AP1000 Plant Overview

Size: px
Start display at page:

Download "AP1000 Plant Overview"

Transcription

1 AP1000 Plant Overview Westinghouse IEEE Subcommittee on Qualification Tom Hayes Passive Plant Projects Slide 1

2 Westinghouse Passive Plants Meet Power Company Needs Satisfies all U.S. Utility Requirements (ALWR URD) 0Cost, construction, operations advantages demonstrated Major Simplifications Achieved 0Construction, design, maintenance & operations Provides New Standard in Safety 0Improved safety and risk performance, margins verified Licensing Certainty 0Rigorous NRC review & comprehensive test program 0Assures licensibility for domestic & international sites Slide 2

3 Design Bounded By: Make it safe Meet US regulatory requirements Satisfy utility requirements Make it simple Use proven technology Make safety systems passive Make it affordable Slide 3

4 Naturally Occurring Physical Phenomena Used in Operation of Safety Systems Natural circulation of air, water, and steam Gravity and gas pressure drive flow of cooling water. Natural heat transfer through conduction, convection, and evaporation Flow and cooling occur in accordance with nature s laws - No support systems One time alignment of active valves (dc battery actuated) 0 No dc actuation power after 24 hours Greatly reduced operator dependency Slide 4

5 AP1000 Approach to Safety Passive Safety Systems 0 Use passive process only, no active pumps, diesels,. 0 One time alignment of valves 0 No support systems required after actuation 0 Reduced dependency on operator actions 0 Mitigate design basis accidents without nonsafety systems 0 Meet NRC safety goals without use of nonsafety systems Active Nonsafety Systems 0 Reliably support normal operation 0 Redundant equipment powered by onsite diesels 0 Minimize challenges to passive safety systems 0 Not required to mitigate design basis accidents Slide 5

6 Major Safety Advancements No Reliance on AC Power No Operator Action Required to Assure Safety Long Term Plant Safety Assured without Active Components (Natural Forces Only) Containment is Not Breached for Postulated Design Basis Events In Severe Accidents, Reactor Vessel Cooling Keeps Core in Vessel Large Margin to Safety Limits Defense in Depth - Active Systems Provide ADDITIONAL first line of defense Slide 6

7 AP1000 Design Features Integrated Power Plant Design Simplified RCS Loops with Canned Motor Pumps Simplified Passive Safety Systems Microprocessor, Digital Technology Based I&C No Requirement for Safety AC Power Compact Control Room, Electronic Operator Interface Optimized Plant Arrangement 0 Construction, Operation, Maintenance, Safety, Cost Extensive Use of Modular Construction Slide 7

8 Approach to Safety: Defense-in-Depth Simple Passive Safety Systems Dedicated safety systems - not required for normal operation Use natural driving forces - no active pumps, diesels One-time alignment of active valves No support systems after actuation Reduced operator dependency Mitigate design basis accidents without nonsafety systems Simple Active Non-Safety Systems Reliable active equipment for normal operation Redundant active equipment powered by nonsafety diesels Minimize unnecessary use of passive safety systems Reduce risk to utility & public Slide 8

9 Simplicity Applies to Every Element of the AP1000/AP600 Simplicity in Design through reduced number of components and bulk commodities Simplicity in Safety through use of passive safety systems Simplicity in Procurement through standardization of components Simplicity in Operation and Maintenance through use of proven systems and components and man-machine interface advancements Slide 9

10 Passive Safety Features: Eliminate the Need for Safety AC Electric Power Passive Decay Heat Removal Natural circulation heat exchanger connected to Reactor Coolant System (RCS) Passive Safety Injection Gravity drain core makeup tanks (RCS pressure) N 2 pressurized accumulators Gravity drain refueling water storage tank (containment pressure) Automatic RCS depressurization Passive Containment Cooling Steel containment shell transfers heat to natural circulation of air and evaporation of water drained by gravity Passive Heating Ventilation Air Conditioning Compressed air for habitability of main control room (MCR) Concrete walls for heat sink (MCR and C&I rooms) Slide 10

11 Passive Containment Cooling Slide 11

12 AP1000 Passive Core Cooling System AP600 System Configuration Retained Capacities Increased to Accommodate Higher Power 0 Core 1933 MW > 3400 MW or 76% 0 PRHR HX Capacity Increased 72% 0 CMT Volume & Flow Increased 25% 0 ADS 4 Flow Increased 93% 0 IRWST Injection Increased 89% 0 Cont. Recirc. Increased 139% System Performance Maintained 0 No core uncovery for SBLOCA 0 < DVI line break 0 Large margin to PCT limit 0 No operator actions required for SGTR Slide 12

13 AP1000 EHVAC MCR Compressed air provides breathable air for operators 0 72 hours of operation 0 65 SCFM air flow pressurizes MCF 1/8 in water Thermal mass of concrete provides temperature control NORMAL HVAC Compressed Air System FC FC FC FC (1 of 8) (1 of 8) MAIN CONTROL ROOM (1 of 8) FC FC (1 of 8) COMPRESSED AIR TANKS Slide 13

14 Approach to Safety: Defense-in-Depth Simple Passive Safety Systems Dedicated safety systems - not required for normal operation Use natural driving forces - no active pumps, diesels One-time alignment of active valves No support systems after actuation Reduced operator dependency Mitigate design basis accidents without nonsafety systems Simple Active Non-Safety Systems Reliable active equipment for normal operation Redundant active equipment powered by nonsafety diesels Minimize unnecessary use of passive safety systems Reduce risk to utility & public Slide 14

