Demand Factor-Diversity Factor-Utilization Factor-Load Factor

Size: px
Start display at page:

Download "Demand Factor-Diversity Factor-Utilization Factor-Load Factor"

Transcription

1 Demand Factor-Diversity Factor-Utilization Factor-Load Factor (1) Demand factor Demand Factor = Maximum demand of a system / Total connected load on the system Demand factor is always less than one. Example: if a residence having 6000W equipment connected has a maximum demand of 300W,Than demand factor = 6000W / 3300W = 55%. The lower the demand factor, the less system capacity required to serve the connected load. Feeder-circuit conductors should have an ampere sufficient to carry the load; the ampere of the feeder-circuit need not always be equal to the total of all loads on all branchcircuits connected to it. Remember that the demand factor permits a feeder-circuit ampere to be less than 100% of the sum of all branch-circuit loads connected to the feeder. Example: One Machine Shop has Fluorescent fixtures=1 No, 5kw each, Receptacle outlets =1 No, 1500w each. Lathe=1No, 10 Hp, Air Compressor=1 No, 20 Hp, Fire Pump=1 No, 15 Hp. After questioning the customer about the various loads, the information is further deciphered as follows: 1. The shop lights are on only during the hours of 8 a.m. to 5 p.m. 2. The receptacle outlets are in the office only, and will have computers and other small loads plugged into them. 3. The lathe is fully loaded for 5 minutes periods. The rest of the time is setup time. This procedure repeats every 15 minutes. 4. The air compressor supplies air to air tools and cycles off and on about half the time. 5. The fire pump only runs for 30 minutes when tested which is once a month after hours. Calculation: Lighting Demand Factor = Demand Interval Factor x Diversity Factor. = (15 minute run time/ 15 minutes) x 1.0 = 1.0 Lighting Demand Load = 5 kw x 1.0 = 5 kw Receptacle Outlet Demand Factor = Demand Interval Factor x Diversity Factor = (15 minute run time / 15 minutes) x 0.1 = 0.1 Receptacle Outlet Demand Load = 15 x 1500 watts x 0.1 = 2.25 kw Lathe Demand Factor = Demand Interval Factor x Diversity Factor. = (5 minute run time / 15 minutes) x 1.0 =0.33 Lathe Demand Load = 10 hp x.746 x.33 = 2.46 kw Air Compressor Demand Factor = Demand Interval Factor x Diversity Factor. = (7.5 minute run time / 15 minutes) x 1.0 = 0.5 Air Compressor Demand Load = 20 hp x.746 x.5 = 7.46 kw Fire Pump Demand Factor = Demand Interval Factor x Diversity Factor.

2 = (15 minute run time/ 15 minutes) x 0.0 = 0.0 Fire Pump Demand Load = 15 hp x.746 x 0.0 = 0.0 kw Summary of Demand Loads : Equipment kw D.F. Demand KW Lighting Receptacle Outlets Lathe Air Compressor Fire Pump TOTAL Kw Kw (2) Diversity factor / simultaneity factor (Ks) Diversity Factor = Sum of Individual Max. Demand. / Max. Demand on Power Station. Diversity Factor = Installed load. / Running load. Diversity factor is usually more than one. (Since the sum of individual max. demands >Max. Demand) The load is time dependent as well as being dependent upon equipment characteristics. The diversity factor recognizes that the whole load does not equal the sum of its parts due to this time Interdependence (i.e. diverseness). When the maximum demand of a supply is being assessed it is not sufficient to simply add together the ratings of all electrical equipment that could be connected to that supply. If this is done, a figure somewhat higher than the true maximum demand will be produced. This is because it is unlikely that all the electrical equipment on a supply will be used simultaneously. The concept of being able to De-rate a potential maximum load to an actual maximum demand is known as the application of a diversity factor. 70% diversity means that the device in question operates at its nominal or maximum load level 70% of the time that it is connected and turned on. If total installed full load ampere is twice your running load ampere then the diversity factor is two. If total installed full load ampere is four times your load a ampere then the diversity factor is four. If everything (all electrical equipment) was running at full load at the same time the diversity factor is equal to One Greater the diversity factor, lesser is the cost of generation of power. Diversity factor in a distribution network is the ratio of the sum of the peak demands of the individual customers to the peak demand of the network. This will be determined by the type of service, i.e., residential, commercial, industrial and combinations of such. Example-I: A distribution feeder serves 5 houses, each of which has a peak demand of 5 KW. The feeder peak turns out to be 20 kw. The diversity is then 20/25 or 0.8. This results from the timing differences between the individual heating/cooling, appliance usages in the individual customers. As supply availability decreases, the diversity factor will tend to increase toward This can be demonstrated when restoring service after outages (called cold starts ) as the system initial surge can be much greater than the historical peak loads.

