ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume

Size: px
Start display at page:

Download "ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume"

Transcription

1 ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume A Treatise on Grounding of AC Electrical Systems, and an Atypical Electrocution Case Study i Author: Noshirwan K. Medora, SMEE, P.E. Reviewer: Ashish Arora, MSEE, P.E. Introduction This article presents information on grounded and grounding conductors in single-phase service panels and also discusses potential reasons for ineffective grounding that could pose an electrocution hazard. The article further presents an unusual case study of an inadvertently ungrounded electric air compressor that was alleged to have resulted in an electrocution. Review of the initial expert report and preliminary electrical tests conducted by the authors indicated a different probable cause cause. Subsequently, the authors performed electrical tests using an IEC human body model (HBM) and confirmed that the alleged air compressor was not the likely cause of the electrocution. Further investigation revealed a different electrical source as the probable cause of the electrocution. National Electrical Code (NEC) The term grounded is as old as the electrical and electronics industry itself, referring to the lowest and safest potential level. The British use the terms earth and earthing. In the United States, grounded and grounding are defined by the National Electrical Code (NEC). The ground is applied by an equipment grounding conductor. The NEC specifies color codes for what is grounded and grounding. NEC 2008 [1], in Article 100, defines a Grounded Conductor as, A system or circuit conductor that is intentionally grounded. Article 100 also defines a Grounding Conductor as, A conductor used to connect equipment or the grounded circuit of a wiring system to a grounding electrode or electrodes.

2 Identification of Equipment Grounding Conductor Article of the NEC 2008 includes Sections A through C on this subject. However, the most common identification of an equipment grounding connector is the following: a. Wire size 6 AWG or smaller: bare, covered, or insulated. Covered or insulated conductors shall have a continuous outer finish that is either green or green with one or more yellow stripes. b. Wire size larger than 6 AWG: Insulated or covered conductor identified at each end and where accessible by stripping the covering or insulation where exposed, coloring the insulation or covering green at the terminations, marking the insulation or covering with green tape or green labels at the termination. Receptacle A duplex receptacle (defined by NEC Article 406.2) for a branch circuit is shown in Figure 1 and is used to illustrate the color coding of wires. In Figure 1, the black wire, which is the live, ungrounded 120-V conductor, would be connected to the dark (brass colored) screws on the receptacle. The white wire, which is the grounded, zero-potential conductor, would be connected to the shiny (silver colored) screws. The green wire, which is the equipment grounding conductor, would be connected to the grounding screw that grounds the metal parts of the receptacle, the metal box, and the faceplate. In some cases, a bare copper wire is used instead of the green wire. Figure 1. New 120-Vac duplex receptacle for a branch circuit, showing the hot, neutral, and ground terminal screws. Black arrows show the brass screws for the hot wires (black), white arrows show the silver-colored screws for the neutral wires (white), and green arrows show the green ground screw for the ground wire (green). Single-Phase Service Panel A typical single-phase service panel is supplied by a utility transformer and a three-conductor service cable. The service cable consists of a neutral conductor, a +120-V conductor and a 120-V conductor. The neutral, the transformer core, and the tank are connected to a grounding electrode at the pole.

3 The designations V and 120 -V refer to the AC voltages at the ends of the secondary winding of the transformer. A partially installed 120/240-Vac circuit-breaker panel with single-phase branch circuits is shown in Figure 2. Two typical branch circuits are also shown. The diagram of Figure 2 does not show the utility meter. The service panel typically contains the following pertinent parts: Main circuit breaker: Two-pole for the +120-V and 120-V conductors that supply the two bus bars. Two bus bars: Rated ±120-V to neutral, 240-V between bus bars. Usually designed for one side of the branch circuit breakers to clamp onto the bus bar. Neutral terminal block: Terminations for the neutral service conductor. The neutral terminal block is connected to the utility neutral conductor. Ground terminal block: Connected to the neutral terminal block. Connected by a bonding conductor to the metal enclosure and to the grounding conductor to earth ground (e.g., water pipe or ground rod). Branch circuit breakers: 2-pole 240-V circuit breakers, 1-pole 120-V circuit breakers, and GFCI (ground-fault circuit interrupter). Each 120-V branch circuit is supplied by a single-pole circuit breaker from the +120 V or 120 V bus bar. It contains the following three conductors to supply ac power to receptacles similar to that shown in Figure 1: Black conductor: ungrounded, hot 120-V, from circuit breaker White conductor: grounded, neutral, from neutral terminal block Green (or bare) conductor: equipment grounding, from ground terminal block The 240-V branch circuit is supplied by a 2-pole circuit breaker from both bus bars. It contains the following four conductors: Black conductors (two) or one black and one red conductor: ungrounded, live 120-V to neutral, 240-V between conductors, supplied from a 2-pole circuit breaker. White conductor: grounded, neutral, from neutral terminal block. Not provided if only 240-V is required. Green (or bare) conductor: equipment grounding, from ground terminal block.

