 DATED SEPTEMBER 2009 This instruction and installation manual is applicable to the model 7710 Intelliboost. WARNING Read and address all safety warnings concerning this system. Warnings may be found in this procedure, in the PVM Pump instruction manual, and in the Variable Speed Drive manual. WARNING The voltage used in this system is very dangerous and if connected incorrectly may cause injury or even death. Please make sure that all instructions are followed, that all precautions are taken, and that all practices are consistent with the National Electric Code and with the Occupational Safety and Health Authority. 1. This system must be properly grounded. 2. Power should be disconnected at a service disconnect prior to opening the panel and servicing. CALIFORNIA PROPOSITION 65 WARNING: This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm. System Receipt and Inspection: Inspect this system for any signs of damage and report this damage to the trucking firm. Check the system for any missing parts and report this to the Aurora Pump representative. Check the system for any loose parts and make corrections. System Installation: Mount, level, align and anchor the system. Attach building piping to the system without adding stress to any part of the system. We recommend that the guidelines of the Hydraulic Institute and the National Building Code be followed regarding anchoring and grouting of the base of the system. Grout the system base in place with non-shrink grout. Pipe thermal relief valves to a common drain. Bring power wiring to the system drives per requirements of the National Electric Code and all local codes. Also bring 110 volts single phase to the master control panel of the system. NOTE: If optional single point power connection has been purchased then bring required power wiring to the system disconnect per the National Electric Code. If the system is equipped with an enhanced controller with Ethernet connection, provide an Ethernet connection to the RJ45 connection on the back of the Magelis touch screen display inside the PLC controller. System Checks to be Made Prior to Start-up Check the drive nameplate for horsepower and voltage ratings. Record the VFD Serial Number on the test form. Check the motors for horsepower and voltage ratings. Record the motor model numbers and brand on the test form. Check inside the primary PLC control panel and VFDs for any loose screws and tighten as needed. Look for any evidence of a possible problem. Check available suction water supplies for water availability to the system.

3 Model 7710 CONSTRUCTION & OPERATING PRINCIPLE: BASIC CONTROLLER PLC The Intelliboost System with a basic controller consists of two to four pumps and motors with a variable frequency drive for each, all interconnected to a primary PLC control panel. The primary PLC control panel has a programmable controller with a proportional integral derivative to aid in precise control. It uses an input from a pressure transducer to stage, alternate, and vary the speed of all pumps to maintain a constant pressure at manifold discharge. All pumps have check valves and suction and discharge isolation valves. Communication from PLC controller to and from drives is through an RS485 port using Modbus Protocol. 1. System Start-up Preliminary Steps Make sure that all variable speed drives and primary PLC control panel are shut off. Bring water to the system through the suction header. Open all system isolation valves. Open petcocks on manifolds and open pumps to insure that all air is purged from the system and pumps. Open a vent plug on the PVM pump at the top of the impeller stack to insure air removal. Close all ports used for air release from the system and pumps. Bring power to the variable speed drives and to the primary PLC control panel. NOTE: Be sure to review the Pentair Variable Speed Drive instruction manual and follow all procedures and warnings. 2. Set Variable Speed Drive Parameters Danfoss VFDs (may be labeled Pentex) Turn the drives disconnect to the on position and note the power up of the drive. Both the primary PLC control panel and the variable speed drives have received a standard program prior to being shipped to make start-up more convenient. However, some information needs to be added reflecting local needs. All information for the PLC controller is displayed and is entered through a touch screen. Information is input to the drive through the keypad and LCD display as follows: PARAMETER DESIGNATION 0-01 US English 0-02 Hertz 0-03 North America 1-03 Variable Torque-VT 1-23 Motor Frequency 60 per motor nameplate 1-24 Full load amps per motor nameplate 1-25 Motor Nominal Speed from nameplate = approx rpm 3-03 Max Ref 60 Hz 3-41 Ramp Time Up 5 sec Ramp Time Down 5 sec Motor High Speed Limit 60 Hertz 4-19 Maximum Output Frequency 60.1 Hz 4-12 Motor Speed Low Limit 6 Hz No Operation 8-01 Control Site Control Word Only 8-03 Control Time Out Limit 20 sec Control Time Out Function = Stop 8-10 Control Word Profile = FC Profile 8-30 Protocol = Mod Bus RTU 8-31 Address 3,4,5,6. Drive1 = 3, Drive 2 = 4, Drive 3 = 5, Drive 4 = FC Port Baud Rate Parity = No Parity 2 Stop Bits 8-50 Thru 56 = Bus 0-50 LCP Copy (1) All To LCP Program all drives in a similar manner. With all program information input to drive # 1 and transferred as in parameter 8-50 above to the LCP, it can then be downloaded to all other drives by placing the LCP from drive #1 in each of the other drives and then using parameter 0-50 (2) to download the LCP to the drive. Refer to parameter 8-30 above to change the address of each drive.

4 Model 7710 Alternate Parameter Settings for ABB Brand VFDs CHANGE TO DEFAULT Group 98- Options 9802 Comm Prot Sel STD Modbus Not Sel Group 99 Start Up Data 9901 Language English AM English 9902 APPLIC Macro AVAC Default 9904 Motor Control Mode Scalar: Freq 9905 Motor Nominal Volt per motor data V 9906 Motor Nominal Curr per motor data 1.0*In A 9907 Motor Nominal Freq per motor data 60.0 Hz 9908 Motor Nominal Speed per motor data 3550 rpm 9909 Motor nominal power per motor data 1.0*Pn hp 9909 ID Run Off Group 10 Start/Stop/Dir 1001 Ext1 Commands Comm D11 Group 11 Reference Select 1103 Ref1 Select Comm Al1 Group 16 System Controls 1604 Fault Reset Sel Comm Keypad 1608 Start Enable 1 Not Enable D14 Group 22 Accel.Decel 2202 Acceler Time sec 30.0 s 2203 Deceller Time sec 30.0 s Group 53 RFB Protocol 5302 EFB Station ID as reqrd (3 thru 6) EFB Party 8N2 8 None 1 NOTE: Power drive off and restart after changes. Upload Drive Parameters to the Keypad Go to the Main Menu Scroll up or down to PAR BACK UP and press enter Scroll up to Upload To Panel and press SEL using the soft keys on the screen The text Copying Parameters is displayed followed by Parameter Upload Successful, Exit and return to the Main Menu Remove Keypad Download Drive Parameters to other drives from Keypad Select Menu Scroll to Par Back Up and press enter Scroll to Download To Drive and press SEL The text Restoring Parameters is displayed followed by Download Successful Refer back to Parameter 5302 above to set the address of each drive Exit and return to main menu Keypad can now be removed to program other drives. 3. Check Pump Rotation Turn the first Variable Speed Drive to the hand on position. Push hand button and observe the motor rotation. Check each motor and drive in this same way to determine the motor rotation. Return the drive to off. The correct rotation for all pumps is CCW when looking down. There is an arrow on each pump to support this. If rotation is wrong, motor leads should be changed to correct rotation. Lock out all power prior to making any wiring changes. Change direction of rotation by switching two motor leads at the drive. Check each pump rotation in the same way and make changes as needed. Return the drive to the manual position and observe manual speed change to verify operation. If any faults in the drive operation are noted refer to the Variable Speed manual for instructions and diagnostics. Check the trouble shooting section of this manual to see if the problem is addressed. Return all drives to the off position. The drives should all be operational but shut off at this point.

