MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION

Size: px
Start display at page:

Download "MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION"

Transcription

1 0 Airpark Dr. Standish, MI Technical Support MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION GENERAL DESCRIPTION The Globe Model RCW* is a hydraulically operated external resetting differential latching style valve designed for use where quick-opening and total flooding of sprinkler system piping is desired. The Model RCW valve is used as an automatic water control valve in deluge applications, including electric, wet pilot, dry pilot actuation. The Model RCW valve serves as the primary water control valve installed in the water supply to a deluge sprinkler system incorporating open sprinklers or nozzles. Setting of the Model RCW valve requires water pressure in the pressure chamber being maintained on the plunger rod. The pressure on the plunger rod forces the lever arm/roller assembly against the clapper which in turn keeps the supply water from entering the sprinkler system piping. Water pressure is provided to the pressure chamber through a connection to the main water supply at a point upstream of the system main control valve. This connection also supplies water pressure up to the solenoid valve (as for electric actuation); to wet pilot sprinklers; or to a dry pilot actuator (in the case of dry pilot actuation). In the normal operating condition, the valve is closed and will automatically activate (trip) upon the activation of the detection system, which may be electrical or mechanical in nature depending on the type of system. The Model RCW valve may also be operated by means of a manual release, which is provided in the trim of all deluge valve trim configurations, to override the automatic detection system. When heat from a fire opens a pilot sprinkler, or operates an electrical device, water pressure in the pressure chamber decays resulting in the movement of the push rod assembly, releasing the lever arm/roller assembly from the clapper. The system water supply pressure forces the valve clapper open resulting in water flow into the system piping. Upon system activation, fire alarm signaling is provided by means of flowing water through the alarm port/intermediate chamber and associated alarm line trim. The flow of water activates a pressure switch which in turn notifies local alarms and/or an alarm signaling monitoring service. After the main control valve has been shut, the system drained and the detection system has been reset, the RCW valve is easily set/reset by means of pushing the reset knob. The reset knob returns the clapper to the closed position, without needing to remove the cover plate of the valve. MODEL RCW DELUGE (wet pilot actuation shown as reference) TECHNICAL DATA Approvals culus FM Maximum System Working Pressure ELECTRIC ACTUATION (Dependent on solenoid valve selection- Standard offering psi (2 Bar)) 00 psi (.6 Bar) Solenoid Available- UL/FM DRY PILOT ACTUATION 00 psi (.6 Bar) UL/FM WET PILOT ACTUATION 00 psi (.6 Bar)UL/FM End Connections Groove x Groove Materials of Construction See Technical Datasheet GFV0 for materials of construction for the Model RCW Valve *Patents Pending SEPT 8 GFV- (Formerly H-2) Page of

2 MODEL RCW DELUGE ELECTRIC ACTUATION An electrical actuation trim is one optional actuation trim configuration for the Globe Model RCW valve (See Figure for schematic of the trim arrangement). With this configuration, an electric fire detection system such as heat detectors, smoke detectors or any other electrical initiating device, which is connected to the releasing control panel can be used to actuate the valve. Water pressure is maintained in the pressure chamber and up to the normally closed solenoid valve through a restricted connection from the main water supply, taken upstream of the system main control valve. (The pressure chamber supply control valve must remain in the open position at all times when the system is in service). When the electric solenoid valve opens, due to the energizing of the releasing circuit from the releasing fire control panel, the discharge of water from the solenoid valve is at a flow rate greater than that which can pass through the restriction in the pressure chamber fill line supplying the pressure chamber. This causes a drop in the water pressure in the pressure chamber. With this drop in pressure, the clapper can no longer be held in the closed position by the lever/ roller assembly. The RCW valve operates and water flows into the system piping. Operation of the hydraulic manual control station at the deluge valve also relieves the water pressure and operates the valve. Note: When ordering Deluge Electric Actuation, non assembled or pretrimmed, the standard included solenoid valve is G80, 2 VDC psi (2 bar). If a different solenoid valve is desired, inform customer service at time of order. More information on solenoid valve offerings can be found on datasheet GFV6. SYSTEM PIPING WITH OPEN NOZZLES/SPRINKLERS RELEASING PANEL (AUTOMATIC CONTROL UNIT) POWER SUPPLY (TYPICALLY VOLTS AC) ELECTRIC DETECTION SYSTEM (TYPICALLY 2 VOLTS DC) HEAT DETECTORS, SMOKE DETECTORS, ETC. DRAIN SOLENOID VALVE (TYPICALLY 2 VOLTS DC) MANUAL CONTROL/ EMERGENCY RELEASE STATION (NORMALLY CLOSED) DRAIN CHAMBER SUPPLY CONTROL VALVE (NORMALLY OPEN) RESTRICTION CHAMBER GAUGE MAIN DRAIN VALVE (NORMALLY CLOSED) WATER SUPPLY GAUGE MAIN CONTROL VALVE (NORMALLY OPEN) WATERFLOW ALARM SWITCH ALARM TEST VALVE (NORMALLY CLOSED) WATER SUPPLY FIGURE :DELUGE ELECTRIC ACTUATION SCHEMATIC SEPT 8 GFV- (Formerly H-2) Page 2 of

3 FIGURE 2: " RCW DELUGE ELECTRIC ACTUATION TRIM ARRANGEMENT NOTE: SOLENOID INCLUDED. IF OTHER THAN STANDARD OFFERING, INFORM CUSTOMER SERVICE AT TIME OF ORDER ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY G 2" x " GALV. NIPPLE 0 06 /2" GALV. PLUG 2 8-G 2" 90 GALV. ELBOW 002-G /" GALV. CROSS 006-G /2" x " GALV. NIPPLE 2 22-G /" x /2" GALV. REDUCING ELBOW 00-G /2" x /2" GALV. NIPPLE 22-G /" x /2" GALV. STREET ELBOW 00-G /2" x /2" GALV. NIPPLE 80 " CHECK VALVE (FxF) VELOCITY CHECK VALVE -G /2" x /2" x /" GALV. TEE 696-R /2" BALL VALVE MxF - RED " 2 G80 SOLENOID VALVE WITH 2V DC COIL 8 -G /" x /2" x /" GALV. TEE 8 9 /2" RESTRICTOR 9 98 DRIP ASSEMBLY 9 0-G /" GALV. UNION 0-G /" x /2" GALV. NIPPLE 0 00-G /" x 2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 9-GR /2" BALL VALVE MxM - GREEN 00-DG /" DOM. GALV. PLUG G /2" x " GALV. NIPPLE 009-D -/2" WATER GAUGE (00PSI) 2 68 /" -WAY VALVE 6 -G /2" GALV. STREET ELBOW 2 00 PS-0-2 ALARM SWITCH 00-G /2" GALV. CROSS 6 00-G /2" x " GALV. NIPPLE 8 00-G /" GALV. PLUG -G /2" GALV. ELBOW 9 86 /" CHECK VALVE MxF 8 -G " GALV. STREET ELBOW 0-G /2" GALV. UNION 9 99-R 2" BALL VALVE (FxF) - RED 2 0-G /2" x /" x /2" GALV. TEE G 2" CLOSE GALV. NIPPLE /" TUBE CONNECTOR 8-G 2" x 2" x " GALV. TEE 2 M-60 /" COPPER TUBE G " x 2" GALV. NIPPLE /2" ELBOW TUBE CONNECTOR G /2" x 2" GALV. NIPPLE M-9 /2" COPPER TUBE G /2" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER 9 00-G /" x 6" GALV. NIPPLE R /2" SPRING LOADED CHECK VALVE /2" BALL VALVE MxM - RED " 8 02-G /2" x 9" GALV. NIPPLE SEPT 8 GFV- (Formerly H-2) Page of

