for Southern Thailand Network Engineering Level 4 Control and Protection System Department Electricity Generating Authority of Thailand
|
|
- Juniper Crawford
- 5 years ago
- Views:
Transcription
1 Design and Implementation of RLS Scheme for Southern Thailand Network by Mr.Yossawin Bureetan Engineering Level 4 Control and Protection System Department Electricity Generating Authority of Thailand
2 Outline 1. Introduction 2. Previous Protection Scheme 3. Power System Analysis 4. Transient Stability Studies 5. Installation of the Protection Scheme 6. Post Event Analysis 7. Conclusion
3 Network Configuration of Southern Thailand - Network configuration before 2011 To PKK 500 kv 230 kv BSP2 BSP 115 kv Power Flow From Central Region CP RN LSN RPB SRT KN TP PK2 PK1 PN KA PP BDN NT TS PU LR HY1 STU Main Load RA SKL HY2 CHN KNE SDO YL2 PTN YL1 BLG NW SUK GURUN BST
4 Problem Solving Method - The previous RLS Scheme System Information To PKK 500 kv BSP2 230 kv BSP 115 kv Areva - Tie-Lines Power Flow - Generation in Southern system - HVDC Status TP PK2 RN SRT RPB PN PK1 LSN KA CP Trip Signal PP LR BDN TS KN PU STU NT Control Box RA SKL HY2 HY1 SDO GURUN KNE CHN YL2 BST HVDC Run Up/Back PTN YL1 BLG Load dshedding (81 Cases Table) NW SUK
5 Current Network Configuration BSP2 CP Changing in Southern Thailand To PKK Network after 2011 BSP Network configuretaion Load Increament RN LSN RPB SRT KN PK3 TP P PN2 N PK1 PK2 500 kv 230 kv 115 kv KA PP BDN NT TS PU RA LR SKL CHN HY HY1 2 PTN STU SDO KNE YL1 YL2 BLG GURUN BST NW SUK
6 Power System Analysis Condition for Steady State Study Load Condition is divided into 3 condition - Evening Peak Load - Day Peak Load - Light Load System Disturbance :Only large disturbance will be investigated, Ex. - CHN Power Plant Full Block Trip (700 MW) - CHN Power Plant Half Block Trip (350 MW) - KA Power Plant Trip - HVDC Trip while importing 300 MW - Central to Southern Tie-Line Trip 2 Circuits - Tie-Transformer 500/230 kv BSP2 Trip
7 Part of study Part 1 Part 2 Part 3 After the system disturbance, the System can remain stable without any protection Scheme response After the system disturbance, the system can remain stable with only the action of HVDC Run Up/Run Back After the system disturbance, the system can remain stable with HVDC Run Up/Run Back and Rapid Load Shedding
8 Studies Result from Part 1 Part 1 : Maximum Pre-condition Tie-Line Power Flow which, After the system disturbance, the System can remain stable without any protection Scheme response. HVDC (+300) CHN (700) KA (300) CHN (350) Tie Line (N-2) KN-CC Bus Evening Day Light
9 Studies Result from Part 2 Part 2 : Maximum Pre-condition Tie-Line Power Flow which, After the system disturbance, the system can remain stable with only the action of HVDC Run Up/Run Back CHN (700) KA (300) CHN (350) Evening Day Light
10 Load Shedding Point Selection The appropriate load shedding point are selected using V-P Characteristics. ti The slope of V-P Characteristic of each load points indicate the weakness of that load points at that condition. V V critical Stable Unstable P
11 Weak point in the system To PKK 500 kv BSP2 BSP 230 kv 115 kv CP Weak Load point PK3 TP PK2 RN SRT RPB P PN2N PK1 LSN Selected Load Shedding Point KN PP BDN NT TS KA LR PU RA STU SKL CHN HY HY1 2 PTN SDO KNE YL1 NW YL2 BLG SUK GURUN BST
12 Studies Result from Part 3 Part 3 : Amount of load shedding which, After the system disturbance, the system can remain stable with action of HVDC Run Up/Run Back and Load Shedding Tie Line Flow Load Shedding (MW) Light Day Evening