3 Example-II: A sub-station has three outgoing feeders: 1. feeder 1 has maximum demand 10 MW at 10:00 am, 2. feeder 2 has maximum demand 12 MW at 7:00 pm and 3. feeder 3 has maximum demand 15 MW at 9:00 pm, 4. While the maximum demand of all three feeders is 33 MW at 8:00 pm. Here, the sum of the maximum demand of the individual sub-systems (feeders) is = 37 MW, while the system maximum demand is 33 MW. The diversity factor is 37/33 = The diversity factor is usually greater than 1; its value also can be 1 which indicates the maximum demand of the individual sub-system occurs simultaneously. Diversity is the relationship between the rated full loads of the equipment downstream of a connection point, and the rated load of the connection point. To illustrate: 1. The building at these co-ordinates is fitted with a 100A main supply fuse. 2. The distribution board has 2no. 6A breakers, 1no. 20A breaker and 5no. 32A breakers, a total, potentially, of 192A. Not all these rated loads are turned on at once. If they were, then the 100A supply fuse would rupture, as it cannot pass 192A. So the diversity factor of the distribution board can be said to be 192A/100A, or 1.92, or 52%. Many designers prefer to use unity as the diversity factor in calculations for planning conservatism because of plant load growth uncertainties. Local experience can justify using a diversity factor larger than unity, and smaller service entrance conductors and transformer requirements chosen accordingly. The diversity factor for all other installations will be different, and would be based upon a local evaluation of the loads to be applied at different moments in time. Assuming it to be 1.0 may, on some occasions, result in a supply feeder and equipment rating that is rather larger than the local installation warrants, and an over-investment in cable and equipment to handle the rated load current. It is better to evaluate the pattern of usage of the loads and calculate an acceptable diversity factor for each particular case. In the case of the example given above, achieving a diversity of 1.0 or 100% would require well over twice the cross-sectional area of copper cable to be installed in a deep trench underneath a field, the rebuild of a feeder cabinet to larger dimensions, more substantial overhead supply cables for a distance exceeding 2km northwards and a different tariff, where one pays rather more for a kwh than at present. The investment required to achieve 1.0 simply isn t justifiable in this particular case. Diversity factor is mostly used for distribution feeder size and transformer as well as to determine the maximum peak load and diversity factor is always based on knowing the process. You have to understand what will be on or off at a given time for different buildings and this will size the feeder. Note for typical buildings diversity factor is always one. You have to estimate or have a data records to create 24 hours load graph and you can determine the maximum demand load for node then you can easily determine the feeder and transformer size. The diversity factor of a feeder would be the sum of the maximum demands of the individual consumers divided by the maximum demand of the feeder. In the same manner, it is possible to compute the diversity factor on a substation, a transmission line or a whole utility system. The residential load has the highest diversity factor. Industrial loads have low diversity factors usually of 1.4, street light practically unity and other loads vary between these limits.

4 Diversity Factor in distribution Network Diversity Factors Elements of System General Large Residential Commercial Power Industrial Between individual users Between transformers Between feeders Between substations From users to transformers From users to feeder From users to substation From users to generating station Diversity Factor for distribution switchboards Number of circuits Diversity Factor (ks) Assemblies entirely tested 2 and and to and more 0.6 Assemblies partially tested in every case choose 1 Diversity Factor for according to circuit function (IEC 60439) Circuits Function Diversity Factor (ks) Lighting 0.9 Heating and air conditioning 0.8 Socket-outlets 0.7 Lifts and catering hoist For the most powerful motor 1 For the second most powerful motor 0.75 For all motors 0.8 Diversity Factor for an apartment block Apartment Diversity Factor (ks) 2 To 4 1 5To To To To To To To To To Above 0.40

5 Example: 5 storey apartment building with 25 consumers, each having 6 kva of installed load. The total installed load for the building is: = 150 kva The apparent-power supply required for the building is: 150 x 0.46 = 69 kva It is a matter of common experience that the simultaneous operation of all installed loads of a given installation never occurs in practice, i.e. there is always some degree of diversity and this fact is taken into account for estimating purposes by the use of a simultaneity factor / Diversity Factor (ks). The Diversity factor ks is applied to each group of loads (e.g. being supplied from a distribution or sub-distribution board). The determination of these factors is the responsibility of the designer, since it requires a detailed knowledge of the installation and the conditions in which the individual circuits are to be exploited. For this reason, it is not possible to give precise values for general application. Designing Size of Electrical Switchgear by use of Demand Factor and Diversity Factor: Diversity factors are used by utilities for distribution transformer sizing and load predictions. Demand factors are more conservative and are used by NEC for service and feeder sizing. Demand factors and diversity factors are used in design. For example, the sum of the connected loads supplied by a feeder is multiplied by the demand factor to determine the load for which the feeder must be sized. This load is termed the maximum demand of the feeder. The sum of the maximum demand loads for a number of sub feeders divided by the diversity factor for the sub feeders will give the maximum demand load to be supplied by the feeder from which the sub feeders are derived. Example-1: Suppose We have four individual feeder-circuits with connected loads of 250 kva, 200 kva, 150 kva and 400 kva and demand factors of 90%, 80%, 75% and 85% respectively.use a diversity factor of 1.5. Calculating demand for feeder-circuits o 250 kva x 90% = 225 kva o 200 kva x 80% = 160 kva o 150 kva x 75% = kva o 400 kva x 85% = 340 kva o kva o The sum of the individual demands is equal to kva. o If the main feeder-circuit were sized at unity diversity: kva = kva 1.00 = kva. o The main feeder-circuit would have to be supplied by an 850 kva transformer. o However, using the diversity factor of 1.5, the kva = kva 1.5 = 558 kva for the main feeder. o o For diversity factor of 1.5, a 600 kva transformer could be used. Example-2: A conveyor belt made up of six sections, each driven by a 2 kw motor. As material is transported along this belt, it is first carried by section 1, and then each section in succession until the final section is reached. In this simple example only one section of conveyor is carrying material at any point in time. Therefore five motors are only handling no-load mechanical losses (say.1 kw) keeping the belts moving whilst one motor is handling the load (say 1 kw). The demand presented by each motor when it is carrying its load is 1 kw, the sum of the demand loads is 6 kw but the maximum load presented by the system at any time is only 1.5 kw.

