1 East Avenue & Queen City Substation Improvement Project VIA FIRST CLASS MAIL August 29, 2017 Judith C. Whitney, Clerk Vermont Public Utility Commission 112 State Street, 4 th Floor Montpelier, VT Re: East Avenue and Queen City Substation Improvement Project Certificate of Public Good Section 248J Permit Process 45-Day Notice of Project Filing Dear Judy: This letter and enclosed information describe the Vermont Electric Power Company Inc. and Vermont Transco LLC (collectively VELCO ) proposed East Avenue and Queen City Substation Improvement Project (the Project ), which includes upgrades to VELCO s existing facilities in the cities of Burlington and South Burlington, and consists of upgrading VELCO s East Avenue Substation located at 74 University Road in Burlington and VELCO s Queen City Substation located at 10 Central Avenue in South Burlington. We anticipate filing our formal petition with the Vermont Public Utility Commission (PUC) on October 16, 2017, requesting a Certificate of Public Good to construct the Project. The state permitting process requires VELCO to provide notice to the cities of Burlington and South Burlington and other stakeholders at least 45 days prior to a formal filing with the PUC 1. For your information, attached to this letter, is a Project overview and substation site layouts. Before the Project is filed with the PUC, VELCO will conduct informal discussions to address concerns you may have about the impact of the Project. VELCO will hold a public meeting on September 19, to share information, collect feedback and address concerns from affected communities. You will also receive a notification of our petition when it is filed with the PUC. Please note the Planning Commissions may make recommendations within 40 days of the submission of this 45-day notice, which date is October 9, So that VELCO has sufficient time to incorporate your feedback prior to the October 16, 2017 anticipated filing date, VELCO is requesting that comments be submitted by October 3, Planning commissions also have the right to make revised recommendations within 45 days after the date the Petition is filed with the PUC, if the Petition contains new or more detailed information that was not previously included in these plans. 1 The process is governed by Public Utility Commission Rule 5.400, which can be viewed on the PUC's website at 2 Public meeting will begin at 6 p.m. September 19 at Burlington Electric Department s Spark Room at 585 Pine Street in Burlington, VT P a g e

2 East Avenue & Queen City Substation Improvement Project For additional information regarding the PUC processes, including your right to participate in the proceeding, please refer to the "Citizen s Guide to the Vermont Public Service Board's Section 248 Process. 3 The Citizens Guide can be found at For information on public participation through public comment or intervention please go to As the Project is still in the design phase, we will continue discussions and expect to receive feedback on this Project from various stakeholders. Please note that we expect to make the formal filing with the PUC on October 16, If you are interested in a presentation on this Project, have comments or want further information, please contact Scott Mallory, Project Manager, at or smallory@velco.com. So that we may better address any questions or concerns you may have, please contact us before October 3, The documents that accompany this letter have been electronically filed using epuc. Sincerely, Scott Mallory, Project Manager Enclosures: Attachment A Project Overview Attachment B East Avenue Substation Overall Ortho Plan Attachment C Queen City Substation Overall Ortho Plan 3 As of July 1, 2017, the Vermont Public Service Board s new name is the Vermont Public Utility Commission. The Citizen s Guide has not yet been updated to reflect the name change P a g e

3 East Avenue and Queen City Substation Improvement Project Overview Introduction Vermont Electric Power Company Inc. (VELCO) was formed in 1956 when local distribution utilities joined together to create the nation's first statewide "transmission only" company in order to provide access to clean hydro power and build and maintain the state s high-voltage electric transmission grid. VELCO constructs, owns and operates most of Vermont s in-state, high-voltage transmission grid (essentially 115 kv and above), that connects Vermont to the regional and national electric power supply system. VELCO s network also provides the electric supply to Burlington Electric Department (BED) and Vermont s 15 other local distribution utilities. The proposed East Avenue and Queen City Substation Improvement Project (the Project) addresses system deficiencies that compromise electric reliability under certain circumstances. The Project is located at VELCO s existing East Avenue Substation in Burlington and Queen City Substation in South Burlington. As is explained in this overview, VELCO expects to file a request with the Vermont Public Utility Commission (PUC) on October 16, 2017, for permission to undertake this Project and, assuming PUC and other approvals are granted, currently plans for the work to be completed and in service by December, This proposed Project overview describes the following: System deficiencies Alternatives evaluated for this Project The Project s description The Project s impact The anticipated Project filing date with the PUC Local and regional planning commissions rights to comment on the Project plans Glossary of italicized terms Description of the system deficiencies Electric energy remains a cornerstone of our local and state economies, our quality of life, and our communities. Households, businesses and public services like schools and hospitals all rely on electricity for communication, lighting, heating, ventilation, and the operation of appliances and equipment. If transmission facilities fail, large geographic areas can lose their electric service. Transmission utilities such as VELCO are required to design, operate and maintain a transmission network according to national and regional reliability standards. VELCO continuously assesses the adequacy of its system to ensure Vermont s transmission network meets national and regional reliability criteria. 1 P a g e