15 Active Nonsafety Systems Active Nonsafety System Functions 0 Reliably support normal operation 0 Minimize challenge to passive safety systems 0 Not required to mitigate design basis accidents 0 Not required to meet NRC safety goals Active Nonsafety System Design Features 0 Redundancy to minimize failures effects 0 Automatic actuation with power from onsite diesels Active Nonsafety System Equipment Design 0 Reliable industrial grade equipment 0 Non-ASME, non-seismic, limited fire / flood / wind protection 0 Availability controlled by procedures, no shutdown requirements 0 Reliability controlled by maintenance program (not maintenance rule) Slide 15

16 System Defense In Depth AP1000 Provides Multiple Levels of Defense 0 First feature is usually nonsafety active feature 0 High quality industrial grade equipment 0 One feature is safety passive feature 0 Provides safety case for DCD 0 Highest quality nuclear grade equipment 0 Other passive features provide additional defense-in-depth 0 Example; passive feed/bleed backs up PRHR HX 0 Available for all shutdown conditions as well as at power 0 More likely events have more levels of defense Slide 16

17 Passive Safety Systems Passive Safety System Functions 0 Dedicated safety systems, not used for normal operation 0 Mitigate design basis accidents without nonsafety systems 0 Meet NRC safety goals without use of nonsafety systems Passive Safety System Design Features 0 Only passive processes; no active pumps, diesels, fans, 0 DBA considerations; margin, single failure 0 PRA considerations; reliability, common mode failures 0 Reduced dependency on operator actions Passive Safety System Equipment Design 0 Reliable, experienced based, nuclear grade equipment 0 ASME, seismic I, full fire / flood / wind protection 0 Availability controlled by Tech Spec with shutdown requirements 0 Reliability controlled by ISI / IST and maintenance program Slide 17

18 Active Nonsafety Systems Active Nonsafety System Functions 0 Reliably support normal operation 0 Minimize challenge to passive safety systems 0 Not required to mitigate design basis accidents 0 Not required to meet NRC safety goals Active Nonsafety System Design Features 0 Simplified designs (fewer components, separation not required) 0 Redundancy for more probable failures 0 Automatic actuation with power from onsite diesels Active Nonsafety System Equipment Design 0 Reliable, experienced based, industrial grade equipment 0 Non-ASME, non-seismic, limited fire / flood / wind protection 0 Availability controlled by procedures, no shutdown requirements 0 Reliability controlled by maintenance program 0 Quality Class D used for components that minimize challenges to passive systems Slide 18

19 AP1000 Electrical Systems Class 1E DC and UPS System (IDS) 0 Provides electrical power to safety components Non-Class 1E DC and UPS System (EDS) 0 Provides electrical power to non-safety components requiring highly-reliable power Main AC Power System (ECS) 0 Provides bulk electrical power Onsite Standby Power System (ZOS) 0 Provides electrical power to defense-in-depth and investment protection loads when offsite power is lost Slide 19

20 AP1000 Class 1E DC & UPS System (IDS) 125 Vdc 120/208Vac 60 Hz (uninterruptible) Four Divisions 0 Divisions A and D each have one 24-hour battery for actuation 0 Divisions B and C each have one 24-hour battery and one 72- hour battery for post-accident monitoring 0 72-hour battery is for monitoring only 0 Spare battery 0 Can be manually connected to replace any of the 6 primary batteries Slide 20

21 AP1000 Class 1E DC & UPS System (IDS) Provides electrical power to safety components 0 Primary Protection System 0 MCR lighting 0 Valve actuators 0 Reactor trip, RCP trip Class 1E 0 Meets IEEE 308, 323, 344, 379, 384, 603, etc. Slide 21

22 AP1000 Non-Class 1E DC & UPS System (EDS) 125 Vdc 120/208Vac 60 Hz (uninterruptible) Two load groups 0 Each group has two 2-hour batteries 0 The IDS spare battery can be used to replace any of the 4 primary nonsafety batteries Slide 22

23 AP1000 Non-Class 1E DC & UPS System (EDS) Provides electrical power to non-safety components requiring highly-reliable power 0 Plant Control System 0 Data Display System 0 Diverse Actuation System 0 Other control systems 0 Communications 0 Hydrogen igniters Non-Class 1E 0 Quality Class D 0 RTNSS Important (portions) Slide 23

24 AP1000 Main AC Power System (ECS) Provides bulk electrical power kv, 480 V, 120/208 V, 60 Hz Normal power supply from main generator Preferred power supply is offsite source through main and auxiliary transformers Maintenance power supply is through reserve auxiliary transformer Standby power source is two diesel generators Two load groups 0 Each group is connected to one standby diesel generator, one auxiliary transformer and the reserve auxiliary transformer Slide 24

25 AP1000 Main AC Power System (ECS) Includes two ancillary diesel generators (35 kw each) for post-72-hour coping 0 Post-accident monitoring instrumentation 0 Control room lighting 0 Passive containment cooling tank refill 0 Spent fuel pool refill Non-Class 1E 0 Equipment Class D (portions) 0 RTNSS Important (portions) Slide 25

26 Onsite Standby Power System (ZOS) Two diesel generators (4000 kw each) Provides electrical power to defense-in-depth and investment protection loads when offsite power is lost Non-Class 1E 0 Quality Class D 0 RTNSS Important Slide 26

27 AP1000 I&C Systems Primary Protection System (PMS) 0 Plant wide system for all safety displays & controls 0 Microprocessor / software based Diverse System (DAS) 0 Limited scope system, PRA based displays & controls 0 Backs up PMS where common mode failure is risk important 0 Different hardware & software than PMS Plant Control System (PLS/DDS) 0 Plant wide system for all normal displays & controls 0 Microprocessor / software based Special Purpose Systems (Seismic Monitoring, Radiation Monitoring, Incore Instrumentation, etc.) Slide 27