4 FIGURE : 6" RCW DELUGE ELECTRIC ACTUATION TRIM ARRANGEMENT NOTE: SOLENOID INCLUDED. IF OTHER THAN STANDARD, INFORM CUS- TOMER SERVICE AT TIME OF ORDER ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY G 2" x " GALV. NIPPLE 0 06 /2" GALV. PLUG 2 8-G 2" 90 GALV. ELBOW 002-G /" GALV. CROSS 006-G /2" x " GALV. NIPPLE G /" x /2" GALV. REDUCING ELBOW 00-G /2" x /2" GALV. NIPPLE 22-G /" x /2" GALV. STREET ELBOW 00-G /2" x /2" GALV. NIPPLE 80 " CHECK VALVE (FxF) VELOCITY CHECK VALVE -G /2" x /2" x /" GALV. TEE 696-R /2" BALL VALVE MxF - RED " 2 G80 SOLENOID VALVE WITH 2V DC COIL 8 -G /" x /2" x /" GALV. TEE 8 9 /2" RESTRICTOR 9 98 DRIP ASSEMBLY 9 0-G /" GALV. UNION 0-G /" x /2" GALV. NIPPLE 0 00-G /" x 2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 9-GR /2" BALL VALVE MxM - GREEN 00-DG /" DOM. GALV. PLUG G /2" x " GALV. NIPPLE D -/2" WATER GAUGE (00PSI) 2 68 /" -WAY VALVE 6 -G /2" GALV. STREET ELBOW 2 00 PS-0-2 ALARM SWITCH 00-G /2" GALV. CROSS 6 00-G /2" x " GALV. NIPPLE 8 00-G /" GALV. PLUG -G /2" GALV. ELBOW 9 86 /" CHECK VALVE MxF 8 -G " GALV. STREET ELBOW 0-G /2" GALV. UNION 9 99-R 2" BALL VALVE (FxF) - RED 2 0-G /2" x /" x /2" GALV. TEE G 2" CLOSE GALV. NIPPLE /" TUBE CONNECTOR 8-G 2" x 2" x " GALV. TEE 2 M-60 /" COPPER TUBE G " x 2" GALV. NIPPLE /2" ELBOW TUBE CONNECTOR G /2" x 2" GALV. NIPPLE M-9 /2" COPPER TUBE G /2" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER G /" x 2 /2" GALV. NIPPLE /2" SPRING LOADED CHECK VALVE 9 00-G /" x 6" GALV. NIPPLE 29 9-R /2" BALL VALVE MxM - RED 82 0-G /2" x 0" GALV. NIPPLE SEPT 8 GFV- (Formerly H-2) Page of

5 DATE: DR.BY: METRIC UNITS SHOWN IN BRACKETS, DUE TO THE CONVERSION, METRIC VALUES MAY BE APPROXIMATE. LIMITS ON: FRACTIONS /6 [.mm]; 2 PLC. DEC..00 [.mm]; PLC. DEC.00 [.mm]; ANGLES /2 APR. BY: FIGURE : DELUGE ELECTRIC ACTUATION TRIM DIMENSIONS C B A TOP D A C H E FRONT F G B RIGHT SIDE 0 AIRPARK DRIVE STANDISH, MI 868 " RCW FLOW CONTROL VALVE; DELUGE TITLE: ELECTRIC ACTUATION TRIM ASSEMBLY JAN6 DWG. NO. 0 SY YR SCALE: : SHEET 2 OF 2 Valve Size Nominal Installation Dimensions Inches (mm) A B C D E F G H " (DN00). (8) 8.9 (8). (29). (6) 2. (2).06 (9) 0.9 (). () 6" (DN). (8) 9.6 (2).6 (296).8 (02).29 (8) 8. (2).8 (289). (68) SEPT 8 GFV- (Formerly H-2) Page of

6 MODEL RCW DELUGE-WET PILOT ACTUATION A wet pilot actuation trim is one optional trim arrangement for the Globe Model RCW valve. The detection system consists of automatic sprinklers or automatic Fixed Temperature Release Devices (typically /2" orifice) spaced throughout the protection area and connected to the deluge valve by means of ½ pilot line piping. Spacing of the pilot sprinklers is to be in accordance with the specific hazard and applicable standard or the Listing of the Fixed Temperature Release Device. Water pressure is maintained in the pressure chamber and up to the wet pilot sprinklers through a restricted connection from the main water supply, taken upstream of the system main control valve. (The pressure chamber supply control valve must remain in the open position at all times when the system is in service). When a pilot sprinkler operates, the water flow through the open pilot sprinkler is at a flow rate greater than that which can pass through the restriction in the pressure chamber supply line. This causes a drop in the water pressure in the pressure chamber. With this drop in pressure, the clapper can no longer be held in the closed position by the lever/roller assembly. The deluge valve operates (trips) and water flows into the system piping. Operation of the manual control station at the deluge valve also relieves the water pressure in the pilot line and operates the valve. Wet pilot lines for " and 6" Model RCW deluge valves are to be installed within the limitations shown on Figure 6. The curves on each graph show the maximum length of /2" pilot piping that may be utilized with the deluge valve in relation to the height of the pilot line above the valve and the water supply static pressure at the valve. The limitations are shown for pressures up to 00 psi, the maximum water working pressure of the Model RCW valves. The length/height/pressure relationship of the pilot line, pilot sprinkler and water supply is one of hydraulics. If there is a need to increase the height or length of the pilot line please consult Globe Technical services for allowable pilot line length, size and heights other than noted in Figure 6. SYSTEM PIPING WITH OPEN NOZZLES/SPRINKLERS WET PILOT SPRINKLER DETECTION (MINIMUM /2" PIPING AND NORMALLY CLOSED SPRINKLERS) REMOTE MANUAL CONTROL STATION AND INSPECTORS TEST CONNECTION (AT THE MOST HYDRAULICALLY DEMANDING LOCATION ON THE DRY PILOT LINE) MANUAL CONTROL/ EMERGENCY RELEASE STATION (NORMALLY CLOSED) DRAIN CHAMBER SUPPLY CONTROL VALVE (NORMALLY OPEN) RESTRICTION CHAMBER GAUGE MAIN DRAIN VALVE (NORMALLY CLOSED) DRAIN WATER SUPPLY GAUGE WATERFLOW ALARM SWITCH MAIN CONTROL VALVE (NORMALLY OPEN) ALARM TEST VALVE (NORMALLY CLOSED) WATER SUPPLY FIGURE :DELUGE WET PILOT ACTUATION SCHEMATIC SEPT 8 GFV- (Formerly H-2) Page 6 of

