Acoustic Assessment Report PRPS Reporting Station R3 and Active Bay Response (ARB) Prepared for:

Size: px
Start display at page:

Download "Acoustic Assessment Report PRPS Reporting Station R3 and Active Bay Response (ARB) Prepared for:"

Transcription

1 Acoustic Assessment Report PRPS Reporting Station R3 and Active Bay Response (ARB) Prepared for: KMA Architects Inc. 147 Portland Street Toronto, Ontario M5V 2N4 T: (416) Attention: Mr. Jason Witalis Prepared By: Fulco Environmental Inc Upper Middle Road W., Suite 318 Oakville, ON L6M 0C2 File: 1255 Final Report v.2: August 21, 2015

2 File: 1255 PRPS Reporting Station Acoustic Assessment Report TOC TABLE OF CONTENTS 1.0 INTRODUCTION NOISE SOURCE SUMMARY POINT-OF-RECEPTION SUMMARY SOUND LEVEL SPECIFICATIONS ASSESSMENT CRITERIA IMPACT ASSESSMENT Steady State Noise Impact CONCLUSIONS... 7 LIST OF TABLES Table 1 Table 2 Table 3 Table 4 Noise Source Summary Point of Reception Noise Impact Attenuated Sound Levels Acoustic Assessment Summary Steady State Sound Levels (Stationary Sources) Acoustic Assessment Summary Steady State Sound Levels (Standby Generator) LIST OF APPENDICES Appendix A Appendix B Appendix C Appendix D Site Plans and Equipment Locations Zoning Map and Land Use Zoning Designation Plan Manufacturer Equipment Specifications Acoustic Calculations

3 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page INTRODUCTION Fulco Environmental Inc. was retained by KMA Architects Inc. to conduct an acoustic assessment of the proposed PRPS Reporting Station R3 and Active Bay Response (ARB) facility located at 2492 Thomas Street, in Mississauga, Ontario (Subject Site). The purpose of the assessment is to determine if the Subject Site is capable of operating in compliance with the published noise guidelines outlined in the City of Mississauga Noise Control By-Law (amended to ), and the Noise Pollution Control Guidelines NPC-300. There are two proposed building structures on site. The PRPS Reporting Station R3 is located on the West side of the property and the Active Bay Response (ARB) is located on the North-East side of the property. The Subject Site will have a Standby Generator located inside the PRPS Building on the North-West side of the building. The Subject Facility is proposing to operate 24 hours per day, 7 days per week, and 52 weeks per year with the Standby Generator being operational between the hours of 0900 to 1500 through the week for a maximum duration of 60 minutes for testing purposes. For the purpose of this assessment we have assumed a 24 hour operation for all equipment to assess compliance during all hours of operation with the exception of the Standby Generator which is restricted to daytime operations during nonemergency situations. In an emergency (power outage) the Standby Generator will be operational during all hours of the day. The Assessment presented herein provides a conservative evaluation of the potential noise impacts from the Subject Facility stationary source noise emissions generated during normal operations at the sensitive receptors located nearest to the facility. The Assessment was prepared consistent with the following MOE guidance: NPC-233, "Information to be Submitted for Approval of Stationary Sources of Sound, dated October 1995; NPC-300, Environmental Noise Guideline Stationary and Transportation Sources Approval and Planning ; dated August 2013; Supporting Information for the Preparation of an Acoustic Assessment Report, dated November The Subject Site is surrounded by residential properties with a major roadway (Erin Mills Parkway) transecting the residences to the West and the Subject Site. A zoning map, zoning definitions, and land use designation plans are provided in Appendix B. A site plan is provided in Appendix A showing the location of all equipment at the site.

4 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page 2 The Subject Site is located in an Acoustical Class 2 area defined by NPC-300 as an area with an acoustical environment typical of a Class 1 and Class 3 area where the background Urban Hum (vehicle traffic) tends to reduce between the hours of Erin Mills parkway runs parallel to the Subject Site on the west side. The topography surrounding the Subject Site consists of flat terrains with reflective characteristics (roads and parking lots) to the north and west side of the Subject Site. Residential properties are situated adjacent to the property on the south and east side of the Subject Site. 2.0 NOISE SOURCE SUMMARY This Assessment focused on the sound emissions from the noise sources identified at the Subject Site with a potential to adversely impact the surrounding sensitive receptors. The Noise Source Summary is provided in Table 1 Noise Source Summary and the significant noise source locations are identified in Appendix A. Fulco Environmental Inc. identified the following significant noise sources at the Subject Facility: PRPS Reporting Station R3 Facility: Source ID FAI-1: One (1) Make Up Fresh Air Unit Roof Intake; Source ID FAI-2: One (1) Make Up Fresh Air Unit Roof Intake. Source ID FAI-3: One (1) Combined Air Intake (Side Wall) 2nd Floor (Passive) serving AHU-1/AHU-2 Mechanical Noise; Source ID FAI-4: One (1) Fan Driven Fresh Air Intake (Side Wall) Serving Generator Room (9000 cfm); Source ID EF-1: One (1) Combined Air Exhaust (Side Wall) 2nd Floor Exhaust Fan Serving AHU-1/AHU-2 Fan Exhaust (4500 cfm). Source ID EF-2: One (1) Roof Mounted Exhaust Fan Serving Emissions from Vehicles; Source ID NG-1: One (1) Natural Gas Generator Roof Exhaust With Silencer; Source ID NG-2: One (1) Natural Gas Generator Ground Floor Side Wall Mechanical Exhaust; Source ID CU-1: One (1) Condenser Unit; Source ID CU-2: One (1) Condenser Unit; Source ID CU-3: One (1) Condenser Unit; Source ID CU-4: One (1) Condenser Unit; Source Id CU-5: One (1) Condenser Unit. Active Response Bay (ARB) Facility: Source ID CU-6: One (1) Condenser Unit; Source ID EF-3: One (1) Roof Mounted Exhaust Fan Serving Emissions

5 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page 3 from Vehicles. Source ID RTU-1: One (1) Roof Top Unit (Air Handling); Source ID HUM-1: One (1) Humidifier Unit. Since the facility is in the preliminary stages of construction and equipment selection the significant noise sources are based on sound level measurements that must be achieved when purchasing the new equipment. The acoustic assessment process must consider all significant noise sources. Some sources of noise are insignificant because they do not contribute to the overall sound level at each sensitive receptor. The following sources were considered insignificant: Natural gas fired comfort heating passive exhaust fans; Washroom exhaust fans; Periodic movement of-onsite vehicles. A conservative assumption was made that all equipment on-site is proposed to be able to operate twenty-four hours per day and seven days per week with the exception of the standby generator. It should be noted that not all equipment will be operational all the time. For example, the exhaust fan serving the vehicle bays will only be operational during vehicle use inside the vehicle bay and the heating and cooling equipment are subject to seasonal variations (summer/winter) in duration of operation. There is a no-idling policy at the facility and no sources of impulse noise are anticipated at the Facility. 3.0 POINT-OF-RECEPTION SUMMARY The objective of this Assessment is to determine the predictable worst-case 1-hour equivalent sound level (1-hour Leq) at the worst-case sensitive receptors or points of reception (POR) which are defined by NPC-300 as any location on a noise sensitive land use where noise from a stationary source is received. Noise sensitive land uses may have one or more points of reception. The most sensitive POR is considered to be the one at which the sound level from the Subject Site noise sources is greatest with respect to the applicable MOE guideline limit. For the purpose of this assessment the following receptors were identified as sensitive in this assessment due to the close proximity to the Subject Site as shown in the zoning map (See Appendix A & B). POR 1 Residences to the North; POR 2 - Residences to the East; POR 3 - Residences to the South; POR 4 Residences to the West.

6 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page 4 The locations of the selected POR s are identified in Appendix B - Zoning Map and Land Use Zoning Designation Plan. 4.0 SOUND LEVEL SPECIFICATIONS Existing proposed manufacturer's specifications, site measurements, and a conservative library search of sources with similar noise levels were used to assess the noise impact of the significant outdoor and indoor stationary noise sources at all POR s. The noise sources selected cannot exceed the sound levels stated at their current proposed locations of install. Attenuation due to barriers, silencers, or administrative controls will have to be assessed, if required, to ensure each noise source meets the maximum permitted sound levels provided over the specified distance. A maximum of a 5 dba standard barrier noise loss was implemented where an existing structure with a surface area of 20 Kg/m 2 breaks the line of sight from the noise source to the nearest sensitive receptor as per ISO The drawings were insufficient at this point to identify all existing barriers on-site; hence, it was assumed that no barriers exist for most sources. Tables D.1 to D.4 identify the sources that had barriers applied to them when assessing various Points of Reception Noise specifications for the outdoor stationary noise sources are provided in Table C.1 of Appendix C Noise Specification Summary Table. 5.0 ASSESSMENT CRITERIA Assessment criteria may be determined for a POR based on the MOE's minimum exclusionary sound level limits, as presented in Table B-1 and Table B-2 of NPC- 300, or on the background sound levels experienced in the area. The "background sound level" is defined as the sound level present in the environment that is produced by noise sources other than those from the Subject Site, and would include traffic sound levels and sound from neighboring industrial/commercial activity. The Subject Site is located at 2492 Thomas Street, in Mississauga, Ontario. The subject area is defined as Class II, as per MOE Publications NPC-300. POR 1 - Residences to the North; POR 2 - Residences to the East; POR 3 Residences to the South; POR 4 Residences to the West. The Subject Site is located in an Acoustical Class 2 area defined by NPC-300 as an area with an acoustical environment typical of a Class 1 and Class 3 Areas

7 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page 5 where the background Urban Hum (vehicle traffic) tends to reduce between the hours of Erin Mills parkway runs parallel to the Subject Site on the west side. The topography surrounding the Subject Site consists of flat terrains with reflective characteristics (roads and parking lots) south and east of the site. The Ministry of the Environments exclusionary limits for Class II areas have been used for daytime and nighttime operations for all sensitive receptors as outlined in Table B-2 Exclusion Limit Values of One hour Equivalent Sound Level Plane of Window of Noise Sensitive Spaces of NPC-300. The exclusionary noise level for daytime operations ( ) in a Class II Area is 50 dba. The exclusionary noise level for nighttime operations ( ) in a Class II Area is 45 dba. Table B-2 Exclusion Limit Values of One-Hour Equivalent Sound Level (L,., dba) Plane of Window of Noise Sensitive Spaces Time of Day Class l Area Class 2 Area Class 3 Area Class 4 Area 07:00-19: :00-23: :00-07: NPC-300 states the following regarding noise limits associated with a Standby Generator: The sound level limits for noise produced by emergency equipment operating in nonemergency situations, such as testing or maintenance of such equipment, are 5 db greater than the sound level limits otherwise applicable to stationary sources, described in Table B2 above. The noise produced by emergency equipment operating in non-emergency situations should be assessed independently of all other stationary sources of noise. Specifically, the emissions are not required to be included with the overall noise assessment of a stationary source facility. In addition, sound level limits do not apply to emergency equipment operating in emergency situations. It should be noted that Point of Reception 4 - Residence to the West is situated close to Erin Mills Parkway which would likely increase the background Urban Hum to the West which would increase the permissible sound level limits. However, due to the short time frame to prepare this report and the availability of vehicle traffic from the City of Mississauga we have assumed a worst case exclusionary noise limit of 50 dba daytime and 45 dba nighttime at all sensitive receptors to the West.

