1 MAIN Report for NERC Initial Investigation NERC TLR Level 5A Flowgate Kewaunee 345/138 kv Transformer for the loss of Point Beach-North Appleton 345kV Line October 15 17, 2001 Submitted January 14, 2002 This report is submitted in accordance with the NERC Transmission Loading Relief (TLR) Investigation Procedure for the TLR event that occurred on Flowgate from October 15 through 17, The NERC TLR Log is attached. Flowgate is an American Transmission Company (ATCo) flowgate. The TLR Level 5A resulted in the curtailment of firm transmission service. ATCo protected all firm transmission service sinking in ATCo using redispatch of generating units in Wisconsin. Tagged firm transactions not sinking in the ATCo system were adjusted as prescribed through IDC calculations. 1. Description of purpose/cause of hold/curtailment Flowgate 10515, an OTDF flowgate, consists of the following elements: Monitored facility: Kewaunee 345/138 kv transformer (382 MW rating) Contingent facility: Point Beach North Appleton 345 kv Line. The Kewaunee-North Appleton 345kV Line was out of service from 0802 CDT on October 15 to 1815 CDT on October 17 when the Kewaunee Nuclear Unit was also schedule out from September 23 at 2353 CDT and is scheduled back December 2. With the Kewaunee- N.Appleton 345kV Line out, the Point Beach-N.Appleton 345kV Line increases in importance as a critical contingency for the Kewaunee Transformer flows. With the outage of Point Beach-N.Appleton 345kV lines, additional Point Beach Nuclear Unit generation outlet flows towards Kewaunee, thus increasing the Kewaunee Transformer 345 to 138kV flow. In addition, the Kewaunee Transformer and multiple transformers at the North Appleton Substation support the 138kV system in the area around Green Bay. With the Kewaunee-N.Appleton out and the possible trip of Point Beach-N.Appleton, the beneficial post contingency flows through the North Appleton transformers are reduced. Because line flows were increased by scheduled outages, the limiting condition was not part of the permanent set of flowgates. For this TLR event a temporary flowgate was created, which will likely become a permanent flowgate. When the Kewaunee-North Appleton 345kV Line was returned to service, the post-contingency loading problem was reduced and the TLR was released. 2. Facility/flowgate limitations and flows at the time the TLR was initiated The Kewaunee 345/138 kv Transformer is rated at 382 MW (winter emergency). At the time of the initial TLR Level 5A, flow on the Kewaunee Transformer was 249 MW and the flow on the Point Beach-North Appleton Line was 477 MW. Using an LODF of 37.5%, the post-contingent flow would be 428 MW. ATCo contingency analysis showed that if Line

2 Page 2 F-84 at E Krok 138kV Substation is opened, the post contingent flow is reduced approximately 60 MW. ATCo would open this line in the event of the loss of the contingent element. For relief beyond non-firm transactions, ATCo reduced the relief requested by 60MW. Below is a summary of the system conditions at the time the TLR was implemented. 1. Indian Lake-Manistique-Hiawatha 69 kv tie with MECS control area opened to mitigate south to north flow in Wisconsin (TLR Level 4, Flowgate 3525, Stiles Amberg 138 kv Line for the loss of Morgan Plains 345 kv Line). 2. TLR Level 3A Flowgate 3707 (Lore-Turkey River 161 kv Line for the outage of Wempletown-Paddock 345 kv Line). 3. North Appleton Kewaunee 345 kv circuit scheduled outage. 4. Kewaunee Nuclear Station off line (Scheduled, Pmax=511 MW). 5. Initial TLR Level 3A issued for Flowgate 3611, Kewaunee 345/138 kv Transformer. Flowgate created (Kewaunee 345/138 for the outage of North Appleton to Point Beach 345 kv (ODF=.375)). GSFs for Flowgate were not available through the NERC GSF viewer and were calculated at MAIN and distributed to ATCo. 6. NERC in full alert status. 7. DOE in SECON 2 (second highest status). 8. NRC level 3 (highest alert status). 9. GSFs for this flowgate were calculated at MAIN and distributed to ATCo operations because new flowgates are not initially available through the normal GSF viewer. The one-line diagram below illustrates the Kewaunee area system configuration during this TLR event (Green breakers indicating open status).