28 AP1000 I&C Systems Licensing Status I&C systems are included in Certified Design. I&C system designs were not reviewed by the NRC. Functional requirements consistent with the safety analyses and PRA were established. A design process was defined. Test and acceptance criteria were established. A conceptual design was developed. A detailed I&C design will be developed based on the functional requirements, using the certified design process, and meeting the certified acceptance requirements after a plant is ordered. Slide 28

29 AP1000 Protection System (PMS) Plant-wide Class 1E system for all safety displays & controls Originally expected to be Eagle, now expected to be Common Q Detects off-nominal conditions and actuates safety functions Provides post-accident monitoring functions 0 Regulatory Guide 1.97 Category 1 and some Category 2 variables Microprocessor / software based Multiplexed communications Class 1E 0 Meets IEEE-603, , 323, 344, 379, 384, etc. Slide 29

30 AP1000 Protection System (PMS) Redundant Trains 0 4 divisions, physically separated with electrical isolation (fiberoptic) 0 Each with own independent battery-backed power supply 0 24-hour batteries for actuation, 72-hour batteries for monitoring 0 Improved HVAC separation/fire protection (2 separate HVAC systems) 0 2-out-of-4 bypass logic, fail safe when appropriate 0 Different plant parameters provide functional diversity Verification and Validation Equipment Qualification 0 Environmental, seismic, EMC Improved In-Plant Testing 0 Built-in continuous self-testing and manual periodic testing Westinghouse Extensive Experience with Digital I&C Designs 0 Operating plant upgrades and new plants (Sizewell, Temelin) Slide 30

31 AP1000 Diverse Actuation System (DAS) Limited scope system 0 PRA-based displays & controls 0 Backs up PMS where common mode failure is risk important Microprocessor / software based Different architecture, hardware & software than PMS No multiplexing Manual controls and indications use no software 0 Direct wiring to actuation devices 0 Compliance with USNRC Branch Technical Position HICB-19, Position 4 Separate sensors from PMS and PLS Slide 31

32 AP1000 Diverse Actuation System (DAS) DAS shares some actuated equipment (e.g., valves) with PMS 0 DAS signals isolated from PMS 0 Separate actuation devices 0 Solenoid valves on AOVs 0 Igniters on squib valves 0 Relays in MCCs controlling AOVs Non-Class 1E 0 Equipment Class D 0 RTNSS Important Slide 32

33 AP1000 Control System (PLS / DDS) Plant-wide system for all normal displays & controls Microprocessor / software based Highly redundant Continuously used Multiplexed communications Includes plant computer functions Non-Class 1E 0 Equipment Class D Slide 33

34 AP1000 Advanced Control Room Compact Control Room 0 Designed for 1 Reactor Operator and 1 Supervisor Displays 0 Plant status / overview via wall panel (DDS, non 1E) 0 Detail display via workstation video displays (DDS, non 1E) 0 Small number of dedicated displays; safety (PMS, 1E) & diverse (DAS, non 1E) Controls 0 Soft controls (DDS, non 1E) 0 Small number of dedicated switches; safety (PMS, 1E) & diverse (DAS, non 1E) Advanced Alarm Management Computer Based Procedures 0 Paper backup Slide 34

35 AP1000 is Different Safety systems are not used for normal operation. 0 Multiple, diverse levels of defense 0 Signals from safety sensors are provided to nonsafety system. No safety source of electrical power. 0 Batteries provided for I&C and lighting. No safety actuation power after 24 hours without ac power. 0 Planned safety actuations are one-time-only. Batteries provided for monitoring are sized for 72 hours. 0 Small non-safety diesels provided for post-72 hour monitoring and water. No safety air conditioning. Safety motors are limited to MOV operators. Compact control room. 0 Limited number of discrete controls Slide 35

APR1400 Electric System Design. KHNP KEPCO E&C November 29, 2017

APR1400 Electric System Design. KHNP KEPCO E&C November 29, 2017 APR1400 Electric System Design KHNP KEPCO E&C November 29, 2017 Contents 1. Introduction 2. Offsite Power System Design 3. Onsite Power System Design Auxiliary Power System DC & IP System Onsite Power

More information

AP1000 European 7. Instrumentation and Controls Design Control Document

AP1000 European 7. Instrumentation and Controls Design Control Document 7.3 Engineered Safety Features AP1000 provides instrumentation and controls to sense accident situations and initiate engineered safety features (ESF). The occurrence of a limiting fault, such as a loss

More information

AP1000 European 8. Electric Power Design Control Document

AP1000 European 8. Electric Power Design Control Document 8.3 Onsite Power Systems 8.3.1 AC Power Systems 8.3.1.1 Description The onsite ac power system is a non-class 1E system comprised of a normal, preferred, maintenance and standby power supplies. The normal,

More information

The B&W mpower TM Small Modular Reactor I&C Design, Architecture and Challenges

The B&W mpower TM Small Modular Reactor I&C Design, Architecture and Challenges The B&W mpower TM Small Modular Reactor I&C Design, Architecture and Challenges IAEA Technical Meeting May 23, 2013 B.K. Arnholt 2013 Generation mpower LLC All rights reserved. Agenda Introduction to the

More information

ams.t.andard REVIEW PLAN.

ams.t.andard REVIEW PLAN. NUREQ-0800 (Formerly NUREG-75/087) US. NUCLEAR REGULATORY COMMISSION t ams.t.andard REVIEW PLAN. OFFICE OF NUCLEAR REACTOR REGULATION 7.6 INTERLOCK SYSTEMS IMPORTANT TO SAFETY REVIEW RESPONSIBILITIES Primary