13 Transient Stability Studies In studies result from transient stability studies, 2-example cases are shown Case 1: CHN full block trip (700 MW) at tie-line flow 400 MW Case 2: CHN full block trip (700 MW) at tie-line flow 700 MW
14 Transient Stability Result : Case 1 Case 1 : CHN Full Block Trip ( 700 MW) : Tie-Line Flow 400 MW T = 1 s : Fault T 1.4 s : HVDC Run up T = 1.1 s : Clear Fault
15 Transient Stability Result : Case 2 Case 2 : CHN Full Block Trip ( 700 MW) : Tie-Line Flow 700 MW T = 1 s : Fault T 1.4 s : HVDC Run up T = 1.2 s : Shed HY2 = MW T = 1.1 s : Clear Fault
16 Special Protection Scheme Operation - The Scheme Operation to prevent system instability after large disturbance To PKK BSP2 BSP Tie-line Flow Areva RN SRT RPB TP PN PN2 PK3 PK1 PK2 KA LSN CP Trip Signal KN PP BDN TS LR PU STU NT Control Box HVDC Run Up/Back RA HY1 SKL HY2 SDO GURUN KNE Load (200 ms) If Tie-line Flow > 700 MW and CHN full block trip 500 ms Load CHN YL2 BST PTN YL1 BLG NW SUK Load2 Shedding 500 kv 230 kv 115 kv Load1 Shedding
17 Special Protection Scheme Operation
18 Special Protection Scheme Installation BSP2 To PKK BSP Tie-line Flow Areva 500 kv 230 kv 115 kv RN SRT RPB TP PN PN2 PK3 PK1 PK2 KA LSN CP Trip Signal KN PP BDN TS LR PU STU NT Control Box HVDC Run Up/Back RA HY1 SKL HY2 SDO GURUN KNE Load (200 ms) If Tie-line Flow > 700 MW and CHN full block trip CHN YL2 BST PTN 500 ms Load YL1 BLG NW NCC Monitor and Control Signal SUK Load1 Shedding Load2 Shedding
19 Challenge and Suggestion The delay of the construction cause delay of scheme installation. Number and location of the communication device have to be consider to minimize the scheme installation cost while remaining effective scheme operation. Changing of load point impact amount of load shedding when the scheme operate. In the scheme installation, the previous scheme was removed then the new scheme was installed. The function of scheme operation during that period had to be able to protect the system from black/brown out.
20 Example Event On 5 th March 2012 : Transmission Line 230 kv SKL2 HY2 KNE cct. 1 and 230 kv HY2 KNE cct. 2 trip while central to southern tie-line flow 442 MW from Central to Southern System and HVDC was importing power 30 MW from Gurun to KNE
21 Special Protection Scheme Operation The event occur in the evening Tie-Line Flow 442 MW RPB-H:232.5 KN-CC:645.6 KK-T :74.3 CHN Full Block 710 MW No KA HVDC Ex. 30 MW BLG-H:73.3
22 Special Protection Scheme Operation
23 Measurement Value from Post Event Ang(TPR)-Ang(KNE) degree Tie-Line Flow 763 MW SRT 1.00 PN 0.98 PN PK KA 0.98 TS 0.99 NT 0.98 No CHN HY PK PK KNE 1.00 HVDC Im. 245 MW
24 Study Result Ang(TPR)-Ang(KNE) degree Tie-Line Flow 929 MW SRT 0.98 PN 0.93 PN PK KA 0.95 TS 0.96 NT 0.97 No CHN HY PK PK KNE 1.00 HVDC Im. 245 MW
25 Actual Value Study Result
26 Actual Value Study Result
27 Conclusion In Southern Thailand Network, a special protection scheme was installed to prevent black out after large disturbance. When the scheme is trig, the scheme will send run up/back command to HVDC and load shedding command to load point simultaneously. After getting the shedding command, load at each will be shedded only when the voltage at that bus is low. Post event analysis show that the scheme can prevent the system black out when large disturbance occur. The load shedding, after the scheme action, can be avoided by controlling of the tie-line flow.