5 Model 7710 LOCAL PROGRAMMING TO PRIMARY PLC CONTROLLER 1. Primary PLC Controller Defined The primary PLC controller consists of a programmable logic controller to handle staging of pumps, timers, logic and alarms. All personal access to the PLC is through an HMI module. The HMI (Human Machine Interface) module consists of a touch screen with access to all information about the system and performance settings. There are three control systems for the primary PLC controller: 1. The Basic Control System uses an HMI that is the Magelis XBT GT 3.8 inch backlit monochrome LCD display, with touch sensitive resistive film, and real time clock. Communication with the variable frequency drives is through a RS 485 port using Modbus. This magelis offers 8 Mb EPROM flash memory. 2. The Advanced Control System has an HMI, which is a Magelis XBT GT inch backlit LCD display with 4096 colors. 3. The Enhanced Control System with Ethernet interface. Additional features: Data logging with a graph of flow, suction pressure, discharge pressure are plotted against time with continuous updates in real time, and a 6 month record of performance. Event logging with a record of faults, alarms, performance, and status, dated, recorded and retrieval for 6 months. Ethernet access using web browser. Advanced System Graphics Display 2. Start-up Turn on the primary PLC controller by a switch on the front of the panel. The panel has an audible alarm system, which will indicate the alarm that the drives are not active. Use the touch screen silence button to silence the audible alarm. The Basic PLC Controller has a 3.8 monochrome screen with tables but with no pictorial graphics as is seen with the advanced color screen. The menu should indicate a Start Up Screen which has a series of pressure settings etc., which need to be input based on local conditions. NOTE: Some of the screen indicators must be touched and held for several seconds continuously to activate On a system, which is not yet programmed, the first screen will say Critical System Settings. Press this button. This screen will not appear after settings are made. Enter the number of pumps in the system and press next to proceed. Enter the System Discharge Pressure Wake Up Pressure (after sleep mode) is usually 5 PSI less than system pressure. Sleep Speed is the single pump churn or no flow speed and will be different Critcal Systems Settings for each system. As a preliminary value use 80 % of full speed. Variations in suction pressure will affect this setting and several actual run tests should be done to fine tune the setting. A. Lag Pump Staging: -To stage the lag pump by pressure, set the value at start is 95-98% of full speed. -If lag pump staging is to be by flow instead of pressure as entered in the Advanced Menu and select staging by flow. Set the staging points as follows: 1. First Lag Pump Set at 98% of the GPM rating of pump # one. 2. Second Lag pump set at 98% of the GPM rating of pumps one and two. 3. Set other pumps in a similar way. B. Lag Pump Stop: -To Stage the lag pump off by pressure set the speed at the same speed as the sleep speed, or as a preliminary use 80%. -If the lag pump is to be staged by flow instead of pressure, set stage off points as follows: 1. Stage off the first lag pump at flow = pump flow x Stage off the second lag pump at flow = pump flow x 2 pumps x Stage off the third lag pump at flow = pump flow x 3 pump x.75. NOTE: If the last lag pump is just a spare pump, set its start point abnormally high to prevent staging.

6 SYSTEM HEAD FEET Model 7710 A= Single pump head at 98% full speed lag start speed B= Head of two pumps at reduced speed or lag pump stop speed A Full speed with one pump with losses Full speed head with two pumps with losses B System Head Duty point one pump 98% Pump speed pump two start Duty point two pump Both pumps reduced speed lag pump stop Suction Pressure FLOW GPM Illustration of Lag Pump Start and Stop Points C. Access To High System Pressure Fault: -High System Pressure Fault (or shut down) should be an abnormal high pressure compared to system pressure. Use system pressure plus 25 PSI. -High System Pressure Reset should be about 12 PSI above system pressure. -High System Pressure Fault can be disabled by entering 999 for the pressure. D. Access To Low Suction Pressure Fault (shut down): NOTE: Some areas have mandatory shut down pressures. This option requires the addition of a suction pressure transducer rated neg 14.7 to 150 PSI. -Low Suction Pressure Fault. This is an abnormal suction pressure shut down and will depend on the location. Some locations have a mandatory shut down pressure. -Low Suction Pressure Fault Reset. This should be about half the pressure difference between normal suction pressure and fault pressure. -Low Suction Pressure Fault can be disabled by entering 999 for the pressure. E. Access to Low System Pressure Alarm: -Low System Pressure Alarm is a warning that the system pressure is abnormally low and should be set at about 10 PSI below system pressure. -Low System Pressure Alarm reset should be set at about 5 PSI below system pressure. -Low System Pressure Alarm can be disabled by entering 999 for the pressure. F. Access to High System Pressure Alarm: -High System Pressure Alarm is a warning that system pressure is higher than it should be. Set at 12 PSI above normal system pressure. -High System Pressure Alarm Reset. This value should be set as half the difference between alarm setting and normal pressure. -High System Pressure Alarm can be disabled by entering 999 for the pressure. G. Access to Low Suction Pressure Alarm: -Low Suction Pressure Alarm. This is a warning that you are close to a low suction pressure shut down. Set this value the same as the suction fault reset pressure. -Low Suction Pressure Alarm Reset This value should be set as half the difference between alarm setting and normal pressure. -Low Suction Pressure Alarm can be disabled by entering 999 for the pressure.

7 Model 7710 Example of alarm settings Suggested settings example(s): Low Suction Pressure. Assume suction pressure varies from 30 PSI to 40 PSI -Low Suction Pressure alarm. Set the alarm condition at 24 PSI and reset at 27 PSI -Low Suction Pressure fault. Set the fault or shut down condition at 18 PSI. Set condition reset at 24 PSI High System Pressure. Assume discharge pressure is 150 PSI -High System Pressure alarm could be set at 162 PSI with a reset at 156 PSI. -High System Pressure fault could be set at 175 PSI with a reset at 156 PSI. Low System Pressure Alarm. -With a discharge pressure of 150 PSI, a Typical Low System Pressure Alarm setting is 140 PSI with a reset of 145 PSI. NOTE: All settings are only approximations and must take into account the system pressure desired, the suction pressure available statically and then suction pressure during times of full flow. TOTAL PRESSURE single pump full speed including losses single pump curve speed High Syst. Pres. Alarm System Pressure Waking Pressure system loss Low System Pressure pump curve at reduced speed for sleep mode Suction Pressure L. S. Pres. Reset L.S. Pres. Alarm L.S. Pres. Fault 0 TDH 0 FLOW Example of System Settings 3. Check the system summary screen to recap settings One of Several Summary Screens

8 Model Programming in the advanced menu Advanced Settings Access Access to System Timer Settings -All timers in this section will have a factory timer setting. Typically timers are set at 5 seconds and do not need to be changed unless there are operating problems. Access to PID Loop -The PID loop has been programmed at the factory and should not be changed unless there are operating issues. Access to Systems Miscellaneous Settings -Flow meter full scale GPM: This applies only to advanced and enhanced system with optional flow meter. -Power Failure Restart Delay: Three seconds is a good rule of thumb. -Alternation Method Standard: system alternate on each complete cycle; however, in the advanced or enhanced system a 24-hour alternator can be chosen. -Lag Pump Staging: In the advanced and enhanced systems with optional flow meter, optional staging by flow can be chosen. If staging by flow is selected then return to the Start Up Assistant to provide staging GPM in the program. Access to Display Settings -Values for the display are set at the factory and should not need adjusting unless there are performance problems with the display. To check ethernet address with this option 1. press Offline 2. Network to display the address 3. Make changes if needed and then OK to Run 4. Shut down & Restart Optional Flow Sensing - Only the advanced and the enhanced IntelliBoost PLC control panels are designed to be able to accept the 4-20 ma signal from a flow transducer to indicate flow in GPM on the display and to sequence pumps using the flow transducer instead of the pressure transducer. Wire the flow transducer per the wiring diagram. Accuracy in flow meter display is dependent on straight-line pipe before and after the flow meter. If mounted in the system piping, we will mount on the suction manifold and slightly compromise the straight-line pipe after the flow meter. For the greatest accuracy allow 10-pipe diameters straight-line pipe before the flow meter. Data input for flow sensing is in the Advanced Menu, under Misc. Settings. Input the flow meter full-scale capacity. To sequence by flow, enter the Type of Lag Pump Control. -All suction pressure related settings in the PLC require a suction pressure transducer with 4-20 ma. Connected to the PLC controller. The PLC controller will accept a pressure switch for low suction pressure shut down in place of the suction pressure transducer. The same input channel can be used for low level shut down if a 4-20 ma level transducer is provided.