6 o Diversity factor =Sum of Individual Max. Demand / Max. Demand = 6 Kw / 1.5 Kw =4. o Demand Factor = Maximum demand / Total connected load = 1.5 Kw / 12 Kw = (3) Load factor Load Factor = Average load. /Maximum load during a given period. It can be calculated for a single day, for a month or for a year. Its value is always less than one. Because maximum demand is always more than avg. demand. It is used for determining the overall cost per unit generated. Higher the load factor, lesser will be the cost per unit. Load Factor = Load that a piece of equipment actually draws / Load it could draw (full load). Example: Motor of 20 hp drives a constant 15 hp load whenever it is on. The motor load factor is then 15/20 = 75%. Load factor is term that does not appear on your utility bill, but does affect electricity costs. Load factor indicates how efficiently the customer is using peak demand. Load Factor = ( energy (kwh per month) ) / ( peak demand (kw) x hours/month ) A high load factor means power usage is relatively constant. Low load factor shows that occasionally a high demand is set. To service that peak, capacity is sitting idle for long periods, thereby imposing higher costs on the system. Electrical rates are designed so that customers with high load factor are charged less overall per kwh. For Example Customer A High Load Factor 82% load factor = (3000 kwh per month x 100%) / 5 kw x 730 hours/month. Customer B Low Load Factor 41% load factor = (3000 kwh per month x 100%) / 10kW x 730 hours/month. To encourage the efficient use of installed capacity, electricity rates are structured so the price per kwh above a certain load factor is lower. The actual structure of the price blocks varies by rate. (4) Utilization factor (Ku) In normal operating conditions the power consumption of a load is sometimes less than that indicated as its nominal power rating, a fairly common occurrence that justifies the application of an utilization factor (ku) in the estimation of realistic values. Utilization Factor = The time that a equipment is in use./ The total time that it could be in use. Example: The motor may only be used for eight hours a day, 50 weeks a year. The hours of operation would then be 2000 hours, and the motor Utilization factor for a base of 8760 hours per year would be 2000/8760 = 22.83%. With a base of 2000 hours per year, the motor Utilization factor would be 100%. The bottom line is that the use factor is applied to get the correct number of hours that the motor is in use. This factor must be applied to each individual load, with particular attention to electric motors, which are very rarely operated at full load. In an industrial installation this factor may be estimated on an average at 0.75 for motors. For incandescent-lighting loads, the factor always equals 1.

7 For socket-outlet circuits, the factors depend entirely on the type of appliances being supplied from the sockets concerned. Maximum demand Maximum demand (often referred to as MD) is the largest current normally carried by circuits, switches and protective devices. It does not include the levels of current flowing under overload or short circuit conditions. Assessment of maximum demand is sometimes straightforward. For example, the maximum demand of a 240 V single-phase 8 kw shower heater can be calculated by dividing the power (8 kw) by the voltage (240 V) to give a current of 33.3 A. This calculation assumes a power factor of unity, which is a reasonable assumption for such a purely resistive load. There are times, however, when assessment of maximum demand is less obvious. For example, if a ring circuit feeds fifteen 13 A sockets, the maximum demand clearly should not be 15 x 13 = 195 A, if only because the circuit protection will not be rated at more than 32 A. Some 13 A sockets may feed table lamps with 60 W lamps fitted, whilst others may feed 3 kw washing machines; others again may not be loaded at all. Lighting circuits pose a special problem when determining MD. Each lamp-holder must be assumed to carry the current required by the connected load, subject to a minimum loading of 100 W per lamp holder (a demand of 0.42 A per lamp holder at 240 V). Discharge lamps are particularly difficult to assess, and current cannot be calculated simply by dividing lamp power by supply voltage. The reasons for this are: 1. Control gear losses result in additional current, 2. the power factor is usually less than unity so current is greater, and 3. Chokes and other control gear usually distort the waveform of the current so that it contains harmonics which are additional to the fundamental supply current. So long as the power factor of a discharge lighting circuit is not less than 0.85, the current demand for the circuit can be calculated from: current (A) = (lamp power (W) x 1.8) / supply voltage (V) For example, the steady state current demand of a 240 V circuit supplying ten 65 W fluorescent lamps would be: I = 10X65X1.8A / 240 = 4.88A Switches for circuits feeding discharge lamps must be rated at twice the current they are required to carry, unless they have been specially constructed to withstand the severe arcing resulting from the switching of such inductive and capacitive loads. (5) Coincidence factor The coincidence factor =Max. demand of a system / sum of the individual maximum demands The coincidence factor is the reciprocal of the diversity factor Demand Factor & Load Factor according to Type of Industries Type of Industry Demand Factor Load Factor Utilization Factor (DF x LF) Arc Furnace Induction Furnace Steel Rolling mills