7 FIGURE 6: DELUGE WET PILOT LINE HEIGHT LIMITATIONS RCW " (DN00) RCW 6" (DN) FIGURE : DELUGE WET PILOT ACTUATION TRIM DIMENSIONS Valve Size Nominal Installation Dimensions Inches (mm) A B C D E F G H I J " (DN00). (8.2) 8.6 (29). (68) 0.9 () 2. (2).06 (9). (.) 9. (22).2 (29) 8.9 (22) 6" (DN). (8.2) 9.6 (2).22 (8).8 (289).9 (2) 8. (2). (6.) 9. (2).6 (296) 9.09 (2) SEPT 8 GFV- (Formerly H-2) Page of

8 FIGURE 8: " RCW DELUGE WET PILOT ACTUATION TRIM ARRANGEMENT DETNO PARTNO DESCRIPTION QTY G 2" x " GALV. NIPPLE 2 8-G 2" GALV. ELBOW 006-G /2" x " GALV. NIPPLE 00-G /2" x /2" GALV. NIPPLE 00-G /2" x /2" GALV. NIPPLE VELOCITY CHECK VALVE 696-R /2" BALL VALVE (MxF) - RED 2 8 -G /" x /2" x /" GALV. TEE 9 98 DRIP ASSEMBLY 0-G /" x /2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 00-DG /" DOM. GALV. PLUG 009-D /2" WATER GAUGE (00PSI) 2 6 -G /2" GALV. STREET ELBOW 2 TO WET PILOT SPRINKLERS G /2" GALV. CROSS 8 00-G /" GALV. PLUG 9 86 /" CHECK VALVE (MxF) 0-G /2" GALV. UNION 2 0-G /2" x /" x /2" GALV. TEE /" TUBE CONNECTOR 2 M-60 /" COPPER TUBE /2" ELBOW TUBE CONNECTOR M-9 /2" COPPER TUBE /2" Y-STRAINER /2" SPRING LOADED CHECK VALVE 29 9-R /2" BALL VALVE (MxM) - RED 0 06 /2" PLUG 002-G /" GALV. CROSS 2 22-G /" x /2" GALV. REDUCING ELBOW 22-G /" x /2" GALV. STREET ELBOW 80 " CHECK VALVE (FxF) G /2" x /2" x /" GALV. TEE 8 9 /2" RESTRICTOR 9 0-G /" GALV. UNION 0 00-G /" x 2" GALV. NIPPLE 9-GR /2" BALL VALVE (MxM) - GREEN G /2" x " GALV. NIPPLE 68 /" -WAY VALVE 00 PS-0-2 ALARM SWITCH G /2" x " GALV. NIPPLE -G /2" GALV. ELBOW 9 8 -G " GALV. STREET ELBOW 9 99-R 2" BALL VALVE (FxF) - RED 0800-G 2" CLOSE GALV. NIPPLE 2 8-G 2" x 2" x " GALV. TEE 2 0-G " x 2" GALV. NIPPLE G /2" x 6" GALV. NIPPLE 9 00-G /" x 6" GALV. NIPPLE 8 02-G /2" x 9" GALV. NIPPLE 2 ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY G 2" x " GALV. NIPPLE 29 9-R /2" BALL VALVE MxM - RED 2 8-G 2" 90 GALV. ELBOW 0 06 /2" PLUG 006-G /2" x " GALV. NIPPLE 002-G /" GALV. CROSS 00-G /2" x /2" GALV. NIPPLE 2 22-G /" x /2" GALV. REDUCING ELBOW 00-G /2" x /2" GALV. NIPPLE 22-G /" x /2" GALV. STREET ELBOW VELOCITY CHECK VALVE 80 " CHECK VALVE (FxF) 696-R /2" BALL VALVE MxF -RED 2 -G /2" x /2" x /" GALV. TEE 8 -G /" x /2" x /" GALV. TEE 8 9 /2" RESTRICTOR 9 98 DRIP ASSEMBLY 9 0-G /" GALV. UNION 0-G /" x /2" GALV. NIPPLE 0 00-G /" x 2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 9-GR /2" BALL VALVE MxM - GREEN 00-DG /" DOM. GALV. PLUG G /2" x " GALV. NIPPLE 009-D -/2" WATER GAUGE (00PSI) 2 68 /" -WAY VALVE 6 -G /2" GALV. STREET ELBOW 2 00 PS-0-2 ALARM SWITCH 00-G /2" GALV. CROSS 6 00-G /2" x " GALV. NIPPLE 8 00-G /" GALV. PLUG -G /2" GALV. ELBOW 9 86 /" CHECK VALVE MxF 8 -G " GALV. STREET ELBOW 0-G /2" GALV. UNION 9 99-R 2" BALL VALVE (FxF) - RED 2 0-G /2" x /" x /2" GALV. TEE G 2" CLOSE GALV. NIPPLE /" TUBE CONNECTOR 8-G 2" x 2" x " GALV. TEE 2 M-60 /" COPPER TUBE G " x 2" GALV. NIPPLE /2" ELBOW TUBE CONNECTOR G /2" x 6" GALV. NIPPLE M-9 /2" COPPER TUBE G /" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER 8 02-G /2" x 9" GALV. NIPPLE /2" SPRING LOADED CHECK VALVE SEPT 8 GFV- (Formerly H-2) Page 8 of