4 VELCO s electric transmission network is connected to its East Avenue Substation, located at 74 University Road in Burlington, and its Queen City Substation, located at 10 Central Avenue in South Burlington. East Avenue Substation is connected to Burlington Electric Department s (BED s) distribution system and Queen City Substation is connected to both BED s and Green Mountain Power s (GMP s) distribution systems, which in turn, provide service to their respective customers. The power grid is a complicated network of transmission and distribution components that work together to deliver safe and reliable power. Recent improvements to the grid have increased the quality and reliability of the power that VELCO is able to deliver. However, as the power grid expanded and grew, and as the topology of the system changed, so did the fault current levels on the system. The fault current is the maximum current available should there be a short circuit, such as a ground fault on the system. These faults can occur for a number of reasons, such as wildlife (squirrels, birds, snakes, etc.), vegetation (tree limbs), weather (wind-blown conductors, lightning, etc.), and structural failure (car driving into a pole). When the fault current reaches or exceeds the capability of the existing infrastructure its electrical ratings system reliability, worker safety and, in some cases, public safety is at risk. Fault current on the system has now reached a level that must be reduced in order to ensure that the ratings on some electrical components of the distribution system are not exceeded. Alternatives evaluated There are several possible methods to mitigate this issue: (1) VELCO can replace the specific electrical components that do not meet the required level of available fault current with components that do; (2) VELCO can install equipment that interrupts the fault current when it does exceed the ratings of the components; or (3) VELCO can install, equipment that reduces the level of fault current. The company evaluated each of these methods to determine the most appropriate solution and concluded that equipment with higher fault current ratings was not available for all the components in question and therefore VELCO did not consider this a viable option. VELCO also determined that the installation of equipment that interrupts the fault current when it does exceed the rating of the components would also result in the interruption of electric service to customers fed from those components. VELCO also deemed this option unacceptable due to the customer impacts it would cause. VELCO evaluated the option of installing equipment that reduces fault current level, namely installing more impedance on the system. This can be done by replacing the three existing 115/13.8 kv transformers at the East Avenue and Queen City Substations with transformers that have a higher impedance, or by installing air core reactors adjacent to these existing transformers. It was determined to be more economical to install the air core reactors rather than replace the transformers. VELCO is proposing to decrease the available short circuit current on the system by installing air core reactors within the existing East Avenue and Queen City Substations. This solution will limit the available fault current on the system to within the electrical ratings of the existing system equipment without reducing the reliability of the power that we deliver. VELCO screened the Project for its potential to be resolved through non-transmission alternatives (e.g., energy efficiency or new generation) using the tool developed by the Vermont System Planning Committee (VSPC). The screening determined that the Project was not a candidate for a non-transmission solution 2 P a g e

5 because the proposed upgrades are being driven by the need to address a short-circuit issue. Thus, nontransmission alternatives could not resolve the present problems at the VELCO East Avenue and Queen City Substations. The screening conclusion was reviewed by the VSPC. Project Description The Project consists of two primary components. Component One Reactor Installation at East Avenue Substation Install two (2), 115 kv, three-phase air core reactor assemblies, each consisting of three (3), single-phase reactors, in a stacked configuration. Each single-phase reactor measures approximately 4 feet tall by 7 feet in diameter. Install two (2) reactor stands (one for each reactor assembly). Install two (2) bus support stands (one for each reactor assembly). Install concrete foundations to support the reactor and bus support stands Modify existing bus work as required, to integrate the new reactors into the electrical circuit. Component Two Reactor Installation at Queen City Substation Install one (1) 115 kv, three-phase reactor assembly, consisting of three (3), single-phase reactors, in a stacked configuration. Each single-phase reactor measures approximately 4 feet tall by 7 feet in diameter. Install one (1) reactor stand. Install two (2) conductor support stands. Install concrete foundations to support the reactor and conductor support stands. Movement of conductors outside of the fence to inside the fence to connect to the reactor assembly. Assuming regulatory approval, construction is expected to start in the spring of 2018 with a targeted completion date of December Although the engineering for this Project is not yet complete, the attachments depict preliminary design layouts for each of the substations. During construction of the proposed solution at Queen City Substation, VELCO will also take the opportunity to improve the physical security of that substation by extending the existing fence approximately 10 feet outside the existing control building in the southwest corner of the substation, as shown in the attached drawing. VELCO s new standard for security is to install a physical security perimeter around all substation infrastructure. The new perimeter will consists of an eight-foot chain link fence, with motion detection sensors that are able to detect when someone touches the fence, topped with one foot of barbed wire. Currently, the control building at Queen City Substation serves as the physical security perimeter without a fence. An extension of the fence around the control building will help us maintain a high level of safety and guard against any potential vandalism or terrorism. 3 P a g e

6 Project s impacts Aesthetics Both the Vermont Natural Resources Board and the PUC utilize the so-called Quechee Lakes standard [set forth in the decision Quechee Lakes Corporation, #3EW0411-EB and #3O439- EB (1986)] to guide their aesthetics analysis. According to the Quechee Lakes standard, regulators must first determine whether a project will have an adverse impact on aesthetics and scenic and natural beauty. A project has an adverse impact if it is out of character with its surroundings. Specific factors that regulators use to make this evaluation include the nature of the project surroundings, the compatibility of the project design with those surroundings, the suitability of the project colors and materials with the immediate environment, the visibility of the project, and the impact of the project on open space. If regulators conclude that a project will have an adverse effect, the next step in the two-part test is to determine whether the adverse effect of the project is undue. The adverse effect is considered undue when regulators find that any one of the following questions is answered yes: (1) Does the project violate a clear, written community standard intended to preserve the aesthetics or scenic beauty of the area? (2) Have the applicants failed to take generally available mitigating steps which a reasonable person would take to improve the harmony of the project with its surroundings? (3) Does the project offend the sensibilities of the average person? Is it offensive or shocking because it is out of character with its surroundings or significantly diminishes the scenic qualities of the area? For transmission upgrades, the PUC s aesthetic analysis, however, does not end with the results of the Quechee test. In addition, the PUC s aesthetic assessment is significantly informed by overall societal benefits of the project. PUC Docket No. 6860, Order of 1/28/05 (footnotes omitted). VELCO s aesthetic consultant, T. J. Boyle Associates, LLC (TJB), a landscape architecture and planning firm, has reviewed the preliminary design plans and performed a visual analysis of the areas of the proposed Project upgrades. The findings of this analysis led them to conclude that the proposed Project will not have an adverse effect on the scenic or natural beauty or aesthetics of the area. This is due to the fact that, while visibility in areas nearby to the East Avenue substation will be possible, the Project will generally not be visible from other publicly accessible locations. The Project at the Queen City substation is not expected to be visible from the roadside due to existing vegetative screening. Where it is visible, the proposed reactor equipment is compatible with the existing substations, and would not constitute a major change to the existing character. Due to the lack of significant Project visibility, and its compatibility with the existing permitted substations, the second part of the Quechee Analysis was not administered. In conclusion, TJB believes this Project meets the Quechee Test insofar as its impact on aesthetics will not be unduly adverse. Noise VELCO s noise consultant, Resource Systems Group, Inc. (RSG) has measured sound levels at the both the existing East Avenue Substation and the existing Queen City Substation and has assessed the potential noise impacts associated with the Project. A complete engineering noise analysis will be provided as part of the Project s filing with the PUC. Preliminary findings from RSG indicate that under normal operating 4 P a g e