8 Mechanical/ Electrical a) Single Shift b) Double Shift Cycle Industry Wire products Auto Parts Forgings Cold Storage a) Working Season b) Non-Working Season Rice Sheller s a) Working Season b) Non-Working Season Ice Candy Units a) Working Season b) Non-Working Season Ice Factories a) Working Season b) Non-Working Season Cotton Ginning a) Working Season b) Non-Working Season Spinning Mills Textile Industry Dyeing and Printing Ghee Mills Oil Mills Solvent Extraction Mills Plastic Soap Rubber (Foot Wear) Distilleries Chemical Industry Gas Plant Industry Pain and Colour Factory Sugar Paper Flour Mills(Single Shift) Atta Chakies Milk Plants Printing Presses Repair Workshops Bottling Plants Radio Stations Telephone exchange Public Water Works Medical Colleges

9 Hospitals Nursing Homes Colleges and Schools Hotels and Restaurants Marriage Palaces Demand Factor & Load Factor according to Type of Buildings: dual Facilities Demand Load Factor Factor Communications buildings Telephone exchange building Air passenger terminal building Aircraft fire and rescue station Aircraft line operations building Academic instruction building Applied instruction building Chemistry and Toxicology Laboratory Materials Laboratory Physics Laboratory Electrical and electronics systems laboratory Cold storage warehouse General warehouse Controlled humidity warehouse Hazardous/flammable storehouse Disposal, salvage, scrap building Hospital Laboratory Dental Clinic Medical Clinic Administrative Office Single-family residential housing Detached garages Apartments Fire station Police station Bakery Laundry/dry cleaning plant K-6 schools schools Churches Post Office Retail store Bank Supermarket Restaurant

10 Auto repair shop Hobby shop, art/crafts Bowling alley Gymnasium Skating rink Indoor swimming pool Theater Library Golf clubhouse Museum

An Introduction to Electrical Power Requirements for Buildings

An Introduction to Electrical Power Requirements for Buildings An Introduction to Electric Power Requirements for Buildings Course# EE910 EZ-pdh.com 301 Mission Dr. Unit 571 New Smyrna Beach, FL 32128 386-882-EZCE(3923) helpdesk@ezpdh.com 1 P a g e Table of Contents

More information

TECHNICAL TERMS AND ABBREVIATIONS

TECHNICAL TERMS AND ABBREVIATIONS THIRD REVISED SHEET NO. 3.1 CANCELS SECOND REVISED SHEET NO. 3.1 TECHNICAL TERMS AND ABBREVIATIONS ALTERNATING CURRENT (A-C): AMPERE: BASE RATES: BRITISH THERMAL UNIT (BTU): CAPACITOR or CAPACITANCE: CAPACITY

More information

Working Principle of Power Saver as per Manufacture:

Working Principle of Power Saver as per Manufacture: Analysis the Truth behind Household Power Savers Introduction: A House hold power saving devices has recently received a lot of attention from both consumers and manufacturers. It is generally used in

More information

Transmission & Distribution Glossary of Electrical Terms

Transmission & Distribution Glossary of Electrical Terms Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The

More information

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith University of California, San Diego Cal (IT) 2 Technical Assignment #2 Brian Smith Advisor: Dr. Moeck 31 October 2005 Brian Smith Lighting/Electrical Option University of California, San Diego Cal (IT)

More information

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC. MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC. CALMANUAL HOW TO APPLY CAPACITORS TO LOW VOLTAGE POWER SYSTEMS. SECTION INDEX SECTION I POWER FACTOR UNDERSTANDING POWER FACTOR...

More information

Electrical Power Electric power electrical electric power Electric power electric electric

Electrical Power Electric power electrical electric power Electric power electric electric Power Calculations Electrical Power Electric power is the rate at which electrical energy is transferred by an electric circuit. The SI unit of power is the watt, one joule per second. Electric power is

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric

More information

Customer and Utility Energy Management Fundamentals 101

Customer and Utility Energy Management Fundamentals 101 Customer and Utility Energy Management Fundamentals 101 Minneapolis October 24 th 2016 Today s Show Brought to you by: Danny Zagotta Barry Mosser Thank you very much, Janet Booker What s your Energy Management

More information

Standard retail electricity supply

Standard retail electricity supply Standard retail electricity supply Schedule of charges from 1 July 2011 Schedule of charges for standard retail electricity supply The following charges have been approved by the Independent Competition

More information

STANDARD FOR OFF-STREET PARKING AND SERVICE FACILITIES

STANDARD FOR OFF-STREET PARKING AND SERVICE FACILITIES STANDARD FOR OFF-STREET PARKING AND SERVICE FACILITIES Page Sec. 101 Scope 2 Sec. 102 General standards for parking space design 2 Sec. 103 Number of parking spaces required 3 Sec. 104 Number of loading

More information

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code... TABLE OF CONTENTS About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... 1 CHAPTER 1 ELECTRICAL THEORY... 7 Unit 1 Electrician s Math and Basic Electrical Formulas...

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE 201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.

More information

Methodology of Cost Allocation

Methodology of Cost Allocation Methodology of Cost Allocation Robin Kliethermes May 17, 2013 1 Purpose of Cost Allocation Determine whether each class of customers is providing the utility with a reasonable level of revenue necessary

More information

DRAFT Commission, based upon the requirements of comparable uses listed.