More information

AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface. September 2017

AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface. September 2017 AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface September 2017 Randy C. Ivey Director Supplier Quality Oversight Westinghouse Electric Company AP1000 is a trademark or registered

More information

GE ABWR & ESBWR. Jeff Suggs ESBWR I&C April 17, Copyright 2006 by GE Energy / Nuclear

GE ABWR & ESBWR. Jeff Suggs ESBWR I&C April 17, Copyright 2006 by GE Energy / Nuclear GE ABWR & ESBWR Jeff Suggs ESBWR I&C April 17, 2007 Copyright 2006 by GE Energy / Nuclear GE Energy Gas Cleaner Coal Hydro Nuclear Wind Solar Biomass Fuel Cells Copyright 2006 by GE Energy / Nuclear 2

More information

STANDARD REVIEW PLAN

STANDARD REVIEW PLAN NUREG-0800 (Formerly NUREG-75/087),jEt R E14 t STANDARD REVIEW PLAN OFFICE OF NUCLEAR REACTOR REGULATION, U.s NUCLEAR REGULATORY COMMISSION 8.1 ELECTRIC POWER - INTRODUCTION REVIEW RESPONSIBILITIES Primary

More information

A Tool for planning the Safety Review of SSCs: Development and Application

A Tool for planning the Safety Review of SSCs: Development and Application PSA 2017 A Tool for planning the Safety Review of SSCs: Development and Application Tony Nakanishi, Mark Caruso Lynn Mrowca September 2017 1 Overview Background Enhanced Safety Focused Review Interdisciplinary

More information

JAMES F. GLEASON, P.E. CHAIRMAN QUALIFICATION COMMITTEE

JAMES F. GLEASON, P.E. CHAIRMAN QUALIFICATION COMMITTEE JAMES F. GLEASON, P.E. CHAIRMAN QUALIFICATION COMMITTEE Presented ese ted at NPEC C Ju July y 27, 7, 2011 0 NPEC Most Nuclear Power Countries Use IEEE NPEC Standards Administrative Qualification Operations,

More information

LESSONS LEARNED FORSMARK EVENT Presented To IEEEE

LESSONS LEARNED FORSMARK EVENT Presented To IEEEE LESSONS LEARNED FORSMARK EVENT Presented To IEEEE Thomas Koshy Member of the Task Group on Forsmark Chief of Mechanical & Electrical Engineering Office of Research, USNRC Thomas.Koshy@nrc.gov 1 Agenda

More information

CC System B B 3.7 PLANT SYSTEMS. B Component Cooling Water (CC) System BASES

CC System B B 3.7 PLANT SYSTEMS. B Component Cooling Water (CC) System BASES CC System B 3.7.7 B 3.7 PLANT SYSTEMS B 3.7.7 Component Cooling Water (CC) System BACKGROUND The CC System provides a heat sink for the removal of process and operating heat from safety related components

More information

AP1000 European 5. Reactor Coolant System and Connected Systems Design Control Document

AP1000 European 5. Reactor Coolant System and Connected Systems Design Control Document CHAPTER 5 REACTOR COOLANT SYSTEM AND CONNECTED SYSTEMS 5.1 Summary Description This section describes the reactor coolant system (RCS) and includes a schematic flow diagram of the reactor coolant system

More information

AP1000 European 7. Instrumentation and Controls Design Control Document

AP1000 European 7. Instrumentation and Controls Design Control Document 7.7 Control and Instrumentation Systems The function of the AP1000 control systems is to establish and maintain the plant operating conditions within prescribed limits. The control system improves plant

More information

Seabrook Substation Reliability Improvement Project

Seabrook Substation Reliability Improvement Project New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Westinghouse AP1000 Plant

Westinghouse AP1000 Plant Westinghouse AP1000 Plant Britain's Energy Coast Business Cluster BECBC Energus Workington 6 th August, 2014 Ken Hampson UK Supply Chain Director, Nuclear Power Plants AP1000 is a trademark or registered

More information

ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES

ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES D.V. Didorin, V.A. Kogut, A.G. Muratov, V.V. Tyukov, A.V. Moiseev (NIKIET, Moscow, Russia) 1. Brief description of the aim and

More information

AP Plant Operational Transient Analysis

AP Plant Operational Transient Analysis www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 3 Issue 2, June 2013 AP1000 1 Plant Operational Transient Analysis LIU Lixin 1, ZHENG Limin 2 Shanghai Nuclear Engineering

More information

The IAEA does not normally maintain stocks of reports in this series.

The IAEA does not normally maintain stocks of reports in this series. IAEA-TECDOC- The IAEA does not normally maintain stocks of reports in this series. However, microfiche copies SAFETY ASPECTS OF STATION BLACKOUT AT NUCLEAR POWER PLANTS IAEA, VIENNA, 1985 IAEA-TECDOC-332

More information

CATERPILLAR 3516B DP2 System

CATERPILLAR 3516B DP2 System CATERPILLAR 3516B DP2 System CONTENTS System Overview 3 Offshore Rig or Ship DP2 Package 3 Main Generator Diesel Skid 3 Main Generator Diesel Engines 3 Instrument, Alarms and Automatic Start/Stop System

More information

EMERGENCY DIESEL GENERATOR SETS FOR NUCLEAR POWER PLANTS

EMERGENCY DIESEL GENERATOR SETS FOR NUCLEAR POWER PLANTS EMERGENCY DIESEL GENERATOR SETS FOR NUCLEAR POWER PLANTS YOUR REQUIREMENT IS OUR ASSIGNMENT. MTU Onsite Energy is one of the core brands of Rolls- Royce Power Systems AG, a world-leading provider of high-