4 Figure 2. A partially installed 120/240-Vac panel. Yellow arrow shows the 200-A main circuit breaker. White arrow shows the neutral terminal block. Red arrows show the +120-V and 120-V bus bars. Blue arrows show the single-pole branch circuit breakers. Green arrows show the green grounding conductor. Orange arrows show 2-pole branch circuit breakers with the red and black wires. The purple arrows show the service cables from the utility, and the gray arrows show the sockets for the utility meter.

5 Electrical Accidents Accidents leading to electric shocks or an electrical fire occur for a variety of reasons. Examples include the following: 1. In Figure 2, the grounding conductor is connected to a metal water pipe, with the expectation that the pipe proceeds to earth. However, a change from metal to a plastic section of the pipe insulates the pipe from earth, and it can prevent all of the metal parts of the electrical system from being grounded by the equipment grounding conductors. When a subsequent undetected short circuit or insulation failure occurs, a person who is grounded, by being in contact with the metal parts, may receive an electric shock. 2. A typical panel may have a 200-A main circuit breaker and up to forty 15-A or 20- A branch circuit breakers. In the event that the main breaker or its conductors are overloaded and the breaker does not trip, a fire could result. 3. Some appliances are "double insulated" and do not require a ground pin in the plug. If the appliance gets wet, the insulation may be compromised, causing the equipment housing to become electrically hot and leading to an electrocution hazard. 4. In Figure 1, the most important elements of the receptacle are the ground pin socket and the green equipment grounding conductor connected to the earth ground. A person using an electric appliance in contact with the earth is typically protected from an electric shock if the appliance cord has a ground pin. However, a damaged or removed ground pin can lead to an electrocution hazard. This is further addressed in the following sections. Equipment Ground for Appliances The human body is susceptible to electric shock, and consequently, electrical equipment, tools, and appliances need to be adequately protected. One of the principal means of protection is a safety ground wire connected to a known earth ground. Electrical equipment is grounded for several reasons: 1. To prevent electric shock if a fault occurs in the equipment 2. To provide a path for the fault current to operate a protection element such as a fuse or a circuit breaker 3. To prevent the buildup of electrostatic charge that can result in errors in computers and data processing equipment 4. To prevent the buildup of electrostatic charge that can cause a spark and possible explosions in a hazardous environment. Typically, the grounding is accomplished by a green safety wire in the cord, or by a separate grounding jumper, or by the metallic conduit that carries the wires to the equipment. As mentioned earlier, the NEC provides specific requirements for grounding.

6 Ineffective Ground A Safety Hazard Grounding of equipment can be ineffective for a number of reasons. These include, but are not limited to, the following: 1. The green safety wire is disconnected at the equipment 2. A two-wire cord is used with no green safety wire 3. The three-prong plug is plugged into a two-socket receptacle, using an adapter, and the grounding pigtail of the adapter is not connected 4. The ground socket of the receptacle is not grounded within the receptacle 5. The green safety wire is broken in the cord 6. The ground connection at the circuit breaker panel is intermittent or has a poor connection An ineffective safety ground can further lead to a fault condition, possibly resulting in an electrocution hazard. The fault condition can be due to a number of different reasons, including, but not limited to: 1. Frayed or damaged insulation within the equipment, resulting in exposed energized conductors making contact with the metal enclosure 2. The ground wire connected to the metal enclosure of the appliance is broken, and the frayed conductors make contact with the hot terminal of the ac supply, energizing the metal enclosure 3. The presence of a conductive foreign object such as an unsecured metal screw bridging the gap between the hot terminal and the metal enclosure 4. Conductive contamination on an insulating member that creates a conduction path from the hot terminal to the metal enclosure. Figure 3 shows the buildup of conductive contamination between the hot and the ground terminals on a terminal strip used in a 115-Vac filter network. Consequently, when an electric tool or appliance loses its safety ground connection, an internal fault can cause the metal housing to become electrically hot, resulting in a safety hazard. Figure 3 (left). Arrow shows build-up of conductive contamination on a three-terminal, lug-type terminal strip used in a 115-Vac filter network, in a shipyard environment. The two outer lugs were also connected to the hot and neutral wires. The center terminal was bolted to the metal housing [2].