28 Thank you
Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection
Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba
More informationNew 115 kv Disconnect Switches at Bloomsburg MTS
115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115
More informationIntentional Islanding Operation to Improve the Service Reliability of Thailand Electric Power System
Intentional Islanding Operation to Improve the Service Reliability of Thailand Electric Power System Pradit Fuangfoo Wei-Jen Lee Energy Systems Research Center University of Texas at Arlington Arlington,
More informationCIGRE US National Committee 2013 Grid of the Future Symposium. Facilitating Bulk Wind Power Integration Using LCC HVDC
CIGRE US National Committee 2013 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC Introduction Many states in US need to meet their renewable energy mandate Wind energy
More informationLife Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic
Life Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic siemens.com/energy-management Motivation Challenge of reduced synchronous generators
More informationWide area monitoring and control activities in Norway and the Nordic power system
Working Group Meeting North American SynchroPhasor Initiative June 8-9, 2010, Vancouver, British Columbia Wide area monitoring and control activities in Norway and the Nordic power system Kjetil Uhlen,
More informationOperational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks
Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and
More informationShunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian
Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission
More informationCHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM
61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this
More informationCHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK
91 CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK CHAPTER CONTENTS: 5.1 INTRODUCTION 5.2 CONDUCTION OF VARIOUS POWER FLOW STUDIES ON THE MODEL 5.3 EXPERIMENTS CONDUCTED FOR VARIOUS POWER FLOW
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationTargeted Application of STATCOM Technology in the Distribution Zone
Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric
More informationREDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION
REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi
More informationTHE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS
THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive
More informationImpact of Islanding and Resynchroniza?on on Distribu?on Systems
1 Impact of Islanding and Resynchroniza?on on Distribu?on Systems Authors: Dr. Vijay Sood Damanjot Singh Kush Duggal 2 Contents Introduction System Description Rural Radial Distribution System Urban Meshed
More informationXXXX. Kokish River Hydroelectric Project. Interconnection System Impact Study
XXXX Kokish River Hydroelectric Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY,
More informationImpact of Distributed Energy Resources on Transmission System Reliability
S E P T E M B E R 1 3, 2 0 1 8 W E B I N A R Impact of Distributed Energy Resources on Transmission System Reliability National Council on Electricity Policy (NCEP) Alan McBride D I R E C T O R, T R A
More informationIntegration of Large Wind Farms into Electric Grids
Integration of Large Wind Farms into Electric Grids Dr Mohammad AlZoubi Introduction Development WHAT IS NEXT!! Over the next 12 years, Europe must build new power capacity equal to half the current total.
More informationBREAKER FAILURE PROTECTION
29 th Annual HANDS-ON RELAY SCHOOL March 12-16, 2012 BREAKER FAILURE PROTECTION Brent Carper, PE Protection & Integration Engineer brent.c@relayapplication.com OUTLINE Protection System Failures and Breaker
More informationFAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE
FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT
ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT By Girija Shankar Sharma, M.Tech (Power System), DGM (O&M-Opn), NTPC-Rihand, E-mail: gssharma@ntpc.co.in Presentation Points System Description and Grid
More informationXXXX. Knob Hill Wind Farm Project. Interconnection System Impact Study
XXXX Knob Hill Wind Farm Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY, LIMITATION
More informationCircuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63
Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10
More informationThank you for the detailed information regarding the Refurbishment Project at Marchwood MTS. This project will facilitate equipment maintainability.