More information

Nuclear L.L. C. 10 CFR 50.55a

Nuclear L.L. C. 10 CFR 50.55a 'I PSEG Nuclear LLC P.O. Box 236,, Hancocks Bridge, NJ 08038-0236 LR-N09-0046 March 05, 2009 0 PSEG Nuclear L.L. C. 10 CFR 50.55a U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington,

More information

FUNCTIONAL SAFETY SOLUTIONS in Solenoid Valves

FUNCTIONAL SAFETY SOLUTIONS in Solenoid Valves FUNCTIONAL SAFETY SOLUTIONS in Solenoid Valves Safety is reality and is part of our daily business. The same applies to ASCO; it is reality and part of your safety. You can rely on our focus on reliable

More information

IMPLEMENTATION OF THE RCP SHIELD MECHANICAL SEAL MODEL IN THE COMANCHE PEAK PRA

IMPLEMENTATION OF THE RCP SHIELD MECHANICAL SEAL MODEL IN THE COMANCHE PEAK PRA IMPLEMENTATION OF THE RCP SHIELD MECHANICAL SEAL MODEL IN THE COMANCHE PEAK PRA Nathan Larson Principal Engineer Daniel Tirsun Fellow Engineer Aaron Moreno Senior Engineer Glen Rose, TX SHIELD is a trademark

More information

MCD 200 Series Soft Starters

MCD 200 Series Soft Starters MCD 200 Series Soft Starters AC motors often cause one or more serious problems during startup acceleration. MCD 200 Series electronic soft starters control motor current to provide a smooth start. When

More information

Hope Creek Variable Frequency Drive

Hope Creek Variable Frequency Drive Hope Creek Variable Frequency Drive 2018 Power Plant Simulation Conference Houston, TX January 14-18, 2018 Hope Creek Variable Frequency Drive Simulation John Stone Senior Engineer - CORYS Presentation

More information

Streamlined RI-ISI. Patrick O Regan EPRI

Streamlined RI-ISI. Patrick O Regan EPRI Streamlined RI-ISI Patrick O Regan EPRI poregan@epri.com Introduction Background Streamlined RI-ISI Methodology Results Discussion, Lessons Learned, Improvements Summary Background GOAL: Based upon the

More information

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER E: THE REACTOR COOLANT SYSTEM AND RELATED SYSTEMS

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER E: THE REACTOR COOLANT SYSTEM AND RELATED SYSTEMS PAGE : 1 / 13 4. PRESSURISER 4.1. DESCRIPTION The pressuriser (PZR) is a pressurised vessel forming part of the reactor coolant pressure boundary (CPP) [RCPB]. It comprises a vertical cylindrical shell,

More information

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA 1 of 10 Mattei rotary vane compressors are the result of 90 years of investments in research and development to improve performance and lessen the impact on the environment. Designed for industrial continuous

More information

596 Rectifier Retrofit

596 Rectifier Retrofit PRODUCT OVERVIEW 596 Rectifier Retrofit Overview GE Energy has offered the 596 family of rectifiers from the early 1990s. 596 rectifiers can be found in the GPS4812, 2424, PXS Shelves, and OCS Cabinet

More information

Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance MP-SEE-THRU-01 Rev. 018

Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance MP-SEE-THRU-01 Rev. 018 Student Operating Procedure Millstone Station Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance Approval Date: 01/12/2011 Effective Date: 01/12/2011 TABLE OF CONTENTS 1. PURPOSE...3

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Probabilistic Risk Assessment for Spent Fuel Pool Decommissioning in the J. Bohunice V1 NPP

Probabilistic Risk Assessment for Spent Fuel Pool Decommissioning in the J. Bohunice V1 NPP Probabilistic Risk Assessment for Spent Fuel Pool Decommissioning in the J. Bohunice V1 NPP by Zoltán Kovács, Robert Spenlinger and Helena Novakova RELKO Ltd, Engineering and Consulting Services Račianska

More information

SUB-CHAPTER B.3 COMPARISON TABLE COMPARISON WITH REACTORS OF SIMILAR DESIGN (N4 AND KONVOI)

SUB-CHAPTER B.3 COMPARISON TABLE COMPARISON WITH REACTORS OF SIMILAR DESIGN (N4 AND KONVOI) CHAPTER B: INTRODUCTION AND GENERAL DESCRIPTION OF THE SUB-CHAPTER: B.3 SECTION : - PAGE : 1 / 9 SUB-CHAPTER B.3 COMPARISON TABLE COMPARISON WITH REACTORS OF SIMILAR DESIGN (N4 AND KONVOI) A comparison

More information

CPC DX (CPC Dual Transfer Skid) Redundant current to pressure converter assembly

CPC DX (CPC Dual Transfer Skid) Redundant current to pressure converter assembly Product Specification 03421 (Revision NEW, 5/2015) CPC DX (CPC Dual Transfer Skid) Redundant current to pressure converter assembly Applications The CPC-DX (current-to-pressure converter dual transfer)

More information

S. Y. Park (*), K. I. Ahn

S. Y. Park (*), K. I. Ahn IEM on Strengthening R&D Effectiveness in the Light of the Accident at the Fukushima Daiichi NPP, Vienna, 16-0 Feb. 015 Assessment of the Mitigative Strategy using External Coolant Injection for OPR-1000

More information

MODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM

MODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM MODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM PowerLine DPA 20 120 kva Full power for industrial applications PowerLine DPA 20 120 kva Full power for industrial applications 2 ABB UPS SYSTEMS POWERLINE

More information

Severe Service Hydraulic Actuators for the Nuclear Power Industry. Enertech Nuclear Qualified Electro-Hydraulic Actuators