7 Case Study Investigation of an Alleged vs. Actual Cause of Electrocution In numerous electrocution cases that this author has investigated, two conditions were present: (1) the ground terminal was inadvertently or purposely broken or disconnected, and subsequently, (2) the grounded metallic housing of the subject equipment was accidentally connected to the hot terminal. This connection could result from: (a) electrically conductive contamination, (b) a metallic foreign object, or (c) frayed or damaged insulation within the equipment that cause exposed energized conductors to make contact with the metal enclosure. This case study involved a 120-Vac, 3-wire electric air compressor connected to a 3-wire extension cord. The subject extension cord was plugged into a three-terminal wall outlet. The air compressor was alleged to have caused an electrocution. Available information indicated that, on the morning of the incident, the air compressor was being used to power several pneumatic tools (including a pneumatic nut driver). The tools were being used to install a high-power 12-Vdc electric recovery winch to a pickup truck. The truck was parked adjacent to a chain-link fence, in a patch of tall, wet grass. The individual working at the site with these tools was discovered in an unresponsive condition, and the coroner s report stated death by electrocution. Figure 4 shows an exemplar electric air compressor similar to the one that was being used at the time of the incident. Figure 5 shows an exemplar 3-wire extension cord. The police report and photographs showed that the individual was found slumped on the ground with one hand on a lower section of the chain-link fence and the other hand on the side of the pickup truck. Initial Theory of Electrocution Multiple Problems in the Electric Air Compressor The initial expert report indicated that the electrocution occurred due to: (1) a missing ground pin in the 3- wire cord of the electric air compressor, and (2) high leakage current in the electric air compressor due to conductive contamination. The combination of the missing ground pin and high leakage current was alleged to have resulted in the air compressor housing being at approximately 120-Vac with respect to earth ground. It was further alleged that, because the air compressor had metal supporting feet and was placed in the bed of the pickup truck, the truck housing was now at an elevated potential of approximately Vac. This fault condition was alleged to have resulted in the electrocution. The expert report listed electrical tests that were conducted and indicated that, when the air compressor was operating with the missing ground pin on the extension cord, the compressor housing was at approximately 89-Vac with respect to earth ground, resulting in an electrocution hazard.

8 Figure 4. Exemplar electric air compressor with the original molded 3-wire, 120-Vac plug. Figure 5. Exemplar 3-wire extension cord with the ground pin cut off. The expert s report concluded that the evidence indicated that the deceased was standing in the wet grassy area and was in contact with the grounded chain-link fence. Further, it stated that, in making contact with the body of the pickup truck, the deceased had inadvertently completed the electric circuit from the electrically hot faulted air compressor to the grounded chain-link fence, and also through his feet to the wet grass and to earth ground.

9 Root-Cause Analysis by Exponent An Exponent engineer reviewed the expert report and inspected the subject electric air-compressor. He also performed electrical tests on an exemplar new compressor and determined that, when the ground pin was floating, the open-circuit voltage measured by a digital multimeter (DMM) between the air compressor metal housing and earth ground was approximately 86.5-Vac. This measured voltage agreed with the initial measurements noted in the expert report. However, further tests revealed that this voltage was not due to a high leakage current, but rather, was primarily due to the parasitic capacitance between the motor windings and the enclosure. Further tests were conducted with the ground pin floating and using an IEC human body model ii (HBM) [3] between the exemplar air compressor housing and earth ground. The measured voltage was approximately Vac. Calculations indicated that the current through the HBM was less than 1mA. Subsequently, electrical tests on the subject air compressor also showed that the leakage current using the HBM was less than 1mA. Figure 6 presents information on the IEC HBM. The fibrillation current (1 sec contact) for a typical adult is approximately ma [2]. The measurements indicated that the faulted system was not capable of supplying sufficient current to result in an electrocution, indicating that the speculated fault scenario was not the cause of the incident. Annex E of IEC [3] states in part: Figure 6. Circuit configuration of the HBM in IEC [3]. Resistor R S = 1.5 kω and capacitance C S = 0.22 µf are used to model the total skin impedance of two points of contact. The internal impedance of the human body is modeled by Resistor R B = 500 Ω.