8 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page IMPACT ASSESSMENT 6.1 Steady State Noise Impact The worst-case assessment of steady state noise sources at the selected POR for the new equipment was based on manufacturer noise specifications, maximum permissible sound levels, and worst case operating conditions. Conservative acoustic calculations following the principles of ISO were used to assess the potential impacts of the significant noise sources. The worst-case cumulative facility-wide stationary source sound levels are estimated at all receptor(s) including attenuation affects due to intermittence barriers, and distance. As outlined in ISO noise emissions from each source is reduced by a factor of 6 dba per doubling of distance. Other attenuation factors for all sources such as geometric divergence, atmospheric attenuation, and ground absorption were not included to provide a conservative assessment. The Subject Site noise impacts at each Point of Reception (POR) were modelled based on the worst-case simultaneous operation of all equipment on-site using the maximum permissible sound levels for each piece of equipment selected. Manufacturer specifications for some sources are shown in Appendix C; however, the noise emissions listed for each source in Table 1 must be achieved in order to show compliance. The sound levels predicted at the nearest Points of Reception (POR-1 to 4) subject to this assessment are summarized below and shown in Table 2 Point of Reception Noise Impact Attenuated Sound Levels. The predicted overall sound levels at the nearest Points of Reception (POR-1 to 4) are summarized below and in Table 3 Acoustic Assessment Summary Attenuated Steady State Sound Levels (Stationary Sources) and Table 4 - Acoustic Assessment Summary Attenuated Steady State Sound Levels (Standby Generator). The noise calculations are provided in Appendix D Acoustic Calculations.

9 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page 7 Stationary Noise Sources Un-attenuated POR ID Daytime/Evening/Night Predicted Noise (dba) Daytime/Evening/ Night Performance Limits (dba) Compliance with Performance Limits R1 43 / 43 / / 50 / 45 Yes / Yes / Yes R2 43 / 43 / / 50 / 45 Yes / Yes / Yes R3 44 / 44 / / 50 / 45 Yes / Yes / Yes R4 40 / 40 / / 50 / 45 Yes / Yes / Yes Standby Generator Noise Sources Un-attenuated POR ID Daytime/Evening/Night Predicted Noise (dba) Daytime/Evening/ Night Performance Limits (dba) Compliance with Performance Limits R1 52 / NA / NA 55 / NA / NA Yes / NA / NA R2 44 / NA / NA 55 / NA / NA Yes / NA / NA R3 48 / NA / NA 55 / NA / NA Yes / NA / NA R4 49 / NA / NA 55 / NA / NA Yes / NA / NA Hence, the worst case noise emissions for the new equipment must meet the sound levels used in the assessment. If the noise levels are deviated, the acoustic assessment must be updated prior to construction to ensure compliance is shown.

10 File: 1255 PRPS Reporting Station Acoustic Assessment Report Page CONCLUSIONS The predicted steady state sound levels from the PRPS Reporting Station R3 at the POR s are below the minimum MOE daytime and nighttime exclusionary sound level limits at all sensitive receptors as outlined in NPC-300. Hence, the facility is capable of operating in compliance with the Municipal and Provincial Noise Criteria. For the purpose of this acoustic assessment the existing background noise (vehicle traffic along Erin Mills Parkway) has not been conducted. We trust the above information has been presented in a straight forward manner. If you have any questions please feel free to contact us directly. Sincerely, FULCO ENVIRONMENTAL INC. Greg Fullarton, EP, (EP)CEA, RIHT, LTRP Upper Middle Rd., W. Suite 318 Oakville, ON, L6M 0C2 T: (905) E: dgf@fulcoenvironmental.com

11 File: 1255 Acoustic Assessment Report Table 1: Noise Source Summary PRPS Reporting Station No. R3 & Active Response Bay Source Type of Noise Uncorrected Sound Power Uncorrected Sound Pressure Corrected Sound Power Corrected Sound Pressure Source Sound Intermittence Noise Control Source Description ID Source Level (1) (dba) Level (1) (dba) Level (1) (dba) Level (1) (dba) Location (2) Characteristics (3) Adjustment Measures (4) FAI-1 One (1) Make Up Fresh Air Unit Roof Intake. Point - 75 dba 7 m - 55 dba 7 m O S None TBD (20 dba) FAI-2 One (1) Make Up Fresh Air Unit Roof Intake. Point - 75 dba 7 m - 55 dba 7 m O S None TBD (20 dba) FAI-3 FAI-4 EF-1 One (1) Combined Air Intake (Side Wall) 2nd Floor (Passive) serving AHU-1/AHU-2 Mechanical Noise. One (1) Fan Driven Fresh Air Intake (Side Wall) Serving Generator Room (9000 cfm). One (1) Combined Air Exhaust (Side Wall) 2nd Floor Exhaust Fan Serving AHU-1/AHU-2 Fan Exhaust (4500 cfm). Point I S None TBD (6 dba) Point O S None None Point O S None Silencer (6 dba) EF-2 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles. Point - 75 dba 7 m 55 dba 7 m O S None Silencer (20 dba) NG-1 One (1) Natural Gas Generator Roof Exhaust With Silencer Point - 88 dba 7 m 68 dba 7 m O S None Silencer (20 dba) NG-2 One (1) Natural Gas Generator Ground Floor Side Wall Mechanical Exhaust Point - 88 dba 7 m - 68 dba 7 m O S None Silencer (20 dba) CU-1 One (1) Condenser Unit Point - 65 dba 5 m - 55 dba 5 m O S None TBD (10 dba) CU-2 One (1) Condenser Unit Point - 65 dba 5 m - 55 dba 5 m O S None TBD (10 dba) CU-3 One (1) Condenser Unit Point - 58 dba 5 m - 53 dba 5 m O S None TBD (5 dba) CU-4 One (1) Condenser Unit Point - 61 dba 5 m - 51 dba 5 m O S None TBD (10 dba) CU-5 One (1) Condenser Unit Point - 65 dba 5 m - 55 dba 5 m O S None TBD (10 dba) CU-6 One (1) Condenser Unit Point - 65 dba 5 m - 45 dba 5 m O S None TBD (20 dba) EF-3 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles. Point - 75 dba 7 m - 50 dba 7 m O S None Silencer (25 dba) RTU-1 One (1) Roof Top Unit (Air Handling) Point - 75 dba 7 m - 50 dba 7 m O S None TBD (25 dba) HUM-1 One (1) Humidifier Unit Point - 72 dba 7 m - 47 dba 7 m O S None TBD (25 dba) Notes: (1) Sound power Level or sound pressure level at a referenced distance based on manufacturer data, noise library search, (4) Noise Control Measures: (4) Noise Control Measures: and actual measurements. S - silencer, acoustic louvre, muffler S - silencer, acoustic louvre, muffler (2) Source Location: A - acoustic lining, plenum B- barrier, berm, screening A - acoustic lining, plenum B- barrier, berm, screening L- lagging O - located/installed outside of building E - acoustic enclosure E - acoustic enclosure I - located/installed inside of building O - other O - other U - uncontrolled U - uncontrolled (3) Sound Characteristics: AC - administrative control AC - administrative control S - Steady TBD - Noise control "to be determined" Q - Quasi Steady Impulsive I - Impulsive B - Buzzing T - Tonal C - Cyclic Int. - Intermittence Adjustment per NPC-104

12 1255 Acoustic Assessment Report Table 2: Point of Reception Noise Impact - Attenuated Sound Levels PRPS Reporting Station No. R3 & Active Response Bay POR-1 Residence to the North POR-2 Residences to the East POR-3 Residences to the South POR-4 Residences to the West Source ID Source Description Distance to Receptor (m) Sound Pressure Level at Receptor 1 (Leq) dba Sound Pressure Level at Receptor 1 (Leq) dba Distance to Receptor (m) Sound Pressure Level at Receptor 2 (Leq) dba Sound Pressure Level at Receptor 2 (Leq) dba Distance to Receptor (m) Sound Pressure Level at Receptor 3 (Leq) dba Sound Pressure Level at Receptor 3 (Leq) dba Distance to Receptor (m) Sound Pressure Level at Receptor 4 (Leq) dba Sound Pressure Level at Receptor 4 (Leq) dba FAI-1 One (1) Make Up Fresh Air Unit Roof Intake FAI-2 One (1) Make Up Fresh Air Unit Roof Intake FAI-3 mbined Air Intake (Side Wall) 2nd Floor (Passive) serving AHU-1/AHU-2 Mechan EF-1 ed Air Exhaust (Side Wall) 2nd Floor Exhaust Fan Serving AHU-1/AHU-2 Fan Exh EF-2 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles CU-1 One (1) Condenser Unit CU-2 One (1) Condenser Unit CU-3 One (1) Condenser Unit CU-4 One (1) Condenser Unit CU-5 One (1) Condenser Unit CU-6 One (1) Condenser Unit EF-3 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles RTU-1 One (1) Roof Top Unit (Air Handling) HUM-1 One (1) Humidifier Unit Worst Case Total Facility Sound Level (1-hr Leq) dba FAI-4 One (1) Fan Driven Fresh Air Intake (Side Wall) Serving Generator Room (9000 cfm) NA NA NA NA NG-1 One (1) Natural Gas Generator Roof Exhaust With Silencer NA NA NA NA NG-2 One (1) Natural Gas Generator Ground Floor Side Wall Mechanical Exhaust NA NA NA NA Notes: Worst Case Total Facility Sound Level (1-hr Leq) dba - 52 NA - 44 NA - 48 NA - 49 NA (1) Sound Level at the Receptor was calculated using conservative manual calculations following the principles of ISO