November 30, 2007 Mr. Ed Donkersteeg Hydro Ottawa Ltd. 1970 Merivale Road Nepean Ontario K2G 6Y9 Dear Mr. Donkersteeg, Marchwood MTS Refurbishment Project Notification of Conditional Approval of Connection
More informationResearch on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC
Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,
More informationExperience on Technical Solutions for Grid Integration of Offshore Windfarms
Experience on Technical Solutions for Grid Integration of Offshore Windfarms Liangzhong Yao Programme Manager AREVA T&D Technology Centre 18 June 2007, DTI Conference Centre, London Agenda The 90MW Barrow
More informationTransmission Grid Reinforcement with Embedded VSC-HVDC. Jonatan Danielsson, Sugam Patel, Jiuping Pan, Reynaldo Nuqui
Transmission Grid Reinforcement with Embedded VSC-HVDC Jonatan Danielsson, Sugam Patel, Jiuping Pan, Reynaldo Nuqui Outline Introduction HVDC-Light Transmission Technologies Embedded VSC-HVDC for AC Grid
More informationIEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008
IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008 Improving Power System Dynamic Performance in Laredo, TX Prepared by Paul Hassink (AEP) Paul Marken (GE) Rob O Keefe (AEP) Gerardo
More informationCascading Fault in AC/DC Hybrid Power Grid Xinzhou Dong
Cascading Fault in AC/DC Hybrid Power Grid Xinzhou Dong Tsinghua University, Beijing, China 30 th March, San Francissico, USA 1 2 3 4 5 Background Cascading Fault in AC/DC Hybrid Grid Model and Simulation
More informationNEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1
Page 1 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 2 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC
More informationTransient Stability Analysis Tool (TSAT) Update April 11, Hongming Zhang EMS Network Applications Manager
Transient Stability Analysis Tool (TSAT) Update April 11, 2016 Hongming Zhang EMS Network Applications Manager Agenda Peak Online TSAT Introduction: Where we are on Wide-wide System Model (WSM) -TSAT online
More informationControl System for a Diesel Generator and UPS
Control System for a Diesel Generator and UPS I. INTRODUCTION In recent years demand in the continuity of power supply in the local distributed areas is steadily increasing. Nowadays, more and more consumers
More informationReview paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques. Milap Akbari 1, Hemal Chavda 2, Jay Chitroda 3, Neha Kothadiya 4 Guided by: - Mr.Gaurang Patel 5 ( 1234 Parul Institute of Engineering &Technology,
More informationFIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION
PJM RTEP - Artificial Island Area FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION Part 1 Report REDACTED VERSION FirstEnergy Corp. Energy Delivery, Transmission Planning and Protection
More informationUse of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems
Advanced Power Transmission Solutions Power Transmission and Distribution Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in Systems s Development of Power Markets Increasing
More informationA Case Study on Aggregate Load Modeling in Transient Stability Studies
A Case Study on Aggregate Load Modeling in Transient Stability Studies Presented by: Daniel Feltes Siemens PTI Coauthors: Carlos Grande-Moran, Bernardo Fernandes, James Feltes, Ming Wu and Robert Wells
More informationPMU-based Wide Area Protection System Concept and application in a large longitudinal system
Dr. U. Kerin, Siemens AG PMU-based Wide Area Protection System Concept and application in a large longitudinal system Siemens AG, EM SG PTI, 215 All rights reserved www.siemens.com Why is there an increasing
More informationEl PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS
El Paso Electric Company El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS 2015 2024 A Review on System Performance Following Extreme Bulk Electric System Events of the
More informationAQUILA NETWORKS WESTPLAINS ENERGY COLORADO CATEGORY C CONTINGENCY STUDIES
AQUILA NETWORKS WESTPLAINS ENERGY COLORADO CATEGORY C CONTINGENCY STUDIES 2008-2012 April 2008 Table of Contents 1.0 INTRODUCTION... 2 2.0 RESULTS... 2 2.1 CATEGORY C NO SOLVE CASES... 2 2.2 CATEGORY C
More informationStandards, Procedures and Policies for Grid Connection
Standards, Procedures and Policies for Grid Connection CONTENTS 1 INTRODUCTION 1 2 EMBEDDED GENERATION 1 2.1.1 OUTLINE OF EMBEDDED GENERATION 1 2.1.2 CHANGES IN EMBEDDED GENERATION 1 2.1.3 ASPECTS OF EMBEDDED
More informationSTABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL
STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL Montree SENGNONGBAN Komsan HONGESOMBUT Sanchai DECHANUPAPRITTHA Provincial Electricity Authority Kasetsart University Kasetsart University
More informationBattery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1
Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 CONTENTS Introduction Types of WECS PQ problems in grid connected WECS Battery
More informationPOWER SESSION. DP3 Class Power System Solutions for Dynamically Positioned Vessels
Return to Session Menu DYNAMIC POSITIONING CONFERENCE October 9-10, 2012 POWER SESSION DP3 Class Power System Solutions for Dynamically Positioned Vessels Stig Settemsdal and Damir Radan Integrated Systems
More information2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited
More informationCHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM
106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,
More informationFeasibility Study Report
Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014
More informationInfrastructure Revitalization in India Power System Operation Corporation (POSOCO) New Delhi, India
Infrastructure Revitalization in India Power System Operation Corporation (POSOCO) New Delhi, India 26th March 2014 Infrastructure Revitalization in India 1 Outline Indian Power System Indian Grid - WAMS
More informationXXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS
XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS El Paso Electric Company System Operations Department System Planning
More informationDynamic Scheduling NI A F S NI S. Where:
Dynamic Scheduling FERC Order 888 defines dynamic scheduling: which is the electronic transfer of the time-varying electricity consumption corresponding to a load or the time-varying generation associated
More informationDISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales
DISTRIBUTION SOLUTIONS HA Breaker Retrofit Medium Voltage Service Marketing and Sales Table of contents Retrofit concept General description Technical specification Necessary details for standard retrofit
More informationPID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation
PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date
More informationGrid Stability Analysis for High Penetration Solar Photovoltaics
Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department
More informationComputer Aided Transient Stability Analysis
Journal of Computer Science 3 (3): 149-153, 2007 ISSN 1549-3636 2007 Science Publications Corresponding Author: Computer Aided Transient Stability Analysis Nihad M. Al-Rawi, Afaneen Anwar and Ahmed Muhsin
More informationElectrical grid stability with high wind energy penetration
ECOWAS Regional Workshop on WIND ENERGY Praia, Cape Verde. November 4 5, 2013 Electrical grid stability with high wind energy penetration Fernando CASTELLANO HERNÁNDEZ Head of Wind Energy Section Renewable
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationAccidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies
CIGRÉ-EPRI Grid of the Future Symposium 21, rue d Artois, F-75008 PARIS Boston, MA, October 20-22, 2013 http : //www.cigre.org Accidental Islanding of Distribution Systems with Multiple Distributed Generation
More informationLarge-scale hybrid simulation of electro-mechanical transient and electro-magnetic transient. Presented by: CEPRI
Large-scale hybrid simulation of electro-mechanical transient and electro-magnetic transient Presented by: CEPRI July 22, 2017 Content 1 Background 2 ADPSS hybrid simulation technology 3 Typical applications
More informationCritical Power Switchboards. Selection and Application Guide
Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation
More informationMVDC PLUS Managing the future grid
MVDC PLUS Managing the future grid Bridge the distance How should we connect Islands, platforms, and remote areas? Connecting weak or unstable grids How will we integrate and stabilize grids? Reduce footprint
More informationInfluence study of a new 220kV Substation access on regional power grid
4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Influence study of a new 220kV Substation access on regional power grid Yongchun Su1, a *, Xiaoming Wang2,b
More informationWelcome to the IDEA Webinar Series