10 Further Investigation A site inspection determined that the chain-link fence was located at the edge of the property, and adjacent to the property was a neighbor s yard. Subsequent inquiry revealed that the neighbor had been using an electric weed wacker on the morning of the incident. The available information indicated that the neighbor had used an old 3-wire extension cord plugged into a non-gfci receptacle to supply ac power to the weed wacker on the morning of the incident. Due to the length of the extension cord, the excess cord was draped over the chain-link fence. An inspection of the extension cord revealed a frayed area where the electrically hot copper conductors were visibly exposed. iii X-ray and optical microscope photographs revealed mechanical damage to numerous strands of the electrically hot copper conductors of the frayed extension cord. The investigation determined that the electrocution likely occurred due to the energized but frayed extension cord being draped over the chain-link fence. The energized, exposed conductors inadvertently made contact with the metal chain-link fence, resulting in the fence voltage rising to 120-V. Although the chain-link fence was installed in the ground, the relatively high ground resistance permitted the fence to reach a high voltage without tripping the 20-A branch circuit breaker. Contact with the electrically energized fence resulted in current flow from the victim s hand to his chest cavity. The return path to ground was most likely through the truck, which was standing in the tall, wet grass, and also through the victim s legs to ground. Conclusions 1. A grounding conductor can be identified by Article of the NEC However, the most common identification is the following: a. Wire size 6 AWG or smaller: bare, covered, or insulated. Covered or insulated conductors shall have a continuous outer finish that is either green or green with one or more yellow stripes. b. Wire size larger than 6 AWG: Insulated or covered conductor identified at each end and where accessible by stripping the covering or insulation where exposed, coloring the insulation or covering green at the terminations, marking the insulation or covering with green tape or green labels at the termination. 2. An IEC human body model can be used when determining if a hazardous potential on the metal housing of equipment results in an electrocution hazard. 3. The absence of a ground pin or damage to wire insulation can result in a safety hazard.

11 For Further Information, Contact: Noshirwan K. Medora, P.E. Senior Managing Engineer References 1. NFPA NFPA 70, National Electrical Code, 2008 Ed. National Fire Protection Association, Quincy, MA. 2. Medora, N.K., Connection Technology. In: P. Martin (Ed.,), Electronic Failure Analysis Handbook, Chapter 17, pp McGraw Hill. 3. IEC International Electrotechnical Commission (IEC) 60990, Second Ed., , Methods of measurement of touch current and protective conductor current. i This article is extracted from a technical paper by Noshirwan K. Medora and Alexander Kusko, titled, A Treatise on Grounding of AC Electrical Systems and an Atypical Electrocution Case Study, presented at the 2008 IEEE Symposium on Product Compliance Engineering, IEEE Product Safety Engineering Society (PSES), Austin, TX, October 20 22, 2008, and also approved for publication in the IEEE PSES 2008 Conference Proceedings. ii IEC 60990:1999, pg. 63 states, The network of figure 4 simulates body impedance and provides weighting to follow the frequency characteristics of the body for current causing involuntary reaction. It has been assumed that the shape of the frequency characteristic is the same for reaction and perception, and the data establishing the frequency characteristic was actually obtained through tests on the threshold of perception. iii The neighbor indicated that the frayed portion was probably due to the extension cord accidentally being run over by the electric lawn mower on previous occasions.