7 conditions there will be a negligible change in sound levels at the nearest residence and under high-load conditions there will be no more than a 2 dba increase in sound levels at the nearest residence at either of the substations and below standard noise limits imposed by the PUC. Transportation The Project poses no long-term traffic impacts in Burlington or South Burlington. VELCO anticipates only minor, short duration traffic impacts, if any, due to deliveries of equipment and material to the substations during the construction period (expected to be from spring 2018 to December 2018). Such deliveries will use existing roads with vehicles that are commonly used on public roads. During delivery of any large equipment, VELCO will employ the services of traffic control personnel to manage traffic flow. Right of the local and regional planning commissions to comment on the Project plans Section 248(f) of Title 30 of the Vermont Statutes Annotated provides that municipal and regional planning commissions are entitled to receive this notice and make recommendations to the PUC and to the Applicant within 40 days of the submission of this 45-day notice to the planning commissions, which date is October 9, So that VELCO has sufficient time to incorporate your feedback prior to the October 16, 2017 anticipated filing date, VELCO is requesting that comments be submitted by October 3, Planning commissions also have the right to make revised recommendations within 45 days after the date the Petition is filed with the PUC, if the Petition contains new or more detailed information that was not previously included in these plans. Recommendations made to the PUC under Section 248(b)(1), or the lack of such recommendations, do not preclude municipal and regional planning commissions from presenting evidence during technical hearings if they exercise their right to appear as a party under Section 248(a)(1)(G) & (H). For additional information regarding the PUC processes, including your right to participate in the proceeding, please refer to the "Citizen s Guide to the Vermont Public Service Board s Section 248 Process. * The Citizens Guide can be found on the PUC s website here: The PUC s website ( also includes a public participation section that contains information on the PUC process. As the Project is still in the design phase, VELCO will continue discussions and expect to receive feedback on this Project from various stakeholders. Please note that the PUC Petition and filing anticipated for October 16, 2017, as well as other pertinent Project updates, will be posted on VELCO s website at: To request a presentation on this Project, make comments or request further information, please contact Scott Mallory, Project Manager, at or smallory@velco.com. * As of July 1, 2017, the Vermont Public Service Board s new name is the Vermont Public Utility Commission. The Citizen s Guide has not yet been updated to reflect the name change. 5 P a g e

8 Glossary of terms Air core reactors are a type of electrical equipment that consists of a coil of wire. They contain no oil and are covered in epoxy. They are used to reduce the short circuit current to levels within the rating of components of the power system. Bus refers to the arrangement of overhead bus bar and associated switching equipment in a substation. Distribution is the final stage in the delivery of electric power. It carries electricity from the transmission system to individual consumers. Vermont has 17 local distribution companies that include municipal utilities like Burlington Electric Department, cooperatives like Vermont Electric Coop, and one large investor-owned utility, Green Mountain Power. Impedance is the effective resistance of an electric circuit or component to alternating current. Party status means the PUC has determined that a person or entity has an interest in the outcome of a case before the commission and can participate fully in hearings, filings and other aspects of the legal proceeding. Formal parties may provide testimony and participate in evidentiary hearings. Hearings. All formal parties must follow the Commission's procedural rules, and are subject to the orders of the Commission. Petition is the formal legal filing. In this case, it is the formal application and supporting materials filed with the PUC to request approval in the form of a Certificate of Public Good to construct the proposed substation upgrades. Transmission refers to the part of the electric system that operates at high voltage and carries large amounts of electricity from generation plants to the lower-voltage distribution system, which supplies electricity to local areas. Vermont Public Utility Commission (PUC) was formerly called the Vermont Public Service Board. The name was changed by the Vermont legislature effective July 1, P a g e

9

10

Ascutney Substation Upgrade

Ascutney Substation Upgrade Ascutney Substation Upgrade VIA MAIL February 18, 2011 Chair Town of Weathersfield Planning Commission P.O. Box 550 Ascutney, VT 05030 Re: Ascutney Substation Upgrade Certificate of Public Good Section

More information

Alberta Electric System Operator Saleski Transmission Project Needs Identification Document

Alberta Electric System Operator Saleski Transmission Project Needs Identification Document Decision 2013-127 Alberta Electric System Operator Saleski Transmission Project Needs Identification Document ATCO Electric Ltd. Saleski 901S Substation and 144-kV Transmission Line 7L142 Facility Application

More information

Alberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation

Alberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation Decision 21781-D01-2016 Alberta Electric System Operator Needs Identification Document Application Facility Applications September 7, 2016 Alberta Utilities Commission Decision 21781-D01-2016: Alberta

More information

February 13, Docket No. ER ; ER Response to Request for Additional Information

February 13, Docket No. ER ; ER Response to Request for Additional Information California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California Independent System

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) )

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) ) UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION The Nevada Hydro Company, Inc. Docket No. EL18-131-000 SOUTHERN CALIFORNIA EDISON COMPANY'S COMMENTS AND PROTEST TO THE NEVADA HYDRO