3 Page 3 3. TLR Levels, timing and relief requested amounts October 15: ATCo requested TLR Level 3A for the Kewaunee 345/138 kv Transformer for the loss of North Appleton-Point Beach 345 kv Line. Since the flowgate element combination did not exist in the IDC, the new Flowgate was created. At 0849 CDT TLR Level 3A was issued for the Kewaunee Transformer (Flowgate 3611) until Flowgate would be available in the IDC after Flowgate was built for the North Appleton-Point Beach contingency. New flowgates are not always ready at the top of the hour. At 0915 CDT, a preliminary TLR Level 3A was confirmed for Flowgate 10515, and Flowgate 3611 was reduced to TLR Level 0. All non-firm transactions affecting this flowgate had been previously curtailed by flowgate 3707, Lore-Turkey River 161 kv Line for the outage of Wempletown-Paddock 345 kv Line. Eight Priority 6 tags totaling 315 MW were providing 41.5 MW relief on Flowgate The IDC Whole Transaction List (WTL) did not show any firm tags sinking outside ATCo for the HB 1000 CDT. Therefore, at 0945 CDT flowgate was increased to TLR Level 4, as ATCo began to redispatch at Pulliam, West Marinette, and Depere generating stations. At 1230 CDT the HB 1300 CDT Whole Transaction List for Flowgate contained two firm transactions not sinking in the ATCo system and therefore not covered under ATCo redispatch for Network Integrated Service Tariff Transactions. The TLR event was increased from TLR Level 4 to TLR Level 5A for the HB 1300 CDT. For that hour, 5.4 MW of tagged firm transactions and 40 MW of ATC redispatch was prescribed. 5.2 MW of tagged firm relief was sinking in the ATCo system and was disregarded in the IDC because the relief was provided through additional redispatch. The amount of relief requested was sufficient to maintain acceptable flows and remained constant through the day. ATCo maintained this level of dispatch even at periods of lighter loading to reduce cycling of nuclear units. At 2200 CDT the Whole Transaction List contained only firm transactions sinking in the ATCo system. ATCo reduced to TLR Level 4 at 2204 CDT and redispatch reduced from 65 MW of relief to 37 MW of relief. At 2325 CDT ATCo had discontinued redispatch and at 0030 CDT the flowgate was reduced to TLR Level 1. During the TLR Level 5A events, the MAIN Security Coordinator issues the TLR without excluding any of the ATCo sinking firm tags. Once issued, the MAIN security coordinator will DISREGARD the tags sinking in ATCo. This will cause them to show up as pink in the acknowledgement column of the congestion management reports. It should also prevent IDC tagging messages to the CAs and PSEs. MAIN then sends out a copy of the IDC screen to its transmission members and makes the appropriate CA calls. MAIN also calls ATCo to give them the redispatch amount which is the total firm curtailments for ATCo sinking tags and the NNL required redispatch for ATCo control areas. During the first hour of the TLR Level 5A event, MAIN conveyed to the sink CAs (WPS/UPPC) that, except for 2 firm tags not sinking in ATCO, all other firm tags would be covered by ATCo redispatch. There was confusion over the Congestion Management Report, and WPS implemented firm tag curtailments for some of the tags. This was noticed in the following hour. The adjustments were corrected and the practices were discussed with ATCo, WPS and MAPP.

4 Page 4 October 16: TLR Level 4 issued at 0450 CDT. Manistique-Hiawatha 69 kv tie was opened and 1 nonfirm transaction curtailed. At 0630 CDT Flowgate Whole Transaction list again contained firm tags not sinking in ATCo and TLR Level 5A was issued with 63 MW of firm relief, of which 62.8 MW of relief achieved through redispatch. At 0930 CDT, ATCo was requested to reduce redispatch from 63 MW to 33 MW. At 1030 CDT ATCo had reduced redispatch to 48.6 MW. This level of redispatch was held constant until 2230 CDT, when TLR Level 4 was issued and redispatch ceased at 2300 CDT. Manistique- Hiawatha 69 kv Circuit remained opened and the TLR was reduced to level 1 at 2330 CDT. October 17: TLR Level 4 issued at 0625 CDT and increased to TLR Level 5A at the bottom of the hour. About 62.5 MW relief was achieved through ATCo redispatch and.2 MW from curtailed firm tags. Requested relief did not change through the day. At 1820 CDT, Line R-304 (North Appleton Kewaunee 345 kv) returned to service and the TLR event was released to zero. 4. Transmission and generation outages or changes from prediction that may have contributed 1. Indian Lake-Manistique-Hiawatha 69 kv Tie with MECS control area opened to mitigate south to north flow in Wisconsin (TLR Level 4, Flowgate 3525, Stiles Amberg 138 kv for the loss of Morgan Plains 345 kv). 2. North Appleton Kewaunee 345 kv Circuit scheduled outage. 3. Kewaunee Nuclear Station scheduled off line. 5. Procedures implemented prior to hold/curtailment During the periods in which all firm transactions in the Whole Transaction List for Flowgate were sinking in the ATCo system, the TLR was reduced to Level 4, curtailing all non-firm transactional flow and redispatching as necessary. GSFs for this flowgate were calculated at MAIN and distributed to ATCo operations because new flowgates are not initially available through the normal GSF viewer. ATCo investigations of potential operating options determined that opening of Line F-84 (Kewaunee-E.Krok 138kV) would reduce the post-contingency loading on the Kewaunee Transformer. Analysis showed that it would reduce the post-contingent flow by 60 MW. ATCo would take the action in the event of the loss of the contingent element. For relief beyond non-firm transactions, ATCo took this operational option into account when requesting relief.

5 Page 5 6. Compare Complete Transaction Curtailment List with the Whole Transaction List as generated by the IDC, before and after curtailments Below is a sample Whole Transaction List from October 15 for hour beginning 1000 CDT. It is typical for the on-peak hours during this TLR. The second transaction list is taken from the Congestion Management Report for the TLR Level 5A reissue for hour beginning 1500 CDT on October 15. In this instance, the 6.7 MW relief required from the firm tags sinking in ATCo was achieved through redispatch, and.2 MW relief was obtained through the curtailment of firm transactions passing through ATCo.