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrical Safety Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock

More information

ELECTRICAL. 60 Minutes

ELECTRICAL. 60 Minutes ELECTRICAL 60 Minutes AGENDA Electrical definitions Electrical shocks, burns and secondary injuries Electrical hazards in the workplace Safety devices and prevention steps Do s and Don ts INTRODUCTORY

More information

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1 Webinar 1 Electrical 2 1 Webinar Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock)

More information

Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution

Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution Electrical Safety Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: What it is made of. Its size. Its temperature. Substances with very little resistance

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

Installing a Downstream Distribution Panelboard

Installing a Downstream Distribution Panelboard Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

Electrical Wiring Practices

Electrical Wiring Practices Chapter 2 Electrical Wiring Practices and Diagrams MElec-Ch2-1 Overview Safety Standards Wiring Considerations Wire Terminations Coaxial Cable Wiring Installations Wiring Diagrams MElec-Ch2-2 Safety Lethal

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace

ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Other

More information

Electrical Workplace Safety

Electrical Workplace Safety Electrical Workplace Safety Alan Kelly 23 rd September 2015 Objectives To provide an understanding of Electrical terms and the concepts of electricity To introduce Electrical Protective Devices and provide

More information

CHAPTER 10 ELECTRICAL. Notes:

CHAPTER 10 ELECTRICAL. Notes: CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

Chapter 21 Practical Electricity

Chapter 21 Practical Electricity Chapter 21 Practical Electricity (A) Electrical Power 1. State four applications of the heating effect of electricity. Home: o Used in electric kettles o Used in electric irons o Used in water heaters

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT All electrical systems and electrically energized equipment

More information

Installing Power Components

Installing Power Components This chapter provides instructions on how to install and reinstall power components in the Cisco NCS 4016 chassis. It also covers connecting and disconnecting power and powering on the chassis. The Cisco

More information

Electrical Hazards in Construction

Electrical Hazards in Construction Electrical Hazards in Construction WELCOME Tim Dawson Presentation developed by Dawson Safety Services - 2013 Dangers of Electrical Shock Currents above 10 ma* can paralyze or freeze muscles. Currents

More information

Chapter 8 Interior Wiring and Lighting

Chapter 8 Interior Wiring and Lighting Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific

More information

The Evolution of Arc Fault Circuit Interruption

The Evolution of Arc Fault Circuit Interruption 51 st IEEE HOLM Conference on Electrical Contacts The Evolution of Arc Fault Circuit Interruption John A. Wafer Electrical Group Eaton Corporation 2003 Eaton Corporation. All rights reserved. 2 Residential

More information

MASTERsine Inverter PXA Series Installation Guide

MASTERsine Inverter PXA Series Installation Guide Backup Power System Expert TM MASTERsine Inverter PXA Series Installation Guide Important Safety Instructions IMPORTANT: Read and save this Installation Guide for future reference. This chapter contains

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

FACT SHEET Standard: Electrical Safety

FACT SHEET Standard: Electrical Safety What is a Ground Fault Circuit Interrupter? FACT SHEET The ground-fault circuit interrupter, or GFCI, is a fast-acting circuit breaker designed to shut off electric power in the event of a ground-fault

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are

More information

ELECTRICAL SAFETY. Safety Training For The Non-Qualified

ELECTRICAL SAFETY. Safety Training For The Non-Qualified ELECTRICAL SAFETY Safety Training For The Non-Qualified LANGUAGE OF ELECTRICITY Electricity: Negatively Charged Particles Moving Over A Conductor Current: Movement Of Electrons Along A Conductor Ground

More information

AVOIDING ELECTROCUTION HAZARDS

AVOIDING ELECTROCUTION HAZARDS Print AVOIDING ELECTROCUTION HAZARDS MODULE DESCRIPTION This module will provide information that helps you recognize and avoid common electrocution hazards in your work environment. OBJECTIVES After completing

More information

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC. INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL INS120P TASCO, INC. THIS TESTER IS DESIGNED FOR USE ONLY BY QUALIFIED ELECTRICIANS. IMPORTANT SAFETY WARNINGS mwarning Read and understand this material

More information

Unrestricted. S.Mukhopadhyay

Unrestricted. S.Mukhopadhyay Unrestricted S.Mukhopadhyay 10.09.15 Electrical safety A report says that every year 5500 Indians die due to electric shock and 800 due to electric fire. 12% work place death due to electrocution ELECTRICAL