13 File: 1255 Acoustic Assessment Report Table 3: Acoustic Assessment Summary - Steady State Sound Levels (Stationary Sources) PRPS Reporting Station No. R3 & Active Response Bay Point of Reception ID Point of Reception Description Daytime Predicted Attenuated Sound Level at Point of Reception (Leq) dba Nighttime Predicted Attenuated Sound Level at Point of Reception (Leq) dba Verified by Acoustic Audit (Yes/No) Daytime Performance Limit (Leq) dba Nighttime Performance Limit (Leq) dba Compliance with Performance Limit (Yes/No) POR-1 Residences to the North No Yes POR-2 Residences to the East No Yes POR-3 Residences to the South No Yes POR-4 Residences to the West No Yes Table 4: Acoustic Assessment Summary - Steady State Sound Levels (Standby Generator) PRPS Reporting Station No. R3 & Active Response Bay Point of Reception ID Point of Reception Description Daytime Predicted Attenuated Sound Level at Point of Reception (Leq) dba Nighttime Predicted Attenuated Sound Level at Point of Reception (Leq) dba Verified by Acoustic Audit (Yes/No) Daytime Performance Limit (Leq) dba Nighttime Performance Limit (Leq) dba Compliance with Performance Limit (Yes/No) POR-1 Residences to the North 52 NA No 55 NA Yes POR-2 Residences to the East 44 NA No 55 NA Yes POR-3 Residences to the South 48 NA No 55 NA Yes POR-4 Residences to the West 49 NA No 55 NA Yes Note: Standby generators are assessed independantly from all other stationary noise sources as outlined in NPC-300.

14 File: 1255 PRPS Reporting Station Acoustic Assessment Report Appendices Appendix A Site Plans & Equipment Locations

15 POR 1 RESIDENCES TO THE NORTH SCALE: 6 CM = M FAI-3 NG-2 EF-1 HUM-1 FAI-4 RTU-1 NG-1 EF-3 CU-6 CU-1 CU-2 POR 4 RESIDENCES TO THE WEST CU-3 CU-4 EF-2 CU-5 FAI-1 FAI-2 POR 3 RESIDENCES TO THE SOUTH POR 2 RESIDENCES TO THE EAST

16

17

18 POR1 POR2 PRPS SITE POR3 POR4

19

20 File: 1255 PRPS Reporting Station Acoustic Assessment Report Appendices Appendix B Zoning Map and Land Use Zoning Designation Plan

21

22 File: 1255 PRPS Reporting Station Acoustic Assessment Report Appendices Appendix C Manufacturer Equipment Specifications

23 File: 1255 Detailed Acoustic Assessment Report Table C.1 - Noise Specification Summary Table Source ID from ESDM Source Label from ESDM Sound Power Level (dba) 1, 2 Reference Sound Pressure Reference Distance Level (dba) 1, 2 (m) PRPS Reporting Station No. R3 Equipment FAI-1 One (1) Make Up Fresh Air Unit Roof Intake FAI-2 One (1) Make Up Fresh Air Unit Roof Intake FAI-3 One (1) Combined Air Intake (Side Wall) 2nd Floor (Passive) serving AHU-1/AHU-2 Mechanical Noise FAI-4 One (1) Fan Driven Fresh Air Intake (Side Wall) Serving Generator Room (9000 cfm) EF-1 One (1) Combined Air Exhaust (Side Wall) 2nd Floor Exhaust Fan Serving AHU-1/AHU-2 Fan Exhaust (4500 cfm) EF-2 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles NG-1 One (1) Natural Gas Generator Roof Exhaust With Silencer NG-2 One (1) Natural Gas Generator Ground Floor Side Wall Mechanical Exhaust CU-1 One (1) Condenser Unit CU-2 One (1) Condenser Unit CU-3 One (1) Condenser Unit CU-4 One (1) Condenser Unit CU-5 One (1) Condenser Unit PRPS Active Response Bay Equipment CU-6 One (1) Condenser Unit EF-3 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles

24 File: 1255 Detailed Acoustic Assessment Report RTU-1 One (1) Roof Top Unit (Air Handling) HUM-1 One (1) Humidifier Unit NOTES: 1 A 5 dba Standard barrier noise loss was used where an existing structure (20 Kg/m 2 ) breaks the line of sight from the noise source to the sensitive receptor. 2 Worst case maximum sound levels permitted for each noise source.

25 Vision Air Handling Unit Job Information Job Name PRPS Reporting Station Date April Submitted By VVG Software Version Unit Tag AHU Unit Overview Model Number Air Volume cfm Technical Data Sheet Supply Static Pressure External Dimensions Air External inwc Total inwc Height in Width in Length in Volume cfm Return/Exhaust Static Pressure External Dimensions External inwc Total inwc Height in Width in CAH008GDAC * 58* * 58* 118 *Not including base rails, coil connectors, drain connectors and control boxes. Length in Unit Model Number: CAH008GDAC Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label) Outer Panel: Painted standard G60 Galvanized Steel Liner: Galvanized Steel (unless noted per section) Insulation: R-13 Injected Foam Unit Configuration: Stacked with opposed air flows Drive (Handling) Location: Right Base: 4" formed channel Wall Thickness: 2 in Altitude: 0 ft Parts Warranty: Standard One Year Exhaust Air Stream Plenum Section Component: 1 Length: 14 in Shipping Section: 4 Opening Location Opening Size Air Pressure Drop End upper 10.00" x 54.00" 0.02 inwc Door Location Width Opening Drive side 10 in Outward Panel Filter Component: 2 Length: 12 in Shipping Section: 4 Type Efficiency Face Velocity Face Area Air Volume Filter Loading Pleated MERV ft/min 8.8 ft² 2000 cfm Side Air Pressure Drop Number of Filters Height Width Depth Clean Air Mean Air Dirty Air 1 24 in 24 in 2 in 0.11 inwc 0.56 inwc 1.00 inwc 1 24 in 20 in 2 in 1 24 in 12 in 2 in Door Location Width Opening Drive side 8 in Outward Intersept Antimicrobial treatment Special Options Special Text Page 1 of 6

26 Vision Air Handling Unit Access Section Component: 3 Length: 24 in Shipping Section: 4 Air Pressure Drop 0.00 inwc Door Location Width Opening Drive side 20 in Outward Energy Recovery Component: 4 Length: 20 in Shipping Section: 3 Heat Wheel Model Media Type Wheel Diameter Supply Air Volume Supply Air Face Velocity Return Air Segmented Wheel Summer Winter Summer Winter SXA-1000-MW Aluminium 30 in 2000 cfm 750 ft/min 750 ft/min 750 ft/min 750 ft/min No Electrical Supply 115/60/1 V/Hz/Phase Bypass Damper Opening x / x Pressure Drop Supply Air Return Air Summer Winter Summer Winter Exhaust Air Volume VFD Motor Power 0.94 inswg 0.77 inswg 0.91 inswg 0.90 inswg 2000 cfm Yes 0.13 HP Summer Conditions Outside Air Return Air Supply Air Exhaust Air Effectiveness Total Energy Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Latent Sensible Total Recovered 88.0 F 74.0 F 75.0 F 62.5 F 78.8 F 66.4 F 84.2 F 70.8 F % % % Btu/hr Winter Conditions Outside Air Return Air Supply Air Exhaust Air Effectiveness Total Energy Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Latent Sensible Total Recovered -4.0 F -5.0 F 72.0 F 54.0 F 49.7 F 40.8 F 18.3 F 17.7 F % % % Btu/hr Door Location Width Opening Drive side 16 in Outward Special Options Static Pressure 0.91 inwc Manual Component Component: 5 Length: 12 in Shipping Section: 1 Pressure Drop 0.00 inwc Location Width Opening Removable panels - in Outward Panel Page 2 of 6

27 Vision Air Handling Unit Return/Exhaust Fan Component: 6 Length: 36 in Shipping Section: 1 Fan Performance Air Volume Static Pressure Brake Horsepower Speed Outlet Velocity External Total Cabinet Operating Maximum 2000 cfm 1.50 inwc 2.98 inwc 0.00 inwc 1.67 BHP 1735 rpm 1934 rpm 1905 ft/min Fan Data Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location Centrifugal DWDI Forward Curved / in N/A Top horizontal To Side of Fan Power Electrical Supply 2.0 HP 575/60/3 V/Hz/Phase Isolator Type: Motor Data Speed Efficiency Enclosure Frame Size Supplier Number of Lock Rotor Full Load Poles Current Current 1750 rpm Premium ODP 145 T frame Generic A 2.1 A Spring Fan Options Drive Package Data* Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type AK39H AK39H A Standard - L50 (200K) *Daikin Applied reserves the right to provide a different but equivalent drive package VFD/Starter/Disconnect Data Selection Type: External J-Box Vendor: Factory Standard Voltage: 575 V Height x Width x Depth: 4.00 in x 6.00 in x 6.00 in Mounting: Door Side Enclosure: NEMA 1 Door Location Width Opening Drive side 20 in Outward Supply Air Stream Combination Filter Component: 1 Length: 22 in Shipping Section: 2 Access Face Velocity Face Area Air Volume Side 246 ft/min 8.1 ft² 2000 cfm Portion Type Efficiency Air Pressure Drop Number of Height Width Depth Clean Air Mean Air Dirty Air Filters Pre-Filter Pleated MERV inwc 0.56 inwc 1.00 inwc 2 24 in 20 in 2 in 1 24 in 12 in 2 in Filter Varicel SH cartridge MERV inwc 0.85 inwc 1.50 inwc Door 2 24 in 20 in 12 in 1 24 in 12 in 12 in Location Width Opening Drive side 18 in Outward Pre-filter Intersept Antimicrobial treatment APM credit for low face velocity Special Options Special Text Page 3 of 6

