DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

Size: px
Start display at page:

Download "DIN Rail UPS Model: DIN-UPS Installation/Operation Manual"

Transcription

1 DIN Rail US odel: DIN-US 12-5 Installation/peration anual Table of Contents Section age Section age Quick Start 2 1) General Information 4 aterials rovided 4 ptional ccessories 4 2) Safety Information 4 ) Installation/Wiring 4 ) ounting 4 ) Wiring 5 1. Input 5 2. utput 5 C) Form C Contact 5 D) Temperature Compensation Sensor 6 4) Settings 6 ) attery Type/Charge Curve 6 ) Time Charge Current Limit/attery 7 Charge Level C) Time uffering/attery Run Time 8 D) System Setttings 8 5) peration 8 ) attery Start w/o resent 8 ush utton ) Status Indicator LD s 8 C) LVD 9 6) rotection 9 7) Specifications 1 8) Troubleshooting 11 9) Warranty DINUS125 S F hone:

2 Figure 1: Quick Start Quick Start Guide Ga Gb H F I J 1) 2) ) K D C a b c j1 j2 ) Input: Wire Input lock (lettered left to right) a) arth Ground b) Hot 2 V: no jumper installed across j1 & j2 Hot 115 V: wire jumper across j1 and j2 c) Neutral j1 & j2) Jumper these two inputs for 115 V operation See page 5 for details. ) attery utput: two terminals each for plus and minus. Utilize dual wiring when battery location is more than 15 feet from unit. See page 5 for details. C) attery Charge Current Limit: llows setting maximum current flow to battery during recharge cycle, use when low amp-hour batteries are applied to system to prevent overheating when recovering dead batteries. djustment range 2-1% of available charge current. (vailable charge current = unit output rating of 1 amps - load demand. Note: the unit has a load priority circuit, all produced power is made available to the load, remaining power is available for battery charging). See page 6 for details. ounting DIN DC USto DIN Rail D) attery Temperature Sensor (optional): lug in port (RJ-45). See page 6 for details. ) Communication odbus: contact factory for more information F) utput to Load, two terminals each for plus and minus, utilize dual wiring when load is more than 15 feet from unit. Note: the unit has a load priority circuit, all produced power is made available to the load, remaining power is available for battery charging. See page 5 for details. G) Form C Contacts: ctivate upon: a. power fail b. Low battery or poor battery condition See page 5 for details. H) System Settings: via plug-in jumper programing terminals located on top of the unit. a. Install jumper per illustration below (Table 1) to: i. Select fl oat voltage per attery Type and enable bsorption Charge (see page page 7 for details) ii. nable attery Test (Functional Setting) iii. Disable/nable Load riority (Functional Setting) See page 8 for details on functional settings. Removing DIN DC US from DIN Rail Insert screwdriver in slot of bottom tab and twist to extend bracket 2 hone:

3 I) Time uffering/attery Run Time Settings: dial in time interval of desired run time of battery without disconnect. a. 1-6 minutes or b. Set at zero for battery run until LVD 1.5 VDC (1.75 VC) See page 7 for details. J) attery Start w/o resent ush utton: a. If system shuts down due to loss of and battery, power push button will allow battery to reconnect and supply the load if sufficient battery voltage is present. K) Status Indicator LD s 1. Fail: perating on battery back-up power (LD n). LD extinguishes when is present. 2. Low battery, or poor battery condition. Charger utput Status and Fault ode Diagnosis: by blink code: Table 1: System Settings: attery Selection/bsorption Charge Note: voltages above are at 2 C with no battery temp. sensor connected. Charge Status link Code: ulk: 5 blink/second - Recovery bsorption: 2 blink/second - ulk Float: 1 blink/second Fault ode Diagnosis link Code: Reverse olarity: 1 blink, pause attery Not Connected: 2 blink, pause verload or Short Circuit: 4 blink, pause ad attery Wire Connection, or ad attery (internal impedance): 5 blink, pause ad Thermal Sensor: 7 blink, pause and diagnostic See page 8 for details. attery Type Selection Float Charge/ Jumper Insert osition bsorption Charge naable/ Jumper Insert osition pen Lead (Default) None 1. VDC os. 6 Sealed Lead Insert Jumper: os. 1 os. 1 os VDC Gel attery Insert Jumper: os. 2 os. 2 os VDC hone:

4 Table 2: System Settings: Functional Settings Function Setting attery Test N Insert Jumper: os os. 4 Insert jumper at position 4 to enable eriodic attery condition test process. (Fault reported by LD diagnosis blink code, see Table 6): attery wiring connection attery efficiency/sulfation (impedance tesst) Shorted Cell Jumper inserted into position 7 making all power from the unit available for battery charging by disabling the load priority output function. Under low battery charge condition, output voltage to load will be equal to that of the battery voltage, thus useful voltage to the load will not be available until the battery recovers to proper levels. Load riority Disable (akes full power available for charging) Insert Jumper: os os. 7 1) General Information This DIN rail mount DC US Combines all system power functions: power supply, battery charger, US circuitry and status monitoring in one compact unit that produces 12 volt, 5 amps allocated via dual outputs for load and battery: Load output: load priority distribution ensures power is dedicated fi rst to the load, with remainder then allocated to battery charging, thus preventing a discharged battery from impacting operation of critical loads. attery output: step charging for rapid battery recovery, programmable for battery type, with optional temperature compensation sensor attery automatically on line to support load anytime fails Low voltage disconnect protects battery from total discharge utomatic periodic battery health diagnosis High operating temperature range to 7 C larm contacts: fail, battery status/condition aterials rovided: 1 ea. DIN-US unit with integral DIN rail mount clip 4 ea. Jumper tabs for programming 1 ea. Jumper wire (orange) for 115 volt input operation ptional quipment: Temperature Compensation Sensor, /N: ) Safety Information WRNING xplosion Hazard. Do not disconnect loads or battery unless input and battery have been switched off. WRNING xplosion Hazard. Substitution of components may impair suitability for class I, Division 2. WRNING Switch off or remove input and battery power before wiring the DIN-US Never work on the DIN US when it is connected to input and battery. The DIN US must be installed in accordance with UL58 or local electrical codes depending upon the application. The DIN US should have a suitability sized input circuit breaker feeding its input. See specification section for maximum input draw for your input voltage for circuit breaker sizing. CUTIN: Hot surface. void touching the DIN US case while operating at or near its full load capacity. Remove and battery power and allow DIN US at least 1 minutes to cool before removing from DIN Rail. ) Installation/Wiring ) ounting: The unit is designed for 5 mm DIN rail mounting in an enclosure and relies on convection (free air) cooling, thus must have a minimum vertical and horizontal distance to adjacent surface of 4 (1 cm) to this power supply in order to assure suffi cient air flow. Note, that depending on the ambient temperature and load of the device, the temperature of the case can become hot to the touch. The unit is designed for vertical mount (+/- 5 ) and has an integral clip on the back to secure it to the rail. To mount, place the top tabs over the top of the DIN rail, and using a long slotted screw driver insert it in the groove at the bottom of the bracket and twist which will extend the spring loaded mounting bracket downward allowing the unit to be positioned against the DIN rail, release the bracket with DIN US positioned vertically and the rail will be captured and the unit secured. 4 hone:

5 6 6 Figure 2: ounting Figure : Removing SLCTIN LW R TI UFFRING Insert screwdriver in slot of bottom tab and twist to extend bracket ) Wiring 1. Input: Terminal lock (lettered left to right) - Figure 4 a) arth Ground b) Hot (note: install jumper provided across terminals j1 and j2 for 115 V input) c) Neutral j1 & j2) Jumper these two terminals for 115 V operation and apply 115V hot to term b and neutral to c Recommended wire size: 16 WG Insert screwdriver in LW R slot of bottom tab and twist to extend bracket STRT i DIGNSIS IN TTR Figure 4: Input Terminal lock CHRGING DIN-US 12-5 INUT: 115-2Vac UTUT: 12Vdc 5 INUT L N JUR FR 2. utput The unit has dual output circuits: one for connection to the Load, the other to the back-up battery. Note: the unit has a load priority circuit, all produced power first is made available to the load with remaining power made available for battery charging. oth outputs are isolated from the case. a b c j1 j2 range Jumper Wire (provided) attery utput: two sets of terminals each for plus and minus. Utilize dual wiring when battery location is more than 15 feet from unit to minimize voltage drop. See page 2 and, Section H for programming per battery type. utput to Load: two terminals each for plus and minus, utilize dual wiring when load is more than 15 feet from unit to minimize voltage drop. Fuse note: We recommend a 5 amp fuse be installed on the hot leg at battery. If using both sets of battery terminals on DIN US (i.e. two pairs of wires, recommended for long wire runs), connect both hot wires to one side of battery fuse. attery/utput wires size (recommended): 1 WG Terminal lock maximum wire size (recommended): 1 WG C) larm Contacts, Form C (Isolated): Form C Contacts for remote monitor: ctivate upon: a. power fail b. Low battery, or poor battery condition SLCTIN TI UFFRING STRT DIN-US 12-5 INUT: 115-2Vac UTUT: 12Vdc 5 Figure 5: utput Terminals Load utput i LW R LW R DIGNSIS attery utput IN X CHRGING LVL (1) (2) UTUT LD INUT JUR FR TTRY L N () (4) T R C D U S U X (714) techservice@newmarpower.com C US 5 hone:

6 6 6 6 Table 2: larm Contacts Contact Input Fail LD The sensor will vary the battery charging voltage depending on the battery s temperature and charge program setting. Table : bsorption Charge Voltage & Float Charge Voltage Settings 2 Fault attery* LD Diagnosis LD Figure 6: larm Contacts Terminals, Form C (Isolated) only closed open open closed off on 2 link-ause att closed open closed open off off 1 link/sec SLCTIN att only open closed closed open on off off LW Low att open closed open closed on on off R 9 1 * Labeled Low attery or attery Replacement on Front anel SLCTIN Relay Contact Rating: Figure 7 & TI 1: Status Indicator LDs UFFRING ax. DC: VDC, 1 amp; : 6 V, 1 amp: Resistive load (N ) LW R in.1m at 5 VDC LW 1 R T D) ptional attery Temperature Compensation Sensor /N: TI UFFRING To install, remove the access tab in the front panel decal labeled STRT i DIGNSIS R LW IN X Temp robe, install the Temp. Sensor into the RJ-45 connector. ttach 2 R sensor to side of battery using RTV silicone. CHRGING LVL DIN-US STRT 12-5 INUT: 115-2Vac UTUT: 12Vdc 5 DIN-US 12-5 INUT: UTUT: INUT 115-2Vac JUR FR 12Vdc 5 Figure 8: attery Temperature Sensor ccess LTab N i DIGNSIS IN X CHRGING LVL T U R SLCTIN ccess Tab INUT L LW R N JUR FR (1) (2) UTUT LD 6 Formula for determining temperature compensated Float or bsorption voltage based on battery temperature: Float Formula: Float Voltage = (1. * VDC ) (sensor temp. 2 C) (.18 VDC) * see Table 1 for Float voltage based on battery type selected TI UFFRING xample Conditions attery selection jumper installed for 1.4 VDC Sealed Lead Float voltage attery temperature = 6 C INUT Float voltage = (1.4 VDC) (6 C 2 C) (.18 VDC) = (1.4 VDC) (4 C x.18 VDC) = 1.4 VDC.72 VDC = VDC 6 C JUR FR TTRY L N () (4) If the battery temperature is less than -2 C or greater than +6 C, an outside its range (temp. sensor) alarm is signalled with code 7 blink. If the sensor is not connected or if the sensor is defective, the LD Low att will illuminate and the LD Diagnosis LD continues to show the status of the battery, i.e., trickle charge, fast charge or recovery charge. STRT DIN-US 12-5 INUT: 115-2Vac UTUT: 12Vdc 5 i LW R DIGNSIS IN X CHRGING LVL T R C D U S U X (714) techservice@newmarpower.com C US hone:

7 6 4) Settings Figure 9: attery Type ) attery Type/Charge Curve Charge curve per battery type: via programing jumpers on top panel of unit left side. Insert jumper tabs for battery selection Using programming jumper tabs provided and a small needle nose pliers, insert programming jumpers to select float voltage and enable absorption voltage per per battery type. Caution do not program unit while connected to power. SLCTIN LW R R Table 4: attery Selection/bsorption Charge TI UFFRING F attery Type Selection pen Lead (Default) Float Charge/ Jumper Insert osition bsorption Charge naable/ Jumper Insert osition None os. 6 STRT i L R R DI Sealed Lead Insert Jumper: os VDC os. 1 os. 6 DIN-US 12-5 INUT: 115-2Vac UTUT: 12Vdc 5 Gel attery Insert Jumper: os VDC os. 2 os. 6 INUT L N JUR FR 1.7 VDC ) attery Charge Current Limit/attery Charge Level llows setting maximum current fl ow to battery during recharge cycle- use when low amp-hour batteries are applied to system to prevent overheating when recovering dead batteries. djustment range 2-1% of available charge current. (vailable charge current = unit output rating of 1 amps minus load demand. Note: the unit has a load priority circuit, all produced power is made available to the load, remaining power is available for battery charging). To set, use small slotted screw driver to rotate selector dial. Set dial between 1 to 2% of battery capacity (mp Hours). Figure 1: Current Limit/attery Charge Level - Dial 7 hone:

8 6 C) Time uffering/attery Run Time This function determines how long the reserve battery will power the system in the event of failure. You may choose a specifi ed time or run until the LVD activates. Settings: dial in time interval of desired run time of battery without disconnect. Using small screw driver to set the dial arrow to the desired setting: a. 1-6 minutes or b. Set at zero for battery run until LVD 1.5 VDC (1.75 VC) Figure 11: Time uffering/attery Run Time - Dial D) System Settings Via plug-in jumper programing terminals located on top of the unit. Install jumper per illustration below to: ii. nable attery Test iii. Disable/nable Load riority Function Setting attery Test N Insert Jumper: os os. 4 Insert jumper at position 4 to enable eriodic attery condition test process. (Fault reported by LD diagnosis blink code, see Table 6): attery wiring connection attery efficiency/sulfation (impedance tesst) Shorted Cell Load riority Disable (akes full power available for charging) Insert Jumper: os os. 7 Jumper inserted into position 7 making all power from the unit available for battery charging by disabling the load priority output function. Under low battery charge condition, output voltage to load will be equal to that of the battery voltage, thus useful voltage to the load will not be available until the battery recovers to proper levels. 5) peration 8 ) attery Start without resent ush utton: If system shuts down due to loss of and battery power, pushing button will allow battery to come on line to supply the load. ress and hold for seconds to re-connect battery to output. Note, if LVD has activated and battery voltage has not recovered above disconnect point, the unit will not cycle on. ) Status Indicator LD s 1. ower source: ains or back up i. K ( Fail LD ff) or ii. perating on battery backup power ( Fail LD n) red 2. Low battery, or battery replacement LD illuminates when: Low attery (capacity less than %) ad connection to battery attery requires replacement diagnosis LD. Figure 12: attery Start LD Charger output status system diagnosis and Fault mode diagnosis: by blink code (Table 6 on next page) Figure SLCTIN1: Status Indicator LDs 1 2 TI UFFRING STRT DIN-US 12-5 INUT: 115-2Vac UTUT: 12Vdc 5 i LW R LW R DIGNSIS IN X CHRGING LVL T R INUT L JUR FRhone: N

9 Table 6: Status Indicator LDs onitoring Control State LD Diagnosis (No.8) LD attery Fault No.7) Float 1 link/sec FF Charging Type bsorption 2 link/sec FF ulk 5 link/sec FF Reverse polarity or 1 link/pause* N high battery Voltage attery Not connected, 2 link/pause N no output power attery shorted cell link/pause N ver Load or short 4 link/pause N circuit on the load ad battery; Internal 5 link/pause N impedance ad or ad battery wire connection attery Life test not 6 link/pause N possible Temp. Sensor outside 7 link/pause N System uto Diagnosis its range oost condition; battery 8 link/pause N discharge after 4 min. of overload. Internal fault 9 link/pause N Low battery detected 1 link/pause N when system activated by battery start button with no ac input Life test not possible; 12 link/pause arallel mode on Slave Device ad battery wire 1 link/pause connection; arallel mode on Slave Device * ause: 1 Second C) LVD) The unit contains a low voltage load disconnect that activates at 1.5 volts (1.75 vpc) which is factory set and cannot be user modified. (See also Section 4-C regarding operation with battery time out circuit) 6) rotection n the Input: the device is equipped with an internal fuse. If the internal fuse is blown, it is most probable that there is a fault in the unit. If this occurs, the unit must be returned to the factory. n the DC uput attery and Load: The device is electrically protected. Reverse polarity: the module is automatically protected against reverse of battery polarity and connection of reverse polarity. ver current and output short circuit: the unit limits the output current. Low voltage disconnect protects battery from deep discharge. 9 hone:

10 Thermal protection perating temperature range -12 to 7 C. Unit will produce full rated power on continuous basis to 5 C, however; system load must be reduced by 2.5% per 1 for continuous operation above 5 C. If the temperature reaches 7 C, the unit will reduce its maximum output to approximately 5% of its rating. If the temperature exceeds 7 C, the unit will shut off and restart once temperature drops. 7) Specifications Input: Voltage: 9-15/ hz mperage: 12 V / 2 V utput: 12 volts, 5 amps total available to power loads and charge battery, with load priority distribution. eak: 7 amps 4 seconds (with battery power boost) utput ground isolated from case, may be used in positive ground applications. LVD function is lost Front anel LD Indicators: ower Source: operating on back up red Fail LD attery and System Diagnostics (via blink code) Settings/Selectors: attery Type: G (Sealed Lead), Gel-Cell and pen Lead (Flooded Cell) attery Charge Current Limit: 2-1% of charge amperage rating ack-up Run Time on atteries: rogrammed time limit: 1-6 min. r Until LVD 1.5V ower Restore utton: connects battery without present larm Contacts (form C): ctive: Fail (on battery back-up) attery abnormal condition (summary contact): Discharged, damaged, disconnected, sulfated/short circuit, reverse polarity, bad thermal sensor perating Temperature: -12 to 7 C. Continuous to 5, de-rate 2.5% per C >5 C Cooling: Free air convection fficiency: 91% Humidity: to 95%, to 25 C rotection: Low Voltage disconnect at 1.75 volts per cell (1.5 VDC) Internal fuse Current limiting Short circuit Reverse polarity Thermal overload shut down and recovery I 2 Designed to UL 195 Terminal locks: Screw type ounting: DIN Rail racket 5 mm 1 hone:

11 8) Troubleshooting Symptom ossible Cause Corrective ction Section. attery requires excessive re-charge time. Load turns off after a couple of seconds when running on battery C. No absoprtion voltage D. Unit does not turn on 1.Load at or near max. recommended load providing minimal current available for charging 2.Charging level current set to low 1.Time buffer set to incorrect position 2.atteries not charged, due to high load demand 1.Reduce load or split load between two separate DIN US units 2.djust attery Charging Level control knob to higher level 1.Verify correct setting with manual 2.Reduce load or split load between two separate DIN US units 1. bsorption jumper not installed 1. Install provided jumper in position 6 1. input is 115 V, no jumper wire installed 1. Install 115V jumper wire across j1 and j2. Trips input breaker 1. shorted to case 1. Verify correct input wiring 2. Defective unit 2. Contact technical service F. No output G. No voltage on battery output terminals 1. DC output wired backwards or shorted 1. Remove input and check DC wiring 2. No input 2. Verify correct input and jumper wire installed if powering from 115 V. xcessive temperature or blocked ventilation. Improve ventilation, unblock vent holes 4. Defective unit 4. Contact technical service 1. No battery installed (voltage 1. Install batteries required for battery output to turn on) 2. issing or blown battery wiring fuse 2. Replace missing or blown battery wiring fuse H. Diagnosis LDs always blinking 1. Normal operation 1. Refer to Chart 2: Diagnosis Table 9) Warranty Newmar warrants that the DIN-US 12-5 DIN Rail US to be free from defects in material and workmanship for two years from date of purchase. If a problem with your DIN-US 12-5, or if you have any questions about the installation and proper operation of the unit, please contact NWR s Technical Services Department: hone: From the hours of 7: a.m. to 5: p.m. weekdays,.s.t.; -mail: techservice@newmarpower.com 11 hone:

DIN Rail UPS Model: DIN-UPS 48-5 Installation/Operation Manual

DIN Rail UPS Model: DIN-UPS 48-5 Installation/Operation Manual DI Rail US Model: DI-US 48-5 Installation/Operation Manual Table of Contents Section age Section age Quick Start 2 1) General Information 4 Materials rovided 4 Optional quipment 4 2) Safety Information

More information

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual DIN Rail UPS Model: DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided 4 Optional Equipment 4 2) Safety Information

More information

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS 24-10 Installation/Operation Manual Table of Contents Section Page Section Page Quick Start 2 1) General Information 4 Materials Provided

More information

DIN Rail DC UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

DIN Rail DC UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual DI ail DC US DC US/attery Detection System odel: DS-DI-US 2-0 Installation/peration anual able of Contents Section age Section age ) verview/quick Start 2-3 2) General Information 3 aterials rovided 4

More information

READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS!

READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS! RAD AD FLLW ALL SAFTY ISTRUCTIS! SAV THS ISTRUCTIS! IMRTAT SAFGUARDS RAD AD FLLW ALL SAFTY ISTRUCTIS. Do not use outdoors. Do not let power supply cords touch hot surfaces. Do not mount near gas or electric

More information

DIN-Rail DC UPS. Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications

DIN-Rail DC UPS. Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications DIN-Rail DC UPS Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications Combines all system power functions: power supply, battery charger, UPS circuitry

More information

Power Distribution System User s Manual. Model: PDS-100

Power Distribution System User s Manual. Model: PDS-100 Power Distribution System User s Manual Model: PDS-0 Section Page Product Overview... 1 I) General Information... 2 II) Important Safety Information... 2 III) Installation... 3 A) Materials Provided...

More information

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...