More information

INSTALL CIRCUIT PROTECTIVE DEVICES

INSTALL CIRCUIT PROTECTIVE DEVICES SUBCOURSE EN5146 EDITION B US ARMY ENGINEER CENTER AND SCHOOL INSTALL CIRCUIT PROTECTIVE DEVICES INSTALL CIRCUIT PROTECTIVE DEVICES Subcourse Number EN5146 EDITION B United States Army Engineer School

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

Ten Deadly Conditions to Check for in Your Boat's Electrical System - Part 2

Ten Deadly Conditions to Check for in Your Boat's Electrical System - Part 2 Ten Deadly Conditions to Check for in Your Boat's Electrical System - Part 2 In the September newsletter, 1 through 5 of the ten deadly conditions were presented (link to previous article). Deadly conditions

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

Assessing a Site for Installation of Consumption Monitoring

Assessing a Site for Installation of Consumption Monitoring TECHNICAL BRIEF Assessing a Site for Installation of Consumption Monitoring About the Enphase Envoy-S Metered The Enphase Envoy-S Metered communications gateway enables performance monitoring and remote

More information

ITS-50R TRANSFER SWITCH OWNER S MANUAL

ITS-50R TRANSFER SWITCH OWNER S MANUAL ITS-50R OWNER S MANUAL IOTA Engineering Transfer Switches provide automatic power switching between two or three separate 120/240 volt AC input sources, including powercords, onboard generators, onboard

More information

GET GROUNDED. Renewable Energy System Grounding Basics

GET GROUNDED. Renewable Energy System Grounding Basics GET GROUNDED Renewable Energy System ing Basics by Christopher Freitas ASK TEN RENEWABLE ENERGY INSTALLERS ABOUT SYSTEM GROUNDING and you ll likely get ten different opinions as to what the National Electrical

More information

Installation and Construction Notes for EVSE4

Installation and Construction Notes for EVSE4 Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process

More information

NFPA 70E Electrical Safety in the Work Place. R. Casey 2/1/05

NFPA 70E Electrical Safety in the Work Place. R. Casey 2/1/05 NFPA 70E Electrical Safety in the Work Place R. Casey 2/1/05 The Other Electrical Hazard Arc flash: high-intensity intensity flash (eye damage) and superheated ball of gas (skin burns and melting)created

More information

Ensuring the Safety Of Medical Electronics

Ensuring the Safety Of Medical Electronics Chroma Systems Solutions, Inc. Ensuring the Safety Of Medical Electronics James Richards, Marketing Engineer Keywords: 19032 Safety Analyzer, Medical Products, Ground Bond/Continuity Testing, Hipot Testing,

More information

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS. SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS Róbert Riedlmajer TRNAVA 2007 Unit 14 - Fundamentals of power system protection

More information

Learning Module 10: Loadcenters. 101 Basic Series

Learning Module 10: Loadcenters. 101 Basic Series Learning Module 10: Loadcenters 101 Basic Series What You Will Learn We ll step through each of these topics in detail: What Does a Loadcenter Do? 4 Applications 4 Basic Circuitry and Wiring 5 Residential

More information

Table of Contents 文管中心 發行章

Table of Contents 文管中心 發行章 ST600-XXX Series Pure Sine Wave Power Inverter User s Manual Table of Contents 1. Important Safety Instructions 1-1 General Safety Precautions 1 1-2 Battery Precautions. 1 2. Basic Descriptions 2-1 Mechanical

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

Not all Low Voltage Switchgear is created equal

Not all Low Voltage Switchgear is created equal White Paper Not all Low Voltage Switchgear is created equal The must-have solution for power distribution systems Prepared by: Tom Hawkins, Consulting Product Engineer Rahul Rajvanshi, Senior Product Engineer

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

Not all Low Voltage Switchgear is created equal

Not all Low Voltage Switchgear is created equal Not all Low Voltage Switchgear is created equal White Paper The must-have solution for power distribution systems Introduction Reliability and safety are the two most important criteria in the proper functioning

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM _ M MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM User's MANUAL Code: MVM Version: 01-BF Date: OCT 2005 Page 1/10 _ 1. INTRODUCTION Before starting to use your Energic plus MVM battery charger, please take

More information

Design Standards NEMA

Design Standards NEMA Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL,

More information

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000 The flow of current through electrical facilities always involves risks. Poorly insulated equipment, faulty wires and incorrect use of an electrical devise cause currents to flow through the wrong path