More information

NEW ECTOR COUNTY NORTH TO MOSS 138 kv TRANSMISSION LINE PROJECT PUBLIC OPEN HOUSE MEETING

NEW ECTOR COUNTY NORTH TO MOSS 138 kv TRANSMISSION LINE PROJECT PUBLIC OPEN HOUSE MEETING NEW ECTOR COUNTY NORTH TO MOSS 138 kv TRANSMISSION LINE PROJECT PUBLIC OPEN HOUSE MEETING TUESDAY AUGUST 17, 2010 4:00 PM 8:00 PM CAVAZOS ELEMENTARY SCHOOL CAFETERIA 9301 WEST 16 TH STREET ODESSA, TEXAS

More information

Decision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L79. October 18, 2016

Decision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L79. October 18, 2016 Decision 21481-D01-2016 October 18, 2016 Alberta Utilities Commission Decision 21481-D01-2016 Proceeding 21481 Application 21481-A001 October 18, 2016 Published by the: Alberta Utilities Commission Fifth

More information

Decision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L82

Decision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L82 Decision 21447-D01-2016 August 23, 2016 Decision 21447-D01-2016 Proceeding 21447 Application 21447-A001 August 23, 2016 Published by the: Fifth Avenue Place, Fourth Floor, 425 First Street S.W. Calgary,

More information

JCP&L Verbatim Response to Middletown Township s Questions

JCP&L Verbatim Response to Middletown Township s Questions JCP&L Verbatim Response to Middletown Township s Questions Township officials sent 13 questions about the proposed Monmouth County Reliability Project to JCP&L on June 10 th. JCP&L provided direct responses

More information

Decision (Errata) Access Pipeline Inc. Errata to Decision Temporary Generation at Smoky Lake Pump Station.

Decision (Errata) Access Pipeline Inc. Errata to Decision Temporary Generation at Smoky Lake Pump Station. Decision 2011-424 (Errata) Access Pipeline Inc. Errata to Decision 2011-424 Temporary Generation at Smoky Lake Pump Station January 4, 2012 The Alberta Utilities Commission Decision 2011-424 (Errata):

More information

Currant Lake Transmission Project

Currant Lake Transmission Project Currant Lake Transmission Project September 2010 Why are you receiving this project information package? New transmission facilities are needed in the Monitor area of southeastern Alberta. ATCO Electric

More information

Umatilla Electric Cooperative Net Metering Rules

Umatilla Electric Cooperative Net Metering Rules Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through

More information

STATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION PUC DOCKET NO. E002/TL OAH DOCKET NO.

STATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION PUC DOCKET NO. E002/TL OAH DOCKET NO. Direct Testimony and Schedules Grant Stevenson STATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION IN THE MATTER OF THE APPLICATION FOR A ROUTE PERMIT FOR THE PLEASANT

More information

Case 13-M Edic to New Scotland 345 kv Transmission Line and Hurley Avenue PARs Project (ED-NS/HA) Article VII Filing ED-NS/HA

Case 13-M Edic to New Scotland 345 kv Transmission Line and Hurley Avenue PARs Project (ED-NS/HA) Article VII Filing ED-NS/HA Submission of Indicated New York Transmission Owners For Authority to Construct and Operate Electric Transmission Facilities in Multiple Counties in New York Case 13-M-0457 Edic to New Scotland 345 kv

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

Submission on the Wellington Town Belt Bill. Local Government and Environment Select Committee Parliament Buildings Wellington

Submission on the Wellington Town Belt Bill. Local Government and Environment Select Committee Parliament Buildings Wellington Wellington Electricity Lines Ltd 2 Submission on the Wellington Town Belt Bill To: Name: Local Government and Environment Select Committee Parliament Buildings Wellington Wellington Electricity Lines Limited

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

Merger of the generator interconnection processes of Valley Electric and the ISO;

Merger of the generator interconnection processes of Valley Electric and the ISO; California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson Vice President, Policy & Client Services Date: August 18, 2011 Re: Decision on Valley Electric

More information

PUBLIC Law, Chapter 539 LD 1535, item 1, 124th Maine State Legislature An Act To Create a Smart Grid Policy in the State

PUBLIC Law, Chapter 539 LD 1535, item 1, 124th Maine State Legislature An Act To Create a Smart Grid Policy in the State PLEASE NOTE: Legislative Information cannot perform research, provide legal advice, or interpret Maine law. For legal assistance, please contact a qualified attorney. Emergency preamble. Whereas, acts

More information

BEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES

BEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES EXHIBIT JC-2 BEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES IN THE MATTER OF THE PETITION OF JERSEY CENTRAL POWER & LIGHT COMPANY PURSUANT TO N.J.S.A. 40:55D-19 FOR A DETERMINATION THAT THE OCEANVIEW

More information

STATE OF ILLINOIS ILLINOIS COMMERCE COMMISSION

STATE OF ILLINOIS ILLINOIS COMMERCE COMMISSION STATE OF ILLINOIS ILLINOIS COMMERCE COMMISSION THE CITIZENS UTILITY BOARD ) and ) THE ENVIRONMENTAL DEFENSE FUND ) ) Docket No. 14- Proceeding to Adopt a GHG Metric for ) Smart Grid Advanced Metering Infrastructure

More information

Operations Center FAQs

Operations Center FAQs RICHARDSON INDEPENDENT SCHOOL DISTRICT Where all students learn, grow and succeed Operations Center FAQs Richardson ISD is constructing an operations center on vacant district land between Greenville Avenue

More information

Coalspur Mines (Operations) Ltd.