More information

LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101194 Document revision: D DCN number: 105128 Date: 3/23/2006 1840 Industrial Circle Longmont, CO 80501 Fax: 303-678-7504 Tel: 303-678-7500

More information

All In one uninterruptible power supply solutions

All In one uninterruptible power supply solutions All In one uninterruptible power supply solutions For the life of your systems with Battery Care concept Integrated Electronic Solution Yet another strong proposition from Adelsystem, result of the continuing

More information

User s Manual. Automatic Switch-Mode Battery Charger

User s Manual. Automatic Switch-Mode Battery Charger User s Manual Automatic Switch-Mode Battery Charger IMPORTANT Read, understand, and follow these safety rules and operating instructions before using this battery charger. Only authorized and trained service

More information

PUMP PLUS 1200 MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

PUMP PLUS 1200 MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL UM LUS 1200 AUTOMATIC SINGLE OUTUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-193-12 INUT: 120 Volt, 60 Hz, 10 Amps OUTUT: 40 Amps File: IM_091-193-12_revH.indd

More information

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger Document: PRODSPEC-140 Revision: G DCN No. 106512 Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger 1. GENERAL DESCRIPTION 1.1 General Description Fully regulated, constant voltage,

More information

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC User s Manual K01-C000304-02 2 TABLE OF CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS..4 2 INSTALLATION....5 2-1 Unpacking...5

More information

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. IMPORTANT SAFEGUARDS INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL When using

More information

PUMP PLUS 2000 PLC MODEL #: PP AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

PUMP PLUS 2000 PLC MODEL #: PP AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL PUMP PLUS 2000 PLC AUTOMATIC DUAL OUTPUT BATTERY CHARGER Supplied with Dual Bar Graph Display MODEL #: 091-237-12-PP INPUT: 120 Volt, 60 Hz, 3.5 Amps OUTPUT BATTERY 1 and 2: 15 or 18

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

CBI All in One DC UPS Power Solutions

CBI All in One DC UPS Power Solutions CBI All in One Power Solutions Everything and more! More efficiency of the battery thanks to continuous control over time. More monitoring in main connection nodes: input, output load, battery. Event logging:

More information

User Manual. Solar Charge Controller 3KW

User Manual. Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5

More information

PUMP PLUS 1000 PLC MODEL #: PP AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

PUMP PLUS 1000 PLC MODEL #: PP AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL PUMP PLUS 1000 PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-215-12-PP INPUT: 120 Volt, 60 Hz, 3.5 Amps OUTPUT BATTERY 1 and 2: 15

More information

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY SMT WITH MPPT TECHNOLOGY Installation and Operation Manual Model:SMT SMT Dimensions Specification Summary System Voltage 12 V/24V Rated Battery Current 12V, 5A 8A 10A 15A 20A 25A 24V, 5A 8A 10A 15A Rated

More information

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE LMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE LMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. IMPORTANT SAFEGUARDS INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL When using

More information

Pure Sine Wave Inverter Charger

Pure Sine Wave Inverter Charger Pure Sine Wave Inverter Charger Renogy 1000W 2000W Pure Sine Wave Inverter Charger Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.6 1 Important Safety Instructions Please save

More information

MDX-300 Series. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL

MDX-300 Series. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL Blank page Contents Caution... 4 Capabilities... 4 Display and Keypad... 4 Preparations Before the Test... 6 Connecting

More information

AUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

AUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL AUTO CHARGE 4000 LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER Unit supplied with this display MODEL #: 091-89-12 INPUT: 120 Volt, 50/60 Hz, 5 Amps OUTPUT: 45 Amps File:

More information

SAVE THESE INSTRUCTIONS

SAVE THESE INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFEGUARDS! When using electrical equipment, basic safety precautions should always be

More information

INSTRUCTION MANUAL CAUTION

INSTRUCTION MANUAL CAUTION FILE: IM_091-128-12E-40-115 Rev B., 2-16-2006 INSTRUCTION MANUAL AUTO CHARGE ODY q AUTOMATIC BATTERY CHARGER MODEL #091-128-12E-40-115 for ODYSSEY AGM BATTERIES CAUTION This charger is calibrated to the

More information

Instruction Manual. Duo-battery Solar Panel Controller EPIP20-DB series For Both 10 and 20 amp. Controllers (for use with solar panels only) + -

Instruction Manual. Duo-battery Solar Panel Controller EPIP20-DB series For Both 10 and 20 amp. Controllers (for use with solar panels only) + - Instruction Manual Duo-battery Solar Panel Controller EPIP20-DB series For Both 10 and 20 amp. Controllers (for use with solar panels only) + - Optional - Switch to disconnect solar panel when engine alternator

More information

User Manual Solar Charge Controller 3KW

User Manual Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...

More information

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:

More information

BBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER

BBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER BBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER Important The BBC -3140 must be used according to the local safety standards with the particular application. All wiring and connections

More information

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH 331-SV User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER Ashland, OH 800-363-5842 WWW.PRIMEXCONTROLS.COM Warranty void if panel is modified. Call factory with servicing

More information

Installation Instructions

Installation Instructions AQU244 & AQU128 Series Installation Instructions Installation Instructions AQU244 24vdc 5A Supervised Power Supply/Charger module AQU128 12vdc 10A Supervised Power Supply/Charger module Both Mounted in

More information

CX-SERIES ADVANCED BATTERY CHARGER

CX-SERIES ADVANCED BATTERY CHARGER CX-SERIES ADVANCED BATTERY CHARGER Table of Content 1. IMPORTANT SAFETY INFORMATION... 2 1-1 General Safety Precautions... 2 1-2 Battery Precautions... 2 2. FEATURES... 3 2-1 Battery Charging Curve...