More information

LEV/Wn Building A Connected World

LEV/Wn Building A Connected World LEV/Wn Building A Connected World PK-93370-10-00-2B Installing and Testing a GFCI Please read this leaflet completely before getting started. A CAUTION To prevent severe shock or electrocution always turn

More information

Electrical Installation

Electrical Installation Electrical Installation Symmetra LX Tower UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva 200 V, 4-16 kva 208/240 V, 4-16 kva 220/230/240 V, 4-16 kva Important Safety Messages SAVE

More information

Electrical Safety. Recognizing & Controlling Hazards

Electrical Safety. Recognizing & Controlling Hazards Electrical Safety Recognizing & Controlling Hazards Introduction Healthcare facilities, including hospitals, physician offices, laboratoratories, dental offices and beyond are vulnerable to a variety of

More information

Basic. Electrical Safety. January 2009

Basic. Electrical Safety. January 2009 Basic Electrical Safety January 2009 Sunday, 10 January 2010 The complete circuit A complete Circuit or loop is necessary for current to flow Sunday, 10 January 2010 2 A complete circuit complete Circuit

More information

Transfer Switch TS-50. Owner s Manual

Transfer Switch TS-50. Owner s Manual Transfer Switch TS-50 Owner s Manual Table of Contents Introduction 2 Installation 2 Operational Testing 7 Troubleshooting 7 Hi-Pot Testing 8 Generator Note 9 Medical Appliances 10 Caution 10 Disclaimer

More information

Understanding RV Electrical Hazards. Do you really want to plug in here?

Understanding RV Electrical Hazards. Do you really want to plug in here? Understanding RV Electrical Hazards Do you really want to plug in here? John Slaughter RV owner for 12 years, 150,000 miles of travel. Electrical Engineer Full disclosure, I am not a safety expert. Takeaways

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Electrical Safety in Medical Equipment. D. J. McMahon rev cewood

Electrical Safety in Medical Equipment. D. J. McMahon rev cewood Electrical Safety in Medical Equipment D. J. McMahon 141008 rev cewood 2017-10-23 Key Points Electrical Safety in Medical Equipment: - know the significance of NFPA-99 and the annual editions - define

More information

DIY 15 Amp Portable Generator Transfer Switch

DIY 15 Amp Portable Generator Transfer Switch DIY 15 Amp Portable Generator Transfer Switch ------------------------------------------------------------------------------------------------- WARNING You MUST read these warnings before proceeding. This

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Electrical Safety. Introduction

Electrical Safety. Introduction Electrical Safety Introduction Electrical hazards 300 electrocutions every year in the U.S. Leading cause is insufficient training ALL were preventable What is Electricity? How Electricity Works Created

More information

Electrical Safety and Overcurrent Protection

Electrical Safety and Overcurrent Protection Electrical Safety and Overcurrent Protection Dave Vallier DSE Bussmann division Contact info: Phone: 586-201-1348 Email: Davemvallier@eaton.com Agenda 1. Electrical hazards overview 2. The role of the

More information

Grounding Systems. Equipment Grounding & Grounded Conductors

Grounding Systems. Equipment Grounding & Grounded Conductors Grounding Systems Equipment Grounding & Grounded Conductors Definitions A Grounded or Earthed system is one that is connected to the earth Grounded Conductor is a conductor that normally carries current

More information

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC 2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC

More information

ELECTRICAL GROUNDING SAFETY PROGRAM

ELECTRICAL GROUNDING SAFETY PROGRAM ELECTRICAL GROUNDING SAFETY PROGRAM PURPOSE / SCOPE The purpose of this program is to ensure the proper installation, maintenance, inspection, and testing of equipment grounding conductors on construction

More information

STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA to

STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA to Safety Services 16 th floor, Commerce Place Tel 1-866/421-6929 10155 102 nd Street Fax 780/427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA 01 01 to 12 31 Regulations

More information

18.5. Electrical Circuits and Safety

18.5. Electrical Circuits and Safety 18.5 Electrical Circuits and Safety Electrical Circuits An electric circuit is a complete path through which a charge can flow. This is called a closed circuit. When the electric current cannot flow, this