Coalspur Mines (Operations) Ltd. Decision 22744-D01-2017 Application for an Exemption Under Section 24 of the Hydro and Electric Energy Act October 5, 2017 Alberta Utilities Commission Decision 22744-D01-2017 Application for an Exemption

More information

Proposed Dounreay - Mybster 275 kv / 132 kv

Proposed Dounreay - Mybster 275 kv / 132 kv Background Scottish Hydro-Electric Transmission Ltd (SHETL) is proposing a new 275 kilovolt (kv) (1 kilovolt = 1000volts) double circuit overhead line (OHL) between the Dounreay sub station and the new

More information

Bohn to Kettle River Transmission Project

Bohn to Kettle River Transmission Project April 2012 Why are you receiving this project information package? New transmission facilities are needed in the Fort McMurray area. ATCO Electric has been directed by the Alberta Electric System Operator

More information

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program. Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative

More information

Reactive Power Requirements and Financial Compensation. Addendum to Draft Final Proposal

Reactive Power Requirements and Financial Compensation. Addendum to Draft Final Proposal Reactive Power Requirements and Financial Compensation July 21, 2016 Table of Contents 1. Introduction... 3 2. Changes to Proposal... 4 3. Plan for Stakeholder Engagement... 4 4.... 4 6. Next Steps...

More information

Evaluating Stakeholder Engagement

Evaluating Stakeholder Engagement Evaluating Stakeholder Engagement Peace River October 17, 2014 Stakeholder Engagement: The Panel recognizes that although significant stakeholder engagement initiatives have occurred, these efforts were

More information

Included in this Stakeholder Information Package:

Included in this Stakeholder Information Package: Who can you contact for more information? Yellowhead Area Transmission Reinforcement: TERA Environmental Consultants Dave Sare Phone: 403-538-5734 Email: dsare@teraenv.com Drayton Valley Area AltaLink

More information

Overview of State Distributed Generation Interconnection Rules

Overview of State Distributed Generation Interconnection Rules Overview of State Distributed Generation Interconnection Rules Presentation to EPA CHP Webinar Series June 26, 2008 Wayne Shirley Director The Regulatory Assistance Project 50 State Street, Suite 3 Montpelier,

More information

Re: California Independent System Operator Corporation

Re: California Independent System Operator Corporation California Independent System Operator October 21, 2014 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California Independent

More information

February 10, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426

February 10, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 California Independent System Operator Corporation February 10, 2016 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California

More information

The Capital Grid Project:

The Capital Grid Project: The Capital Grid Project: Building Tomorrow s Energy Grid Today Lamond- Riggs Citizens Association October 2, 2017 Agenda Welcome How Safe, Clean, and Affordable Energy is Delivered Our Current System

More information

Regular Meeting and Public Hearing of the Zoning Subcommittee

Regular Meeting and Public Hearing of the Zoning Subcommittee Regular Meeting and Public Hearing of the Zoning Subcommittee Tuesday, October 02, 2018 7:00 PM Council Chambers, City Hall, 2nd Floor, 27 West Main Street, New Britain, Connecticut NOTICE - The Common

More information

Decision on Merced Irrigation District Transition Agreement

Decision on Merced Irrigation District Transition Agreement California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson, Vice President Policy & Client Services Date: March 13, 2013 Re: Decision on Merced Irrigation

More information

D.P.U A Appendix B 220 CMR: DEPARTMENT OF PUBLIC UTILITIES

D.P.U A Appendix B 220 CMR: DEPARTMENT OF PUBLIC UTILITIES 220 CMR 18.00: NET METERING Section 18.01: Purpose and Scope 18.02: Definitions 18.03: Net Metering Services 18.04: Calculation of Net Metering Credits 18.05: Allocation of Net Metering Credits 18.06:

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

NOTICE OF PUBLIC HEARING ANAHEIM PUBLIC UTILITES BOARD IS HOLDING A PUBLIC HEARING ON THE FORMATION OF UNDERGROUND DISTRICT No. 66 (BEACH) TO UNDERGROUND OVERHEAD FACILTIIES, INCLUDING POWER AND COMMUNICATION

More information

Please Refer to Attached Sample Form

Please Refer to Attached Sample Form Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 32105-E Cancelling Revised Cal. P.U.C. Sheet No. 28313-E Electric Sample Form No. 62-0686 Application for Service

More information

July 24, Docket No EI FPL s Petition for Approval of a New Depreciation Class and Rate for Energy Storage Equipment

July 24, Docket No EI FPL s Petition for Approval of a New Depreciation Class and Rate for Energy Storage Equipment John T. Butler Assistant General Counsel-Regulatory Florida Power & Light Company 700 Universe Boulevard Juno Beach, FL 33408-0420 (561) 304-5639 (561) 691-7135 (Facsimile) John.Butler@fpl.com July 24,

More information

Brion Energy Corporation

Brion Energy Corporation Decision 20907-D01-2015 MacKay River Commercial Project October 29, 2015 Alberta Utilities Commission Decision 20907-D01-2015 MacKay River Commercial Project Proceeding 20907 Application 20907-A001 October

More information

Western NY Public Policy Transmission Planning Report

Western NY Public Policy Transmission Planning Report Western NY Public Policy Transmission Planning Report Dawei Fan Supervisor, Public Policy and Interregional Planning Business Issues Committee September 12, 2017 Operating Committee September 15, 2017

More information

SOUTHWEST CALGARY RING ROAD (SWCRR)

SOUTHWEST CALGARY RING ROAD (SWCRR) PROJECT OVERVIEW Alberta Transportation has started planning for the construction of the SW portion of the road that will complete the Calgary Ring Road. The completion of the SWCRR requires the relocation

More information

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST BEFORE THE FLORIDA PUBLIC SERVICE COMMISSION In re: Staff's Second Data Request on OUC' s Review of Electric Utility Hurricane Preparedness and Restoration Actions Docket No. 20170215-EU Filed: January

More information

Kettle River Transmission Project

Kettle River Transmission Project April 2012 Why are you receiving this project information package? New transmission facilities are needed in the Fort McMurray area. ATCO Electric has been directed by the Alberta Electric System Operator

More information

Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1

Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1 Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide Version 1.1 October 21, 2016 1 Table of Contents: A. Application Processing Pages 3-4 B. Operational Modes Associated

More information

Joint Operating Procedures for First Nations Consultation on Energy Resource Activities

Joint Operating Procedures for First Nations Consultation on Energy Resource Activities Joint Operating Procedures for First Nations Consultation on Energy Resource Activities October 31, 2018 Contents Revision History... iv Definitions of Key Terms... v 1 Background... 1 2 Roles and Responsibilities...