DRAFT Commission, based upon the requirements of comparable uses listed. Chapter 345 OFF-STREET PARKING AND LOADING 345.01 Purpose 345.02 General Provisions 345.03 Off-Street Parking Standards 345.04 Off-Street Loading Standards Commission, based upon the requirements of comparable

More information

Chapter 3.1: Electrical System

Chapter 3.1: Electrical System Part-I: Objective type Questions and Answers Chapter 3.1: Electrical System 1. The heat input required for generating one kilo watt-hour of electrical output is called as. a) Efficiency b) Heat Rate c)

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49 UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1 PART A ELECTRICIAN S MATH...1 Introduction...1 1.1 Whole Numbers...1 1.2 Decimal...1 1.3 Fractions...1 1.4 Percentages...2 1.5

More information

National Grid. Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES. 2 nd Amended Compliance Filing

National Grid. Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES. 2 nd Amended Compliance Filing National Grid Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES 2 nd Amended Compliance Filing Attachment 1: Book 2 of 2 April 2010 Submitted to: Rhode Island

More information

ACTEWAGL DISTRIBUTION SCHEDULE OF ELECTRICITY NETWORK CHARGES

ACTEWAGL DISTRIBUTION SCHEDULE OF ELECTRICITY NETWORK CHARGES ACTEWAGL DISTRIBUTION SCHEDULE OF ELECTRICITY NETWORK CHARGES. The following charges will apply from 1 July 2016. Accounts issued on or after this date will be charged on a pro-rata basis. The charges

More information

INCREASE YOUR POWER FACTOR Manufactured By XZERES Corp.

INCREASE YOUR POWER FACTOR Manufactured By XZERES Corp. M A D E I N T H E U S A INCREASE YOUR POWER FACTOR Manufactured By XZERES Corp. Endelos family of Power Efficiency products are designed to improve the power factor and reduce the amount of reactive power

More information

PHEV Design Impacts. Jason Taylor Ph.D. South West Electric Distribution Exchange May 6 th, 2010

PHEV Design Impacts. Jason Taylor Ph.D. South West Electric Distribution Exchange May 6 th, 2010 PHEV Design Impacts Jason Taylor Ph.D. South West Electric Distribution Exchange May 6 th, 2010 1 Annual Energy Usage Electrical Appliances Home Heating System Central Air Conditioning Refrigerator/Freezer

More information

ARTICLE 7 OFF-STREET PARKING AND LOADING/UNLOADING 7.02 OFF STREET PARKING AND LOADING SPACE REQUIREMENTS

ARTICLE 7 OFF-STREET PARKING AND LOADING/UNLOADING 7.02 OFF STREET PARKING AND LOADING SPACE REQUIREMENTS ARTICLE 7 OFF-STREET PARKING AND LOADING/UNLOADING 7.01 STORAGE IN FRONT YARD Nothing in this Ordinance shall permit the storage or parking of any vehicle or non-permanent structure within the required

More information

TABLE 1 - PERMITTED USES RESIDENTIAL USES

TABLE 1 - PERMITTED USES RESIDENTIAL USES TABLE 1 - PERMITTED USES RESIDENTIAL USES Specific Use R SER R-2 R-4 R-6 R-8 MFR-12 RMH SO LB GB AB M-1 M-2 OS Building Accessory C Garage Private Home Occupation C C C C C C C C Mobile Home Mobile Home

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

UPPCO SERVICE MANUAL

UPPCO SERVICE MANUAL Revised 01/2015 Section 6 ELECTRIC SERVICE - GENERAL Page 1 of 10 Section 6 Electric Service - General 6-1 Number of Services and Voltages / Meter... 2 6-2 Energy Conversion Factors... 7 6-3 Lightning

More information

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN APPLICATION The KNK capacitors are used for power - factor correction of inductive consumers (transformers, electric motors, rectifiers) in industrial networks for voltages of up to 660 V. DESIGN Cylindrical

More information

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey

More information

Electric Drive Vehicle Infrastructure Training. Instructor s Manual. National Alternative Fuels Training Consortium

Electric Drive Vehicle Infrastructure Training. Instructor s Manual. National Alternative Fuels Training Consortium Electric Drive Vehicle Infrastructure Training Instructor s Manual National Alternative Fuels Training Consortium Part 4: : Service Panel to Receptacle Overview of Service Panel The role of the service

More information

DIVISION 400 OFF-STREET PARKING AND LOADING

DIVISION 400 OFF-STREET PARKING AND LOADING Page 238 of 268 DIVISION 400 OFF-STREET PARKING AND LOADING INDEX Section 401 Provision of Off-Street Parking 402 Off-Street Parking for New and Existing Buildings, Structures and Uses 403 Voluntary Establishment

More information

Power Factor Correction

Power Factor Correction AE9-1249 R10 August 2008 Power Factor Correction Index Page 1. Introduction... 1 2. Electrical Fundamentals... 1 3. Electrical Formulas... 2 4. Apparent Power and Actual Power... 2 5. Effects of Poor Power

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 TABLE OF CONTENTS Introduction...xv About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 Unit 1 Electrician s Math and Basic Electrical Formulas... 1 Part A Electrician s Math...