More information

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

Match 19 GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19 UPS. Match 19" Uninterruptible Power Supply 700-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com

More information

HMW Filtered Fuse Panel for GMT Fuses

HMW Filtered Fuse Panel for GMT Fuses FUSE MP CIRCUIT FUSE MP 1 3 2 5 3 1 2 5 CIRCUIT L P R O D U C T S P E C I F I C T I O N November 8, 1999 HMW 06020 Filtered Fuse Panel for GMT Fuses -2 to DC 7-000015-H POWER POWER F F 1 5 10 15 20 1 5

More information

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL 1. INTRODUCTION VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down DC-DC Converter has a digitally adjustable output in 0.2V increments. This

More information

WITH TRAKSTAR TM MPPT TECHNOLOGY. Installation and Operation Manual MAXIMUM POWER POINT TRACKING. Model: SS-MPPT-15L

WITH TRAKSTAR TM MPPT TECHNOLOGY. Installation and Operation Manual MAXIMUM POWER POINT TRACKING. Model: SS-MPPT-15L SUNSAVER MPPT TM WITH TRAKSTAR TM MPPT TECHNOLOGY Installation and Operation Manual MAXIMUM POWER POINT TRACKING Model: SS-MPPT-15L 1098 Washington Crossing Road Washington Crossing, PA 18977 USA www.morningstarcorp.com

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

Intelligent Charging System Series

Intelligent Charging System Series R Intelligent Charging System Series OWNER S MANUAL ON BOARD BATTERY CHARGERS Models Amperage No. Of Banks Volts 16061 s 1 Bank 12 16102 6,s 2 Banks 12 or 24 16153 6,6,s 3 Banks 12 or 24 or 36 16202 10,10

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product

More information

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER INSTRUCTION MANUAL FILE: IM_091-120-XX-XX-(XXX)(XX)_revA.P65 REV: A REVISED BY: PSS DATE: 07-19-13 AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER R MODEL #091-120-XX-XX-(XXX)(XX) 3 YEAR WARRANTY 170 Cherry

More information

Liebert PowerSure PSI UPS

Liebert PowerSure PSI UPS Liebert UPS GUIDE SPECIFICATIONS 1000VA to 3000VA Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical and mechanical characteristics and

More information

EMIU 720W Mini Inverter

EMIU 720W Mini Inverter THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using

More information

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS

More information

Battery Management Innovation. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL

Battery Management Innovation. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL Battery Management Innovation For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL ! CAUTION Because of the possibility of personal injury, always use extreme caution

More information

IV. PROOF OF PURCHASE: A warranty claim must be accompanied by proof of the date of purchase.

IV. PROOF OF PURCHASE: A warranty claim must be accompanied by proof of the date of purchase. PD9100 / 9200 SERIES POWER CONVERTER OWNERS MANUAL PROGRESSIVE DYNAMICS, INC. POWER CONVERTER LIMITED WARRANTY I. LIMITED WARRANTY: Progressive Dynamics, Inc. warrants its power converter to be free from

More information

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality GE Digital Energy Power Quality User Manual Digital Energy Uninterruptible Power Supply ML Series UPS 350-500-700-1000 VA GE imagination at work GB User Manual Digital Energy Uninterruptible Power Supply

More information

AUTO CHARGE DUAL MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:

AUTO CHARGE DUAL MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax: INSTRUCTION MANUAL AUTO CHARGE DUAL AUTOMATIC DUAL OUTPUT BATTERY CHARGER MODEL #: 091-145-12 INPUT: 120 Volt, 50/60 Hz, 3.5 Amps OUTPUT BAT 1: 10 Amps OUTPUT BAT 2: 10 Amps File: IM_091-145-12_revb.indd

More information

AUTO CHARGE 12 HO MODEL #: MODEL #: MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

AUTO CHARGE 12 HO MODEL #: MODEL #: MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL AUTO CHARGE 12 HO AUTOMATIC SINGLE OUTPUT BATTERY CHARGER MODEL #: 091-170-6 MODEL #: 091-170-12 MODEL #: 091-170-24 File: IM_091-170-xx_revd.indd Rev: D Revised By: MFG Date: 10-23-2013

More information

BBT-205. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL

BBT-205. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL Blank page Contents Registering Your tester... 5 Caution... 6 Capabilities... 6 Display and Keypad... 6 Preparations

More information

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Special Specification 6058 Battery Back-Up System for Signal Cabinets Special Specification Battery Back-Up System for Signal Cabinets 1. DESCRIPTION 2. DEFINITIONS Install a Battery Back-Up System (BBU System) for traffic signals that will provide reliable emergency power

More information

The Power of Reliability INSTRUCTION MANUAL

The Power of Reliability INSTRUCTION MANUAL The Power of Reliability INSTRUCTION MANUAL SAFETY & WARNINGS Read this manual carefully and understand all Warnings and Cautions before connections are made to the Inverter. If unsure about any aspects

More information

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL E13 TEMPERATURE PROBE FAILURE E16 HIGH LIMIT 1 EXCEEDED A. TEMP Probe reading out of range. B. Bad Connection. C. Problem with the temperatur e measuring circuitry including the probe. High limit temperature

More information

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION! INSTALLATION INSTRUCTIONS FOR SYMCOM S MOTORSAVER MODEL 460 BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

More information

LPC 40 MODEL #: LOW PROFILE CHARGER WITH PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

LPC 40 MODEL #: LOW PROFILE CHARGER WITH PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL LPC 40 LOW PROFILE CHARGER WITH PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-200-12 INPUT: 120 Volt, 50/60 Hz, 5 Amps OUTPUT: 40

More information

CX Series User s Manual

CX Series User s Manual CX Series User s Manual Advanced Converter / Charger Legal Provisions Copyrights 2016 COTEK Electronic IND. CO. All Rights Reserved. Any part of this document may not be reproduced in any form for any

More information

Sola/Hevi-Duty S3K Series Mini-Tower UPS

Sola/Hevi-Duty S3K Series Mini-Tower UPS Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical

More information

A6Z OPERATING MANUAL

A6Z OPERATING MANUAL A6Z OPERATING MANUAL TABLE OF CONTENTS Introduction... p. 2 Features... p. 2 Description... p. 3 Theory of Operation... p. 3 Installation... p. 4 Electrical Connections... p. 5 Options... p. 6 Warranty.p.