6 Page 6 7. Known Transactions not in the IDC and actions taken There were no known transactions not listed in the IDC Whole Transaction List. 8. SCIS or other system messages SCIS message for October 15, 2001 to October 18, 2001 that may be considered relevant to the TLR Level Level 5. MAIN (for Alliant) 10/17/2001 7:56:00 AM Critical Infrastructure Protection Stage 1 Report Reported by MAIN (for Alliant) Lou Leffler 10/15/2001 9:57:00 AM Security Alert update Lou Leffler 10/15/ :56:00 PM SCIS Cutover-Please note MAIN Time Stamp (CST) 10/16/2001 9:17:00 AM MAIN called the IDC help desk. Subject IDC reboot They stated they are doing a quick reboot. Sender OATI Time Stamp (CST) 10/16/2001 9:26:00 AM Subject IDC up again imo 10/16/ :37:00 AM ISO-NE Time Stamp (CST) 10/16/2001 6:25 PM It should be up again soon. The IDC system is available again, Thank you for your patience, IDC Helpdesk NYISO evacuating to backup control center - due to failure of redundant UPS SUSPICIOUS PLANT ACTIVITY David Souder Time Stamp (CST) 10/17/2001 4:06:00 AM Subject System Frequency MAIN security desk Time Stamp (CST) 10/17/2001 5:03:00 AM Subject Called help desk about IDC alarms Last 2 mornings system frequency has dipped to Hz across the 06:00 ramp. Can anyone provide information? MAIN called the IDC help desk about the IDC alarms. They appear to be about 20 minutes late. Sometimes they don't have an audible. They will investigate.

7 Page 7 Lou Leffler Time Stamp (CST) 10/17/2001 6:26:00 AM Subject SCIS note Main scop Time Stamp (CST) 10/18/2001 8:41:00 AM Subject new SCIS??? Tom Campbell Time Stamp (CST) 10/18/2001 9:00:00 AM Subject Free Form Messages are now posting properly Lynn Constantine Time Stamp (CST) 10/18/ :00:00 AM Subject SCIS We will be moving to the secure SCIS server today.. the new SCIS alarms, but does not show new messages. I also show 10 TLR messages, but the amount can't be cleared. Please investigate. Message that were posted earlier are list (we deleted most of the test messages though). SCIS experienced problems this morning, but we believe they have been rectified. We just completed testing -- posting test messages and then deleting them. All appears to be working as expected. If you continue to experience any difficulties, please me at support@nerc.com. Lynn Costantini 9. State estimator snapshots and security analysis including and contingency analysis or stability analysis along with any other recorded data indicating the need for TLR Not Available 10. ATC Limitations before, during, and after the event The implementation of TLR Level 3A or higher resulted in the posting of 0 MW ATC for hourly and daily transmission service for directions relating to WPS, MGE, DPC, and UPPC imports. MAIN restricts ATC for paths with TDFs greater than or equal to 3% on monitored facilities determined to be constraining in the ATC calculations. The hourly and daily ATCs for imports into WUMS were 0 MW from the day before and same day ATC calculations. These directions were limited by the Kewaunee Transformer and were calculated to be 0 MW for all day ahead and same day studies for the period of October 15 through 17, the duration of the TLR event. With the North Appleton-Kewaunee 345 kv circuit in service, WPS, UPPC, and MGE had a positive ATC value for directions previously affected by Flowgate The CE-DPC direction remained 0, but was limited by ALTW line Savanna York 161 kv. 11. Actions taken to avoid future hold/curtailments The transmission outage was coordinated with the outage of the Kewaunee Plant outage to minimize the effect on the transmission system. ATC values were reduced during the outage and will be for future outages.

8 Page Re-dispatch actions taken Below is a table which details hourly redispatch actions taken by generating unit.

9 Page 9

10 Page 10

11 Page 11

12 Page If Firm transaction curtailment took place, description of Transactional Contribution Factor calculation and results as well as how necessary relief was obtained through network service and native load contribution Below is a sample Congestion Management Report with the curtailments of network service and native load contributions during this TLR. ATCo fulfilled all firm curtailment obligations through redispatch. Tagged firm transactions sinking in the ATCo system were disregarded in the Interchange Distribution Calculator and the ATCo operator was alerted to the additional relief required through redispatch. The Congestion Management Report below was generated for hour beginning 1700 on October 16. A typical TLR Level 5A issue for this event would have the approximate ratios: 86.2% 41.8 MW (NNL responsibility for a ATCO CAs, provided by ATCo redispatch) 13.4% 6.5 MW (firm tags sinking in ATCO, covered by ATCO redispatch) 0.4 % 0.2 MW (curtailed firm tags not covered by ATCo redispatch) 14. Other options considered before/during to avoid hold/curtailment ATCo studies show that if they open line F-84 at E Krok 138, it will bring the post-contingent flow down approximately 60 MW. This action would be implemented upon the loss of the contingent element.