9 Model 7710 Troubleshooting 1. One common problem is incomplete or inconsistent information given to the PLC controller and to the drives. Go back and check all input fields to see that they are complete and consistent with system operating parameters. Go through the PLC set-up; then go through the drive set-up with uplink to keypad and then downlink to each drive. 2. One of the biggest problems to a packaged system is variable suction pressure. The only sure way to eliminate variable suction pressure is to use a suction break tank (open reservoir). In the absence of a break tank the times in the PID loop may need to be changed to respond more rapidly. Retain the factory settings so that they could be reproduced if needed. Initial settings of the PID loop could be as follows: -Gain: This is the largest component to set point correction and should be set as large as the system will allow. Start with a settings of 1. -Integral Time: This setting is important to moderating the effects of gain. Give the system an artificial surge or drop in pressure and observe the time for a complete cycle of drop in pressure and return to normal. Set the integral time to 1.5 times this cycle time. Try 2 seconds. -Derivative Time: The derivative has little value due to the short cycle times. Set to 0 seconds. -PID Control Scan: The PID scan time is the time for each monitoring cycle and associated changes to control. A long set time may make the system sluggish and a short time will not give enough time for corrections to be made in each cycle. Start with a 0.1 second scan time. 3. Another source of poor control is the VFD ramp times. However, any changes in the VFD ramp time should be as a last resort. Consult Aurora Pump for advice. This is the time from full stop to full speed. Since we control between 2600 and 3500 RPM typically and most variations in speed would be about 50 RPM, we are controlling this 50-RPM in.2 seconds. Ramp time for a smooth system could be 10 seconds, and for an erratic system try 30 seconds. 4. In low flow situations, the IntelliBoost is designed to shut down all drives and restart on a pressure drop. If this does not happen it is likely that the settings of sleep RPM, Start Pressure, and shut down timer are not set properly. This shut down depends heavily on changes in suction pressure and should be reset accordingly. 5. Low System Pressure may indicate that set points are not set correctly. Examine system pressure setting in the PLC panel, and RPM limits that may be set in the drives. The PLC will display system pressure. See if this pressure agrees with your system gage on the manifold. The system transducer maintains 1% accuracy but can easily be changed. Check the transducer input to the PLC. Look for a cable or connector problem. 6. The drive may give a high current alarm. Check the acceleration ramp time, which may be too short. 7. The drive may give a high or low voltage alarm. Check the building supply power for adequacy. 8. The drive may trip out with a DC Buss failure alarm. This may be caused by a deceleration time or ramp down time being to short. In this case, the drive powers down quickly leaving the motor to coast, and generate power into the drive. The drive responds with a DC Bus failure alarm. 9. For other drive related problems, consult the VFD manual. 10. Contact Aurora Pump Systems Group for advice in system set up (boostersystems@pentair.com). If your system is equipped with Ethernet, and has an IP Address assigned, give this to the Aurora Pump representative so that they can observe your settings over the Internet.

10 THIS PAGE INTENTIONALLY LEFT BLANK

11 THIS PAGE INTENTIONALLY LEFT BLANK

12 WARRANTY Seller warrants equipment (and its component parts) of its own manufacture against defects in materials and workmanship under normal use and service for one (1) year from the date of installation or start-up, or for eighteen (18) months after the date of shipment, whichever occurs first. Seller does not warrant accessories or components that are not manufactured by Seller; however, to the extent possible, Seller agrees to assign to Buyer its rights under the original manufacturer's warranty, without recourse to Seller. Buyer must give Seller notice in writing of any alleged defect covered by this warranty (together with all identifying details, including the serial number, the type of equipment, and the date of purchase) within thirty (30) days of the discovery of such defect during the warranty period. No claim made more than 30 days after the expiration of the warranty period shall be valid. Guarantees of performance and warranties are based on the use of original equipment manufactured (OEM) replacement parts. Seller assumes no responsibility or liability if alterations, non-authorized design modifications and/or non-oem replacement parts are incorporated If requested by Seller, any equipment (or its component parts) must be promptly returned to Seller prior to any attempted repair, or sent to an authorized service station designated by Seller, and Buyer shall prepay all shipping expenses. Seller shall not be liable for any loss or damage to goods in transit, nor will any warranty claim be valid unless the returned goods are received intact and undamaged as a result of shipment. Repaired or replaced material returned to customer will be shipped F.O.B., Seller's factory. Seller will not give Buyer credit for parts or equipment returned to Seller, and will not accept delivery of any such parts or equipment, unless Buyer has obtained Seller's approval in writing. The warranty extends to repaired or replaced parts of Seller's manufacture for ninety (90) days or for the remainder of the original warranty period applicable to the equipment or parts being repaired or replaced, whichever is greater. This warranty applies to the repaired or replaced part and is not extended to the product or any other component of the product being repaired. Repair parts of its own manufacture sold after the original warranty period are warranted for a period of one (1) year from shipment against defects in materials and workmanship under normal use and service. This warranty applies to the replacement part only and is not extended to the product or any other component of the product being repaired. Seller may substitute new equipment or improve part(s) of any equipment judged defective without further liability. All repairs or services performed by Seller, which are not covered by this warranty, will be charged in accordance with Seller's standard prices then in effect. THIS WARRANTY IS THE SOLE WARRANTY OF SELLER AND SELLER HEREBY EXPRESSLY DISCLAIMS AND BUYER WAIVES ALL OTHER WARRANTIES EXPRESSED, IMPLIED IN LAW OR IMPLIED IN FACT, INCLUDING ANY WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Seller's sole obligation under this warranty shall be, at its option, to repair or replace any equipment (or its component parts) which has a defect covered by this warranty, or to refund the purchase price of such equipment or part. Under the terms of this warranty, Seller shall not be liable for (a) consequential, collateral, special or liquidated losses or damages; (b) equipment conditions caused by normal wear and tear, abnormal conditions of use, accident, neglect, or misuse of said equipment; (c) the expense of, and loss or damage caused by, repairs or alterations made by anyone other than the Seller; (d) damage caused by abrasive materials, chemicals, scale deposits, corrosion, lightning, improper voltage, mishandling, or other similar conditions; (e) any loss, damage, or expense relating to or resulting from installation, removal or reinstallation of equipment; (f) any labor costs or charges incurred in repairing or replacing defective equipment or parts, including the cost of reinstalling parts that are repaired or replaced by Seller; (g) any expense of shipment of equipment or repaired or replacement parts; or (h) any other loss, damage or expense of any nature. The above warranty shall not apply to any equipment which may be separately covered by any alternate or special warranties. PERFORMANCE: In the absence of Certified Pump Performance Tests, equipment performance is not warranted or guaranteed. Performance curves and other information submitted to Buyer are approximate and no warranty or guarantee shall be deemed to arise as a result of such submittal. All testing shall be done in accordance with Seller's standard policy under Hydraulic Institute procedures. LIABILITY LIMITATIONS: Under no circumstances shall the Seller have any liability under the Order or otherwise for liquidated damages or for collateral, consequential or special damages or for loss of profits, or for actual losses or for loss of production or progress of construction, regardless of the cause of such damages or losses. In any event, Seller's aggregate total liability under the Order or otherwise shall not exceed the contract price. ACTS OF GOD: Seller shall in no event be liable for delays in delivery of the equipment or other failures to perform caused by fires, acts of God, strikes, labor difficulties, acts of governmental or military authorities, delays in transportation or procuring materials, or causes of any kind beyond Seller's control. COMPLIANCE WITH LAW: Seller agrees to comply with all United States laws and regulations applicable to the manufacturing of the subject equipment. Such compliance shall include: The Fair Labor Standards Acts of 1938, as amended; Equal Employment Opportunity clauses of Executive Order 11246, as amended; Occupational Safety and Health Act of 1970 and the standards promulgated thereunder, if applicable. Since compliance with the various Federal, State, and Local laws and regulations concerning occupational health and safety, pollution or local codes are affected by the use, installation and operation of the equipment and other matters over which Seller has no control, Seller assumes no responsibility for compliance with those laws and regulations, whether by way of indemnity, warranty, or otherwise. It is incumbent upon the Buyer to specify equipment which complies with local codes and ordinances. 800 Airport Road North Aurora, Illinois