More information

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements 1. PURPOSE sponsored by ABYC, BMF, ICOMIA, IMCI, and NMMA Author: Wieger de Wit Guideline Number 3 Electrical

More information

POWERLINE 2000 Energy Management System TM

POWERLINE 2000 Energy Management System TM Display Panel TM The PowerLine 00 EMS is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed in the standard main distribution

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER FALL-OF-POTENTIAL GROUND RESISTANCE TESTER Models 3620, 3640 & 4610 Call toll free (800) 537-0351 or visit www.allspec.com Measures soil resistivity (4-Point) (Model 4610) Measures ground resistance (2-

More information

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual Combiner Box Installation & Operations Manual SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual TABLE OF CONTENTS Notices and Safety Precautions Pages 1-2 Combiner

More information

Basic Electrical Safety

Basic Electrical Safety Basic Electrical Safety Concerned About Electricity? How many sets of holiday lights do you plug into one extension cord? Do you still use your hot and sparking electric drill? Is your vacuum cleaner s

More information

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service No One Does It Like Mipco Mipco Interlocked Reefer Power Outlets are used extensively in port terminals and shipboard applications to provide a safe, watertight electrical connection for refrigerated containers.

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

Chapter 4 Utility Systems Electrical

Chapter 4 Utility Systems Electrical Chapter 4 Utility Systems Electrical Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9 Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

PART B BRAND SPECIFIC MANUAL

PART B BRAND SPECIFIC MANUAL SPA OWNER S MANUAL IMPORTANT SAFETY INSTRUCTIONS PART B BRAND SPECIFIC MANUAL ELECTRICAL CONNECTION KEYPAD OPERATION 200 Series 200-M-B-16 Read in conjunction with Part A General Manual to form a complete

More information

1000 Watt Pure Sine Wave Power Inverter, Users Manual

1000 Watt Pure Sine Wave Power Inverter, Users Manual WF-5100 Series 1000 Watt Pure Sine Wave Power Inverter, Users Manual Distributed in the USA and Canada by Arterra Distribution 2021 Aeroplex Drive North. Elkhart, IN. 46514 Phone: 877-294-8997, Fax: 547-294-8698

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Electrical Equipment and Terminology

Electrical Equipment and Terminology Youth Explore Trades Skills Description Understanding the language of the electrical trade and knowing what electrical equipment is named and its purpose are very important. Anyone who is exposed to a

More information

Boardworks Ltd Mains Electricity

Boardworks Ltd Mains Electricity 1 of 22 Boardworks Ltd 2016 Mains Electricity Mains Electricity 2 of 22 Boardworks Ltd 2016 Direct current 3 of 22 Boardworks Ltd 2016 There are two main types of electric current: direct current (DC)

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

ANZI Transfer Switch and Generator Wiring Installation Addendum

ANZI Transfer Switch and Generator Wiring Installation Addendum ANZI Transfer Switch and Generator Wiring Installation Addendum Reference all appropriate documentation. NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. THIS PRODUCT CAN BE INSTALLED BY THE

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

Section 02: Pre-Installation Procedures

Section 02: Pre-Installation Procedures Section 02: Pre-Installation Procedures Foundation! WARNING The MUST be placed on a surface that will support the combined weight of the, options, fixtures, and tooling, etc. (refer to the Specifications

More information

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules. Fuseology Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression Optima Fuse Holders & Overcurrent Protection Modules Compact, full-featured modules that deliver Type 2 coordinated protection,

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Appendix B PCC Electrical Safety Training

Appendix B PCC Electrical Safety Training Appendix B PCC Electrical Safety Training ELECTRICAL SAFETY TRAINING OBJECTIVES OSHA regulations have been adopted on electrical safety-related work practices for general industry. These new standards

More information

COLDWATER LAKE FACILITIES DUPLEX PUMP STATION

COLDWATER LAKE FACILITIES DUPLEX PUMP STATION COLDWATER LAKE FACILITIES DUPLEX PUMP STATION TROUBLESHOOTING GUIDE REFERENCE: Operation Instructions Ladder Schematic Diagrams SCOPE The following troubleshooting guide has been specifically prepared

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors Eilis M. Logan UPRR Marvin J. Frazier Corr. Comp Co. Electromagnetic Interference Magnet and Paper Clip

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information