13 Attachment

Highly Constrained Elements Within ATC Footprint

Highly Constrained Elements Within ATC Footprint Highly Constrained Elements Within ATC Footprint Feb. 21, 2008 Presented by Dale Burmester Compiled by ATC Economic Planning Team: Tom Dagenais, Todd Tadych, Arash Ghodsian, Chris Hagman Solutions to Market

More information

Northeast Wisconsin/Upper Peninsula Separation 11/14/01. Incident Investigation Report

Northeast Wisconsin/Upper Peninsula Separation 11/14/01. Incident Investigation Report Northeast Wisconsin/Upper Peninsula Separation 11/14/01 Incident Investigation Report Summary Contact by a high voltage electric transmission line with a tree in northeastern Wisconsin initiated a series

More information

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR #

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR # Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #75669514, under the SaskPower Open Access Transmission Tariff (OATT). The TSR consists

More information

Seabrook Substation Reliability Improvement Project

Seabrook Substation Reliability Improvement Project New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability

More information

Table of Contents. Purpose. Eldorado Intertie and System (Eldorado- Moenkopi) Scheduling at Willow Beach. Operating Procedure

Table of Contents. Purpose. Eldorado Intertie and System (Eldorado- Moenkopi) Scheduling at Willow Beach. Operating Procedure No. 6930 Table of Contents Purpose... 1 1. Limits, Ratings, & Effectiveness Factors... 2 2. Contingency Operations... 2 2.1 Transmission Lines Outages... 2 2.2 APS Terminal Equipment Outages... 2 2.3 SCE

More information

EMET Investigation Report for TLR 5a Event on June 6, 2001 Kanawha River-Matt Funk 345 kv for Outage of Baker-Broadford 765 kv Flowgate 2403

EMET Investigation Report for TLR 5a Event on June 6, 2001 Kanawha River-Matt Funk 345 kv for Outage of Baker-Broadford 765 kv Flowgate 2403 EMET Investigation Report for TLR 5a Event on June 6, 2001 Kanawha River-Matt Funk 345 kv for Outage of Baker-Broadford 765 kv Flowgate 2403 This report is submitted in accordance with the NERC Transmission

More information

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew. Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...

More information

SPP-RTO: Operational Characteristics

SPP-RTO: Operational Characteristics SPP-RTO: Operational Characteristics Derek Hawkins, Supervisor Real Time Support May 23, 2018 SouthwestPowerPool SPPorg southwest-power-pool 2 The SPP Footprint: Members in 14 States Arkansas Kansas Iowa

More information

ATTACHMENT Y STUDY REPORT

ATTACHMENT Y STUDY REPORT Attachment Y Study Presque Isle 5, 6, 7, 8, & 9: 344 MW Coal Retirement, Effective 10/15/2014 ATTACHMENT Y STUDY REPORT August 15, 2014 EXECUTIVE SUMMARY Pursuant to the Tariff, an Attachment Y Notification

More information

Hurricane Sandy. Preparations, Response & Recovery. Wes Yeomans Vice President Operations Management Committee Meeting November 2, 2012

Hurricane Sandy. Preparations, Response & Recovery. Wes Yeomans Vice President Operations Management Committee Meeting November 2, 2012 Hurricane Sandy Preparations, Response & Recovery Wes Yeomans Vice President Operations Management Committee Meeting November 2, 2012 Topics Storm Preparation Sequence of Events Infrastructure Status Operations

More information

Power Systems Fundamentals

Power Systems Fundamentals Power Systems Fundamentals Yachi Lin Senior Manager, Transmission Planning New York Independent System Operator Market Overview Course September 20, 2017 Rensselaer, NY 2017 New York Independent System

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

IMM Quarterly Report: Summer 2017

IMM Quarterly Report: Summer 2017 IMM Quarterly Report: Summer 2017 MISO Independent Market Monitor David Patton, Ph.D. Potomac Economics September 19, 2017 Highlights and Findings: Summer 2017 The MISO markets performed competitively

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

EXCEPTIONS TO RELIABILITY RULES Revision 11 February 9, 2018

EXCEPTIONS TO RELIABILITY RULES Revision 11 February 9, 2018 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES Revision 11 February 9, 2018 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed

More information

Facilities Study for Alberta to US Available Transfer Capability

Facilities Study for Alberta to US Available Transfer Capability Facilities Study for Alberta to US Available Transfer Capability Report No: NPP2002-05 June 3, 2002 System Planning & Grid Operations, Transmission Line of Business Engineering Services Executive Summary

More information

MINIMUM OIL BURN/AUTOMATIC FUEL SWAPPING CAPABILITY

MINIMUM OIL BURN/AUTOMATIC FUEL SWAPPING CAPABILITY 1.0 PURPOSE... 2 2.0 MINIMUM OIL BURNING/AUTOMATIC FUEL SWAPPING CAPABILITY NOTIFICATIONS... 3 3.0 MINIMUM OIL BURNING/AUTOMATIC FUEL SWAPPING CAPABILITY CRITERIA... 5 4.0 MINIMUM OIL BURNING/AUTOMATIC

More information

Supplemental Report on the NCTPC Collaborative Transmission Plan

Supplemental Report on the NCTPC Collaborative Transmission Plan Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for

More information

EXCEPTIONS TO RELIABILITY RULES REVISION 4 MAY 8, 2015

EXCEPTIONS TO RELIABILITY RULES REVISION 4 MAY 8, 2015 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES REVISION 4 MAY 8, 2015 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed its LTE