More information

AC CONVERTER / BATTERY CHARGER

AC CONVERTER / BATTERY CHARGER AC CONVERTER / BATTERY CHARGER User s Manual MODEL #: CON120AC12/24VDC Listed to UL 458 and CSA 22.2 NO. 107.1 Standards Contents INTRODUCTION... 3 Important Safety Instructions... 3 1. General Description...

More information

MINE CHARGER INSTALLATION AND OPERATION MANUAL MODEL NUMBERS: MSP MSQ MSR MSS

MINE CHARGER INSTALLATION AND OPERATION MANUAL MODEL NUMBERS: MSP MSQ MSR MSS MINE CHARGER INSTALLATION AND OPERATION MANUAL MODEL NUMBERS: MSP MSQ MSR MSS Sec# Table of Contents Pg# 1 INSTALLATION 1.1 Receiving 1 1.2 Location 1 1.3 Line Voltage Adjustments 2 1.4 A.C. Service Requirements

More information

Unity Low Voltage Disconnect & Monitor

Unity Low Voltage Disconnect & Monitor Unity Low Voltage Disconnect & Monitor Installation/Operation Manual Model: ULM-100 Table of Contents Page Table of Contents Page 1.0 Overview 2 5.14 LVD Level Mapping 4 2.0 Materials Provided 2 5.2 Meter

More information

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries. 1 Elmdene International Ltd Tel: +44 (0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk STANDBY 220V AC POWER SYSTEM IDEAL

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual SEI 150/48-SEL-XXX DC-UPS SEI Incorporated 5115 Pegasus Court, Suite Q Frederick, Md 21704 Phone 301-694-9601 Fax 301-694-9608 Email Info@seipower.com Web http://www.seipower.com

More information

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work GE Digital Energy Power Quality User Manual Digital Energy Uninterruptible Power Supply ML Series UPS 350-500-700-1000 VA GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno)

More information

DCT SERIES CASE SIZE 3A FILTERED BATTERY CHARGER 12V/200A 24V/ A 48V/100A 120V/50A 240V/25A OPERATION & MAINTENANCE GUIDE

DCT SERIES CASE SIZE 3A FILTERED BATTERY CHARGER 12V/200A 24V/ A 48V/100A 120V/50A 240V/25A OPERATION & MAINTENANCE GUIDE DCT SERIES CASE SIZE 3A FILTERED BATTERY CHARGER 12V/200A 24V/150-200A 48V/100A 120V/50A 240V/25A OPERATION & MAINTENANCE GUIDE SENS part number: 101137-3 Document revision: B DCN number: 105286 Date:

More information

Installation Instructions

Installation Instructions Installation Instructions AQU243-8C1R -8F8R -8C8R 24VDC/3.3Amp Supervised (AC & Battery) Power Supply/Charger Module, 85-264vac, 14 x 9 x 3.5" Enclosure, UL294, UL603 & UL1481 Listed AQU243 with one PDB-8C1R

More information

LPC 20 MODEL #: LOW PROFILE CHARGER AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

LPC 20 MODEL #: LOW PROFILE CHARGER AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL INSTRUCTION MANUAL LPC 20 LOW PROFILE CHARGER AUTOMATIC SINGLE OUTPUT BATTERY CHARGER Unit supplied with one of these displays MODEL #: 091-207-12 INPUT: 120 Volt, 50/60 Hz, 7 Amps OUTPUT: 20 Amps File:

More information

UCS-CHR24V55W. Combined Power Supply & Battery Charger. Data Sheet

UCS-CHR24V55W. Combined Power Supply & Battery Charger. Data Sheet Combined Power Supply & Battery Charger Data Sheet INTRODUCTION UCS-CHR24V55W is a combined charger and power supply with dedicated outputs for both charging and power supply. With a large input range

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

SBC / 2140 / Stage Battery Charger User Manual

SBC / 2140 / Stage Battery Charger User Manual SBC - 2130 / 2140 / 2150 3 Stage Battery Charger User Manual Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation instructions for correct

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

Innovative Circuit Technology Ltd.

Innovative Circuit Technology Ltd. Innovative Circuit Technology Ltd. IntelliCharge Battery Charger Series INSTRUCTION MANUAL 855-342-000 Models: ICT24012-30BC2, ICT24012-30BC2M ICT24012-15BC2, ICT24012-15BC2M ICT24024-15BC2, ICT24024-15BC2M

More information

ST Charger. Industrial Battery Charger

ST Charger. Industrial Battery Charger ST Charger Industrial Battery Charger Installation and Operation Manual ST_13 Table of Contents Pg# 1.0 INSTALLATION 1 1.1 Receiving 1 1.2 Location 1 1.3 Line Voltage 1 1.4 A.C. Service Requirements 2

More information

Installation and Operation Back-UPS BX550CI-CN

Installation and Operation Back-UPS BX550CI-CN Installation and Operation Back-UPS BX550CI-CN Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or where there

More information

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

User Manual Back-UPS BX650CI-MS 230 Vac with AVR User Manual Back-UPS BX650CI-MS 230 Vac with AVR Overview Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. Read the Safety

More information

Phoenix Inverter

Phoenix Inverter Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC

More information

Service Manual. Extractor Model XR28QP. For The. For: Troubleshooting Adjustments