More information

GLX. Series. 1kW to 16kW Central System

GLX. Series. 1kW to 16kW Central System GLX Series 1kW to 16kW Central System GLX Series Sine Wave RATINGS TABLE Size Input Current @120V Output Current @120V Input Current @277 Output Current @277 Output Watts Battery (DC) Voltage 1kW 16 8

More information

Rate Schedules. Effective 1/1/2019

Rate Schedules. Effective 1/1/2019 Rate Schedules 2019 Effective 1/1/2019 SUMMARY OF RATE SCHEDULES REVISIONS FOR RATES EFFECTIVE JANUARY 1, 2019 (1) Rate component changes for Residential and Heating Service rate schedules. (2) General

More information

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA 94596 (925) 943-5834 phone (925) 256-3500 fax Issued September 30, 2017 Policy Bulletin No. PB-72 Background Residential

More information

6.16 OFF-STREET PARKING AND LOADING REQUIREMENTS

6.16 OFF-STREET PARKING AND LOADING REQUIREMENTS 6.16 OFF-STREET PARKING AND LOADING REQUIREMENTS 6.16.1 Off-Street Parking Off-street parking and loading spaces shall be required for all land uses as set forth in this section. A. Minimum Parking Space

More information

Application of Primary Fuses

Application of Primary Fuses Application of Primary Fuses Introduction The wide variety of fuse links offered by the A.B. Chance Company is instrumental in reducing the many problems facing today s coordination engineers. Besides

More information

4.10 Off-Street Parking Regulations.

4.10 Off-Street Parking Regulations. 4.10. A. Parking for Buildings, Structures or Uses. All new development, Building additions or conversions of use for which an Improvement Location Permit is required by this Ordinance shall provide required

More information

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions Installation Contactors Z-SCH These switching devices have been designed and rated particularly for modular installation in modular distribution boxes for electrical installation or cabinets with device

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( ) CHAPTER 1 ElECTRiCAl THEoRY... 1 UniT 1 electrician s MaTH and BasiC electrical formulas... 3 Introduction to Unit 1... 3 Part A Electrician s Math... 3 Introduction... 3 1.1 Whole Numbers... 3 1.2 Decimals...

More information

CITY OF BOWLING GREEN, OHIO MUNICIPAL UTILITIES ELECTRIC RATE SCHEDULES

CITY OF BOWLING GREEN, OHIO MUNICIPAL UTILITIES ELECTRIC RATE SCHEDULES MUNICIPAL UTILITIES S BOARD OF PUBLIC UTILITIES WILLIAM CULBERTSON MIKE FROST JOYCE KEPKE JOHN MEKUS MEGAN NEWLOVE MAYOR RICHARD A. EDWARDS MUNICIPAL ADMINISTRATOR JOHN S. FAWCETT UTILITIES DIRECTOR BRIAN

More information

Parking and Loading. Page 1 of 7

Parking and Loading. Page 1 of 7 Parking and Loading 21.03.020 Off-street parking and loading. A. Purpose. The purpose of this section is to ensure that sufficient off-street parking and loading areas are provided and properly designed

More information

BASIC ELECTRICAL MEASUREMENTS By David Navone

BASIC ELECTRICAL MEASUREMENTS By David Navone BASIC ELECTRICAL MEASUREMENTS By David Navone Just about every component designed to operate in an automobile was designed to run on a nominal 12 volts. When this voltage, V, is applied across a resistance,

More information

EV Charging Station Submittal Requirements

EV Charging Station Submittal Requirements EV Charging Station Submittal Requirements To obtain a permit for an Electric Vehicle Charging Station, please provide the following: Plan and details of the charging system installation o Print applicable

More information

DEWALT Electrical Licensing Exam Guide CONTENTS

DEWALT Electrical Licensing Exam Guide CONTENTS DEWALT Electrical Licensing Exam Guide v ONTENTS How to Prepare for the Exam................................................ 2 How to Study.............................................................

More information

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 A. GENERAL 1. The character of service available at any particular location must be ascertained by the Company business office, and will depend upon the

More information

Panola-Harrison Electric Cooperative, Inc. Louisiana Tariff Effective: March 3, 2004

Panola-Harrison Electric Cooperative, Inc. Louisiana Tariff Effective: March 3, 2004 Rate Schedule: R Page 1 of 1 RESIDENTIAL RATE SCHEDULE R Available in all territory served by the Cooperative, in accordance with the established rules and regulations of the Cooperative. Residential uses

More information

Chapter 1 Electrical Theory...1

Chapter 1 Electrical Theory...1 Electrical Formulas with Sample Calculations Table of Contents Chapter 1 Electrical Theory...1 Unit 1 Electrician s Math and Basic Electrical Formulas...3 Part A Electrician s Math...3 1 1 Fractions...3

More information

Customers with solar PV units in NSW producing and consuming electricity

Customers with solar PV units in NSW producing and consuming electricity Independent Pricing and Regulatory Tribunal FACT SHEET Customers with solar PV units in NSW producing and consuming electricity Based on Solar feed-in tariffs - Setting a fair and reasonable value for

More information

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2 WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 DESCRIPTION OF SERVICE A. General: RULE NO. 2 1. Alternating current service at 60-hertz (cycles per second)

More information

Schedule of Electrical Permit Fees. Contractor

Schedule of Electrical Permit Fees. Contractor Schedule of Electrical Permit Fees Contractor Effective: August 1, 2018 Issued By: Manitoba Hydro Customer Metering & Electrical Codes c2018-05-02 Available in accessible formats upon request Table of

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

The FREEDM System: components, main functions, system control

The FREEDM System: components, main functions, system control Short course on the FREEDM System Session L3 The FREEDM System: components, main functions, system control Dr. I. Husain, North Carolina State University Dr. G. T. Heydt, Arizona State University October,

More information

Power Quality Luis Vargas Research Engineer 9/18/2008

Power Quality Luis Vargas Research Engineer 9/18/2008 Page: 1 of 5 Luis Vargas Research Engineer 9/18/2008 Page: 2 of 5 As we make advances on green technology, we get a better understanding of the efficiencies and deficiencies on how we consume electricity.