28 Vision Air Handling Unit Access Section Component: 2 Length: 26 in Shipping Section: 2 Air Pressure Drop 0.00 inwc Door Location Width Opening Drive side 22 in Outward Energy Recovery Section Component: 3 Length: 20 in Shipping Section: 3 See Exhaust Air Stream Access Section Component: 4 Length: 24 in Shipping Section: 5 Air Pressure Drop 0.00 inwc Door Location Width Opening Drive side 20 in Outward Hot Water Coil Component: 5 Length: 34 in Shipping Section: 5 Coil Model Total Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row) 5WH0804B Btu/hr in 1.50 in x in Air Volume Air Temperature Coil Air Pressure Finned Height Finned Length Face Area Face Velocity Entering Leaving Drop Dry Bulb Dry Bulb 2000 cfm -4.0 F 76.7 F 0.11 inwc 24 in 45 in 7.50 ft² 267 ft/min Fluid Flow Rate Pressure Drop Velocity Volume Weight Entering Leaving F 99.3 F gpm 2.30 fthd 1.70 ft/s 4.0 gal lb Connection Glycol Type Min. Fin Type Quantity Size Location Material Surface Temp. Threaded in Drive side Carbon steel Propylene (50%) Min. Tube Wall Surface Temp. Fouling Factor 99.3 F 99.3 F Material Fin Tube Header Case Aluminum.0075 in Copper.020 in Copper Galv. steel AHRI 410 Certification Coil is NOT certified by AHRI Door Location Width Opening Drive side 20 in Outward Page 4 of 6

29 Vision Air Handling Unit Direct Expansion Coil Component: 6 Length: 20 in Shipping Section: 5 Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row) 5EJ0606B Btu/hr Btu/hr in 1.50 in x in Air Volume Air Temperature Coil Air Entering Leaving Pressure Drop Finned Height Finned Length Face Area Face Velocity Dry Bulb Wet Bulb Dry Bulb Wet Bulb 2000 cfm 78.8 F 66.4 F 55.0 F 53.2 F 0.22 inswg 24 in 45 in 7.50 ft² 267 ft/min Fluid Sub-Cooled Refrigerant Suction Vapor Superheat Design Saturated Suction Temp. Refrigerant Liquid Temp. Temp. at Coil Outlet Condensing Temp F R410a F 8.0 F F Connection Min. Fin Surface Temp. Min. Tube Wall Surface Temp. Type Liquid Quantity Suction Size Location Material OD Sweat in in Drive side Copper tube 32.0 F 32.0 F Material Drain Pan Drain Side Fin Tube Header Case Aluminum.0075 in Copper.020 in Copper Galv. steel Microbial resistant coated galvanized Drive side AHRI 410 Certification Coil is NOT certified by AHRI Supply Fan Component: 7 Length: 36 in Shipping Section: 5 Fan Performance Air Volume Static Pressure Brake Horsepower Speed Outlet Velocity External Total Cabinet Operating Maximum 2000 cfm 1.50 inwc 3.48 inwc 0.00 inwc 1.97 BHP 1879 rpm 2518 rpm 1905 ft/min Fan Data Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location Centrifugal DWDI Forward Curved / in N/A Top horizontal To Side of Fan Power Electrical Supply 3.0 HP 575/60/3 V/Hz/Phase Isolator Type: Motor Data Speed Efficiency Enclosure Frame Size Supplier Number of Lock Rotor Full Load Poles Current Current 1750 rpm Premium ODP 182 T frame Generic A 3.1 A Spring Fan Options Drive Package Data* Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type AK44H AK46H A Standard - L50 (200K) *Daikin Applied reserves the right to provide a different but equivalent drive package VFD/Starter/Disconnect Data Selection Type: External J-Box Vendor: Factory Standard Voltage: 575 V Height x Width x Depth: 4.00 in x 6.00 in x 6.00 in Mounting: Door Side Enclosure: NEMA 1 Door Location Width Opening Drive side 20 in Outward Page 5 of 6

30 Vision Air Handling Unit Unit Sound Power (db) Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Radiated: Unit Discharge: Unit Return: Shipping Section Details Section Length in Weight lb Corner Weights (lb) Center of Gravity (in) P1 P2 P3 P4 XX YY ZZ Entire Unit 182 Lower level only 3191 n/a n/a n/a n/a n/a n/a n/a NOTE: Special components aren't included in the corner weights and center of gravity data. AHRI Certification Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on AHRI Standard 430. Notes Standard 1. As a standalone component, unit meets or exceeds requirements of ASHRAE The approving authority is responsible for compliance of multi-component building systems. Page 6 of 6

31

32 Vision Air Handling Unit Job Information Job Name PRPS Reporting Station Date April Submitted By VVG Software Version Unit Tag AHU Unit Overview Model Number Air Volume cfm Technical Data Sheet Supply Static Pressure External Dimensions Air External inwc Total inwc Height in Width in Length in Volume cfm Return/Exhaust Static Pressure External Dimensions External inwc Total inwc Height in Width in CAH010GDAC * 64* * 64* 122 *Not including base rails, coil connectors, drain connectors and control boxes. Length in Unit Model Number: CAH010GDAC Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label) Outer Panel: Painted standard G60 Galvanized Steel Liner: Galvanized Steel (unless noted per section) Insulation: R-13 Injected Foam Unit Configuration: Stacked with opposed air flows Drive (Handling) Location: Right Base: 4" formed channel Wall Thickness: 2 in Altitude: 0 ft Parts Warranty: Standard One Year Exhaust Air Stream Plenum Section Component: 1 Length: 14 in Shipping Section: 4 Opening Location Opening Size Air Pressure Drop End upper 10.00" x 60.00" 0.02 inwc Door Location Width Opening Drive side 10 in Outward Panel Filter Component: 2 Length: 12 in Shipping Section: 4 Type Efficiency Face Velocity Face Area Air Volume Filter Loading Pleated MERV ft/min 9.5 ft² 2500 cfm Side Air Pressure Drop Number of Filters Height Width Depth Clean Air Mean Air Dirty Air 0.14 inwc 0.57 inwc 1.00 inwc 3 24 in 20 in 2 in Door Location Width Opening Drive side 8 in Outward Intersept Antimicrobial treatment Special Options Special Text Page 1 of 6

33 Vision Air Handling Unit Access Section Component: 3 Length: 24 in Shipping Section: 4 Air Pressure Drop 0.00 inwc Door Location Width Opening Drive side 20 in Outward Energy Recovery Component: 4 Length: 20 in Shipping Section: 3 Heat Wheel Model Media Type Wheel Diameter Supply Air Volume Supply Air Face Velocity Return Air Segmented Wheel Summer Winter Summer Winter SXA-1200-MW Aluminium 38 in 2500 cfm 606 ft/min 606 ft/min 606 ft/min 606 ft/min No Electrical Supply 115/60/1 V/Hz/Phase Bypass Damper Opening x / x Pressure Drop Supply Air Return Air Summer Winter Summer Winter Exhaust Air Volume VFD Motor Power 0.74 inswg 0.61 inswg 0.72 inswg 0.72 inswg 2500 cfm Yes 0.13 HP Summer Conditions Outside Air Return Air Supply Air Exhaust Air Effectiveness Total Energy Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Latent Sensible Total Recovered 88.0 F 74.0 F 75.0 F 62.5 F 78.3 F 65.8 F 84.7 F 71.3 F % % % Btu/hr Winter Conditions Outside Air Return Air Supply Air Exhaust Air Effectiveness Total Energy Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Dry Bulb Wet Bulb Latent Sensible Total Recovered -4.0 F -5.0 F 72.0 F 54.0 F 52.5 F 42.7 F 15.5 F 14.9 F % % % Btu/hr Door Location Width Opening Drive side 16 in Outward Special Options Static Pressure 0.72 inwc Manual Component Component: 5 Length: 12 in Shipping Section: 1 Pressure Drop 0.00 inwc Location Width Opening Removable panels - in Outward Panel Page 2 of 6

34 Vision Air Handling Unit Return/Exhaust Fan Component: 6 Length: 40 in Shipping Section: 1 Fan Performance Air Volume Static Pressure Brake Horsepower Speed Outlet Velocity External Total Cabinet Operating Maximum 2500 cfm 2.00 inwc 3.31 inwc 0.00 inwc 2.24 BHP 1538 rpm 2091 rpm 1701 ft/min Fan Data Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location Centrifugal DWDI Forward Curved / in N/A Top horizontal To Side of Fan Power Electrical Supply 3.0 HP 575/60/3 V/Hz/Phase Isolator Type: Motor Data Speed Efficiency Enclosure Frame Size Supplier Number of Lock Rotor Full Load Poles Current Current 1750 rpm Premium ODP 182 T frame Generic A 3.1 A Spring Fan Options Drive Package Data* Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type AK49H AK44H A Standard - L50 (200K) *Daikin Applied reserves the right to provide a different but equivalent drive package VFD/Starter/Disconnect Data Selection Type: External J-Box Vendor: Factory Standard Voltage: 575 V Height x Width x Depth: 4.00 in x 6.00 in x 6.00 in Mounting: Door Side Enclosure: NEMA 1 Door Location Width Opening Drive side 24 in Outward Supply Air Stream Combination Filter Component: 1 Length: 22 in Shipping Section: 2 Access Face Velocity Face Area Air Volume Side 265 ft/min 9.4 ft² 2500 cfm Portion Type Efficiency Air Pressure Drop Number of Clean Air Mean Air Dirty Air Filters Height Width Depth Pre-Filter Pleated MERV inwc 0.57 inwc 1.00 inwc 3 24 in 20 in 2 in Filter Varicel SH cartridge MERV inwc 0.86 inwc 1.50 inwc 3 24 in 20 in 12 in Door Location Width Opening Drive side 18 in Outward Pre-filter Intersept Antimicrobial treatment APD credit for low face velocity Special Options Special Text Page 3 of 6