Severe Service Hydraulic Actuators for the Nuclear Power Industry. Enertech Nuclear Qualified Electro-Hydraulic Actuators Severe Service Hydraulic Actuators for the Nuclear Power Industry Enertech Nuclear Qualified Electro-Hydraulic Actuators Engineered Solutions for the Nuclear Power Industry Enertech, formerly Paul Munroe

More information

Operational risks of old nuclear power plants in Switzerland

Operational risks of old nuclear power plants in Switzerland 111 NPP Beznau NPP Mühleberg Operational risks of old nuclear power plants in Switzerland 1 Five nuclear power plants in Switzerland Beznau seit 1969 in Betrieb Mühleberg seit 1971 in Betrieb Gösgen seit

More information

Presented at SC-2, Meeting October 5-6, 2010,, Seattle, WA

Presented at SC-2, Meeting October 5-6, 2010,, Seattle, WA U.S. EPR EQ Program Update Nissen M. Burstein Technical Consultant Presented at SC-2, Meeting 10-02 October 5-6, 2010,, Seattle, WA EPR is a trademark of the AREVA Group. Overview of U.S. EPR Reactor Redundant

More information

Duke Power Company DOCUMENT TRANSMITTAL FORM REFERENCE MCGUIRE NUCLEAR STATION SELECTED LICENSEE COMMITMENTS MANUAL. Page 2 of 3

Duke Power Company DOCUMENT TRANSMITTAL FORM REFERENCE MCGUIRE NUCLEAR STATION SELECTED LICENSEE COMMITMENTS MANUAL. Page 2 of 3 PRIORITY Rush 1) 01623 G L MONTGOMERY MG01IE 2) 02049 NGO PRA MANAGER ECO81 3) 02188 NPA MANAGER EC05N 4) 02467 ELECT. LICENSING LIBRARY EC050 5) 02532 MCG NRC INSP MG01A 6) 02546 M D RAINS MG01WC 7) 03044

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

VariStroke II Electro hydraulic Actuator

VariStroke II Electro hydraulic Actuator Product Specification 03378 (Revision B, 9/2013) Applications VariStroke II Electro hydraulic Actuator The VariStroke-II is a linear electro-hydraulic actuator that is designed to provide the linear actuation

More information

NSTD Introductory Course

NSTD Introductory Course NSTD Introductory Course New Gen III+ Reactor Power Plant Designs Economic Simplified Boiling Water Reactor (ESBWR) ESBWR Overview 1 Disclaimer Information contained herein is derived exclusively from

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph VEGA INDUSTRIAL UNINTERRUPTIBLE POWER SUPPLY 10 20KVA 3Ph/1Ph 10 120KVA 3Ph / 3Ph - 6 pulse SCR rectifier - IGBT inverter - Power output transformer - Low and stable ripple on battery for the highest battery

More information

Cisco Nexus 7700 Switches Environment

Cisco Nexus 7700 Switches Environment Data Sheet Cisco Nexus 7700 Switches Environment Data Sheet Product Overview The Cisco Nexus 7700 platform is the latest extension to the modular Cisco Nexus 7000 Series Switches. Capable of 83 terabits

More information

AIR LUBRICATION SYSTEM INSTALLATION

AIR LUBRICATION SYSTEM INSTALLATION Guide for Air Lubrication System Installation GUIDE FOR AIR LUBRICATION SYSTEM INSTALLATION OCTOBER 2018 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 2018

More information

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW) Product datasheet Characteristics ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/400...440V(45kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

Super-Critical Water-cooled Reactors

Super-Critical Water-cooled Reactors Super-Critical Water-cooled Reactors (SCWRs) SCWR System Steering Committee T. Schulenberg, H. Matsui, L. Leung, A. Sedov Presented by C. Koehly GIF Symposium, San Diego, Nov. 14-15, 2012 General Features

More information

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller DISCONTINUED PRODUCT CSI 15621 - Mainframe Cooling Systems 1.1 SUMMARY Liebert CSU3000 CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller GUIDE SPECIFICATIONS 1.0 GENERAL These specifications describe

More information

TRIMOD HE UPS. MODULAR THREE-PHASE UPS from 10 to 80 kw THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

TRIMOD HE UPS. MODULAR THREE-PHASE UPS from 10 to 80 kw THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES TRIMOD HE UPS MODULAR THREE-PHASE UPS from 10 to 80 kw THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES TRIMOD HE HIGH performance HIGH efficiency LOW environmental impact DEVELOPMENTS

More information

BAC Custom Engineered Controls

BAC Custom Engineered Controls BAC Custom Engineered Controls Product Detail Product Introduction......................................... K2 BAC Custom Engineered Controls Benefits....................................................

More information

Electronic Governor System For Steam Turbine Applications

Electronic Governor System For Steam Turbine Applications Electronic Governor System For Steam Turbine Applications WWW.CW-EMS.COM/SAS Company, incorporated an electronic governor module (EGM), electronic governor regulator (EGR), and remote servo drive that

More information

Nuclear. Enertech Nuclear Class Electro-Hydraulic Actuators.