430B SERIES HORIZONTAL SPLIT CASE PUMP

430B SERIES HORIZONTAL SPLIT CASE PUMP 430B SERIES TWO Stage - DIAGONALLY HORIZONTAL SPLIT CASE PUMP REPAIR PARTS INDEX NOTE! Read and understand the pump and motor instructions before attempting to install, disassemble or repair the pump.

More information

VERTICAL AND HORIZONTAL SPLIT CASE FIRE PUMPS

VERTICAL AND HORIZONTAL SPLIT CASE FIRE PUMPS 480 MODELS VERTICAL AND HORIZONTAL SPLIT CASE FIRE PUMPS REPAIR PARTS INDEX NOTE! Read and understand the pump and driver instructions before attempting to install, disassemble or repair the pump. Part

More information

900 SERIES SPLIT CASE FIRE PUMP REPAIR PARTS INDEX

900 SERIES SPLIT CASE FIRE PUMP REPAIR PARTS INDEX 900 SERIES SPLIT CASE FIRE PUMP REPAIR PARTS INDEX Read and understand the pump and motor instructions before attempting to install, disassemble or repair the pump. Part # AF-03-326 2015 Pentair Ltd. 01/30/15

More information

1800,1900 MODELS VERTICAL AND HORIZONTAL SPLIT CASE FIRE PUMPS

1800,1900 MODELS VERTICAL AND HORIZONTAL SPLIT CASE FIRE PUMPS 1800,1900 MODELS VERTICAL AND HORIZONTAL SPLIT CASE FIRE PUMPS REPAIR PARTS INDEX NOTE! Read and understand the pump and driver instructions before attempting to install, disassemble or repair the pump.

More information

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II Document No.: LMSII_V100_OM Page 1 of 8 LMS II Document No.: LMSII_V100_OM Page 2 of 8 1. Operation: When the wet well level rises above the on level set point, the lead pump will start after an adjustable

More information

10VT Series/12VT Series

10VT Series/12VT Series INSTALLATION, OPERATION AND MAINTENANCE MANUAL VERTICAL TURBINE PUMPS 10VT Series/12VT Series ENGLISH: PAGES 1-64 Installation, Operation and Maintenance Manual NOTE! To the installer: Please make sure

More information

HR-20P Pneumatically Controlled Pressure Regulator

HR-20P Pneumatically Controlled Pressure Regulator HR-20P Pneumatically Controlled Pressure Regulator Instruction and Service Manual Hydroplex Corporation 230 West Gloria Switch Rd. Lafayette, LA 70507 337-233-0626 www.hydroplexpumps.com I. General Instructions

More information

7710 SERIES INTELLIBOOST WATER BOOSTER SYSTEM BASIC OPERATION MANUAL

7710 SERIES INTELLIBOOST WATER BOOSTER SYSTEM BASIC OPERATION MANUAL 7710 SERIES INTELLIBOOST WATER BOOSTER SYSTEM BASIC OPERATION MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains

More information

MODELS 3801 AND 3804 END SUCTION PUMPS INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL. Model Model 3804

MODELS 3801 AND 3804 END SUCTION PUMPS INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL. Model Model 3804 Model 3801 Model 3804 MODELS 3801 AND 3804 END SUCTION PUMPS INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the

More information

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTOSYNC MODEL ASPSS DUAL COMPRESSOR SEQUENCER CONSOLE S/N 1638 AND ABOVE

INSTRUCTIONS FOR INSTALLING AND OPERATING THE UNIVERSAL AUTOSYNC MODEL ASPSS DUAL COMPRESSOR SEQUENCER CONSOLE S/N 1638 AND ABOVE COMPRESSOR 1 EMERGENCY SHUTDOWN OFF POWER ON COMP LOADED COM PRESSOR OPERATING HOURS SYSTEM PRESSURE COMPRESSOR 2 EMERGENCY SHUTDOWN OFF POWER ON COMP LOADED COM PRESSOR OPERATING HOURS LEAD/LAG CONTROL

More information

30100 Module Installation Guide L

30100 Module Installation Guide L 30100 Module Installation Guide 1997-2006 12.0L Mack Engines Up to 30% HP Gain 10-20% Fuel Savings AgDieselSolutions.com 1997-2006 Mack 12.0L Engine Module +12 volts red wire. Ground black wire Injector

More information

II DISTRIBUTION & SUBSTATION TYPE C

II DISTRIBUTION & SUBSTATION TYPE C CapCheckIII DISTRIBUTION & SUBSTATION TYPE Ca p a c i t o r C h e c ke r Operating & Instruction Manual 1475 Lakeside Drive Waukegan, Illinois 60085 U.S.A. 847.473.4980 f a x 8 4 7. 4 7 3. 4 9 8 1 w e

More information

Vehicle Programming Instructions Ford Powerstroke 7.3 liter

Vehicle Programming Instructions Ford Powerstroke 7.3 liter Vehicle Programming Instructions 1994 2003 FORD Powerstroke 7.3 liter 2003, Edge Products Incorporated All rights reserved. Edge Products Incorporated 1080 South Depot Dr. Ogden, UT 84404 (801) 476-3343

More information

15100 Module Installation Guide Mercedes EPA07 w/dpf

15100 Module Installation Guide Mercedes EPA07 w/dpf 15100 Module Installation Guide 2007-2009 Mercedes EPA07 w/dpf 7.2L Engines Up to 30% HP Gain 10-20% Fuel Savings AgDieselSolutions.com 2007-2009 Mercedes 7.2L Engine Module +12 volts red wire. Ground

More information

Mercedes MBE 906/ L & 7.2L Engine Module. Part # Installation Instructions

Mercedes MBE 906/ L & 7.2L Engine Module. Part # Installation Instructions 1999-2006 Mercedes MBE 906/926 6.4L & 7.2L Engine Module Part # 15000 Installation Instructions 15000_revC 1999-2006 Mercedes 6.4L & 7.2L Engine Module +12 volts red wire. Ground black wire Injector Terminals

More information

Owner s Manual Ford Powerstroke 7.3 liter CAUTION: THIS IS A HIGH PERFORMANCE PRODUCT. USE AT YOUR OWN RISK.