9 FIGURE 9: 6" RCW DELUGE WET PILOT ACTUATION TRIM ARRANGEMENT DETNO PARTNO DESCRIPTION QTY G 2" x " GALV. NIPPLE G 2" GALV. ELBOW 006-G /2" x " GALV. NIPPLE 2 00-G /2" x /2" GALV. NIPPLE 2 00-G /2" x /2" GALV. NIPPLE VELOCITY CHECK VALVE 696-R /2" BALL VALVE (MxF) - RED 8 -G /" x /2" x /" GALV. TEE 9 98 DRIP ASSEMBLY 0-G /" x /2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 00-DG /" DOM. GALV. PLUG 009-D /2" WATER GAUGE (00PSI) 2 6 -G /2" GALV. STREET ELBOW 2 00-G /2" GALV. CROSS 8 00-G /" GALV. PLUG 9 86 /" CHECK VALVE (MxF) 0-G /2" GALV. UNION 2 0-G /2" x /" x /2" GALV. TEE /" TUBE CONNECTOR 2 M-60 /" COPPER TUBE /2" ELBOW TUBE CONNECTOR M-9 /2" COPPER TUBE /2" Y-STRAINER /2" SPRING LOADED CHECK VALVE 29 9-R /2" BALL VALVE (MxM) - RED 0 06 /2" GALV. PLUG 002-G /" GALV. CROSS 2 22-G /" x /2" GALV. REDUCING ELBOW 22-G /" x /2" GALV. STREET ELBOW TO WET PILOT SPRINKLERS " CHECK VALVE (FxF) -G /2" x /2" x /" GALV. TEE 8 9 /2" RESTRICTOR 9 0-G /" GALV. UNION 0 00-G /" x 2" GALV. NIPPLE 9-GR /2" BALL VALVE (MxM) - GREEN G /2" x " GALV. NIPPLE 2 68 /" -WAY VALVE 00 PS-0-2 ALARM SWITCH 6 00-G /2" x " GALV. NIPPLE -G /2" GALV. ELBOW 8 -G " GALV. STREET ELBOW R 2" BALL VALVE (FxF) - RED 0800-G 2" CLOSE GALV. NIPPLE 2 8-G 2" x 2" x " GALV. TEE 2 0-G " x 2" GALV. NIPPLE G /2" x 2" GALV. NIPPLE G /2" x 6" GALV. NIPPLE G /" x 2 /2" GALV. NIPPLE 9 00-G /" x 6" GALV. NIPPLE 82 0-G /2" x 0" GALV. NIPPLE 2 ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY G 2" x " GALV. NIPPLE 0 06 /2" GALV. PLUG 2 8-G 2" 90 GALV. ELBOW 002-G /" GALV. CROSS 006-G /2" x " GALV. NIPPLE G /" x /2" GALV. REDUCING ELBOW 00-G /2" x /2" GALV. NIPPLE 2 22-G /" x /2" GALV. STREET ELBOW 00-G /2" x /2" GALV. NIPPLE 80 " CHECK VALVE (FxF) VELOCITY CHECK VALVE -G /2" x /2" x /" GALV. TEE 696-R /2" BALL VALVE MXF - RED /2" RESTRICTOR 8 -G /" x /2" x /" GALV. TEE 9 0-G /" GALV. UNION 9 98 DRIP ASSEMBLY 0 00-G /" x 2" GALV. NIPPLE 0-G /" x /2" GALV. NIPPLE 9-GR /2" BALL VALVE MxM - GREEN 2 00-G /" x /2" GALV. NIPPLE G /2" x " GALV. NIPPLE 2 00-DG /" DOM. GALV. PLUG 68 /" -WAY VALVE 009-D -/2" WATER GAUGE (00PSI) 2 00 PS-0-2 ALARM SWITCH 6 -G /2" GALV. STREET ELBOW G /2" x " GALV. NIPPLE 00-G /2" GALV. CROSS -G /2" GALV. ELBOW 8 00-G /" GALV. PLUG 8 -G " GALV. STREET ELBOW 9 86 /" CHECK VALVE MxF 9 99-R 2" BALL VALVE (FxF) - RED 0-G /2" GALV. UNION 0800-G 2" CLOSE GALV. NIPPLE G /2" x /" x /2" GALV. TEE 2 8-G 2" x 2" x " GALV. TEE /" TUBE CONNECTOR 2 0-G " x 2" GALV. NIPPLE 2 2 M-60 /" COPPER TUBE G /2" x 2" GALV. NIPPLE 2 06 /2" ELBOW TUBE CONNECTOR G /2" x 6" GALV. NIPPLE M-9 /2" COPPER TUBE G /" x 2 /2" GALV. NIPPLE 2 9 /2" Y-STRAINER 9 00-G /" x 6" GALV. NIPPLE /2" SPRING LOADED CHECK VALVE 82 0-G /2" x 0" GALV. NIPPLE 29 9-R /2" BALL VALVE MxM - RED SEPT 8 GFV- (Formerly H-2) Page 9 of

10 MODEL RCW DELUGE DRY PILOT ACTUATION A dry pilot actuation trim is one optional trim arrangement for the Globe Model RCW deluge valve. This arrangement is typically utilized when the pilot line is subject to areas exposed to freezing or close to freezing temperatures. The detection system consists of automatic sprinklers or automatic Fixed Temperature Release Devices (typically /2" orifice) spaced throughout the protection area and connected to the deluge valve by means of ½ pilot line piping. Spacing of the pilot sprinklers is to be in accordance with the specific hazard and applicable standard or the Listing of the Fixed Temperature Release Device. Water pressure is maintained in the valve pressure chamber up to the dry pilot actuator through a restricted connection from the main water supply which is taken upstream of the system main control valve. (The pressure chamber supply valve must remain in the open position at all times when the system is in service.) The dry pilot actuator is normally held in the closed position by the pilot line air pressure supplied by the automatic air or nitrogen maintenance device. When a pilot sprinkler operates, the air flow rate through the open pilot sprinkler is at a flow rate greater than that which can be supplied through the automatic air or nitrogen maintenance device. This causes a pressure drop in the pilot line and the upper chamber of the dry pilot actuator. Once the pressure in the upper chamber of the dry pilot actuator drops sufficiently, the upper chamber can no longer hold the diaphragm in the closed position. The dry pilot actuator opens and allows water to flow from the pressure chamber to the drain at a flow rate greater than that which can be supplied through the restriction in the pressure chamber supply line. The opening of the dry pilot actuator results in a drop in pressure in the pressure chamber and the deluge valve operates (trips) allowing water to flow into the system piping. The automatic actuation of the feature of the valve can be bypassed by manually rotating the handle on the "Manual Control/ Emergency Release" valve located on the Model RCW trim to activate the Model RCW valve. Note: More information about the operation of the Dry Pilot Actuator can be found in Technical Literature H-. LOW AIR ALARM SWITCH DRY PILOT AIR SUPPLY VALVE (NORMALLY OPEN) AUTOMATIC AIR/NITROGEN MAINTENANCE DEVICE FROM AIR SUPPLY SYSTEM PIPING WITH NORMALLY OPEN NOZZLES/SPRINKLERS PILOT LINE GAUGE DRAIN MANUAL CONTROL/ EMERGENCY RELEASE STATION (NORMALLY CLOSED) DRAIN DRY PILOT SPRINKLER DETECTION (MINIMUM /2" PIPING AND NORMALLY CLOSED SPRINKLERS) CHAMBER DRY PILOT GAUGE ACTUATOR CHAMBER SUPPLY CONTROL VALVE (NORMALLY OPEN) RESTRICTION MAIN DRAIN VALVE (NORMALLY CLOSED) REMOTE MANUAL CONTROL STATION AND INSPECTORS TEST CONNECTION (AT THE MOST HYDRAULICALLY DEMANDING LOCATION ON THE DRY PILOT LINE) DRAIN WATER SUPPLY GAUGE MAIN CONTROL VALVE (NORMALLY OPEN) WATERFLOW ALARM SWITCH ALARM TEST VALVE (NORMALLY CLOSED) WATER SUPPLY FIGURE 0: DELUGE DRY PILOT ACTUATION SCHEMATIC SEPT 8 GFV- (Formerly H-2) Page 0 of