Welcome to the IDEA Webinar Series The webinar will start promptly at 2:00pm EDT (Boston time) and is scheduled to last one (1) hour. Please mute your phone during the webinar. All lines are muted. If
More informationHamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha
1 Military Technical College Kobry El-Kobbah, Cairo, Egypt 10 th International Conference on Electrical Engineering I. ICEENG 2016 Voltage Stability Investigation of the Egyptian Grid With High Penetration
More informationABB POWER SYSTEMS CONSULTING
ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February
More informationPOWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS
POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS Farhad Shahnia Saeed Tizghadam Seyed Hossein Hosseini farhadshahnia@yahoo.com s_tizghadam@yahoo.com hosseini@tabrizu.ac.ir Electrical and
More informationTransmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting
Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting BHE Wyoming Q4 Stakeholder Meeting November 17, 2016 @ 1:00PM MT Black Hills Energy Service Center 409 Deadwood Avenue, Rapid
More information16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12
16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting
More informationSPIDER Modeling Sub-Group DER Modeling, CAISO Experience
SPIDER Modeling Sub-Group DER Modeling, CAISO Experience Irina Green, Modeling Sub-Group Chair Regional Transmission Senior Advisor, California ISO NERC SPIDER Work Group Meeting, January 2019 Presentation
More informationCascading & Discrimination
Cascading & Discrimination Typical LV System Level 1 ACBs - 6300A General LV Switchboard Level 2 ACB - 3200A MCCB 3200A Level 3 MCCB 1250A Fuses 630A Switchboard, Panelboard or MCC Level 4 MCBs - 100A
More informationComputation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation
Computation of Sensitive Node for IEEE- 4 Bus system Subjected to Load Variation P.R. Sharma, Rajesh Kr.Ahuja 2, Shakti Vashisth 3, Vaibhav Hudda 4, 2, 3 Department of Electrical Engineering, YMCAUST,
More informationSystem Impact Study Report
Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS
More informationFifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
Performance Evaluation of Composite Islanding and Load Management System using Real Time Digital Simulator Sachin Srivastava, Meera K.S, R.S. Shivakumara Aradhya and Sunil Verma Abstract A Composite Islanding
More informationCase Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI
Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising
More informationDynamic Study of Bonaire Island Power System: Model Validation and Project Experience
Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Y. Sun 1, 2,*, W. G. Kuijpers 3, E. C. W. de Jong 1,2, and H. Pustjens 3 1 Electrical Energy System, Eindhoven University
More informationINTERCONNECT CHALLENGES IN THE DEVELOPING WORLD S DISTRIBUTED GENERATION INFANCY. David C. Oehl, P.E. President MAVEN POWER
INTERCONNECT CHALLENGES IN THE DEVELOPING WORLD S DISTRIBUTED GENERATION INFANCY David C. Oehl, P.E. President MAVEN POWER September 2006 TABLE OF CONTENTS OVERVIEW...3 PROJECT BACKGROUND...4 POWER PLANT
More informationBlackout Prevention with Special Protection Systems for Isolated Power System
APAP2009, October 18~21, 2009 Jeju, Korea 1 Blackout Prevention with Special Protection Systems for Isolated Power System Chao-Rong Chen, Member,IEEE, Wen-Ta Tsai, Ching-Yin Lee Abstract--The work presents
More informationAPPENDIX E: Project Need and Description
APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Lakeville 115 kv Bus Upgrade Installation of a sectionalizing breaker to be installed on 115 kv bus section
More informationVACAR STABILITY STUDY OF PROJECTED 2014/2015 WINTER PEAK LOAD CONDITIONS
VACAR STABILITY STUDY OF PROJECTED 2014/2015 WINTER PEAK LOAD CONDITIONS April 2009 Prepared by VACAR Stability Working Group: Kirit Doshi Anthony Williams John O Connor Joe Hood Art Brown Dominion Virginia
More informationBreaker-failure protection RAICA
Breaker-failure protection RAICA Features Provides local back-up protection when the primary breaker fails to operate Initiates tripping of adjacent back-up breakers for disconnection of the fault, thus
More informationRenewable and Distributed Energy Resource Technologies
OCIECE EACJ5300/ELG7114i - 2013 Winter Term Renewable and Distributed Energy Resource Technologies Chapter 1 Power System Basics Instructor: Xiaoyu Wang, Assistant Professor Department of Electronics,