35 Vision Air Handling Unit Access Section Component: 2 Length: 30 in Shipping Section: 2 Air Pressure Drop 0.00 inwc Door Location Width Opening Drive side 26 in Outward Energy Recovery Section Component: 3 Length: 20 in Shipping Section: 3 See Exhaust Air Stream Access Section Component: 4 Length: 24 in Shipping Section: 5 Air Pressure Drop 0.00 inwc Door Location Width Opening Drive side 20 in Outward Hot Water Coil Component: 5 Length: 34 in Shipping Section: 5 Coil Model Total Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row) 5WH0704B Btu/hr in 1.50 in x in Air Volume Air Temperature Coil Air Pressure Finned Height Finned Length Face Area Face Velocity Entering Leaving Drop Dry Bulb Dry Bulb 2500 cfm -4.0 F 76.0 F 0.10 inwc 27 in 51 in 9.56 ft² 261 ft/min Fluid Flow Rate Pressure Drop Velocity Volume Weight Entering Leaving F 99.6 F gpm 3.10 fthd 1.90 ft/s 6.0 gal lb Connection Glycol Type Min. Fin Type Quantity Size Location Material Surface Temp. Threaded in Drive side Carbon steel Propylene (50%) Min. Tube Wall Surface Temp. Fouling Factor 99.6 F 99.6 F Material Fin Tube Header Case Aluminum.0075 in Copper.020 in Copper Galv. steel AHRI 410 Certification Coil is NOT certified by AHRI Door Location Width Opening Drive side 20 in Outward Page 4 of 6

36 Vision Air Handling Unit Direct Expansion Coil Component: 6 Length: 20 in Shipping Section: 5 Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row) 5EJ0606B Btu/hr Btu/hr in 1.50 in x in Air Volume Air Temperature Coil Air Entering Leaving Pressure Drop Finned Height Finned Length Face Area Face Velocity Dry Bulb Wet Bulb Dry Bulb Wet Bulb 2500 cfm 78.8 F 66.4 F 54.8 F 53.0 F 0.22 inswg 27 in 51 in 9.56 ft² 261 ft/min Fluid Sub-Cooled Refrigerant Suction Vapor Superheat Design Saturated Suction Temp. Refrigerant Liquid Temp. Temp. at Coil Outlet Condensing Temp F R410a F 8.0 F F Connection Min. Fin Surface Temp. Min. Tube Wall Surface Temp. Type Liquid Quantity Suction Size Location Material OD Sweat in in Drive side Copper tube 32.0 F 32.0 F Material Drain Pan Drain Side Fin Tube Header Case Aluminum.0075 in Copper.020 in Copper Galv. steel Microbial resistant coated galvanized Drive side AHRI 410 Certification Coil is NOT certified by AHRI Supply Fan Component: 7 Length: 40 in Shipping Section: 5 Fan Performance Air Volume Static Pressure Brake Horsepower Speed Outlet Velocity External Total Cabinet Operating Maximum 2500 cfm 2.00 inwc 3.79 inwc 0.00 inwc 2.59 BHP 1651 rpm 2091 rpm 1701 ft/min Fan Data Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location Centrifugal DWDI Forward Curved / in N/A Top horizontal To Side of Fan Power Electrical Supply 3.0 HP 575/60/3 V/Hz/Phase Isolator Type: Motor Data Speed Efficiency Enclosure Frame Size Supplier Number of Lock Rotor Full Load Poles Current Current 1750 rpm Premium ODP 182 T frame Generic A 3.1 A Spring Fan Options Drive Package Data* Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type AK46H AK44H A Standard - L50 (200K) *Daikin Applied reserves the right to provide a different but equivalent drive package VFD/Starter/Disconnect Data Selection Type: External J-Box Vendor: Factory Standard Voltage: 575 V Height x Width x Depth: 4.00 in x 6.00 in x 6.00 in Mounting: Door Side Enclosure: NEMA 1 Door Location Width Opening Drive side 24 in Outward Page 5 of 6

37 Vision Air Handling Unit Unit Sound Power (db) Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Radiated: Unit Discharge: Unit Return: Shipping Section Details Section Length in Weight lb Corner Weights (lb) Center of Gravity (in) P1 P2 P3 P4 XX YY ZZ Entire Unit 190 Lower level only 3628 n/a n/a n/a n/a n/a n/a n/a NOTE: Special components aren't included in the corner weights and center of gravity data. AHRI Certification Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on AHRI Standard 430. Notes Important 1. This unit may not meet ASHRAE Standard fan motor power limitations. If that code applies, alternate fan selections may be required. 2. The designer and installer must ensure compliance with applicable codes. A component supplier cannot determine the brake horsepower ("BHP") for other motors in the air handling system. 3. Before approving this unit, determine whether ASHRAE Standard has been adopted in the specific jurisdiction or contract specifications in which the unit will be installed. Page 6 of 6

38

39 EDUS R2 Sound Levels (Reference Data) 11.Sound Levels (Reference Data) REYQ72TTJU 4D REYQ-TTJU Heat Recovery (208/230V) 113

40 Sound Levels (Reference Data) EDUS R2 REYQ96TTJU / REYQ120TTJU 4D REYQ-TTJU Heat Recovery (208/230V)

41 EDUS R2 Sound Levels (Reference Data) REYQ144TTJU / REYQ168TTJU 4D REYQ-TTJU Heat Recovery (208/230V) 115

42 File: 1255 PRPS Reporting Station Acoustic Assessment Report Appendices Appendix D Acoustic Calculations

43 File: 1255 Acoustic Assessment Report Table D.1 - Acoustic Assessment Summary Table (POR-1) Source ID from ESDM Source Label from ESDM Fan Type Source Parameters Flow Pressure (in. (cfm) (Q) of water) (P) Size QxP Equation Number Used Source Description from Noise Red Flag Tables D 50 (m) D A (m) Sound Power Level (dba) 2 Reference Sound Pressure Level (dba) 2 Reference Distance (m) Maximum 1-Hour Operation NPC-104 Time Adjustment (1-Hour Leq) Shielded from POR by Permanent Barrier? Barrier Correction (dba) 1 Predicted SL at POR (dba) PRPS Reporting Station No. R3 Equipment FAI-1 One (1) Make Up Fresh Air Unit Roof Intake min 0 No 0 33 FAI-2 One (1) Make Up Fresh Air Unit Roof Intake min 0 No 0 32 FAI-3 One (1) Combined Air Intake (Side Wall) 2nd Floor (Passive) serving AHU-1/AHU-2 Mechanical Noise min 0 No 0 35 EF-1 One (1) Combined Air Exhaust (Side Wall) 2nd Floor Exhaust Fan Serving AHU-1/AHU-2 Fan Exhaust (4500 cfm) min 0 No 0 34 EF-2 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles min 0 No 0 34 CU-1 One (1) Condenser Unit min 0 No 0 31 CU-2 One (1) Condenser Unit min 0 No 0 31 CU-3 One (1) Condenser Unit min 0 No 0 29 CU-4 One (1) Condenser Unit min 0 No 0 27 CU-5 One (1) Condenser Unit min 0 No 0 31 Active Response Bay Station Equipment CU-6 One (1) Condenser Unit min 0 Yes 5 13 EF-3 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles min 0 No 0 27 RTU-1 One (1) Roof Top Unit (Air Handling) min 0 No 0 27 HUM-1 One (1) Humidifier Unit min 0 No 0 24 Total (Daytime) Total (Nighttime) Standby Generator PRPS Reporting Station FAI-4 One (1) Fan Driven Fresh Air Intake (Side Wall) Serving Generator Room (9000 cfm) min 0 No 0 34 NG-1 One (1) Natural Gas Generator Roof Exhaust With Silencer min 0 No 0 49 NG-2 One (1) Natural Gas Generator Ground Floor Side Wall Mechanical Exhaust min 0 No 0 50 Total (Daytime) Compliance with MOE Daytime Limits Compliance with MOE Nighttime Limits Yes Yes NOTES: 1 A 5 dba Standard barrier noise loss was used where an existing structure (20 Kg/m 2 ) breaks the line of sight from the noise source to the sensitive receptor. 2 Worst case maximum sound levels permitted for each noise source. = Daytime only source ( ) NEGLIGIBLE SOURCES: All washroom and passive gas comfort heating exhaust fans as well as minor vehicle movements on-site. A no idling policy is in effect at the site during non-emergency situations.