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

More Complex Circuit

More Complex Circuit Series and Parallel Circuits Circuits usually include three components. One is a source of voltage difference that can be provided by a battery or an electrical outlet. Another is one or more devices that

More information

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1 Introduction... x About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... xviii About the Author...xxi About the Graphic Illustrator...xxii Mike Holt Enterprises Team...

More information

Paramount HRC Cartridge

Paramount HRC Cartridge Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

Building (Stat Class) Description Codes

Building (Stat Class) Description Codes Building (Stat Class) Description Codes 107 NON-LIVING UNIT OF RESIDENTIAL VARIETY 110 CLASS 1 SINGLE FAMILY HOME 112 CLASS 1 CONDO OR TOWNHOUSE 113 CLASS 1 PREFAB OR MODULAR 120 CLASS 2 SINGLE FAMILY

More information

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

CITY OF BOWLING GREEN, OHIO MUNICIPAL UTILITIES ELECTRIC RATE SCHEDULES

CITY OF BOWLING GREEN, OHIO MUNICIPAL UTILITIES ELECTRIC RATE SCHEDULES MUNICIPAL UTILITIES S BOARD OF PUBLIC UTILITIES AMY CRAFT-AHRENS WILLIAM CULBERTSON MIKE FROST MEGAN NEWLOVE MATT PAQUETTE MAYOR RICHARD EDWARDS MUNICIPAL ADMINISTRATOR LORI TRETTER UTILITIES DIRECTOR

More information

Power Quality and Energy Management

Power Quality and Energy Management Power Quality and Energy Management 1 2 Contents Power Quality...2 Power Factor Correction...4 Voltage Optimisation...8 Harmonic Filters and Reactors...12 1 Captech is Power Investigation and identification

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission

More information

N.H.P.U.C. No ELECTRICITY GRANITE STATE ELECTRIC COMPANY DBA LIBERTY UTILITIES. SUPERSEDING N.H.P.U.C. No. 17 TEMPORARY RATES

N.H.P.U.C. No ELECTRICITY GRANITE STATE ELECTRIC COMPANY DBA LIBERTY UTILITIES. SUPERSEDING N.H.P.U.C. No. 17 TEMPORARY RATES Revised Title Page Superseding Original Title Page GRANITE STATE ELECTRIC COMPANY DBA SUPERSEDING N.H.P.U.C. No. 17 TEMPORARY RATES TARIFF for RETAIL DELIVERY SERVICE Applicable in Twenty-three towns in

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Technical Series, Edition 16

Technical Series, Edition 16 Totally Integrated Power Technical Series, Edition 16 Transformer Selection according to Utilisation Profiles siemens.com/tip-cs 1. Regulations concerning efficiency requirements of dry-type transformers

More information

BUILDING PERMIT FEES BUILDING VALUATION DATA

BUILDING PERMIT FEES BUILDING VALUATION DATA BUILDING PERMIT FEES BUILDING VALUATION DATA The unit costs are intended to comply with the definition of "valuation" in Section 223 of the 1997 Uniform Building Code and thus include architectural, structural,

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Permitting, Installation and Inspection Residential EV Chargers Be aware that there are different types of Electric Vehicle (EV) Chargers.

Permitting, Installation and Inspection Residential EV Chargers Be aware that there are different types of Electric Vehicle (EV) Chargers. Be aware that there are different types of Electric Vehicle (EV) Chargers. There are 2 basic types of EV chargers for home use (Level 1 and Level 2). Level 1 Chargers are smaller units that plug directly

More information

APUA TARIFFS ELECTRICITY TARIFFS

APUA TARIFFS ELECTRICITY TARIFFS APUA TARIFFS ELECTRICITY TARIFFS General Purposes Tariff (G.P.T.): Applicable to general lighting of all premises and temporary supplies: o All units @.45 cents per unit o Minimum Charge: $15.00 per month

More information

51A USES. 2/2/2018 Page 1

51A USES. 2/2/2018 Page 1 51A USES Subarea A Subarea B Subarea C Subarea D Agricultural uses Current Proposed Current Proposed Current Proposed Current Proposed Animal Production Commercial Stable Crop production private stable

More information

TARIFFS AND ECONOMIC CONSIDERATIONS

TARIFFS AND ECONOMIC CONSIDERATIONS CONTENTS C H A P T E R50 Learning Objectives Economic Motive Depreciation Indian Currency Factors Influencing Cost and Tariffs of Electric Supply Demand Average Demand Maximum Demand Demand Factor Diversity

More information

CHAPTER 3. Basic Considerations and Distribution System Layout

CHAPTER 3. Basic Considerations and Distribution System Layout CHAPTER 3 Basic Considerations and Distribution System Layout Utility Load Classifications The electrical power distribution system is that portion of the electrical system that connects the individual