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

Memorandum. This memorandum requires Board action. EXECUTIVE SUMMARY

Memorandum. This memorandum requires Board action. EXECUTIVE SUMMARY California Independent System Operator Memorandum To: ISO Operations (MRTU) Committee From: Armando J. Perez, Director of Grid Planning cc: ISO Board of Governors ISO Officers Date: April 29, 2005 Re:

More information

The purpose of this report is to respond to the Notice of Motion CS-16-51, Generators for Fire Halls and Recreation Facilities, including:

The purpose of this report is to respond to the Notice of Motion CS-16-51, Generators for Fire Halls and Recreation Facilities, including: Public Report To: From: Report Number: Community Services Committee Ron Diskey, Commissioner, Community Services Department CS-17-18 Date of Report: March 24, 2017 Date of Meeting: March 30, 2017 Subject:

More information

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST BEFORE THE FLORIDA PUBLIC SERVICE COMMISSION In re: Staff's Second Data Request on OUC' s Review of Electric Utility Hurricane Preparedness and Restoration Actions Docket No. 20170215-EU Filed: January

More information

ATC Report Aug 14, 2003 Event Part 1. Edina Bajrektarević Transmission Operations

ATC Report Aug 14, 2003 Event Part 1. Edina Bajrektarević Transmission Operations ATC Report Aug 14, 2003 Event Part 1 Edina Bajrektarević Transmission Operations ATC Overview 1. ATC owns, plans, maintains and operates transmission assets in portions of Wisconsin, Michigan and Illinois

More information

2016 Load & Capacity Data Report

2016 Load & Capacity Data Report Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation, accuracy, completeness

More information

APPENDIX F: Project Need and Description

APPENDIX F: Project Need and Description APPENDIX F: Project Need and Description California ISO/MID F-1 Intentionally left blank California ISO/MID F-2 Name Brief Description Type Lugo Victorville 500 kv Upgrade (SCE portion) The project was

More information

IMM Quarterly Report: Winter 2018

IMM Quarterly Report: Winter 2018 IMM Quarterly Report: Winter 2018 MISO Independent Market Monitor David Patton, Ph.D. Potomac Economics March 27, 2018 Highlights and Findings: Winter 2018 The MISO markets performed competitively this

More information

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER 1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview

More information

April 2, Docket No. ER Independent Assessment Department of Market Monitoring Report on Performance of Energy Imbalance Market

April 2, Docket No. ER Independent Assessment Department of Market Monitoring Report on Performance of Energy Imbalance Market California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 April 2, 2015 Re: California Independent

More information

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8 Header Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations RT 007-11 Balhannah and Uraidla - Final Draft Page 1 of 8 DISCLAIMER The purpose of this document is to inform customers,

More information

State Regulatory Affairs and Local Relations Update. ATC Customer Meeting November 19, 2009

State Regulatory Affairs and Local Relations Update. ATC Customer Meeting November 19, 2009 State Regulatory Affairs and Local Relations Update ATC Customer Meeting November 19, 2009 Project Certification Steve Parker Manager State Regulatory Affairs CA/CPCN Applications (Filed/Ordered/Under

More information

Consulting Agreement Study. Completed for Transmission Customer

Consulting Agreement Study. Completed for Transmission Customer Completed for Transmission Customer Proposed Resource & Transmission Carbon County, MT & 230 kv Transmission in North Wyoming August 2016 Table of Contents 1.0 Description... 1 2.0 Overall Assumptions...

More information

EXCEPTIONS TO NYSRC RELIABILITY RULES

EXCEPTIONS TO NYSRC RELIABILITY RULES 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES REVISION 1 MAY 11, 2010 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed its

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

North Oregon Coast Area Study. Adam Lint

North Oregon Coast Area Study. Adam Lint North Oregon Coast Area Study Adam Lint PAGE 2 North Oregon Coast System Overview - Clatsop Study Covers: Transmission Switching Stations (Clatsop District): Astoria Lewis and Clark 115 kv Distribution

More information

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Puget Sound Area Study Team Bonneville Power Administration, Puget Sound Energy, Seattle City Light,

More information

Capacity Market Rules for Energy Storage Resources

Capacity Market Rules for Energy Storage Resources Capacity Market Rules for Energy Storage Resources Zachary T Smith Manager, Capacity Market Design ICAPWG August 23 rd, 2018 Agenda Background Energy Storage Resource (ESR) overview Capacity Market Rules

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

BC Hydro OATT - Balancing Area Transmission Service Workshop. January 20, 2014

BC Hydro OATT - Balancing Area Transmission Service Workshop. January 20, 2014 T BC Hydro OATT - Balancing Area Transmission Service Workshop January 20, 2014 1 AGENDA Topic Time Speaker Welcome and Introduction 09:00 09:15 Gord Doyle Background 09:15 10:00 Martin Huang Enforcement

More information

Merger of the generator interconnection processes of Valley Electric and the ISO;

Merger of the generator interconnection processes of Valley Electric and the ISO; California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson Vice President, Policy & Client Services Date: August 18, 2011 Re: Decision on Valley Electric

More information

Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station

Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station East Asian Alternative Energy Futures Workshop By the Nonproliferation Policy Education Center