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

August 15, Please contact the undersigned directly with any questions or concerns regarding the foregoing.

August 15, Please contact the undersigned directly with any questions or concerns regarding the foregoing. California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 August 15, 2017 Re: California

More information

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application

More information

April 18, Mr. David Schmit, County Manager Arapahoe County 5334 S. Prince Street Littleton, CO Conoco Phillips Section 6 Swan Well

April 18, Mr. David Schmit, County Manager Arapahoe County 5334 S. Prince Street Littleton, CO Conoco Phillips Section 6 Swan Well April 18, 2018 Mr. David Schmit, County Manager Arapahoe County 5334 S. Prince Street Littleton, CO 80120 Re: Conoco Phillips Section 6 Swan Well Dear David, It is our understanding that Conoco Phillips

More information

Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any

Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any Draft Version 1 Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation,

More information

Updates. Pat Reiten President and CEO, PacifiCorp Transmission

Updates. Pat Reiten President and CEO, PacifiCorp Transmission PacifiCorp Transmission and Regional Updates Pat Reiten President and CEO, PacifiCorp Transmission PacifiCorp Transmission Overview 16,400 circuit-miles of transmission lines 12,685 MW record peak demand

More information

Examinations of Working Places in Metal and Nonmetal Mines. AGENCY: Mine Safety and Health Administration, Labor.

Examinations of Working Places in Metal and Nonmetal Mines. AGENCY: Mine Safety and Health Administration, Labor. This document is scheduled to be published in the Federal Register on 05/22/2017 and available online at https://federalregister.gov/d/2017-10474, and on FDsys.gov 4520.43-P DEPARTMENT OF LABOR Mine Safety

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

Public Information Centre

Public Information Centre Junction Street Wastewater Pumping Station & Forcemain Schedule B Municipal Class Environmental Assessment Study Public Information Centre June 28, 2017. 6:00 to 8:00 pm. The Burlington Performing Arts

More information

FITCHBURG GAS AND ELECTRIC LIGHT COMPANY NET METERING SCHEDULE NM

FITCHBURG GAS AND ELECTRIC LIGHT COMPANY NET METERING SCHEDULE NM Sheet 1 FITCHBURG GAS AND ELECTRIC LIGHT COMPANY SCHEDULE NM Applicability The following tariff provisions shall be applicable to a Host Customer, as defined herein, that requests net metering services

More information

City of Lafayette Staff Report Circulation Commission

City of Lafayette Staff Report Circulation Commission City of Lafayette Staff Report Circulation Commission Meeting Date: September 5, 2016 Staff: Subject: James Hinkamp, Transportation Planner Consideration of a No Parking Zone on Victoria Avenue Summary

More information

Wal-Mart Canada Corp.

Wal-Mart Canada Corp. Decision 2010-596 New 500-kW Emergency Back-up Generator for Wal-Mart Perishable Foods Distribution Centre Balzac, Alberta December 17, 2010 ALBERTA UTILITIES COMMISSION Decision 2010-596: Wal-Mart Canada

More information

Frequently Asked Questions Leander-Round to Rock 138-kV Transmission Line Project Williamson County

Frequently Asked Questions Leander-Round to Rock 138-kV Transmission Line Project Williamson County Frequently Asked Questions Leander-Round to Rock 138-kV Transmission Line Project Williamson County Q. What is the Leander-Round Rock 138-kV Transmission Line Project? A. The Leander-Round Rock project

More information

BOARD OF ZONING ADJUSTMENT STAFF REPORT Date: November 7, 2016

BOARD OF ZONING ADJUSTMENT STAFF REPORT Date: November 7, 2016 # 2 HOLDOVER Revised ZON2016-01992 BOARD OF ZONING ADJUSTMENT STAFF REPORT Date: November 7, 2016 CASE NUMBER 6065 APPLICANT NAME LOCATION VARIANCE REQUEST ZONING ORDINANCE REQUIREMENT ZONING AREA OF PROPERTY

More information

October 17, Please contact the undersigned directly with any questions or concerns regarding the foregoing.

October 17, Please contact the undersigned directly with any questions or concerns regarding the foregoing. California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 October 17, 2017 Re: California

More information

ACTION TRANSMITTAL No

ACTION TRANSMITTAL No Transportation Advisory Board of the Metropolitan Council of the Twin Cities DATE: January 4, 2016 TO: ACTION TRANSMITTAL No. 2016-19 TAC Funding and Programming Committee PREPARED BY: Joe Barbeau, Senior

More information

WOLVERINE TO BHP JANSEN NEW TRANSMISSION LINE PROJECT FALL 2017

WOLVERINE TO BHP JANSEN NEW TRANSMISSION LINE PROJECT FALL 2017 WOLVERINE TO BHP JANSEN NEW TRANSMISSION LINE PROJECT FALL 2017 TODAY WE LL TALK ABOUT Our challenges and how we re meeting them Why we re building this project Our planning process and considerations

More information

Addressing ambiguity in how electricity industry legislation applies to secondary networks

Addressing ambiguity in how electricity industry legislation applies to secondary networks In Confidence Office of the Minister of Energy and Resources Chair, Cabinet Business Committee Addressing ambiguity in how electricity industry legislation applies to secondary networks Proposal 1 This

More information

welcome to the BC Hydro community open house

welcome to the BC Hydro community open house welcome to the BC Hydro community open house Dawson Creek/ Chetwynd Area Transmission ProjecT Open House welcome Dawson Creek/Chetwynd Area Transmission Project (DCAT) The purpose of this open house is