More information

Chapter 4 Utility Systems Electrical

Chapter 4 Utility Systems Electrical Chapter 4 Utility Systems Electrical Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

Power factor correction: a guide for the plant engineer

Power factor correction: a guide for the plant engineer Supersedes April 2008 Power factor correction: banks and passive harmonic filters Contents Description Page Description Page Part one: power factor What is power factor?.... 2 Should I be concerned about

More information

STL. Series. Emergency Lighting Inverter 3kW to 160kW Central System

STL. Series. Emergency Lighting Inverter 3kW to 160kW Central System STL Series Emergency Lighting Inverter 3kW to 160kW Central System STL Series Sine Wave APPLICATIONS: The STL Series Inverter will operate incandescent, fluorescent, HID and LED lamps. *Depending on the

More information

ARTICLE 24. OFF-STREET PARKING AND LOADING REQUIREMENTS

ARTICLE 24. OFF-STREET PARKING AND LOADING REQUIREMENTS ARTICLE 24. OFF-STREET PARKING AND LOADING REQUIREMENTS 1. APPLICABILITY : A. C-1 Exempt: Off-street parking and loading space, as required in this article, shall be provided for all new buildings or additions

More information

Tariff cover sheets reflecting all rates approved for April 1 in Dockets 4218 (ISR) and 4226 (Reconciliation Filing).

Tariff cover sheets reflecting all rates approved for April 1 in Dockets 4218 (ISR) and 4226 (Reconciliation Filing). Thomas R. Teehan Senior Counsel April 4, 2011 VIA HAND DELIVERY & ELECTRONIC MAIL Luly E. Massaro, Commission Clerk Rhode Island Public Utilities Commission 89 Jefferson Boulevard Warwick, RI 02888 RE:

More information

ELECTRIC WATER SEWER STORMWATER 3 Industrial Loop Drive PO Box 1589 Hannibal, MO (573)

ELECTRIC WATER SEWER STORMWATER 3 Industrial Loop Drive PO Box 1589 Hannibal, MO (573) ELECTRIC WATER SEWER STORMWATER 3 Industrial Loop Drive PO Box 1589 Hannibal, MO 63401 (573)-221-8050 www.hannibalbpw.org GENERAL PROVISIONS ELECTRIC SERVICE SCHEDULE Effective with usage beginning July

More information

City of Perris Development Services Building & Safety

City of Perris Development Services Building & Safety Western Riverside County Code Uniformity Program City of Perris Development Services Building & Safety Residential Electric Vehicle (EV) Charger Guidelines PHONE NUMBER 951-943-5003 Inspection Request

More information

ACTEWAGL DISTRIBUTION SCHEDULE OF ELECTRICITY NETWORK CHARGES

ACTEWAGL DISTRIBUTION SCHEDULE OF ELECTRICITY NETWORK CHARGES ACTEWAGL DISTRIBUTION SCHEDULE OF ELECTRICITY NETWORK CHARGES. The following charges will apply from 1 July 2017. Accounts issued on or after this date will be charged on a pro-rata basis. The charges

More information

COUNTY OF RIVERSIDE BUILDING AND SAFETY DEPARTMENT

COUNTY OF RIVERSIDE BUILDING AND SAFETY DEPARTMENT COUNTY OF RIVERSIDE BUILDING AND SAFETY DEPARTMENT RESIDENTIAL ELECTRIC VEHICLE (EV) CHARGER GUIDELINES Mike Lara Director The purpose of this guideline is to assist permit applicants in streamlining the

More information

Indoor electrical installation

Indoor electrical installation Indoor electrical installation Standard scheme of electrical installation TP CC MB LB LB LB SR TP transformation plant (electrical power in the grid system) 400 kv (national grid system) transformers 33

More information

IN THE MATTER OF the Ontario Energy Board Act, 1998, S.O. 1998, c.15, Schedule B;

IN THE MATTER OF the Ontario Energy Board Act, 1998, S.O. 1998, c.15, Schedule B; Ontario Energy Board Commission de l énergie de l Ontario IN THE MATTER OF the Ontario Energy Board Act, 1998, S.O. 1998, c.15, Schedule B; AND IN THE MATTER OF an Application by Thunder Bay Hydro Electricity

More information

Flanders Electric Engineering Division

Flanders Electric Engineering Division Flanders Electric Engineering Division Welcomes You to an Overview of Reconditioned Switchgear Lou York Bill Oxby Reasons for Reconditioning Switchgear Cost Savings Reuse material Buswork Building/enclosure

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

ENMAX POWER CORPORATION ( EPC ) DISTRIBUTION TARIFF RATE SCHEDULE

ENMAX POWER CORPORATION ( EPC ) DISTRIBUTION TARIFF RATE SCHEDULE Page 2 of 22 ENMAX POWER CORPORATION ( EPC ) DISTRIBUTION TARIFF RATE SCHEDULE RATES IN EFFECT AS OF APRIL 1, 2018 Page 2 of 22 Page 3 of 22 EPC DISTRIBUTION TARIFF RATE SCHEDULE Rate Code Rate Description

More information

ELECTRICAL CONSISTENCY MEETING

ELECTRICAL CONSISTENCY MEETING ELECTRICAL CONSISTENCY MEETING Date: 10/14/2015 Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and economically viable to serve

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information