More information

Interconnection Feasibility Study Report GIP-084-FEAS-R2

Interconnection Feasibility Study Report GIP-084-FEAS-R2 Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power

More information

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS Interconnection Feasibility Study Report GIP-023-FEAS-R1 Generator Interconnection Request # 23 100 MW Wind Generating Facility Inverness (L6549), NS February 16, 2006 Control Centre Operations Nova Scotia

More information

August 14, 2003 Blackout

August 14, 2003 Blackout August 14, 2003 Blackout Gerry Cauley Director Reliability Performance North American Electric Reliability Council NERC Response First hours Working with reliability coordinators assessing restoration

More information

ICT Strategic Transmission Plan (ISTEP) Review and Status Update

ICT Strategic Transmission Plan (ISTEP) Review and Status Update ICT Strategic Transmission Plan (ISTEP) Review and Status Update Entergy Transmission Summit July 29, 2008 Astor Crown Plaza New Orleans, Louisiana Douglas Bowman, PE Lead Engineer, ICT Planning 501-688-1640

More information

Ancillary Services. Horace Horton Senior Market Trainer, Market Training, NYISO. New York Market Orientation Course (NYMOC)

Ancillary Services. Horace Horton Senior Market Trainer, Market Training, NYISO. New York Market Orientation Course (NYMOC) Ancillary Services Horace Horton Senior Market Trainer, Market Training, NYISO New York Market Orientation Course (NYMOC) June 5-8, 2018 Rensselaer, NY 12144 1 Ancillary Services SESSION OBJECTIVES: attendees

More information

CUSTOMER/ TWIN ARROWS PROJECT

CUSTOMER/ TWIN ARROWS PROJECT A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset

More information

Transmission Planning for Wind Energy Resources in the Eastern United States. Dale Osborn

Transmission Planning for Wind Energy Resources in the Eastern United States. Dale Osborn Transmission Planning for Wind Energy Resources in the Eastern United States Dale Osborn Layered Design Typical utility planning Distribution delivery to loads Lower voltage transmission delivery from

More information

EXCEPTIONS TO RELIABILITY RULES Revision 10 August 11, 2017

EXCEPTIONS TO RELIABILITY RULES Revision 10 August 11, 2017 1 NYPA Run Back of EXCEPTIONS RELIABILITY RULES Revision 10 August 11, 2017 Post Contingency Flow on Marcy-New Scotland The post-contingency flow on the Marcy-New Scotland 18 line is allowed to exceed

More information

Deploying Smart Wires at the Georgia Power Company (GPC)

Deploying Smart Wires at the Georgia Power Company (GPC) Deploying Smart Wires at the Georgia Power Company (GPC) January, 2015 Contents Executive Summary... 3 Introduction... 4 Architecture of the GPC Installations... 5 Performance Summary: Long-term Test...

More information

1997 System Disturbances

1997 System Disturbances N ORTH A MERICAN ELECTRIC RELIABILITY COUNCIL Princeton Forrestal Village, 116-390 Village Boulevard, Princeton, New Jersey 08540-5731 1997 System Disturbances Review of Selected Electric System Disturbances

More information

Generation Resource Cold Weather Operational Exercise

Generation Resource Cold Weather Operational Exercise Generation Resource Cold Weather Operational Exercise David Schweizer Manger, Generation Operating Committee April 5, 2016 Cold Weather Resource Operational Exercise ICAP by Category 2 Cold Weather Exercise

More information

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY Transmission Department Transmission Planning Duke Energy Progress TABLE OF CONTENTS I. SCOPE 3 II. TRANSMISSION PLANNING OBJECTIVES 3 III. TRANSMISSION

More information

4. Context and Preconditions for the Blackout: The Northeastern Power Grid Before the Blackout Began

4. Context and Preconditions for the Blackout: The Northeastern Power Grid Before the Blackout Began 4. Context and Preconditions for the Blackout: The Northeastern Power Grid Before the Blackout Began Summary This chapter reviews the state of the northeast portion of the Eastern Interconnection during

More information

Frequently Asked Questions New Tagging Requirements

Frequently Asked Questions New Tagging Requirements Frequently Asked Questions New Tagging Requirements Q: Are there new E-tagging requirements related to the new fifteen minute market FERC Order No. 764 fifteen minute scheduling implemented on May 1, 2014?

More information

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders Reasonableness Test: Salisbury Substation 11kV Feeders DISCLAIMER The purpose of this document is to inform customers, Interested Parties,

More information

ATTACHMENT Y STUDY REPORT

ATTACHMENT Y STUDY REPORT Attachment Y Study Edwards Unit 1: 90 MW Coal Retirement December 31, 2012 ATTACHMENT Y STUDY REPORT 7/5/2013 PUBLIC / EXECUTIVE SUMMARY MISO received an Attachment Y Notification of Potential Generation

More information

Electric Power Transmission: Research Needs to Sustain a Critical National Infrastructure

Electric Power Transmission: Research Needs to Sustain a Critical National Infrastructure Electric Power Transmission: Research Needs to Sustain a Critical National Infrastructure Robert J. Thomas Cornell University Energy Council s 2003 Federal Energy and Environmental Matters Conference March