Owner s Manual Ford Powerstroke 7.3 liter CAUTION: THIS IS A HIGH PERFORMANCE PRODUCT. USE AT YOUR OWN RISK. Owner s Manual 1994 2003 Ford Powerstroke 7.3 liter CAUTION: THIS IS A HIGH PERFORMANCE PRODUCT. USE AT YOUR OWN RISK. Edge Products Inc distributed by BD Power Evolution FORD Powerstroke 7.3 liter - 1

More information

StormPro BA Series Sump Pump

StormPro BA Series Sump Pump Page 1 of 8 Marks & Meanings DANGER: Keep the pump equipment out of the reach of children! Warns that the failure to follow the directions given could cause serious risk to individuals or objects. WARNING:

More information

20250 Module Installation Guide

20250 Module Installation Guide 20250 Module Installation Guide 2013.5-2017 RAM 6.7L Cummins Up to 90HP Gain 1-3 MPG Fuel Savings AgDieselSolutions.com Adjustable switch connector Power +12 volts (Red wire) & Ground (Black wire) Injector

More information

TW W-40 FLAG FRAME VARIABLE SPEED BOOSTER SYSTEM

TW W-40 FLAG FRAME VARIABLE SPEED BOOSTER SYSTEM TW1000-20W-40 FLAG FRAME VARIABLE SPEED BOOSTER SYSTEM TW1000-20W-40 FLAG FRAME The TW1000-20W-40 Flag Frame Booster System is equipped with a centrifugal pump regulated by a variable frequency drive that

More information

Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007

Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007 B R A N D Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007 For Sales, Support and Service phone: 407-331-4793 fax: 407-331-4708 website: www.xenotronix.com email:

More information

GARNET. SEE Tester II TM INSTRUMENTS LTD. Model 900M Manual PRINTED IN CANADA

GARNET. SEE Tester II TM INSTRUMENTS LTD. Model 900M Manual PRINTED IN CANADA GARNET INSTRUMENTS LTD. SEE EELEVE EVEL II Tester II TM Model 900M Manual PRINTED IN CANADA GARNET INSTRUMENTS LTD. L II TM SEE EELEVE EVEL II Tester Model 900M Manual TABLE OF CONTENTS 1) OVERVIEW and

More information

TW G-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM

TW G-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM TW1000-75G-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM The TW1000-75G-40 Flag Frame Booster System is equipped with a centrifugal pump regulated by a variable frequency drive that controls the pump

More information

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02 SELECT DIAGNOSTIC GUIDE INST028 Doc 3.02 CONTENTS General Information...2 Select Call-Outs...3 Wire Diagram and Legend...4 Diagnostics...6 Excessive Voltage Drop Diagnostics...6 Static Diagnostics...7

More information

Speedometer Interface

Speedometer Interface Pacific Performance Engineering, Inc. www.ppediesel.com Speedometer Interface Technical Support (714) 985-4825 Rev: 12/19/12 v5 DISCLAIMER OF LIABILITY This is a performance product which can be used with

More information

TW W-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM

TW W-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM TW1000-20W-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM TW1000-20W-40 FLAG FRAME The TW1000-20W-40 Flag Frame Booster System is equipped with a centrifugal pump regulated by a variable frequency drive

More information

Duplex Booster System Instruction Manual

Duplex Booster System Instruction Manual Duplex Booster System Instruction Manual ISO 9001 Certified Walrus America Inc Congratulations on your purchase of Walrus IC Series Inverter Control System. Please read all instructions carefully before

More information

Attitude Instructions Ford 6.0 Powerstroke

Attitude Instructions Ford 6.0 Powerstroke Attitude Instructions Ford 6.0 Powerstroke Attitude 2003, Edge Products Incorporated All rights reserved. Edge Products Incorporated 5875 South Adams Avenue Suite 100 Ogden, UT 84405 (801) 476-3343 www.edgeproductsinc.com

More information

PVI 1800/PVI Residential/Commercial Grid-Tied Photovoltaic Inverter WARRANTY MANUAL. Subject to Change REV , Solectria Renewables

PVI 1800/PVI Residential/Commercial Grid-Tied Photovoltaic Inverter WARRANTY MANUAL. Subject to Change REV , Solectria Renewables PVI 1800/PVI 2500 WARRANTY MANUAL Residential/Commercial Grid-Tied Photovoltaic Inverter 2009, Solectria Renewables Subject to Change REV 10.09 1 Product Warranty & RMA Policy 1.1 Warranty Policy The Solectria

More information

TW1000E-20W-70-DCA In Enclosure w/ Double Check Assembly VARIABLE SPEED BOOSTER SYSTEM

TW1000E-20W-70-DCA In Enclosure w/ Double Check Assembly VARIABLE SPEED BOOSTER SYSTEM TW1000E-20W-70-DCA In Enclosure w/ Double Check Assembly VARIABLE SPEED BOOSTER SYSTEM Revised 7/28/16 The TW1000E-20W-70-DCA booster system is equipped with a Stainless Steel centrifugal pump and regulated

More information

GM 6.6L Duramax. Up to 90HP Gain. AgDieselSolutions.com

GM 6.6L Duramax. Up to 90HP Gain. AgDieselSolutions.com 21700 Module Installation Guide 2017 GM 6.6L Duramax *L5P* Up to 90HP Gain 1-3 MPG Fuel Savings AgDieselSolutions.com Adjustable Switch Female Fuel Pressure Sensor Connector Male Fuel Pressure Sensor Connector

More information

Rig Master Power by Mobile Thermo Systems Inc.

Rig Master Power by Mobile Thermo Systems Inc. RigMaster Power Dealer Warranty Policy The Limited Warranty This limited warranty applies to the RigMaster Auxiliary Power Unit (RigMaster APU) which consists of the following components: 1. The generator

More information

Power. On Your Terms.

Power. On Your Terms. Power. On Your Terms. 10 YEAR LIMITED WARRANTY PHI 1310 TM 1 SIMPLIPHI POWER, INC. REV102016 10 YEAR LIMITED WARRANTY: PHI 1310 TM LIMITED PRO-RATED WARRANTY COVERAGE The SimpliPhi Power PHI 1310 as supplied

More information

Fifth Wheel Power Hitch Operations Manual

Fifth Wheel Power Hitch Operations Manual Fifth Wheel Power Hitch Operations Manual ITD1253 Fifth Wheel Power Hitch 208 587 7960 www.intheditch.com This page is intentionally left blank. Operations Manual 1 TABLE OF CONTENTS TABLE OF CONTENTS...

More information

Presoak & Tire/Engine Cleaner Systems (Air Pump) DU TC_A & DU PS_A

Presoak & Tire/Engine Cleaner Systems (Air Pump) DU TC_A & DU PS_A Presoak & Tire/Engine Cleaner Systems (Air Pump) DU TC_A & DU PS_A Owner s Manual #0795 Customer Number: Model Number: Serial Number: Installation Date: IMPORTANT Please read and u n d e r s t a n d t

More information

FOLD CONTROL FOR 600FC

FOLD CONTROL FOR 600FC FOLD CONTROL FOR 600FC Conversion Manual 09040122b HEADSIGHT.COM 574.546.5022 About Headsight Headsight Contact Info Headsight, Inc. 4845 3B Road Bremen, IN 46506 Phone: 574-546-5022 Fax: 574-546-5760

More information

JD2800 Module Installation Guide

JD2800 Module Installation Guide Up to 30% More Horsepower 10-20% Fuel Savings John Deere 9.0L Tier III Denso Common Rail Engines JD2800 Module Installation Guide AgDieselSolutions.com Ground Terminal Power (+12V constant) Terminal Injector

More information

Remote Vehicle Control System CA-150. Owner's Manual. Vehicle Security System With Remote Keyless Entry