Nuclear. Enertech Nuclear Class Electro-Hydraulic Actuators. Nuclear Enertech Nuclear lass Electro-Hydraulic Actuators www.cwnuclear.com Enertech Nuclear lass Electro-Hydraulic Actuators for Valve and Damper ontrol Who We Are Enertech, formerly Paul-Munroe Hydraulics,

More information

There s a new power in Solar 1500V ultra-high power string inverters for utility-scale PV applications

There s a new power in Solar 1500V ultra-high power string inverters for utility-scale PV applications PRODUCT MANAGEMENT, REV. NOVEMBER- 2018 There s a new power in Solar 1500V ultra-high power string inverters for utility-scale PV applications Andrea Genovesi, Gianluca Marri, Marco Trova [MW] Utility-scale

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION... CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...6 4.1. DISPLAY PANEL...6 4.2. LCD ICON INSTRUCTION...7 4.3. DISPLAY INSTRUCTIONS...7 4.4. DISPLAY DESCRIPTION...8

More information

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS CENTRALIZED Battery System BS-EN-50171 Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS 10KVA-40KVA The systems running

More information

Current Status of the Melcor Nodalization for Atucha I Nuclear Power Plant. Zárate. S.M. and Valle Cepero, R.

Current Status of the Melcor Nodalization for Atucha I Nuclear Power Plant. Zárate. S.M. and Valle Cepero, R. Current Status of the Melcor Nodalization for Atucha I Nuclear Power Plant Zárate. S.M. and Valle Cepero, R. presentado en USNRC Cooperative Severe Accident Research Program (CSARP), Maryland, EE. UU.,

More information

Module 03 Pressurized Water Reactors (PWR) Generation 3+

Module 03 Pressurized Water Reactors (PWR) Generation 3+ Module 03 Pressurized Water Reactors (PWR) Generation 3+ Status 1.10.2013 Prof.Dr. Böck Vienna University of Technology Atominstitute Stadionallee 2 A-1020 Vienna, Austria ph: ++43-1-58801 141368 boeck@ati.ac.at

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

Flight Systems. Replacement for KASSEC DESCRIPTION

Flight Systems.   Replacement for KASSEC DESCRIPTION DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most

More information

Power Conversion System for ESS 100 kw to 30 MW Bi-directional Inverters

Power Conversion System for ESS 100 kw to 30 MW Bi-directional Inverters Power Conversion System for ESS 100 kw to 30 MW Bi-directional Inverters Energy Storage Solutions Power Conversion Systems With more than 125 years experience in power engineering and over a decade of

More information

CPS2000 Cabinet Power System

CPS2000 Cabinet Power System Input (Nominal): 90 Vac to 264 Vac (Autoranging) Output (Nominal): -48 Vdc (up to 28.8 A) and Optional 50 VA Ringing Generator The low-maintenance, outside-plant CPS2000 (Cabinet Power System) integrates

More information

GENCORE 5 FUEL CELL SYSTEM System Fundamentals

GENCORE 5 FUEL CELL SYSTEM System Fundamentals GENCORE 5 FUEL CELL SYSTEM System Fundamentals GenCore 5T48 GenCore 5B48 GenCore 5U48 GenCore 5T24 GenCore 5U120 Revision 1 December 1, 2004 GENCORE DESCRIPTION GenCore fuel cell systems are direct hydrogen

More information

W Datasheet: UPS AVARA Modular kVA (1-8 x 15kvA)

W Datasheet: UPS AVARA Modular kVA (1-8 x 15kvA) W Datasheet: UPS AVARA Modular 15-120kVA (1-8 x 15kvA) ONLINE Modular Service 1st start DATACENTER E-MEDICAL USMGC W SCHRACK-INFO The AVARA Modular UPS is a scalable three-phase/ three-phase uninterruptible

More information

Module 03 Pressurized Water Reactors (PWR) Generation 3+

Module 03 Pressurized Water Reactors (PWR) Generation 3+ Module 03 Pressurized Water Reactors (PWR) Generation 3+ 1.3.2017 Prof.Dr. Böck Technical University Vienna Atominstitut Stadionallee 2, 1020 Vienna, Austria ph: ++43-1-58801 141368 boeck@ati.ac.at Flow

More information

OPAL Engineering Early Modifications Relating to AOC: Loss of Offsite Power (LOOP)

OPAL Engineering Early Modifications Relating to AOC: Loss of Offsite Power (LOOP) OPAL Engineering Early Modifications Relating to AOC: Loss of Offsite Power (LOOP) Paul Metcalf and Chris Humphrey OPAL Engineering and Maintenance September 2010 IGORR 2010: KNOXVILLE TN SEPTEMBER 19-23

More information

Versatile and Powerful. Liduro Wind Frequency Converter System

Versatile and Powerful. Liduro Wind Frequency Converter System Versatile and Powerful Liduro Wind LCW300-series The liquid-cooled Liduro Wind frequency converter systems from Liebherr have been specially developed for reliable operation in onshore and offshore wind

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Smart-UPS VT APC Smart-UPS VT 30kVA 208V w/4 Batt. Modules, Start-Up 5X8, Internal Maintenance Bypass

Smart-UPS VT APC Smart-UPS VT 30kVA 208V w/4 Batt. Modules, Start-Up 5X8, Internal Maintenance Bypass Smart-UPS VT APC Smart-UPS VT 30kVA 208V w/4 Batt. Modules, Start-Up 5X8, Internal Maintenance Bypass APC Smart-UPS VT, 24 kw / 30 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9

More information

A. General Specifications. B. Dimensional Layout. BTU International Specification: Model 150Nz12 Reflow Solder System Date: 11/05/09 Page: 1/6

A. General Specifications. B. Dimensional Layout. BTU International Specification: Model 150Nz12 Reflow Solder System Date: 11/05/09 Page: 1/6 Page: 1/6 A. General Specifications Maximum temperature rating (all zones): 350 C Nominal operating temperature: 80-350 C Number of controlled heated zones: 12 Top 12 Bottom Oven atmosphere: Air/N 2 Working