Service Manual. Extractor Model XR28QP. For The. For: Troubleshooting Adjustments Service Manual For The X Ride 28 Rider Extractor Model XR28QP For: Training Troubleshooting Adjustments Contents 1 Cautions ------------------------------------------------------------------------------

More information

Battery Care the new Battery Charger Philosophy Battery Charger and Battery Tester. Charge & Testing. Integrated Electronic Solutions

Battery Care the new Battery Charger Philosophy Battery Charger and Battery Tester. Charge & Testing. Integrated Electronic Solutions Battery Care the new Battery Charger Philosophy Battery Charger and Battery Tester Charge & Testing Integrated Electronic Solutions Connect Multimediality The new ADELSystem platform communication ADELBus

More information

Installation and Operation Manual Back-UPS BX1100CI-CN

Installation and Operation Manual Back-UPS BX1100CI-CN Installation and Operation Manual Back-UPS BX1100CI-CN Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or

More information

DIN Rail Power Module

DIN Rail Power Module 800 W ax 500 W ax 500 W ax 500 W ax i Temp 230 V~ 50 / 60 z 10 A www.lutron.com +44.(0)20.7702.0657 DIN Rail odule omeworksr QS Phase Adaptive Fixture Controller DIN Rail odule The DIN Rail odule family

More information

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System POWER TROLLEY 8 Model: SINE 1548 Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System Version 07 CONTENTS Page 1. INTRODUCTION... 1 2. USING THE POWER TROLLEY.... 2 3. BATTERY BACKUP

More information

AUTOMATIC BATTERY CHARGER

AUTOMATIC BATTERY CHARGER AUTOMATIC BATTERY CHARGER SAMLEX AMERICA. MODELS SEC - 1215A SEC - 1230A SEC - 2415A OWNER S MANUAL Please read this manual before operating your charger CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION

More information

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery

More information

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual DC AC POWER INVERTER LIV 10 / LIV 20 / LIV 30 User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the Power Inverter. This

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

PM Series Power Module Power Supply/Battery Charger

PM Series Power Module Power Supply/Battery Charger PM Series Power Module Power Supply/Battery harger INSTALLATION / OPERATION MANUAL MODELS: PM-24-80, PM-48-50 Table Of ontents Topic Page QUIK REFERENE ONTENTS 2 I) OVERVIEW 3 II) A POWER QUALITY AND EMI

More information

DC TO AC POWER INVERTER PWRIC150012W INSTRUCTION MANUAL

DC TO AC POWER INVERTER PWRIC150012W INSTRUCTION MANUAL DC TO AC POWER INVERTER PWRIC150012W INSTRUCTION MANUAL SAVE THIS MANUAL You will need the manual for the safety warnings and precautions, assembly instructions, operating and maintenance procedures, parts

More information

Manual Installation & Operation

Manual Installation & Operation Manual Installation & Operation Model: NCxxLxx 12A or 30A Solid State Solar Charging Regulator and 12A Load Controller. 231 Patent #: 5,642,030 Applies Page 1 Warnings When Installing, connect grounds,

More information

7 Stage Automatic Smart Battery Charger (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL

7 Stage Automatic Smart Battery Charger (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL 7 Stage Automatic Smart Battery Charger Desulphuration& Maintainer (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL THIS MANUAL CONTAINS IMPORTANT SAFETY AND OPERATING INSTRUCTIONS 1

More information

HPP1 MK5 Owner s Manual

HPP1 MK5 Owner s Manual J Wolmarans Page 1 2017/03/07 Page 1 of 10 TABLE OF CONTENTS Page 1 Introduction...2 2 Models...2 3 Safety warnings...3 4 Features...3 5 Contents...3 6 Installation...3 6.1 Mounting the unit:...3 6.2 Connecting

More information

BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL

BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL THIS MANUAL CONTAINS IMPORTANT SAFETY AND OPERATING INSTRUCTIONS 1 IMPORTANT

More information

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101037 Document revision: A Engineering change number: 105073 Date: 1/13/2006 1840 Industrial Circle

More information

CALTRAP INSTALLATION AND OPERATIONS MANUAL

CALTRAP INSTALLATION AND OPERATIONS MANUAL INSTALLATION AND OPERATIONS MANUAL NOTE Please read this entire installation and operations manual before energizing the. Safety Considerations: Installing and servicing capacitor equipment can be hazardous.

More information

ST - II Series POWER SUPPLIES USER INSTRUCTIONS

ST - II Series POWER SUPPLIES USER INSTRUCTIONS Introduction ST - II Series POWER SUPPLIES These instructions detail the installation and operation requirements for the ST20-II & ST35-II power supplies. These have been designed for operation in RV s

More information

AUTOMATIC BATTERY CHARGER MODELS SEC A SEC A OWNER S MANUAL

AUTOMATIC BATTERY CHARGER MODELS SEC A SEC A OWNER S MANUAL AUTOMATIC BATTERY CHARGER MODELS SEC - 1245A SEC - 2425A OWNER S MANUAL Please read this manual before operating your charger CONTENTS Important safety precautions...2 Description...3 Features...3 Components

More information

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version MD10 Engine Controller Installation and User Manual for the MD10 Engine Controller. Full Version File: MartinMD10rev1.4.doc May 16, 2002 2 READ MANUAL BEFORE INSTALLING UNIT Receipt of shipment and warranty

More information

Rover Series. Rover 20A 40A Maximum Power Point Tracking Solar Charge Controller

Rover Series. Rover 20A 40A Maximum Power Point Tracking Solar Charge Controller Rover Series Rover 20A 40A Maximum Power Point Tracking Solar Charge Controller 0 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.5 Important Safety Instructions Please save these

More information