11 FIGURE : " RCW DELUGE DRY PILOT ACTUATION TRIM ARRANGEMENT DETNO PARTNO DESCRIPTION QTY G 2" x " GALV. NIPPLE 2 8-G 2" GALV. ELBOW 006-G /2" x " GALV. NIPPLE 00-G /2" x /2" GALV. NIPPLE 00-G /2" x /2" GALV. NIPPLE VELOCITY CHECK VALVE 696-R /2" BALL VALVE (MxF) - RED 8 -G /" x /2" x /" GALV. TEE 9 98 DRIP ASSEMBLY 0-G /" x /2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 00-DG /" DOM. GALV. PLUG D /2" WATER GAUGE (00PSI) 2 00-D /2" AIR GAUGE (2PSI) 6 -G /2" GALV. STREET ELBOW 00-G /2" GALV. CROSS G /" GALV. PLUG 9 86 /" CHECK VALVE (MxF) 0-G /2" GALV. UNION 2 0-G /2" x /" x /2" GALV. TEE /" TUBE CONNECTOR 2 M-60 /" COPPER TUBE /2" ELBOW TUBE CONNECTOR 2 06 /2" TUBE CONNECTOR M-9 /2" COPPER TUBE /2" Y-STRAINER /2" SPRING LOADED CHECK VALVE 29 9-R /2" BALL VALVE (MxM) - RED 0 06 /2" PLUG 002-G /" GALV. CROSS 2 22-G /" x /2" GALV. REDUCING ELBOW 22-G /" x /2" GALV. STREET ELBOW 80 " CHECK VALVE (FxF) -G /2" x /2" x /" GALV. TEE /2" RESTRICTOR G /" GALV. UNION 0 00-G /" x 2" GALV. NIPPLE 9-GR /2" BALL VALVE (MxM) - GREEN TO DRY PILOT LINE FROM AIR MAINTENANCE DEVICE G /2" x " GALV. NIPPLE 68 /" -WAY VALVE 00 PS-0-2 ALARM SWITCH 00 PS-0-2 ALARM SWITCH 6 00-G /2" x " GALV. NIPPLE -G /2" GALV. ELBOW 8 -G " GALV. STREET ELBOW 9 99-R 2" BALL VALVE (FxF) - RED 0800-G 2" CLOSE GALV. NIPPLE G 2" x 2" x " GALV. TEE 2 0-G " x 2" GALV. NIPPLE 2 00-G /" x /2" GALV. NIPPLE 6 DRY PILOT ACTUATOR 9 0-G /2" GALV. TEE G 62 /2" x /" GALV. REDUCING BUSHING /" RELIEF VALVE (ADJ. PSI) FACTORY PSI G /2" x 6" GALV. NIPPLE 00-G /" x 2 /2" GALV. NIPPLE /" ELBOW GR /2" BALL VALVE (MxF) - GREEN 9 00-G /" x 6" GALV. NIPPLE G /2" x 9" GALV. NIPPLE ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY G 2" x " GALV. NIPPLE 2 22-G /" x /2" GALV. REDUCING ELBOW 2 8-G 2" 90 GALV. ELBOW 22-G /" x /2" GALV. STREET ELBOW 006-G /2" x " GALV. NIPPLE 80 " CHECK VALVE (FxF) 00-G /2" x /2" GALV. NIPPLE -G /2" x /2" x /" GALV. TEE 2 00-G /2" x /2" GALV. NIPPLE 8 9 /2" RESTRICTOR VELOCITY CHECK VALVE 9 0-G /" GALV. UNION 696-R /2" BALL VALVE MxF - RED G /" x 2" GALV. NIPPLE 8 -G /" x /2" x /" GALV. TEE 9-GR /2" BALL VALVE MxM - GREEN 9 98 DRIP ASSEMBLY G /2" x " GALV. NIPPLE 0-G /" x /2" GALV. NIPPLE 68 /" -WAY VALVE 2 00-G /" x /2" GALV. NIPPLE 00 PS-0-2 ALARM SWITCH 00-DG /" DOM. GALV. PLUG 2 00 PS-0-2 ALARM SWITCH 009-D -/2" WATER GAUGE (00PSI) G /2" x " GALV. NIPPLE 00-D -/2" AIR GAUGE (2PSI) -G /2" GALV. ELBOW 6 -G /2" GALV. STREET ELBOW 8 -G " GALV. STREET ELBOW 00-G /2" GALV. CROSS R 2" BALL VALVE (FxF) - RED 8 00-G /" GALV. PLUG 0800-G 2" CLOSE GALV. NIPPLE /" CHECK VALVE MxF 8-G 2" x 2" x " GALV. TEE 0-G /2" GALV. UNION 2 0-G " x 2" GALV. NIPPLE G /2" x /" x /2" GALV. TEE 2 00-G /" x /2" GALV. NIPPLE /" TUBE CONNECTOR 6 DRY PILOT ACTUATOR 2 M-60 /" COPPER TUBE - 0-G /2" GALV. TEE 2 06 /2" ELBOW TUBE CONNECTOR G /2" x /" GALV. REDUCING BUSHING 2 06 /2" TUBE CONNECTOR 62 /" RELIEF VALVE (ADJ. PSI) FACTORY PSI M-9 /2" COPPER TUBE G /2" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER 00-G /" x 2 /2" GALV. NIPPLE /2" SPRING LOADED CHECK VALVE /" ELBOW 29 9-R /2" BALL VALVE MxM - RED GR /2" BALL VALVE MxF (NINGBO) - GREEN 0 06 /2" GALV. PLUG 9 00-G /" x 6" GALV. NIPPLE 002-G /" GALV. CROSS 8 02-G /2" x 9" GALV. NIPPLE SEPT 8 GFV- (Formerly H-2) Page of