More information

Project #148. Generation Interconnection System Impact Study Report

Project #148. Generation Interconnection System Impact Study Report Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection

More information

Wholesale Electric Market Economics

Wholesale Electric Market Economics Wholesale Electric Market Economics Sponsored by the Institute for Policy Integrity 15 June 2011 Presented by Doug Hurley and Paul Peterson New England Markets and Relative Size All other ancillary services

More information

The Role of Electricity Storage on the Grid each location requires different requirements

The Role of Electricity Storage on the Grid each location requires different requirements Functional Requirements for Energy on the Utility Grid EPRI Renewable Council Meeting Bill Steeley Senior Project Manager Dan Rastler Program Manager April 5-6, 2011 The Role of Electricity on the Grid

More information

Project #94. Generation Interconnection System Impact Study Report Revision

Project #94. Generation Interconnection System Impact Study Report Revision Project #94 Generation Interconnection System Impact Study Report Revision October 2, 2009 Electric Transmission Planning Table of Contents Table of Contents...2 Executive Summary...3 Energy Resource Interconnection

More information

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

More information

Electric Power Research Institute, USA 2 ABB, USA

Electric Power Research Institute, USA 2 ABB, USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Congestion Reduction Benefits of New Power Flow Control Technologies used for Electricity

More information

Commuter Rail Performance. October

Commuter Rail Performance. October Commuter Rail Performance October 31 2016 1 Background - overall performance Year To Date: 89.67% YTD 125,629 trains North: 90.79% YTD 48,426 trains South: 89.07% YTD 77,203 trains 2 Background - overall

More information

Rate Schedules. Effective 1/1/2019

Rate Schedules. Effective 1/1/2019 Rate Schedules 2019 Effective 1/1/2019 SUMMARY OF RATE SCHEDULES REVISIONS FOR RATES EFFECTIVE JANUARY 1, 2019 (1) Rate component changes for Residential and Heating Service rate schedules. (2) General

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

PSE Attachment K Puget Sound Area Transmission Meeting

PSE Attachment K Puget Sound Area Transmission Meeting PSE Attachment K Puget Sound Area Transmission Meeting Stephanie Lu Senior Engineer December 15, 2011 Agenda Attachment K Review Economic Studies Process PSE Planning Process and Assumptions PSE Projects

More information

2015 Grid of the Future Symposium

2015 Grid of the Future Symposium 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http ://www.cigre.org 2015 Grid of the Future Symposium Flexibility in Wind Power Interconnection Utilizing Scalable Power Flow Control P. JENNINGS,

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

Appendix G Examples and Recommended Methods

Appendix G Examples and Recommended Methods Reporting Outages to the Generating Availability Data System (GADS) Introduction The examples in this appendix illustrate the reporting of outages and deratings to GADS. They are based on a fictional 600

More information

Amtrak Signal and Train Control Systems PRACTICAL PTC. On Amtrak Owned Property. November 20, 2008

Amtrak Signal and Train Control Systems PRACTICAL PTC. On Amtrak Owned Property. November 20, 2008 Amtrak Signal and Train Control Systems PRACTICAL PTC On Amtrak Owned Property November 20, 2008 PRACTICAL POSITIVE TRAIN CONTROL on Amtrak ACSES / ATC in the Northeast Corridor + ITCS for the Emerging

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Cost Reflective Tariffs

Cost Reflective Tariffs Cost Reflective Tariffs for Large Government,Commercial and Industrial Customers Customer Guide Introduction On September 2016, the Council of Ministers had approved the introduction Cost of Reflective

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

New Jersey State Report

New Jersey State Report New Jersey State Report July 2017 Table of Contents 1. Planning Generation Portfolio Analysis Transmission Analysis Load Forecast 2. Markets Capacity Market Results Market Analysis 3. Operations Emissions

More information

ATC Year Asessment Network Project List. Zone 2 switching initiative ASAP*** Operating flexibility Proposed -- --

ATC Year Asessment Network Project List. Zone 2 switching initiative ASAP*** Operating flexibility Proposed -- -- ATC 20 10-Year Asessment Project List Project ACEC Dellwood Substation: Install line breakers to sectionalize Y- 146 20*** 20 1 T-D interconnection Planned A 7741 Zone 2 switching initiative ASAP*** 20

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

February 10, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426

February 10, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 California Independent System Operator Corporation February 10, 2016 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California

More information

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting BHE Wyoming Q4 Stakeholder Meeting November 17, 2016 @ 1:00PM MT Black Hills Energy Service Center 409 Deadwood Avenue, Rapid

More information

SPN High Value Project PO Route. RIIO-ED1 Investment Justification Reinforcement for PO Route Network: SPN

SPN High Value Project PO Route. RIIO-ED1 Investment Justification Reinforcement for PO Route Network: SPN SPN High Value Project PO Route RIIO-ED1 Investment Justification Reinforcement for PO Route Network: SPN Document History Version Date Details Originator V0.1 20/06/2013 Initial version Chris Winch V0.2

More information

Midway/Monument Area TTC Study

Midway/Monument Area TTC Study Midway/Monument Area TTC Study (includes the following lines: Midway Geesen 115 kv, Geesen Falcon 115 kv, Falcon Fuller 115 kv, Fuller Black Squirrel 115 kv, and Black Squirrel Monument 115 kv) Johnny