More informationThe 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027)
The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) February 2013 Contents I. Introduction 1 II. Status of Electricity Supply and Demand 2 1. Electricity Demand 2 2. Electricity
More informationCigre SC B4 Activities Towards HVDC Grids. HVDC Grid Workshop Belgium
Cigre SC B4 Activities Towards HVDC Grids Bjarne Andersen Chairman of Cigre Study Committee B4 HVDC and Power Electronics HVDC Grid Workshop Belgium 2014 1 Contents Why build HVDC Grids? Types of HVDC
More informationComparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 124-129 www.iosrjournals.org Comparative Analysis
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationTOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY
TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY January 7, 2002 Prepared by Jorge Chacon (Consultant) Tucson Electric Power Company Ed Beck ii EXECUTIVE SUMMARY
More informationREPORT. System Impact Assessment Report. Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID
REPORT IESO_PRO_0499 System Impact Assessment Report Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID 2008-309 Applicant: Richview Resources Inc Market Facilitation Department 2009
More informationAlberta Remedial Actions Schemes
Alberta Remedial Actions s Date: Oct. 31, 2018 20 Anderson 801s 240 kv Line 9L933, 9L934 and 9L950 Thermal Protection to Sheerness Plant ATCO Electric, Other MP Mitigates overloads on each line by sending
More informationJournal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E
Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity
More informationANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE ENERGY): FOCUS PV
ANCILLARY SERVICES WITH VRE (VARIABLE RENEWABLE ENERGY): FOCUS PV September 2017 1st International Conference on Large-Scale Grid Integration of Renewable Energy in India Andreas Falk, Ancillary services
More informationInnovative Power Supply System for Regenerative Trains
Innovative Power Supply System for Regenerative Trains Takafumi KOSEKI 1, Yuruki OKADA 2, Yuzuru YONEHATA 3, SatoruSONE 4 12 The University of Tokyo, Japan 3 Mitsubishi Electric Corp., Japan 4 Kogakuin
More informationApplication Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS
Application Note GET-8558 RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS REVISION 01 March 17 th, 2016 1 INDEX 1. INTRODUCTION 4 2. RELAY ORDER CODE 5 3. RELAY IO CONNECTIONS
More informationA Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design
A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the
More informationSemiconductor (AC) fuses
Main characteristics 450 TO 700VAC / 63 TO 2800A Recognized Exceptionally low I 2 T, Watt losses. Non-magnetic construction, Highly reliable low voltage Trip-indicator system, conformity to UL, IEC, DIN
More informationGlobal Grid Reliability Advances
1 Global Grid Reliability Advances Jay Giri Director, Power Systems Technology & Strategic Initiatives Redmond, WA jay.giri@ge.com Background The Interconnected Power Grid 3 One of the Most Complex & Immense,
More informationECEN 667 Power System Stability Lecture 19: Load Models
ECEN 667 Power System Stability Lecture 19: Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter 7 Homework 6 is
More informationHardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance
Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance I Abdulhadi*, A Dyśko *Power Networks Demonstration Centre, UK, ibrahim.f.abdulhadi@strath.ac.uk University of Strathclyde,
More informationBC HYDRO REAL TIME OPERATIONS SYSTEM OPERATING ORDER 7T-35. PEACE 138/230 kv NETWORK OPERATION Supersedes 7T-35 issued 15 June 2017
BC HYDRO REAL TIME OPERATIONS SYSTEM OPERATING ORDER 7T-35 PEACE 138/230 kv NETWORK OPERATION Supersedes 7T-35 issued 15 June 2017 Review Year: 2021 Original signed by Brett Hallborg for: APPROVED BY:
More informationAPPENDIX F: Project Need and Description
APPENDIX F: Project Need and Description California ISO/MID F-1 Intentionally left blank California ISO/MID F-2 Name Brief Description Type Lugo Victorville 500 kv Upgrade (SCE portion) The project was
More informationXXXX. Skookum Creek Power Project. Interconnection System Impact Study
XXXX Skookum Creek Power Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY, LIMITATION
More information