More information

,ILLS CITY OF BEVERLY HILLS TRAFFIC AND PARKING COMMISSION. July 12, 2018 TO: Traffic and Parking Commission FROM: Transportation Staff SUBJECT:

,ILLS CITY OF BEVERLY HILLS TRAFFIC AND PARKING COMMISSION. July 12, 2018 TO: Traffic and Parking Commission FROM: Transportation Staff SUBJECT: Transportation Staff TO: FROM: Traffic and Parking Commission July 12, 2018 A. Preferential Parking Permit Test District Survey and FAQ Sheet All businesses and households located within 1,000 feet of

More information

Louisville Gas and Electric Company

Louisville Gas and Electric Company P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer

More information

Interconnection Process for Generation Systems

Interconnection Process for Generation Systems Interconnection Process for Generation Systems I. INTRODUCTION...1 II. GENERAL INFORMATION...2 A. Definitions...2 B. Nodak Electric Cooperative, Inc. Generation Interconnection Contacts...3 C. Engineering

More information

REGIONAL TRANSMISSION ORGANIZATIONS / INDEPENDENT SYSTEM OPERATORS AND THE ENERGY IMBALANCE MARKET: AN OVERVIEW OF THE PICTURE IN THE WEST

REGIONAL TRANSMISSION ORGANIZATIONS / INDEPENDENT SYSTEM OPERATORS AND THE ENERGY IMBALANCE MARKET: AN OVERVIEW OF THE PICTURE IN THE WEST REGIONAL TRANSMISSION ORGANIZATIONS / INDEPENDENT SYSTEM OPERATORS AND THE ENERGY IMBALANCE MARKET: AN OVERVIEW OF THE PICTURE IN THE WEST MEGAN O REILLY COALITION FOR CLEAN AFFORDABLE ENERGY EPE IRP STAKEHOLDER

More information

1. Thank you for the opportunity to comment on the Low Emissions Economy Issues Paper ( Issues Paper ).

1. Thank you for the opportunity to comment on the Low Emissions Economy Issues Paper ( Issues Paper ). 20 September 2017 Low-emissions economy inquiry New Zealand Productivity Commission PO Box 8036 The Terrace Wellington 6143 info@productivity.govt.nz Dear Commission members, Re: Orion submission on Low

More information

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS. 25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements

More information

11 October 12, 2011 Public Hearing APPLICANT:

11 October 12, 2011 Public Hearing APPLICANT: 11 October 12, 2011 Public Hearing APPLICANT: CARING TRANSITIONS PROPERTY OWNER: HARDEE REALTY CORPORATION REQUEST: Conditional Use Permit (motor vehicle rental) STAFF PLANNER: Leslie Bonilla ADDRESS /

More information

November 8, 2004 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION

November 8, 2004 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION Akbar Jazayeri Director of Revenue and Tariffs November 8, 2004 ADVICE 1656-E-A (U 338-E) PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION SUBJECT: Supplemental to Advice 1656-E,

More information

Overview of ISO New England and the New England Wholesale Power Markets

Overview of ISO New England and the New England Wholesale Power Markets Overview of ISO New England and the New England Wholesale Power Markets Boston Chapter of IEEE PES Technical Meeting June 15, 2010 Stephen J. Rourke Vice President, System Planning About ISO New England

More information

City of Palo Alto (ID # 6416) City Council Staff Report

City of Palo Alto (ID # 6416) City Council Staff Report City of Palo Alto (ID # 6416) City Council Staff Report Report Type: Informational Report Meeting Date: 1/25/2016 Summary Title: Update on Second Transmission Line Title: Update on Progress Towards Building

More information

Hours of Service of Drivers: Application for Exemption; Power and. AGENCY: Federal Motor Carrier Safety Administration (FMCSA), DOT.

Hours of Service of Drivers: Application for Exemption; Power and. AGENCY: Federal Motor Carrier Safety Administration (FMCSA), DOT. This document is scheduled to be published in the Federal Register on 09/14/2017 and available online at https://federalregister.gov/d/2017-19512, and on FDsys.gov 4910-EX-P DEPARTMENT OF TRANSPORTATION

More information

Peninsula Corridor Electrification Project (PCEP)

Peninsula Corridor Electrification Project (PCEP) Peninsula Corridor Electrification Project (PCEP) Q4 Quarterly Update #11 April 1 June 30, 2017 JPB Board Meeting August 3, 2017 Agenda Item # 8a Electrification - Infrastructure Design Build Contract

More information

P.L. 2007, c.348 Approved January 13, 2008

P.L. 2007, c.348 Approved January 13, 2008 P.L. 2007, c.348 Approved January 13, 2008 INTRODUCED JUNE 11, 2007 ASSEMBLY, No. 4314 STATE OF NEW JERSEY 212th LEGISLATURE Sponsored by: Assemblyman JOHN S. WISNIEWSKI District 19 (Middlesex) Assemblyman

More information

Thank you for your time and attention to this matter. Please feel free to contact me if you have any questions regarding the filing.

Thank you for your time and attention to this matter. Please feel free to contact me if you have any questions regarding the filing. Mary L. Cottrell, Secretary March 27, 2009 Page 1 Stacey M. Donnelly Counsel September 23, 2009 Mark D. Marini, Secretary Department of Public Utilities One South Station Boston, MA 02110 Re: D.P.U. 09-03

More information

Patrick Wruck Commission Secretary

Patrick Wruck Commission Secretary Patrick Wruck Commission Secretary Commission.Secretary@bcuc.com bcuc.com Suite 410, 900 Howe Street Vancouver, BC Canada V6Z 2N3 P: 604.660.4700 TF: 1.800.663.1385 F: 604.660.1102 June 15, 2018 Sent via

More information

Frequently Asked Questions Trico Proposed Net Metering Tariff Modifications

Frequently Asked Questions Trico Proposed Net Metering Tariff Modifications Frequently Asked Questions Trico Proposed Net Metering Tariff Modifications 1. Who is a self-generation or Net Metering Member? This is a Member who has installed grid-connected renewable generation, such