More information

ROLLOVER RIGHTS OF LONG TERM FIRM TRANSMISSION SERVICE

ROLLOVER RIGHTS OF LONG TERM FIRM TRANSMISSION SERVICE ROLLOVER RIGHTS OF LONG TERM FIRM TRANSMISSION SERVICE In this Section: Overview Evaluation of Initial Requests Rollover Request Competing Request Competing Examples 1.0 OVERVIEW Pursuant to Section 2.2

More information

Smart Grid Automation and Centralized FISR

Smart Grid Automation and Centralized FISR Smart Grid Automation and Centralized FISR March 21, 2016 Mike Colby Senior Engineer Distribution Control Center Smart Grid Automation and Centralized FISR Remote Controlled Devices & Communication Distribution

More information

2011 Special Reliability Assessment: Power Interdependency in the United States

2011 Special Reliability Assessment: Power Interdependency in the United States 2011 Special Reliability Assessment: A Primer on the Natural Gas and Electric Power Interdependency in the United States John Moura Highlights Key differences exists between gas and electricity producers

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

Appendix D Black Hills Project Summary

Appendix D Black Hills Project Summary Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain

More information

March 14, Please contact the undersigned directly with any questions or concerns regarding the foregoing.

March 14, Please contact the undersigned directly with any questions or concerns regarding the foregoing. California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 March 14, 2017 Re: California

More information

Essential Reliability Services From PV Plants

Essential Reliability Services From PV Plants Essential Reliability Services From PV Plants Mahesh Morjaria, Ph. D. VP, PV Systems Enabling a world powered by reliable, affordable solar electricity. Utility-Scale PV Plants Support Grid Stability &

More information

Department of Market Quality and Renewable Integration November 2016

Department of Market Quality and Renewable Integration November 2016 Energy Imbalance Market March 23 June 3, 216 Available Balancing Capacity Report November 1, 216 California ISO Department of Market Quality and Renewable Integration California ISO i TABLE OF CONTENTS

More information

August 15, Please contact the undersigned directly with any questions or concerns regarding the foregoing.

August 15, Please contact the undersigned directly with any questions or concerns regarding the foregoing. California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 August 15, 2017 Re: California

More information

Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth

Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth Satoru Ihara Retired (urotas@ieee.org) Tetsuo Sasaki, Toshihisa

More information

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS OVERVIEW Interconnected systems Generator scheduling/dispatching Load-generation balancing Area Control Error (ACE) Load

More information

CAPACITY LIMITED RESOURCES (CLR) / ENERGY LIMITED RESOURCES (ELR)

CAPACITY LIMITED RESOURCES (CLR) / ENERGY LIMITED RESOURCES (ELR) CAPACITY LIMITED RESOURCES (CLR) / ENERGY LIMITED RESOURCES (ELR) 1 INTRODUCTION A new bidding mechanism is available for qualified generators which allows them to offer generation in the New York market

More information

Running the Electric Power Grid

Running the Electric Power Grid Running the Electric Power Grid Your electricity needs never stop, and neither do we. We keep power flowing across New England. Inside Our Control Room Before electricity is delivered to your street, it

More information

Proposed Incorporation of Merced Irrigation District into ISO Balancing Authority Area in Stakeholder Webconference February 28, 2013

Proposed Incorporation of Merced Irrigation District into ISO Balancing Authority Area in Stakeholder Webconference February 28, 2013 Proposed Incorporation of Merced Irrigation District into ISO Balancing Authority Area in 2015 Stakeholder Webconference February 28, 2013 Page 2 Merced Irrigation District (Merced) Background Merced Irrigation

More information

OMAR - Power Generation AUTOMATION

OMAR - Power Generation AUTOMATION OMAR - Power Generation AUTOMATION SYRIA Power System Overview POWER GENERATION & DISTRIBUTION SYSTEM - OMAR in Al Furat oil fields - Omar, Syria Location: Gas Plant Generators: 2 Devices: 18 Large consumers:

More information

Flexible Capacity Needs and Availability Assessment Hours Technical Study for 2020

Flexible Capacity Needs and Availability Assessment Hours Technical Study for 2020 Flexible Capacity Needs and Availability Assessment Hours Technical Study for 2020 Clyde Loutan Principal, Renewable Energy Integration Hong Zhou Market Development Analyst, Lead Amber Motley Manager,

More information

Industry Recommendation Loss of Solar Resources during Transmission Disturbances due to Inverter Settings - II

Industry Recommendation Loss of Solar Resources during Transmission Disturbances due to Inverter Settings - II Loss of Solar Resources during Transmission Disturbances due to Inverter Settings - II Initial Distribution: May 1, 2018 NERC has identified adverse characteristics of inverter-based resource performance

More information

DFO STATEMENT OF NEED REPORT

DFO STATEMENT OF NEED REPORT APPENDIX E DFO STATEMENT OF NEED REPORT Table of Contents 1.0 Executive Summary... 1 2.0 Description of the Area... 2 2.1 Geographic Study Area... 2 2.2 2016 System Configuration... 2 3.0 Area Loading

More information