44 File: 1255 Acoustic Assessment Report Table D.2 - Acoustic Assessment Summary Table (POR-2) Source ID from ESDM Source Label from ESDM Fan Type Source Parameters Flow Pressure (in. (cfm) (Q) of water) (P) Size QxP Equation Number Used Source Description from Noise Red Flag Tables D 50 (m) D A (m) Sound Power Level (dba) 2 Reference Sound Pressure Level (dba) 2 Reference Distance (m) Maximum 1-Hour Operation NPC-104 Time Adjustment (1-Hour Leq) Shielded from POR by Permanent Barrier? Barrier Correction (dba) 1 Predicted SL at POR (dba) PRPS Reporting Station No. R3 Equipment FAI-1 One (1) Make Up Fresh Air Unit Roof Intake min 0 No 0 32 FAI-2 One (1) Make Up Fresh Air Unit Roof Intake min 0 No 0 32 FAI-3 One (1) Combined Air Intake (Side Wall) 2nd Floor (Passive) serving AHU-1/AHU-2 Mechanical Noise min 0 Yes 5 23 EF-1 One (1) Combined Air Exhaust (Side Wall) 2nd Floor Exhaust Fan Serving AHU-1/AHU-2 Fan Exhaust (4500 cfm) min 0 Yes 5 23 EF-2 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles min 0 No 0 31 CU-1 One (1) Condenser Unit min 0 No 0 27 CU-2 One (1) Condenser Unit min 0 No 0 27 CU-3 One (1) Condenser Unit min 0 No 0 25 CU-4 One (1) Condenser Unit min 0 No 0 23 CU-5 One (1) Condenser Unit min 0 No 0 27 Active Response Bay Station Equipment CU-6 One (1) Condenser Unit min 0 Yes 5 29 EF-3 One (1) Roof Mounted Exhaust Fan Serving Emissions From Vehicles min 0 No 0 38 RTU-1 One (1) Roof Top Unit (Air Handling) min 0 No 0 36 HUM-1 One (1) Humidifier Unit min 0 No 0 33 Total (Daytime) Total (Nighttime) Standby Generator PRPS Reporting Station FAI-4 One (1) Fan Driven Fresh Air Intake (Side Wall) Serving Generator Room (9000 cfm) min 0 Yes 5 23 NG-1 One (1) Natural Gas Generator Roof Exhaust With Silencer min 0 No 0 43 NG-2 One (1) Natural Gas Generator Ground Floor Side Wall Mechanical Exhaust min 0 Yes 5 38 Total (Daytime) Compliance with MOE Daytime Limits Compliance with MOE Nighttime Limits Yes Yes NOTES: 1 A 5 dba Standard barrier noise loss was used where an existing structure (20 Kg/m 2 ) breaks the line of sight from the noise source to the sensitive receptor. 2 Worst case maximum sound levels permitted for each noise source. = Daytime only source ( ) NEGLIGIBLE SOURCES: All washroom and passive gas comfort heating exhaust fans as well as minor vehicle movements on-site. A no idling policy is in effect at the site during non-emergency situations.

SUBMITTAL DATA. for. MWSU-Popplewell Hall 1st Floor

SUBMITTAL DATA. for. MWSU-Popplewell Hall 1st Floor SUBMITTAL DATA for Prepared by Kevyn Gordon 4/27/2017 Job Name: 1 of 35 www.daikinapplied.com Table of Contents Technical Data Sheet for AHU-1st Floor... 3 Fan Curve for AHU-1st Floor... 7 Drawing for

More information

Custom Air Handling Unit

Custom Air Handling Unit Job Information Technical Data Sheet Job Name 21571221 - Tomlson Date February 06 2017 Submitted By JGK Software Version 11.10 Unit Tag AHU-1 Unit Overview Model Number cfm External Wc Static Pressure

More information

SUBMITTAL. Palm Beach Gardens Fire Station. Fausto Frias

SUBMITTAL. Palm Beach Gardens Fire Station. Fausto Frias SUBMITTAL Project Palm Beach Gardens Fire Station Date February 5, 2018 Fausto Frias Prepared For TLC Attention- Steve Job Name Palm Beach Gardens Fire Station Mark for AHU-1 Date February 5, 2018 Unit

More information

Appendix A. Cooling Coil

Appendix A. Cooling Coil Appendix A COILS FOR RUN-AROUND HEAT RECOVERY SYSTEM Cooling Coil Model number D--B45 Coil Information Tag Exhaust Wint Actual airflow Quantity System type 1 Chilled Water Entering dry bulb Entering wet

More information

Prepared By : Checked By : Approved By : Page 1 out of 6

Prepared By : Checked By : Approved By : Page 1 out of 6 Software Name Carrier AHU - Version 1.0, Patch R1.1X UNIT MODEL GENERAL SPECIFICATIONS GENERAL LOCATION / WEIGHT UNIT DIMENSION Configuration : Quick Selection Wizard Unit Orientation : Horizontal Box

More information

CH5000 Heat Recovery Ventilator

CH5000 Heat Recovery Ventilator ADVANCED COMMERCIAL Heat Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 3500-5500 CFM CASING Double-wall cabinet White exterior paint, 22-gauge galvanized steel -gauge

More information

Mississauga Bus Rapid Transit Preliminary Design Project

Mississauga Bus Rapid Transit Preliminary Design Project Mississauga Bus Rapid Transit Preliminary Design Project PUBLIC INFORMATION CENTRE OCTOBER 2008 WELCOME The Mississauga Bus Rapid Transit (BRT) Project Thank you for attending this Public Information Centre.

More information

A. NU2035 HRV Specifications NU2035

A. NU2035 HRV Specifications NU2035 A. NU2035 HRV Specifications NU2035 B. Available Options CUSTOMIZATION: This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

DUFFERIN AGGREGATES ACTON QUARRY EXTENSION PROJECT

DUFFERIN AGGREGATES ACTON QUARRY EXTENSION PROJECT DUFFERIN AGGREGATES ACTON QUARRY EXTENSION PROJECT Noise Impact Study Project#: 06183 Prepared By: Steven Titus, B.A.Sc. P.Eng. Bob Rimrott, M.A.Sc, P.Eng AERCOUSTICS ENGINEERING LIMITED 50 Ronson Drive

More information

RECORD SUBMITTAL COVER SHEET

RECORD SUBMITTAL COVER SHEET RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AERO AIR-HANDLING UNIT AHU-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED

More information

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow. NU2540 ERV Specifications Available Options CUSTOMIZATION: This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

More information

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow. NU1030 HRV Specifications Available Options CUSTOMIZATION: This series of H/ERVs is highly customizable and purpose built for the project it was designed into. See the nomenclature details that follow.

More information

EFFICIENCY 17 SEER TWO STAGE AIR CONDITIONER WITH OBSERVER

EFFICIENCY 17 SEER TWO STAGE AIR CONDITIONER WITH OBSERVER ENVIRONMENTALLY SOUND REFRIGERANT HCA7 QuietComfort DXT+ Product Specifications HIGH EFFICIENCY 17 SEER TWO STAGE AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208/230

More information

HCH6. Product Specifications

HCH6. Product Specifications HCH6 Product Specifications HIGH EFFICIENCY 16 SEER TWO- STAGE HEAT PUMP WITH OBSERVERt COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland

More information

APPENDIX D NOISE IMPACT ASSESSMENT

APPENDIX D NOISE IMPACT ASSESSMENT APPENDIX D NOISE IMPACT ASSESSMENT AURORA ACOUSTICAL CONSULTANTS Inc. 745 Warren Drive East Aurora, New York 14052 716-655-2200 info@auroraacoustical.com NOISE IMPACT ASSESSMENT OF NIGHTTIME PARKING LOT

More information

Complete HVAC Capability

Complete HVAC Capability Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option

More information

SPECIFICATION SHEET. C5000 ( cfm)

SPECIFICATION SHEET. C5000 ( cfm) (3500 5500 cfm) CASING Double wall cabinet White exterior paint, 22GA steel Galvanized 18GA steel inner wall Access door with ¼ turn handle Insulation : 2 in 18GA Stainless Steel drain pan Drain connection

More information

Report Addendum. Terry Keller, SDDOT. Noise Study Technical Report I-29 from Tea Interchange to Skunk Creek Sioux Falls, South Dakota

Report Addendum. Terry Keller, SDDOT. Noise Study Technical Report I-29 from Tea Interchange to Skunk Creek Sioux Falls, South Dakota Report Addendum To: Terry Keller, SDDOT From: HDR Project: Noise Study Technical Report I-29 from Tea Interchange to Skunk Creek Sioux Falls, South Dakota cc: file Date: May 28, 2010; rev July 16, July

More information

FDCLP2 Constant Volume Series Flow, Low Profile

FDCLP2 Constant Volume Series Flow, Low Profile The Price low profile series fan powered terminal unit is an ideal product for use in typical series fan powered applications with limited ceiling space. The is designed for constant air volume applications,

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

R4A5. Product Specifications EFFICIENT 14 SEER/ EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT

R4A5. Product Specifications EFFICIENT 14 SEER/ EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT ENVIRONMENTALLY SOUND REFRIGERANT R4A5 Product Specifications EFFICIENT 14 SEER/11.7 12.2 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1 phase,

More information

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI Air Terminal Units Models MQTH, MQFCI and MQFVI Catalog 903-1 Model MQTH Model MQFCI Model MQFVI Table of Contents Single Duct Air Terminal Units.... 3 Introduction....3 MQTH-500 Single Duct Air Terminal

More information

OPERATIONS NOISE STUDY FOR A PROPOSED AUTOMATIC CAR WASH IN THE SHERMAN OAKS DISTRICT OF LOS ANGELES

OPERATIONS NOISE STUDY FOR A PROPOSED AUTOMATIC CAR WASH IN THE SHERMAN OAKS DISTRICT OF LOS ANGELES OPERATIONS NOISE STUDY FOR A PROPOSED AUTOMATIC CAR WASH IN THE SHERMAN OAKS DISTRICT OF LOS ANGELES October 12, 2017 PREPARED FOR: Ms. Chantly Banayan 4822 Van Nuys Blvd. Sherman Oaks, CA 91403 PREPARED

More information

TSTAT0201CW (Sold Separately) Qualifying models only. Max. Fuse or Breaker

TSTAT0201CW (Sold Separately) Qualifying models only. Max. Fuse or Breaker HVA9 Product Specifications HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Future Solar Developments Inc.