Remote Vehicle Control System CA-150. Owner's Manual. Vehicle Security System With Remote Keyless Entry Remote Vehicle Control System CA-150 Owner's Manual Vehicle Security System With Remote Keyless Entry IMPORTANT NOTE: The operation of the Security and Convenience System as described in this manual is

More information

i n s t r u c t i o n m a n u a l

i n s t r u c t i o n m a n u a l i n s t r u c t i o n m a n u a l 8006 Six-Station AC Timer Residential/Light Commercial Independent Program Irrigation Controllers Installation, Programming and Operating Instructions Features Operates

More information

7.3L POWERSTROKE BANJO BOLT KIT Fits L Powerstroke Diesel. Installation Guide

7.3L POWERSTROKE BANJO BOLT KIT Fits L Powerstroke Diesel. Installation Guide 7.3L POWERSTROKE BANJO BOLT KIT Fits 94-03 7.3L Powerstroke Diesel Installation Guide INSPECT CONTENTS OF THIS KIT THOROUGHLY BEFORE STARTING THE INSTALLATION PROCESS! IF YOU FIND A PROBLEM WITH YOUR PACKAGE:

More information

Motorized Stainless 2-Way Valves

Motorized Stainless 2-Way Valves Installation and Operation Manual Motorized Stainless 2-Way Valves Safety Valve ETV Applications WARNING This Heat-Timer valve is strictly an operating valve; it should never be used as a primary limit

More information

PVI 60KW, PVI 82KW, PVI 95KW

PVI 60KW, PVI 82KW, PVI 95KW PVI 60KW PVI 82KW PVI 95KW WARRANTY MANUAL Commercial, Grid-Tied Photovoltaic Inverters 2008, Solectria Renewables LLC Subject to Change DOC-020099 rev 024 1 1 Product Warranty & RMA Policy Warranty Policy

More information

Water Jetter Units DU JT50 / DU JT100

Water Jetter Units DU JT50 / DU JT100 Water Jetter Units DU JT50 / DU JT100 Serial Number: Owner s Manual #0818 102011 Installation Date: IMPORTANT Please read and u n d e r s t a n d t h i s manual. Store in safe location for future reference.

More information

Female Plug. connecting to Fuel Quantity

Female Plug. connecting to Fuel Quantity **Ag Diesel Solutions recommends replacing the Transorb/Suppressor Diode before the installation of this module*** Red wire = 12V Constant power. Male Plug connecting to Fuel Quantity Valve Black wire

More information

DODGE CUMMINS GDP Big Line Kit

DODGE CUMMINS GDP Big Line Kit Installation Manual P/N 9852BLK 1998.5-2002 DODGE CUMMINS GDP Big Line Kit Installation Instructions P/N 9852BLK GDP Big Line Kit Installation PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

More information

JDCR2000 Module Installation Guide

JDCR2000 Module Installation Guide Up to 30% More Horsepower 10-20% Fuel Savings John Deere 4.5L, 8.1L & 9.0L Tier III Denso Common Rail Engines JDCR2000 Module Installation Guide AgDieselSolutions.com FEMALE FUEL PRESSURE CONNECTOR (FPC)

More information

DODGE CUMMINS Arctic-Heat Grid Relocation Kit

DODGE CUMMINS Arctic-Heat Grid Relocation Kit Installation Manual P/N 07509-350-GRK 2007.5-09 DODGE CUMMINS Arctic-Heat Grid Relocation Kit Installation Instructions P/N 07509-350-GRK GDP Arctic-Heat Grid Heater Installation PLEASE READ ALL INSTRUCTIONS

More information

ST-70 CONTROL OPERATING MANUAL REVISION DATE: PART#:

ST-70 CONTROL OPERATING MANUAL REVISION DATE: PART#: ST-70 CONTROL OPERATING MANUAL REVISION DATE: 05-15-07 PART#: 98-0002-09 SERVICE & CUSTOMER INFORMATION CUSTOMER MUST HAVE PART NUMBER WHEN ORDERING ITEMS THROUGH THE SERVICE DEPARTMENT. IF FURTHER HELP

More information

10 Year Limited Warranty

10 Year Limited Warranty Power. On Your Terms. 10 Year Limited Warranty PHI 2.7 TM PHI 3.5 TM 60A SIMPLIPHI POWER, INC. REV020618 10 Year Limited Warranty: PHI 2.7 TM PHI 3.5 TM 60A 24V 48V Limited Pro-Rated Warranty Coverage

More information

Superchips Model 2704 MAX MicroTuner GM Trucks with 6.6L Duramax Diesel Engines Vehicle Programming Instructions

Superchips Model 2704 MAX MicroTuner GM Trucks with 6.6L Duramax Diesel Engines Vehicle Programming Instructions Page 1 of 12 Form 0137D 11/30/2004 Superchips Inc. Superchips Model 2704 MAX MicroTuner 2004-2005 GM Trucks with 6.6L Duramax Diesel Engines Vehicle Programming Instructions PLEASE READ THIS ENTIRE INSTRUCTION

More information

MODEL MCL /8 SPEEDOMETER/TACHOMETER for 2004 up

MODEL MCL /8 SPEEDOMETER/TACHOMETER for 2004 up MODEL MCL-3204 3-3/8 SPEEDOMETER/TACHOMETER for 2004 up IMPORTANT NOTE! This gauge has an odometer preset option that is only available one time in the first 100 miles (160km) of operation. See Odometer

More information

HA/HAB Fiberglass Wall Mount Ventilators

HA/HAB Fiberglass Wall Mount Ventilators HA/HAB Fiberglass Wall Mount Ventilators INSTALLATION, OPERATION & MAINTENANCE MANUAL IM-3100 August 2015 Throughout this manual, there are a number of HAZARD S that must be read and adhered to in order

More information

CU6703 Module Installation Guide

CU6703 Module Installation Guide Up to 30% More Horsepower 10-20% Fuel Savings Cummins 6.7L Tier III Engines CU6703 Module Installation Guide AgDieselSolutions.com MAP sensor male and female connectors. Power and Ground wires. Module

More information

MODELS CX10 and CX20 INDUSTRIAL PUMPS INSTRUCTIONS AND SERVICE MANUAL

MODELS CX10 and CX20 INDUSTRIAL PUMPS INSTRUCTIONS AND SERVICE MANUAL MODELS CX0 and CX20 INDUSTRIAL PUMPS INSTRUCTIONS AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains

More information

Generator Start Control Module

Generator Start Control Module Generator Start Control Module Part# GSCM-mini-i ATKINSON ELECTRONICS, INC. 14 West Vine Street Murray, Utah 84107 Contact cbdsales@atkinsonel.com for the proper hookup diagram. Please include the generator

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

TOUGH GARD Anti-Spatter Multi-Feed System

TOUGH GARD Anti-Spatter Multi-Feed System OM-MF-1.0 June 2016 Processes MIG (GMAW) Welding Description MIG (GMAW) Welding Peripheral TOUGH GARD Anti-Spatter Multi-Feed System OWNER S MANUAL Tregaskiss 2570 North Talbot Road Windsor, Ontario N0R

More information

END USER TERMS OF USE

END USER TERMS OF USE END USER TERMS OF USE The following is the End Users Terms of Use as it currently appears in the Mobileye User Manual and Warranty information. This is here for your review and information; it is subject

More information

Table of Contents. How the Surestart SE 433 Operates Starting the Vehicle with the Remote Starter... 3

Table of Contents. How the Surestart SE 433 Operates Starting the Vehicle with the Remote Starter... 3 Table of Contents How the Surestart SE 433 Operates... 3 Starting the Vehicle with the Remote Starter... 3 Stopping the Vehicle While It Is Running Via the Remote Starter... 4 Operating Your Vehicle While