More information

Solar-Wind Specific Request for Proposals

Solar-Wind Specific Request for Proposals Program Description Solar-Wind Specific Request for Proposals Power Production from Green Resources in North Carolina 04/19/2006 NC GreenPower (NCGP) is a statewide program designed to improve the quality

More information

SAN FRANCISCO MUNICIPAL TRANSPORTATION AGENCY

SAN FRANCISCO MUNICIPAL TRANSPORTATION AGENCY THIS PRINT COVERS CALENDAR ITEM NO.: 10.3 DIVISION: Transit Services BRIEF DESCRIPTION: SAN FRANCISCO MUNICIPAL TRANSPORTATION AGENCY Approving traffic and parking modifications to implement a new bus

More information

Willingdon Substation Decommission

Willingdon Substation Decommission November 2012 Why are you receiving this project information package? New transmission facilities have been proposed in central east Alberta. As a result, some existing facilities are no longer needed.

More information

HydroGenerations PROGRAM HANDBOOK

HydroGenerations PROGRAM HANDBOOK HydroGenerations PROGRAM HANDBOOK TABLE OF CONTENTS Please ensure you are reading the most recent version of this handbook by visiting the NV Energy website, www.nvenergy.com/hydro. Contents HydroGenerations

More information

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers DISTRIBUTION CODE Contents 1 Introduction 2. Advisory and Information Systems 3. Supply 3.1 Quality of Electric Supply 3.2 Interference with other Customers 3.3 Application for the Supply of Electricity

More information

Powering Sydney s Future

Powering Sydney s Future Powering Sydney s Future Frequently Asked Questions December 2017 Project background Q: Why is this project needed? A: Inner Sydney is one of the most critical parts of the NSW electricity network. However,

More information

P. SUMMARY: The Southeastern Power Administration (SEPA) establishes Rate Schedules JW-

P. SUMMARY: The Southeastern Power Administration (SEPA) establishes Rate Schedules JW- This document is scheduled to be published in the Federal Register on 08/29/2016 and available online at http://federalregister.gov/a/2016-20620, and on FDsys.gov 6450-01-P DEPARTMENT OF ENERGY Southeastern

More information

January 24, Re: Small Refiner Exemptions. Dear Administrator Pruitt:

January 24, Re: Small Refiner Exemptions. Dear Administrator Pruitt: January 24, 2018 The Honorable Scott Pruitt Administrator U.S. Environmental Protection Agency 1200 Pennsylvania Avenue, N.W., 1101A Washington, DC 20460 Re: Small Refiner Exemptions Dear Administrator

More information

Summer Reliability Assessment Report Electric Distribution Companies Perspective

Summer Reliability Assessment Report Electric Distribution Companies Perspective Energy Association of Pennsylvania Summer Reliability Assessment Report Electric Distribution Companies Perspective to the Pennsylvania Public Utility Commission June 9, 2011 Harrisburg, PA Terrance J.

More information

The Narragansett Electric Company. d/b/a National Grid (Interstate Reliability Project) RIPUC Dkt. No Testimony of. David M. Campilii, P.E.

The Narragansett Electric Company. d/b/a National Grid (Interstate Reliability Project) RIPUC Dkt. No Testimony of. David M. Campilii, P.E. (Interstate Reliability Project) RIPUC Dkt. No. 0 Testimony of David M. Campilii, P.E. November, 0 -v RIPUC Dkt. No. 0 PREFILED TESTIMONY OF DAVID M. CAMPILII 0 0 INTRODUCTION Q. Please state your name

More information

Minnesota Public Utilities Commission Staff Briefing Papers

Minnesota Public Utilities Commission Staff Briefing Papers Minnesota Public Utilities Commission Staff Briefing Papers Meeting Date: September 9, 2004................................ Agenda Item # Company: Docket No. Issue(s): Mankato Energy Center IP-6345/CN-03-1884

More information

CITY COUNCIL OF THE CITY OF NOVATO ORDINANCE NO. 1620

CITY COUNCIL OF THE CITY OF NOVATO ORDINANCE NO. 1620 G-12 CITY COUNCIL OF THE CITY OF NOVATO ORDINANCE NO. 1620 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF NOVATO AMENDING THE NOVATO MUNICIPAL CODE BY ADDING SECTION 4-19 (ELECTRIC VEHICLE CHARGING SYSTEMS)

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION Regional Reliability Standards ) VAR-002-WECC-2 and VAR-501-WECC-2 ) Docket No. RD15-1-000 COMMENTS OF DOMINION RESOURCES SERVICES,

More information

Appendix D Black Hills Project Summary

Appendix D Black Hills Project Summary Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain

More information

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION Presentation by Engr. O. C. Akamnnonu Chief Executive Officer, Ikeja Electricity Distribution Company AGENDA WORK THROUGH

More information

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Puget Sound Area Study Team Bonneville Power Administration, Puget Sound Energy, Seattle City Light,

More information

Re: Comments on the 12/7/09 Dynamic Transfer Stakeholder Meeting

Re: Comments on the 12/7/09 Dynamic Transfer Stakeholder Meeting Joseph H. Rowley Vice President Project Development 101 Ash Street, HQ14A San Diego, CA 92101-3017 Tel: 619.696.4455 Fax: 619.696.2911 JRowley@SempraGeneration.com December 15, 2009 Ms. Anjali Sheffrin

More information

Welcome. Hello and welcome to this information stall about our proposals for the expansion of the Orchard Centre.

Welcome. Hello and welcome to this information stall about our proposals for the expansion of the Orchard Centre. Welcome Hello and welcome to this information stall about our proposals for the expansion of the Orchard Centre. Our proposals for the expansion of the Orchard Centre are part of a multi-million pound

More information