Future Solar Developments Inc. Future Solar Developments Inc. Acoustic Assessment Report Type of Document Final Project Name Acoustic Assessment Report LP#7 Project Location 9274 Union Drive, Strathroy-Caradoc, ON Project Number WSL-00002250-A0

More information

FILTERED SUPPLY CENTRIFUGAL Belt Drive

FILTERED SUPPLY CENTRIFUGAL Belt Drive FILTERED SUPPLY CENTRIFUGAL Belt Drive FILTERED SUPPLY CENTRIFUGAL - BELT DRIVE SECTION 9 Carnes Models VSBB and VHBB centrifugal filtered roof supply fans are available in six sizes - 8 through 20 with

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

N4A6. Product Specifications

N4A6. Product Specifications ENVIRONMENTALLY SOUND REFRIGERANT N4A6 Product Specifications EFFICIENT UP TO 16.5 SEER/12.2 13.0 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt,

More information

Factory Option Codes L M E S P R D V F F H E

Factory Option Codes L M E S P R D V F F H E I N D O O R A I R Q U A L I T Y P R O D U C T S P E C I F I C AT I O N S ENERGY RECOVERY SYSTEM FOR L-SERIES ROOFTOP UNITS - 60 HZ Bulletin No. 10533 January 011 Supersedes October 010 800 to 600 cfm Capacity

More information

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm Product Data 42BH System Fan Coil 800 to 4000 Cfm Satisfy All Your Design Requirements with Carrier s Versatile 42BH Fan Coil Unit A selection of 6 sizes covers capacities from 800 to 4000 cfm Choice of

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 39M Central Station Air-Handling Units Sizes 03-30 Installation, Start-Up and Service Instructions CONTENTS Page INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................

More information

BAC, BAF, BAH Central Station Air Handlers

BAC, BAF, BAH Central Station Air Handlers PRODUCT DATA & INSTALLATION Bulletin B80-BA-PDI-5 Part # 1097717 PRODUCT SUPPORT web: b-rp.ca/bah email: ahu@b-rp.ca call: 1-844-893-3222 x527 scan: BAC, BAF, BAH Central Station Air Handlers Indoor and

More information

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators Version: Dec. 01, 2004 RERV & RERVX Rotary Energy Recovery Ventilators Indoor and Outdoor Installations 250 20,000 CFM Capacities RERVLP Low Profile Indoor Rotary Energy Recovery Ventilators Ideal for

More information

Appendix J. Noise Impact Assessment Report

Appendix J. Noise Impact Assessment Report Appendix J Noise Impact Assessment Report Appendix J Sheridan Park Drive Extension Municipal Class Environmental Assessment Noise Impact Assessment Report City of Mississauga R.J. Burnside & Associates

More information

CSA6. Product Specifications. SoftSound SXC 2600

CSA6. Product Specifications. SoftSound SXC 2600 16 SEER SINGLE STAGE AIR CONDITIONER WITH OBSERVERr COMMUNICATING CONTROL SYSTEM 1½ THRU 5 TONS SPLIT SYSTEM 208 / 2 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland Scroll compressors on all models

More information

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES FAN TERMINAL UNIT SPECIFIABLE FEATURES Galvanized steel casing, mechanically sealed for low leakage construction NEMA TYPE 1 rated hinged control enclosure with standoff to prevent penetration of casing

More information

Engine Performance 1500 RPM

Engine Performance 1500 RPM CUMMINS ENGINE COMPANY, INC Columbus, Indiana 471 ENGINE PERFORMANCE CURVE Basic Engine Model: QST-G3 Engine Critical Parts List: CPL: 284 Curve Number: FR-188 Date: 23Dec3 Q 1 Displacement :.48 liter

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: 036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections

More information

Environmental Noise Assessment Stonebridge Golf & Country Club Maintenance Facility. Nepean, Ontario

Environmental Noise Assessment Stonebridge Golf & Country Club Maintenance Facility. Nepean, Ontario Environmental Noise Assessment Stonebridge Golf & Country Club Maintenance Facility Nepean, Ontario REPORT: GmE 09-042-Noise Prepared For: Rob Pierce 3584 Jockvale Road Nepean, Ontario K2C 3H2 Prepared

More information

Energy Recovery Laboratory Exhaust

Energy Recovery Laboratory Exhaust Energy Recovery Laboratory Exhaust Model Vektor ERS-M For Vektor-M Fan Systems September 2012 Model Page Header Vektor ERS-M Greenheck s Vektor -ERS is a pre-engineered laboratory exhaust energy recovery

More information

High Performance Fan Coils FCHG Genesis Series Horizontal

High Performance Fan Coils FCHG Genesis Series Horizontal Dimensional Data 5 7 /8 (150) D 14 (356) 2 (51) Diverter - Slides Into Discharge Ductwork Optional: Second Drain Pan Connection E Coil Section X Dimensional Data - IP (in.) / SI [mm] Unit Fan Outlet Duct

More information

"SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units

SPOAU DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units "SPOAU" DEDICATED 100% OUTSIDE AIR UNITS Self Contained Single Package or Split System Units Spinnaker Industries Inc. Model Series SPOAU 100% Outdoor Air Systems shall be factory assembled, wired and

More information

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ PRODUCT SPECIFICATIONS Low-sound, standard or high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has

More information

DOUBLE SKIN MODULAR AIR HANDLING UNIT. Round Edge (ADM-AHU)

DOUBLE SKIN MODULAR AIR HANDLING UNIT. Round Edge (ADM-AHU) DOUBLE SKIN MODULAR AIR HANDLING UNIT Round Edge (ADM-AHU) AIR HANDLING UNIT Acson Double Skin Modular Air Handling Unit is designed based on a modular concept, making it suitable for breaking down into

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES EER 8.5 ARI RATINGS* K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS 550.13-TG11Y (0500) SPLIT-SYSTEM EVAPORATOR BLOWER K2ES120A25 10 NOMINAL TONS WITH TWO 5 TON CIRCUITS EER 8.5 DESCRIPTION This completely assembled dual circuit evaporator blower includes a well-insulated

More information

Energy Recovery Laboratory Exhaust

Energy Recovery Laboratory Exhaust Energy Recovery Laboratory Exhaust Model Vektor -ERS For Vektor-M, MH and MS Systems January 2018 Model Vektor -ERS Greenheck s Vektor -ERS is a pre-engineered laboratory exhaust energy recovery system.

More information

ELTAFANTECH Air Handling Unit 700 up to 42,000 CFM

ELTAFANTECH Air Handling Unit 700 up to 42,000 CFM an ELTA GROUP company ELTAFANTECH 700 up to 42,000 CFM INNOVATIVE Design & Performance INTRODUCTION There are 24 standard sizes of optimally engineered s to handle air volumes from 700 CFM to 42,000CFM.

More information

VAHU Vertical Air Handling Unit

VAHU Vertical Air Handling Unit 500 to 5,400 CFM @ up to 6.00" TSP 2" double wall construction, perforated or solid lined 18 gauge G90 galvanized steel cabinet 4 standard cabinet sizes available Internally isolated direct drive plug

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc. ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT 15 Metal Industries, Inc. BENEFITS: Fan powered terminals are typically used for heating and cooling of perimeter zones.

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

Curve Number: FR Engine Critical Parts List: CPL 2893 Date: 19Jun00. Aspiration : Turbocharged and Aftercooled

Curve Number: FR Engine Critical Parts List: CPL 2893 Date: 19Jun00. Aspiration : Turbocharged and Aftercooled Curve Number: FR-90766 Engine Critical Parts List: CPL 2893 Date: 19Jun00 Displacement : 5.88 litre (359.0 in 3 ) Bore : 102 mm (4.02 in.) Stroke : 120 mm (4.72 in.) No. of Cylinders : 6 Aspiration : Turbocharged

More information

BRIZA 22 HYBRID HEATING & COOLING

BRIZA 22 HYBRID HEATING & COOLING BRIZA 22 HYBRID HEATING & COOLING Built-in Ceiling: BABC/BT BABC/FT Built-in Wall: BABW/BT BABW/BF BABW/FT BABW/FF INFO SHEET BRIZA 22 HYBRID, COMPACT FANCOIL With EC Greentech EBM-PAPST technology Europe

More information

R4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT

R4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT R4A4 Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors

More information

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381)

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381) FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1-1/2, 2, 2-1/2, and 3 Tons Upflow application only Accessory field- installed electric heat kits available in, 7., or 10 kw 208/230-1-

More information

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS ZEPHYR CABINET Single & Twin Unit Cabinet Fans Moving Your Way TABLE OF CONTENTS Introduction, Certifications & Listings, Features & Benefits 3 Options & Accessories 4 Typical Applications & Belt Drive

More information

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology AIR HANDLERS LTD PVHRU Max Quiet Packaged Void Heat Reclaim Unit 1262 Acoustic Testing Laboratory College of Science & Technology Engineering Solutions The Company Air Handlers has been trading since May

More information

Product Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES

Product Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES FFMA BASE SERIES FAN COIL SIZES 018 TO 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split- system

More information

Product Data PH3Z 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS ( )

Product Data PH3Z 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS ( ) 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS (024-0) Product Data Fig. 1 - Unit 664B Single -Packaged Heat Pump Units with: S easy installation

More information

TVS/R FAN COIL UNITS HI-RISE, VERTICAL

TVS/R FAN COIL UNITS HI-RISE, VERTICAL TVS/R FAN COIL UNITS HI-RISE, VERTICAL TVRM TVRP Riser TVRS TVSE TVSM TVSR TVSS Redefine your comfort zone. www.titus-hvac.com Redefine your comfort zone www.titus-hvac.com Model TVS/R: CONCEALED, HI-RISE

More information

VHIA High-Static Ducted Indoor Units - 60HZ

VHIA High-Static Ducted Indoor Units - 60HZ PRODUCT SPECIFICATIONS Compact design for limited space requirements. Installs out of sight between the drop ceiling and ceiling slab with ducted distribution to the indoor space. All models have three-stage

More information

Nomenclature. Contents. Air Handling Unit SR AH 250 LP HS

Nomenclature. Contents. Air Handling Unit SR AH 250 LP HS SARAN Mf g. Group 1 Contents Features...... 2-4 Selection Procedures... 5-7 Capacity Ratings (Chilled Water, D.X Coil, Hot Water, Steam Ratings)... 8-15 Correction Factor Tables... 16-18 Dimensions (Horizontal