More information

Users Guide for Ac-sync

Users Guide for Ac-sync Problem solved. Users Guide for Ac-sync Thank you for choosing Anywhere Cart! The AC-SYNC is designed to sync, charge and store 1-36 ipads or tablets. Adjustable device divider bays allow fitment of any

More information

WARRANTY POLICY. Grid-Tied Photovoltaic Inverters. Revision D. 2014, Solectria Renewables, LLC DOCIN

WARRANTY POLICY. Grid-Tied Photovoltaic Inverters. Revision D. 2014, Solectria Renewables, LLC DOCIN WARRANTY POLICY Revision D 2014, Solectria Renewables, LLC DOCIN-070360 1 Product Warranty & RMA Policy 1. Warranty Policy Warranty Registration: It is important to have updated information about the inverter

More information

MODEL MCL-3212 SPEEDOMETER/TACHOMETER for 2012 up Dyna and Softail with 4 gauge

MODEL MCL-3212 SPEEDOMETER/TACHOMETER for 2012 up Dyna and Softail with 4 gauge MODEL MCL-3212 SPEEDOMETER/TACHOMETER for 2012 up Dyna and Softail with 4 gauge IMPORTANT NOTE! This gauge has an odometer preset option that is only available one time in the first 100 miles (160km) of

More information

Series 2100 Operating Instructions

Series 2100 Operating Instructions Series 2100 Operating Instructions Installation Instructions Visit the link below or scan the QR code to watch a detailed installation video: http://triteqlock.com/fresh After the lock, temperature probe,

More information

Power Float Manifold. Installation and Operations Manual Module 11A

Power Float Manifold. Installation and Operations Manual Module 11A Power Float Manifold Installation and Operations Manual Module 11A 2/14 Table of Contents 1 Features 3 2 Functional Purpose 3 3 4 Specifications System Installation 3 4 4.1 Hydraulic Connection 4 4.2 Electric

More information

DODGE CUMMINS GDP Twin CP-3 Big Line Kit

DODGE CUMMINS GDP Twin CP-3 Big Line Kit Installation Manual P/N 0306-TCP3 2003-07 DODGE CUMMINS GDP Twin CP-3 Big Line Kit Installation Instructions P/N 0306-TCP3 GDP Twin CP-3 Big Line Kit Installation PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING

More information

INTRODUCTION INSTALLATION

INTRODUCTION INSTALLATION INTRODUCTION INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS This instruction manual includes installation, operation and maintenance information for the figure G73 gear operator. The figure G73 is

More information

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-122 REV A 12/09

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-122 REV A 12/09 HAND CRANK WELDING CABLE REEL: SERIES 100WC COXREELS The technical data and images which appear in this manual are for informational purposes only. NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES

More information

SUNTURA HD SOLAR TRACKER

SUNTURA HD SOLAR TRACKER WindyNation SUNTURA HD SOLAR TRACKER SOT-TRKS-NFHD User s Manual Page 1 of 11 WindyNation 08/09/2012 Table of Contents 1! Introduction... 3! 1.1! Limited Warranty... 3! 1.2! Restrictions... 3! 1.3! Warranty

More information

Service Letter. Ariens Company 655 W. Ryan St. Brillion, WI

Service Letter. Ariens Company 655 W. Ryan St. Brillion, WI Date: Dec. 2012 No. L-2124R Service Letter Ariens Company 655 W. Ryan St. Brillion, WI 54110 www.ariens.com Product Family: Ariens and Gravely Products with Hydro-Gear Components Subject: Hydro-Gear Warranty

More information

SUNTURA SOLAR TRACKER

SUNTURA SOLAR TRACKER WindyNation SUNTURA SOLAR TRACKER SOT-TRKS-NF User s Manual Page 1 of 10 WindyNation 08/09/2012 Table of Contents 1 Introduction... 3 1.1 Limited Warranty... 3 1.2 Restrictions... 3 1.3 Warranty Claims

More information

ECLIPSE Laundry Dispenser Controller

ECLIPSE Laundry Dispenser Controller ECLIPSE Laundry Dispenser Controller Reference Manual Programming and Operation Online and downloadable Product Manuals and Quick Start Guides are available at www.hydrosystemsco.com Please check online

More information

L DODGE CUMMINS Maximizer System

L DODGE CUMMINS Maximizer System Installation Manual P/N 07509MAX 2007.5-09 6.7L DODGE CUMMINS Maximizer System Installation Instructions P/N 07509MAX GDP Big Line Kit Installation PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

More information

Cummins N14 Celect & Celect Plus Engine Module. For Agricultural Applications Only. Part # 31200

Cummins N14 Celect & Celect Plus Engine Module. For Agricultural Applications Only. Part # 31200 1994-2003 Cummins N14 Celect & Celect Plus Engine Module For Agricultural Applications Only Part # 31200 31200_revA Adjustable Switch Agricultural Cummins N14 Engine Module Power and Ground terminals Timing

More information

Components. Options Accessory Harness USB Charger. Quick Connector. Hook & Loop / Cable-ties. RFID Antenna. Module. Main Harness.

Components. Options Accessory Harness USB Charger. Quick Connector. Hook & Loop / Cable-ties. RFID Antenna. Module. Main Harness. SRX SERIES Table of Contents - Components - Planning The Install - Mounting - Switched Power - Attach Accessory Harness - Plug In Module - Back-Up Battery - Remote Encoding - 2-Way RFID Remote User Instructions

More information

StormPro BCV400 Sewage Ejector Pump

StormPro BCV400 Sewage Ejector Pump Page 1 of 8 Marks & Meanings DANGER: Keep the pump equipment out of the reach of children! Warns that the failure to follow the directions given could cause serious risk to individuals or objects. WARNING:

More information

½ DODGE CUMMINS OEM BYPASS LIFT PUMP KIT Installation Instructions Part #

½ DODGE CUMMINS OEM BYPASS LIFT PUMP KIT Installation Instructions Part # 29 July 2005 2003-04.5 Dodge Cummins OEM Bypass Lift Pump Kit # 1050227-1 - 2003-04½ DODGE CUMMINS OEM BYPASS LIFT PUMP KIT Installation Instructions Part # 1050227 PLEASE READ ALL INSTRUCTIONS CAREFULLY

More information

PreSoak System (NonFoaming) DU PS1-HP DU PS6-HP

PreSoak System (NonFoaming) DU PS1-HP DU PS6-HP PreSoak System (NonFoaming) DU PS1-HP DU PS6-HP Serial Number: Owner s Manual #0786 040810 Installation Date: Please read and u n d e r s t a n d t h i s manual. Store in safe location for future reference.

More information

DODGE CUMMINS MK-2 Micro-Kleen System

DODGE CUMMINS MK-2 Micro-Kleen System Installation Manual P/N MK20306 2003-07 DODGE CUMMINS MK-2 Micro-Kleen System Installation Instructions P/N MK20306 2 Micron Fuel Filter Installation PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

More information

Filtered PWM Speed Control for Permanent Magnet DC Motors

Filtered PWM Speed Control for Permanent Magnet DC Motors Instructions for Installation and Operation Filtered PWM Speed Control for Permanent Magnet DC Motors Model 0794 Speed and Direction Control up to 5/8 HP NEMA-1/IP-20 Specifications Product Type:... WPM-2148E1

More information

Remote Vehicle Control System. Keyless Entry & Remote Start System

Remote Vehicle Control System. Keyless Entry & Remote Start System 1 Remote Vehicle Control System PC 7400 TM Owner's Manual Keyless Entry & Remote Start System IMPORTANT NOTE: The operation of the Power Code as described in this manual is applicable to most vehicles.