12 FIGURE 2: 6" RCW DELUGE DRY PILOT ACTUATION TRIM ARRANGEMENT TO DRY PILOT LINE 8 FROM AIR MAINTENANCE DEVICE ITEM NO. PART NO. DESCRIPTION QTY. ITEM NO. PART NO. DESCRIPTION QTY G 2" x " GALV. NIPPLE 22-G /" x /2" GALV. STREET ELBOW 2 8-G 2" 90 GALV. ELBOW 80 " CHECK VALVE (FxF) 006-G /2" x " GALV. NIPPLE 2 -G /2" x /2" x /" GALV. TEE 2 00-G /2" x /2" GALV. NIPPLE 8 9 /2" RESTRICTOR 00-G /2" x /2" GALV. NIPPLE 9 0-G /" GALV. UNION VELOCITY CHECK VALVE 0 00-G /" x 2" GALV. NIPPLE 696-R /2" BALL VALVE MxF - RED 2 9-GR /2" BALL VALVE MxM - GREEN 8 -G /" x /2" x /" GALV. TEE G /2" x " GALV. NIPPLE DRIP ASSEMBLY 68 /" -WAY VALVE 2 0-G /" x /2" GALV. NIPPLE 00 PS-0-2 ALARM SWITCH 2 00-G /" x /2" GALV. NIPPLE 00 PS-0-2 ALARM SWITCH 00-DG /" DOM. GALV. PLUG G /2" x " GALV. NIPPLE 009-D -/2" WATER GAUGE (00PSI) 2 -G /2" GALV. ELBOW 00-D /2" AIR GAUGE (2PSI) 8 -G " GALV. STREET ELBOW 6 -G /2" GALV. STREET ELBOW 9 99-R 2" BALL VALVE (FxF) - RED 00-G /2" GALV. CROSS G 2" CLOSE GALV. NIPPLE G /" GALV. PLUG 8-G 2" x 2" x " GALV. TEE 9 86 /" CHECK VALVE MxF 2 0-G " x 2" GALV. NIPPLE 2 0-G /2" GALV. UNION 002-G /2" x 2" GALV. NIPPLE 2 0-G /2" x /" x /2" GALV. TEE 2 00-G /" x /2" GALV. NIPPLE /" TUBE CONNECTOR 6 DRY PILOT ACTUATOR 2 M-60 /" COPPER TUBE - 0-G /2" GALV. TEE 2 06 /2" ELBOW TUBE CONNECTOR G /2" x /" GALV. REDUCING BUSHING 2 06 /2" TUBE CONNECTOR 62 /" RELIEF VALVE (ADJ. PSI) FACTORY PSI M-9 /2" COPPER TUBE G /2" x 6" GALV. NIPPLE 2 9 /2" Y-STRAINER G /" x 2 /2" GALV. NIPPLE /2" SPRING LOADED CHECK VALVE 00-G /" x 2 /2" GALV. NIPPLE 29 9-R "/2"" BALL VALVE MxM - RED /" ELBOW 0 06 /2" GALV. PLUG GR /2" BALL VALVE MxF (NINGBO) - GREEN 002-G /" GALV. CROSS 9 00-G /" x 6" GALV. NIPPLE 2 22-G /" x /2" GALV. REDUCING ELBOW 82 0-G /2" x 0" GALV. NIPPLE SEPT 8 GFV- (Formerly H-2) Page 2 of

13 DATE: DR.BY: APR. BY: MOD GX FX FX METRIC UNITS SHOWN IN BRACKET MAY BE APPROXIMATE. LIM 2 PLC. DEC..00 [.mm]; FIGURE :DELUGE DRY PILOT TRIM DIMENSIONS B A TOP C A G H " D FRONT E F I RIGHT SIDE 2 UPDATED TITLE BLOCK INITIAL SKETCH NO. REVISION Valve Size Nominal Installation Dimensions Inches (mm) A B C D E F G H I TITLE: " RCW FLOW C DRY PILOT ACT APR6 DWG. NO. SY YR " (DN00). (8.2) 8.6 (29.). (9.) 2. (2.).06 (9.) 0.9 (6.6).62 (29.2). (.) 9. (22.) 6" (DN). (8.2) 9.6 (2.).69 ().9 (2.) 8. (2.6).8 (289).6 (29.). (6.) 9. (2) SEPT 8 GFV- (Formerly H-2) Page of

14 INSTALLATION AND MAINTENANCE INSTALLATION Proper operation of the RCW Valve (i.e., opening of the RCW Valve as during a fire condition) is highly dependent on the correct installation of the trim. It is necessary to install the trim components as described in the figures above for the valve to function properly. Failure to do so may prevent the valve from functioning and could void Listings, Approvals, and/or the manufacturer's warranty. All tubing directed to the "drip cup" must have smooth bends. Abrupt changes in direction or kinks in the tubing could result in a restriction of flow and an adverse effect on the functionality of the valve. The Model RCW Valve must be installed in an accessible and visible location, which is maintained at or above a minimum temperature of 0ºF (ºC). The RCW Valve must be installed in the vertical orientation. All valves must be installed in accordance with the appropriate installation standard (i.e. NFPA, NFPA or other). All electrical connections must be made per the applicable installation standard and/or the National Electric Code (i.e. NFPA 0, NFPA 2 or other). Proper hydrostatic test procedure must be followed per NFPA. The velocity check valve must be replaced with a plug temporarily, the pressure chamber must be vented during the hydrostatic test procedure by opening the manual release valve and the clapper must be latched in the open position. DELUGE VALVE SETTING PROCEDURE The following steps are to be followed for initial setting, after a trip test of the fire protection system or, after any system operation of the Model RCW valve for deluge systems. Refer to Figures,, or 0, as appropriate. STEP. Close the main control valve. STEP 2. Close the pressure chamber supply control valve. STEP 2b. Dry Pilot Actuation - Close dry pilot line air supply valve. STEP. Open the main drain valve, low body (Aux) drain valve, and all low point drain valves and auxiliary drain valves on the system. Open the manual emergency release control valve. Depress the plunger of the velocity check valve to verify that it is not under pressure and that the system piping is completely drained. After system is completely drained, close all low point and auxiliary drain valves that were open. The manual emergency release control valve and main drain valve should remain open until directed in the following steps. STEP. Depress the reset plunger located at the top of the pressure chamber to reset the clapper of the RCW valve (the sound of the clapper falling into position should be heard). Close the manual emergency release control valve. STEP a. Electric Actuation The detection system is to be cleared and reset in accordance with the detection system and/or control panel manufacturer s instructions. Once reset, verify the solenoid valve is closed (de-energized). When closed, the solenoid valve should have no magnetic charge on the nut on the top of the coil. Test the nut to make sure it has no magnetic charge by contacting the nut with a conductive item such as a screwdriver. If still magnetized, the detection system/panel is not properly set for service. An alternate method of verifying if the solenoid valve is closed is to open the manual emergency release control valve and then the pressure chamber supply control valve slowly. Proceed to close the manual emergency release control valve and verify water ceases to discharge from the drain tubing to the drip cup. If no water is seen discharging from the drain tubing continue to Step 6. STEP b. Wet Pilot Actuation - open the remote wet pilot line test valve. Replace any operated wet pilot sprinklers that operated with the same type, i.e. orientation, orifice, temperature, and thermal sensitivity. Open the manual emergency release control valve and then the pressure chamber supply control valve. Verify water is flowing out of the manual emergency release control valve to the drip cup and proceed to slowly close the manual emergency release control valve. Allow water to fill the wet pilot piping. Slowly close the remote test valve as soon as water begins to discharge to allow pressure to build up in the pilot line and pressure chamber, continue to Step 6. STEP c. Dry Pilot Actuation open the remote dry pilot line test valve. Replace any operated dry pilot sprinklers that operated with the same type, i.e. orientation, orifice, temperature, and thermal sensitivity. Close the remote test valve and open the dry pilot line air supply valve to reestablish normal dry pilot line pressure. Open the manual emergency release control valve and then the pressure chamber supply control valve. Slowly close the manual emergency release control valve and allow pressure to build up in the pressure chamber. Continue to Step 6. STEP 6. Observe all drain tubing at the drip cup. If any leakage is observed, the source of the leakage must be identified and corrected. STEP. Partially open the main control valve. Slowly close the main drain valve when water discharges from the drain connection. Observe the supply pressure gauge and the pressure chamber gauge. Both gauges should indicate the same pressure reading. Depress the plunger on the automatic velocity check valve for leaks. If leakage is apparent, the cause of the leakage must be identified and corrected. If there are no leaks, open the system control valve fully, and the RCW valve is reset and is ready to be placed back in service. The releasing control panel may need to be cleared/reset one additional time to clear any supervisory conditions that may be connected to the system control valve. SEPT 8 GFV- (Formerly H-2) Page of