More information

Multi-Path RTU-TYPE 9 (RTU-1) CES-MPU-025-RE-VAV9

Multi-Path RTU-TYPE 9 (RTU-1) CES-MPU-025-RE-VAV9 ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 9 (RTU1) CESMPU025REVAV9 Date: December 1, 2014 2013 Consolidated Energy Solutions, Inc. UNIT FEATURES CES TYPE VAV9 Unit features include: 25 ton MultiPath

More information

Central Station Air-Handling Units

Central Station Air-Handling Units 2008 STANDARD FOR Standard 430 Central Station Air-Handling Units ISHRAE ( INDIAN SOCIETY OF HEATING, REFRIGERATING & AIR CONDITIONING ENGINEERS 4100 N. FAIRFAX DR., STE. 200 ARLINGTON, VIRGINIA 22203

More information

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO technical sales guide - 60Hz Taurus R Ducted Split Units UPTO HIGH AMBIENT OPERATION 52 O C Page CONTENTS Nomenclature.. 2 Description. 3 Features.. 3 Product Data. 4 Condensing Unit Cooling Performance

More information

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

A Division of Nailor International Inc. ECONOMY AIR HANDLERS A Division of Nailor International Inc. MODEL : ECONOMY AIR HANDLERS Thermal Model Standard Specification MODEL 800-4000 CFM AIR HANDLERS Description Model air handlers are designed for efficient and economical

More information

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h CPC Commercial 15- & 20-Ton, Three-Phase Packaged Air Conditioner 15-Ton Cooling Capacity: 180,000 BTU/h 20-Ton Cooling Capacity: 240,000 BTU/h Contents Nomenclature...2 Product Features...3 Product Specifications...4

More information

Margaret M. Alkek Building for Biomedical Research Baylor College of Medicine. Appendix A Runaround Loop Component Information

Margaret M. Alkek Building for Biomedical Research Baylor College of Medicine. Appendix A Runaround Loop Component Information Justin Mulhollan Spring 06 Mechanical Option Margaret M. Alkek Building for Biomedical Research Baylor College of Medicine Houston, TX Appendix A Runaround Loop Component Information 47 Pump Data Sheet

More information

VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT

VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT VERTICAL SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING WITH HOT WATER OR ELECTRIC HEAT SIZES FROM 600 TO 4,000 All Technical Specifications are Subject to Change without Notice.

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Single stage cooling capacity control on all 0 241 models Two stage cooling capacity control on

More information

Product Catalog. Variable Refrigerant Flow (VRF) VRF-PRC026A-EN. Mid-Static Concealed (Ducted) Indoor Units. November 2015

Product Catalog. Variable Refrigerant Flow (VRF) VRF-PRC026A-EN. Mid-Static Concealed (Ducted) Indoor Units. November 2015 Product Catalog Variable Refrigerant Flow (VRF) Mid-Static Concealed (Ducted) Indoor Units Indoor Unit Model number: 4TVD****C***** November 2015 VRF-PRC026A-EN Introduction Trane variable refrigerant

More information

The highest energy recovery available.

The highest energy recovery available. The highest energy recovery available. RG S e r i e s Dual Core Energy Recovery Temperature Efficiency Tempeff North America products employ Dual Core regenerative technology that offers up to 95% temperature

More information

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDA Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Slim, compact design for limited space requirements. Installs out of sight between the

More information

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES FFMA Base Series Fan Coil Sizes 018 thru 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split -system

More information

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL PREPARED FOR: DATE: JOB NAME: WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL EQUIPMENT DETAILS ITEM TAG DESCRIPTION MODEL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 EQUIPMENT

More information

R4H4. Product Specifications

R4H4. Product Specifications ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons Product Data Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 1 Nominal Tons The 50XCA single-package cooling units with integral air-cooled condensers

More information

V33B High Efficiency 360 Cassette Indoor Models - 60HZ

V33B High Efficiency 360 Cassette Indoor Models - 60HZ PRODUCT SPECIFICATIONS Low-sound, high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has motor-driven

More information

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL

RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL RAV Sales Guide FAN COIL UNITS HI-RISE, VERTICAL RAVS RARM RARS RAVE RAVM RAVL RARP RISER www.superiorrex.com RAV Series: VERTICAL HI-RISE CONCEALED SO TOUGH, WE GUARANTEE IT! www.superiorrex.com Model

More information

D09. 6 Advertised BHP 343 (460) 2100

D09. 6 Advertised BHP 343 (460) 2100 CUMMINS ENGINE COMPANY, INC Columbus, Indiana 47202-3005 ENGINE PERFORMANCE CURVE Basic Engine Model: Curve Number: -C460 FR-1914 Engine Family: CPL Code: Date: D09 1921 19Jan95 Construction 1 Displacement:

More information

Noise Impact Assessment

Noise Impact Assessment Noise Impact Assessment Deer Creek Energy Limited Joslyn North Mine Prepared For Millennium EMS Solutions Prepared By Mr. James Farquharson, CET Mr. Clifford Faszer, P. Eng. Faszer Farquharson & Associates

More information

ERU ENERGY RECOVERY UNIT

ERU ENERGY RECOVERY UNIT TECHNICAL GUIDE ERU ENERGY RECOVERY UNIT TGERU-1 Energy Recovery Technical Guide When you need outside air that s clean and dry, Sierra delivers. When you need that same performance each and every day

More information

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS Product Specifications DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Multi position design for horizontal or vertical installation without

More information

PRELIMINARY. Engine Speed Standby Power Prime Power Continuous Power. RPM kwm BHP kwm BHP kwm BHP. Litre / hour

PRELIMINARY. Engine Speed Standby Power Prime Power Continuous Power. RPM kwm BHP kwm BHP kwm BHP. Litre / hour Cummins Inc. Columbus, Indiana 47201 Engine Data Sheet Basic Engine Model: 1-G8 Engine Critical Parts List: CPL: 2816 Curve Number: FR-10302 Date: 3Oct01 1 Displacement : 1 liter (912 in 3 ) Bore : 137

More information

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MADE IN USA SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change without

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

PHR5. Product Specifications

PHR5. Product Specifications PHR5 Product Specifications UP to 15.5 SEER, UP to 12.5 EER, PACKAGE HEAT PUMP UNITS, 2 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT Environmentally balanced R

More information

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION

ERV ENERGY RECOVERY VENTILATOR 60 HZ. Indoor / Outdoor 500 to 10,000 cfm Capacity ERV I - D - D - P - 1 MODEL NUMBER IDENTIFICATION P R O D U C T S P E C I F I C AT I O N S I N D O O R A I R Q U A L I T Y ERV ENERGY RECOVERY VENTILATOR 60 HZ Bulletin No. 20245 March 200 Supersedes April 2009 Indoor / Outdoor 500 to 0,000 cfm Capacity

More information

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING

MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING MODULAR SINGLE AND DOUBLE WALL BELT DRIVE AIR HANDLER DX OR CHILLED WATER COOLING HOT WATER OR ELECTRIC HEATING SIZES FROM 600 TO 9,000 All Technical Specifications are Subject to Change without Notice.

More information

MG L. MG Series Paralleling Unit. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. MG kw

MG L. MG Series Paralleling Unit. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. MG kw MG Series Paralleling Unit 12.9L Industrial Spark-Ignited Generator Set EPA Certified Stationary Emergency 250 kw Power Rating 250 kw 313 kva 60 Hz Codes and Standards Generac products are designed to

More information

WCA4**4. Product Specifications

WCA4**4. Product Specifications WCA4**4 AIR CONDITIONER EFFICIENT 14 SEER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz Use of the AHRI Certified TM Mark indicates a manufacturer s participation

More information

Performance Rating of Central Station Air-handling Unit Supply Fans

Performance Rating of Central Station Air-handling Unit Supply Fans AHRI Standard 430 (I-P) With Addendum 1 2014 Standard for Performance Rating of Central Station Air-handling Unit Supply Fans AHRI STANDARD 430 (I-P)-2014 WITH ADDENDUM 1, PERFORMANCE RATING OF CENTRAL

More information

Precision Cooling For Business-Critical Continuity. Liebert CW. System Design Manual kW, 50 & 60Hz

Precision Cooling For Business-Critical Continuity. Liebert CW. System Design Manual kW, 50 & 60Hz Precision Cooling For Business-Critical Continuity Liebert CW System Design Manual - 26-181kW, 50 & 60Hz TABLE OF CONTENTS LIEBERT CW MODEL NUMBER NOMENCLATURE....................................1 1.0

More information

AIR HANDLING UNIT. MODEL: PM0809 to PM CFM to CFM

AIR HANDLING UNIT. MODEL: PM0809 to PM CFM to CFM AIR HANDLING UNIT MODEL: PM0809 to PM2738 700CFM to 41000 CFM POWER METAL TECHNOLOGIES (M) SDN BHD Lot 37830, Jalan Bukit Naga, Kampung Bukit Naga, Section 32, 40460 Shah Alam, Selangor Darul Ehsan. Tel:

More information

AIR-AIR ENERGY CONSERVATION MODULE

AIR-AIR ENERGY CONSERVATION MODULE AIR-AIR ENERGY CONSERVATION MODULE BC-ECW SERIES INDOOR/OUTDOOR INSTALLATION MANUFACTURED BY TABLE OF CONTENTS BC-ECW - Description...3 Components and fabrication details...3-4 Frost prevention & selection

More information

Power Ratings. Standby SG kva / 160 kw. Prime and standby ratings based on 3-Phase voltages. Model number based on kw rating.

Power Ratings. Standby SG kva / 160 kw. Prime and standby ratings based on 3-Phase voltages. Model number based on kw rating. SG/PG Series 200 kva 14.2L Industrial Spark-Ignited Generator Set Generac International Products Image used for illustration purposes only Power Ratings Standby SG160 200 kva / 160 kw Prime PG128 160 kva

More information

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A)

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A) Product Data OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A) 5 to 20 Nominal Tons The 50XCR single-package remote aircooled units offer: Compact, durable,

More information

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15 ENVIRONMENTALLY SOUND REFRIGERANT FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits available

More information