More information

April 23, U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC

April 23, U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC Cwnsunme, EIneIUY A CMS Energy Compan}y Daniel J. Malone foireotor, Ffgineeung April 23, 2001 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 DOCKET 50-255 - LICENSE

More information

Features and Benefits

Features and Benefits Symmetra PX 250/500 Scalable from 25 kw to 500 kw, Parallel-capable up to 2,000 kw Modular, Scalable, Ultra-high Efficiency Power Protection for Data Centers High-performance, right-sized, modular, hot-scalable,

More information

Uninterruptible Power Supplies

Uninterruptible Power Supplies SDU Series, Direct Current Uninterruptible Power Supply (DC UPS) System The SDU DIN Rail DC UPS is an advanced uninterruptible power system that combines an industry leading design with a wide operational

More information

ABB central inverters ULTRA-750/1100/ kW to 1560kW

ABB central inverters ULTRA-750/1100/ kW to 1560kW Solar inverters ABB central inverters ULTRA-750/1100/1500 750kW to 1560kW * ABB s utility-scale ULTRA inverters combine high efficiency with a wide input voltage range and multiple maximum power point

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems.

LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems. LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems. LDX-U20 monitors the voltage supplied by a DC source and in case of power failure a backup battery is connected

More information

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER I. REFERENCE: 1 30 [1] Snow Engineering Co. Drawing 80504 Sheet 21, Hydraulic Schematic [2] Snow Engineering Co. Drawing 60445, Sheet 21 Control Logic Flow Chart [3] Snow Engineering Co. Drawing 80577,

More information

Pressurized Air Cooled Generators

Pressurized Air Cooled Generators PGI Orlando Dec. 13, 2016 Pressurized Air Cooled Generators Mike Zborovsky New App Generator Portfolio Owner siemens.com Pressurized Air-Cooled Generator (SGenX-2000P) Table of content Introduction 3 Portfolio

More information

Balanced Stator Seal for Reactor Coolant Pump Retrofits

Balanced Stator Seal for Reactor Coolant Pump Retrofits Balanced Stator Seal for Reactor Coolant Pump Retrofits Sulzer Pumps Sulzer Pumps is a leading global supplier of reliable products and innovative pumping solutions for end users. Our active research and

More information

The 3 kw Models will accept 200*/230 VAC single phase and 200*/208 VAC three phase input power.

The 3 kw Models will accept 200*/230 VAC single phase and 200*/208 VAC three phase input power. Sorensen DLM 3 & 4 kw Series DC Power Supply High Power Density : 3 kw and 4 kw models, 2U (3½ high), (19 wide); no top or bottom clearance spacing required Preview Push-button : Overvoltage protection

More information

UK ABWR Generic Design Assessment. Generic PCSR Chapter 15 : Electrical Power Supplies

UK ABWR Generic Design Assessment. Generic PCSR Chapter 15 : Electrical Power Supplies Form10/00 Document ID Document Number Revision Number : : : GA91-9101-0101-15000 XE-GD-0648 C Generic Design Assessment Generic PCSR Chapter 15 : Electrical Power Supplies Hitachi-GE Nuclear Energy, Ltd.

More information

Submersible Vacuum Fault Interrupters

Submersible Vacuum Fault Interrupters Submersible Vacuum Fault Interrupters UG Distribution Medium Voltage Vacuum Fault Interrupters Functional Specification Guide PS024002EN Functional Specification for 2.4kV to 17.5kV UG Distribution Medium

More information

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids Static frequency converter couples US paper mill s 2-Hz and 0-Hz electricity grids Before 0 Hz was adopted as the standard frequency for electricity distribution in the USA, power companies across the

More information

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC User s Manual K01-C000304-02 2 TABLE OF CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS..4 2 INSTALLATION....5 2-1 Unpacking...5

More information

HIGH POWER RECTIFIER SYSTEMS

HIGH POWER RECTIFIER SYSTEMS HIGH POWER RECTIFIER SYSTEMS STATE OF THE ART DESIGN AND ENGINEERING Dynapower Company is the world s largest independent manufacturer of High Power Rectifier Systems. We design, manufacture and test integrated

More information

Three-phase UPS system DPA UPScale ST kw The modular UPS designed for lowand medium-power applications

Three-phase UPS system DPA UPScale ST kw The modular UPS designed for lowand medium-power applications Three-phase UPS system DPA UPScale ST 10 200 kw The modular UPS designed for lowand medium-power applications DPA UPScale ST always protecting your critical applications Up to 10 modules in parallel per

More information

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal

More information

UPS. MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES

UPS. MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES UPS MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to 10000 THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES Modular UPS redundant and upgradable up to 10k with perfomance and functions

More information

SERIES Pulse and 12 Pulse DC Power Supplies for Electrocoating and Industrial DC Powered Systems MODELS 506 & 5012

SERIES Pulse and 12 Pulse DC Power Supplies for Electrocoating and Industrial DC Powered Systems MODELS 506 & 5012 100V to 1000V DC 100A to 5000A DC SERIES 50 MODELS 506 & 5012 6 Pulse and 12 Pulse DC Power Supplies for Electrocoating and Industrial DC Powered Systems Applications: Electrocoating Ion Nitriding Magnet

More information

1 Phase electronic contactor (SC 1)

1 Phase electronic contactor (SC 1) 1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or

More information

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 SECTION 1. 600V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 Soft Starters SECTION 2. LIQUID COOLED VFD I 3 Liquid Cooled

More information

TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT

TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT Page 1 (7) TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT Title Document Asynchronous electric motors TBE 103 Issue 6 (E) Contents 1 GENERAL... 2 2 DEFINITIONS... 2 3 GENERAL PRODUCT REQUIREMENTS... 3

More information