More information

PREMIER, MARINE, & STANDARD

PREMIER, MARINE, & STANDARD INSTA LLATION INSTRUCTION AND SERVICE MANUAL I TITAN 12" x 2" BRAKES FREE BACKING. UNI-SERVO. DUO-SERVO PREMIER, MARINE, & STANDARD Limited Warranty TITAN Inc. ("TITAN') warrants its products to be free

More information

QUICK START GUIDE OWNER S MANUAL AL50 SERIES SAND FILTRATION TECHNOLOGY PLEASE CALL DO NOT RETURN TO STORE

QUICK START GUIDE OWNER S MANUAL AL50 SERIES SAND FILTRATION TECHNOLOGY PLEASE CALL DO NOT RETURN TO STORE QUICK START GUIDE OWNER S MANUAL SAFETY, INSTALLATION, OPERATION & PARTS AL50 SERIES SAND FILTRATION TECHNOLOGY PLEASE CALL 877-278-2797 DO NOT RETURN TO STORE! WARNING This equipment must be installed

More information

CA 5054 Owner s Guide

CA 5054 Owner s Guide PROFESSIONAL SERIES CA 5054 Owner s Guide Remote Start and Keyless Entry System IMPORTANT NOTE: The operation of the Security and Convenience System as described in this manual is applicable to most vehicles.

More information

MODEL V-24 OWNER'S MANUAL PARTS

MODEL V-24 OWNER'S MANUAL PARTS OWNER'S MANUAL MODEL V-24 PARTS NOTE: MANUAL including SPECIFICATIONS, subject to change without notice All ratings specified are based on structural factors only, not vehicle capacities or capabilities.

More information

FREQUENTLY ASKED QUESTION SERIES. BANJO BOLTS WHY THE BAD RAP? 6.0L Powerstroke Diesel. Last Updated: 7/2/2018 Page 1 of 3 S Diesel, LLC

FREQUENTLY ASKED QUESTION SERIES. BANJO BOLTS WHY THE BAD RAP? 6.0L Powerstroke Diesel. Last Updated: 7/2/2018 Page 1 of 3 S Diesel, LLC FREQUENTLY ASKED QUESTION SERIES BANJO BOLTS WHY THE BAD RAP? 6.0L Powerstroke Diesel Last Updated: 7/2/2018 Page 1 of 3 S Diesel, LLC Ihave been getting a bunch more comments and questions from customers

More information

Firstmate Installation Manual and User's Guide May, 2003

Firstmate Installation Manual and User's Guide May, 2003 Firstmate Installation Manual and User's Guide May, 2003 Aqualogic Marine, Inc. 506-D Terry Lane - Washington - Missouri - 63090 Warning No user serviceable parts are located inside your Firstmate unit.

More information

Owner s Guide CA 5055

Owner s Guide CA 5055 PROFESSIONAL SERIES Owner s Guide For Model: CA 5055 Vehicle Remote Start and Keyless Entry System IMPORTANT NOTE: The operation of the Security and Convenience System as described in this manual is applicable

More information

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 B R A N D Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 For Sales, Support and Service phone: 407-331-4793 fax: 407-331-4708 website: www.xenotronix.com email: information@xenotronix.com

More information

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the

More information

DODGE CUMMINS 24V ISB OEM BYPASS LIFT PUMP KIT Installation Instructions Part #

DODGE CUMMINS 24V ISB OEM BYPASS LIFT PUMP KIT Installation Instructions Part # 2/15/2006 2000-2002 Dodge Cummins OEM Bypass Lift Pump Kit # 1050229-1 - 2000-02 DODGE CUMMINS 24V ISB OEM BYPASS LIFT PUMP KIT Installation Instructions Part # 1050229 PLEASE READ ALL INSTRUCTIONS CAREFULLY

More information

DSL-1 E DIESEL TACH INTERFACE UNIT

DSL-1 E DIESEL TACH INTERFACE UNIT DSL-1 E DIESEL TACH INTERFACE UNIT This unit can provide a tachometer signal to drive a standard ignition system tachometer. The input signal can be from a tachometer output from the alternator, from a

More information

L DODGE CUMMINS MK-2 + BLK APPS Mount

L DODGE CUMMINS MK-2 + BLK APPS Mount Installation Manual P/N MK20305-APPS 2003-05 5.9L DODGE CUMMINS MK-2 + BLK APPS Mount Installation Instructions P/N MK20305-APPS 2 Micron + Big Line Kit APPS Mount Installation PLEASE READ ALL INSTRUCTIONS

More information

RETROFIT SYSTEMS INSTALLATION AND SERVICE MANUAL. Engineered for quick and easy replacement of existing progressive cavity grinder systems.

RETROFIT SYSTEMS INSTALLATION AND SERVICE MANUAL. Engineered for quick and easy replacement of existing progressive cavity grinder systems. RETROFIT SYSTEMS INSTALLATION AND SERVICE MANUAL Engineered for quick and easy replacement of existing progressive cavity grinder systems. Fully assembled Uses existing ball valve and latch Uses existing

More information

Model 20 Constant Speed Blender : 115 Volt : 230 Volt. Instruction Manual. Updated 11/14/2017 Ver. 4.0

Model 20 Constant Speed Blender : 115 Volt : 230 Volt. Instruction Manual. Updated 11/14/2017 Ver. 4.0 Model 20 Constant Speed Blender 120-65: 115 Volt 120-65-1: 230 Volt Instruction Manual Updated 11/14/2017 Ver. 4.0 OFI Testing Equipment, Inc. 11302 Steeplecrest Dr. Houston, Texas 77065 U.S.A. Tele: 832.320.7300

More information

ME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt.

ME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt. ME3H SUMP/EFFLUENT PUMP ME3F SUMP/EFFLUENT PUMP ME3H/ME3F SERIES SUBMERSIBLE SUMP AND EFFLUENT PUMPS INSTALLATION AND SERVICE MANUAL Automatic and manual models. Single phase power only 115 or 230 volt.

More information

IAQ-CALC INDOOR AIR QUALITY METER MODEL 7515

IAQ-CALC INDOOR AIR QUALITY METER MODEL 7515 IAQ-CALC INDOOR AIR QUALITY METER MODEL 7515 OPERATION AND SERVICE MANUAL P/N 1980571, REVISION D FEBRUARY 2016 Copyright TSI Incorporated / May 2007-2016 / All rights reserved. Address TSI Incorporated

More information

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES Instruction D12043 June 2016 DeZURIK Instructions These instructions provide installation, operation and maintenance information for APCO CRF-100A Rubber

More information

Dodge Ram 5.9L Cummins LOW FUEL PRESSURE ALARM LIGHT - Installation Manual -

Dodge Ram 5.9L Cummins LOW FUEL PRESSURE ALARM LIGHT - Installation Manual - 29 September 2005 Dodge Cummins Low Fuel Pressure Alarm Light Kit 1081130-33 1 1999-2005 Dodge Ram 5.9L Cummins LOW FUEL PRESSURE ALARM LIGHT - Installation Manual - Part Number Sequence: 1081130 Red 1081133

More information

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list OPERATOR'S MANUAL Automatic Genset Controller, AGC-4 Display readings Push-button functions handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

This document describes:

This document describes: Thank you for purchasing this product from ERM. We appreciate your interest in our unique product line as we try to offer our customers an alternative to today s traditional products. This programmable

More information

Owner s Guide. ca5154

Owner s Guide. ca5154 PROFESSIONAL SERIES Owner s Guide for models: ca5154 Automatic / Manual Transmission Remote Start and Keyless Entry System IMPORTANT NOTE: The operation of the Security and Convenience System as described

More information