15 TESTING Reference NFPA 2, Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems. Before proceeding with any tests involving water flow, the following precautions need to be taken:. Check the location where the test connection discharges to make sure that all is clear and that there is no possibility of the water flow causing damage or injury. 2. Check the end of the test connection to make sure that it is unobstructed. To achieve a satisfactory test, there must be an unrestricted flow of water when the test valve is wide open.. Check for alarm connections to a central station or fire department. If such connections are found, give proper notice to the signal receiving station before proceeding with the test. Note: A main drain test may also operate local fire alarms unless they are temporarily disabled. DELUGE TRIP TEST PROCEDURE Proper operation of the RCW Valve (i.e., opening of the RCW Valve as during a fire condition) must be verified, at the frequency described by the applicable Inspection Testing and Maintenance Standard (i.e. NFPA 2) or by the Local AHJ. The steps to perform a trip test are as follows: STEP. If a partial flow trip test is required, perform the following additional steps. If a full flow test is being performed continue to Step 2:. Close the Main Control Valve. 2. Open the Main Drain Valve.. Open the Main Control Valve one turn beyond the position at which water just begins to flow from the. Close the Main Drain Valve. Note: Be sure to close the main control valve quickly after the trip of the valve has been verified. STEP 2a. Electric Actuation -Activate the releasing circuit of the releasing panel in accordance with the manufacturer s instructions to energize the solenoid valve. STEP 2b. Wet Pilot Actuation -Open the test valve at the end of the wet pilot line. STEP 2c. Dry Pilot Actuation - Open the test valve at the end of the dry pilot line. STEP. Verify that the RCW Valve has tripped, as indicated by the flow of water into the system and activation of the water flow alarm. STEP. Close the system s Main Control Valve. STEP. Reset the RCW Deluge Valve in accordance with the Deluge Valve Setting Procedure. DELUGE- WATERFLOW ALARM TEST PROCEDURE Testing of the system water flow alarms must be performed at the frequency described by the applicable Inspection Testing and Maintenance Standard (i.e. NFPA 2) or by the Local AHJ. To test the water flow alarm, open the Alarm Test Valve, which will allow a flow of water to the Pressure Alarm Switch and/or Water Motor Alarm. Upon satisfactory completion of the test, close the Alarm Test Valve. MAINTENANCE Note: All valves should be carefully inspected, tested, and maintained in accordance with NFPA 2 or other applicable Standard. It is important to ensure a clean water supply free of debris and solid particles such as sand, gravel, or mud. If, during an inspection of a water control valve, sediment or free particles of matter are noted, a further examination of internal valve parts is necessary. All deposits should be removed from all operating parts and ports. Vent holes through intermediate chamber should be thoroughly cleaned and flushed with clean water. Where difficulty in performance is experienced, the manufacturer or its authorized representative shall be contacted before any field adjustment is to be made. Clapper Facing. The rubber clapper facing should be checked for wear or damage to determine that it is free of dirt and other foreign substances. If found to be worn or damaged (e.g., foreign matter embedded in the surface), the facing should be replaced. If it is dirty, it should be cleaned. Compounds which could damage the rubber facing must never be used. Seat Ring. The seat ring should be checked for nicks and for stones, dirt or other foreign matter lodged in the grooves or holes. It should be cleaned thoroughly. If the seat ring is found to be damaged, valve should be replaced. Alarm Line Check Valve. The ¾ check valve connected to the intermediate chamber should be checked for clapper and seat condition. RCW Valve. Main Drain Valve and all controlling valves which are normally closed when the deluge valve is in the set position should be checked to be sure that they are fully closed and not leaking. SEPT 8 GFV- (Formerly H-2) Page of

16 ORDERING INFORMATION The RCW Valve with Deluge Electric, Wet Pilot, or Dry Pilot Actuation trim can be ordered pre-trimmed or non-assembled as separate items. The standard offering comes with galvanized nipples and fittings (Standard galvanized trim is not domestic). For non-assembled the following items must be ordered separately: RCW Water Control Valve Deluge Electric Actuation Trim or; Deluge Wet Pilot Trim or; Deluge Dry Pilot Trim Solenoid Valve (If applicable) Accessories (as needed) Pre-Trimmed With Model GLR00G Control Valve Electric actuation standard solenoid valve is the Skinner 2 VDC; psi rated solenoid. If different solenoid valve is desired, inform Customer Service at time of order placement. Pre-Trimmed RCW Deluge Electric Actuation w/ Model GLR00G Contol Valve Specify: RCW Deluge Electric Actuation Pretrimmed w/ BFV(specify valve size), PN: Inch G x G... 0-B 6 Inch G x G... 8-B DN (6, mm) GXG... 8-D-B Pre-Trimmed RCW Deluge Wet Pilot Actuation w/ Model GLR00G Contol Valve Specify: RCW Deluge Wet Pilot Actuation Pre-trimmed w/ BFV(specify valve size), PN: Inch G x G...8-B 6 Inch G x G...8-B DN (6, mm) GXG...8-D-B Pre-Trimmed RCW Deluge Dry Pilot Actuation w/ Model GLR00G Contol Valve Specify: RCW Deluge Dry Pilot Actuation Pre-trimmed w/ BFV(specify valve size), PN : Inch G x G... -B 6 Inch G x G B DN (6, mm) GXG D-B PRE-TRIMMED WITHOUT GROOVED BFV CONTROL VALVE Pre-Trimmed RCW Deluge Electric Actuation Specify: RCW Deluge Electric Actuation Pre-trimmed (specify valve size), PN: Inch G x G Inch G x G... 8 DN (6, mm) GXG... 8-D Pre-Trimmed RCW Deluge Wet Pilot Actuation Specify: RCW Deluge Wet Pilot Actuation Pre-trimmed (specify valve size), PN: Inch G x G Inch G x G...8 DN (6, mm) GXG...8-D Pre-Trimmed RCW Deluge Dry Pilot Actuation Specify: RCW Deluge Dry Pilot Actuation Pre-trimmed (specify valve size), PN (see Part Number Below): Inch G x G... 6 Inch G x G DN (6, mm) GXG D NON-ASSEMBLED Valve body ordered separately Trim Kit includes extra pieces to accommodate different size valves Standard offering solenoid valve included (Electric Actuation Trim), inform Customer Service at time of order if other than standard solenoid valve required. RCW Water Control Valve Specify: RCW Valve Only (specify valve size) inch RCW GxG inch RCW GxG... DN (6, mm) RCW GXG...-D RCW Deluge Electric Trim inch or 6 inch or DN Specify: RCW Deluge Electric Trim Kit, PN : Deluge Electric Trim Kit...8 RCW Deluge Wet Pilot Trim inch or 6 inch or DN Specify: RCW Deluge Wet Pilot Trim Kit, PN: Deluge Wet Pilot Trim Kit... 9 RCW Deluge Dry Pilot Trim inch or 6 inch or DN Specify: RCW Deluge Dry Pilot Trim Kit, PN : Deluge Dry Pilot Trim Kit... Solenoid Valve A Solenoid Valve compatible with the anticipated maximum water supply pressure and releasing panel, when ordering an electric actuation trim. Refer to Technical Data Sheet GFV6 for ordering information. Specify: 2 VDC, ( psi, 2 psi or 00 psi) Solenoid Valve: ASCO psi (2 Bar) UL/FM....G829G ASCO 00 psi (. Bar) UL/FM...GHV2900 *Skinner psi (2 Bar) UL/FM G80 Skinner 2 psi (.2 Bar) UL/FM...G802 *Standard Model H-, H-2 or H- Air Maintenance Device Specify: Model (Specify Model) Air Maintenance Device (see Part Number below) H-...8 H H See Technical Literature G- and G-2 for more information on Air Maintenance Devices Note: 00 psi (.6 Bars) Pressure Gauges Standard (600 psi (.2 Bars) Ordered Separately PN D See trim drawings for trim replacement part numbers See Technical Data Sheet GFV0 for RCW Valve replacement part numbers SEPT 8 GFV- (Formerly H-2) Page 6 of

17 GLOBE PRODUCT WARRANTY Globe agrees to repair or replace any of its manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). 0 Airpark Dr. Standish, MI 868 Ph Technical Support techservice@globesprinkler.com SEPT 8 GFV- (Formerly H-2) Page of

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

MODEL RCW NON-INTERLOCK PREACTION SYSTEM GENERAL DESCRIPTION The Globe Model RCW non-interlock preaction valve is a hydraulically operated external resetting differential latching style valve designed for use where quickopening and total flooding

More information

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4 AND 6 MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS SHORTER. LIGHTER. MORE VERSATILE. " AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS Globe is proud to introduce the new Model RCW Water Control Valve for dry pipe, preaction

More information

MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve) 1¼", 1½", 2", 2½", 76.1mm, 3", 4", 6",165.1mm, 8"

MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve) 1¼, 1½, 2, 2½, 76.1mm, 3, 4, 6,165.1mm, 8 4077 Airpark Dr. Standish, MI 48658 989-846-4583 www.globesprinkler.com Technical Support 989-414-2600 techservice@globesprinkler.com MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve)

More information

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation Deluge Valve DV-5 Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation GeneralDescription The Model DV-5 Deluge Valve (described in Technical

More information

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA 1-1/2 (dn40) July 1, 2011 Deluge Valves 209a DESCRIPTION The Viking Model E-3 1-1/2 Deluge Valve is a quick-opening, differential type flood valve with a rolling diaphragm clapper. The deluge valve is used to control

More information

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications 1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P) 1 of 9 1. DESCRIPTION The Viking 2 (DN50) is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction sprinkler

More information

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA. Q= C v P S 1 of 9 1. DESCRIPTION The Viking Model E-1 Deluge Valve is a quick-opening, differential diaphragm, flood valve with one moving part. The deluge valve is used to control water flow in deluge and preaction

More information

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet) Flow Control 500a DESCRIPTION The Viking 1-1/2 is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The can be used to facilitate manual or automatic on/off

More information

TECHNICAL DATA. Trimpac 244a. April 15, 2011

TECHNICAL DATA. Trimpac 244a. April 15, 2011 April 15, 2011 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally required

More information

TECHNICAL DATA. Trimpac 249a. September 16, 2013

TECHNICAL DATA. Trimpac 249a. September 16, 2013 September 16, 2013 Trimpac 249a 1. DESCrIpTION DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked with a pneumatic release module in a metal enclosure.

More information

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description Worldwide Contacts www.tycofire.com DV Deluge Valve, Diaphragm Style, / thru Inch (DN0 thru DN00), Deluge System Wet Pilot Actuation General Description The DV Deluge Valve (described in Technical Data

More information

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150) January 13, 2006 Deluge Valves 211 a 1. PRODUCT NAME Viking Model E-1 Deluge Valve 3 (DN80) Available since 1985 4 (DN100) Available since 1985 6 (DN150) Available since 1984 2. MANUFACTURER THE VIKING

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 407 Rev. T Model E Alarm Check Valve Bulletin 407 Rev. T Instructions for Installation, Operation, Care and Maintenance 4 (100 mm), 6 (150 mm), 8 (200 mm) Sizes With Model E3 Trim Listed by Underwriters

More information

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE Page 1 of 20 1. DESCRIPTION TRIMPAC Model B-4, B-4B & B-4S is a factory assembled trim package for a single interlocked preaction system with a pneumatic release module in a metal enclosure. The standard

More information

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : NOMINAL SIZE MATERIAL MAXIMUM SERVICE PRESSURE 200, 150, 100, 80 & 50NB Cast Iron 12 Bar (175 PSI) THREADED OPENING MOUNTING FACTORY HYDROSTATIC TEST PRESSURE

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 59 Model DDX Deluge Valve (50 mm), ½ (65 mm), (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (00 mm) Bulletin 59 Instructions for Installation, Operation, Care and Maintenance Wet Pilot Line,

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model D Dry Pipe Valve Bulletin 350 Rev. S Bulletin 350 Rev. S Instructions for Installation, Operation, Care and Maintenance 4 (100mm) 6 (150mm) Valve With Model D Trimmings Listed by Underwriters Laboratories,

More information

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5A Automatic

More information

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/ Inch to Inch (DN40 to DN00) General Description The TYCO DV-5a Automatic

More information

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465 Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Double Interlock Electric/Electric Actuation General Description The TYCO DV5 Double Interlock Preaction System with Electric/Electric

More information

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description Worldwide Contacts www.tyco-fire.com DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to Inch (DN40 to DN200) General Description The TYCO DV-5a Automatic

More information

DELUGE VALVE DATA SHEET

DELUGE VALVE DATA SHEET FIRE FIGHTING EQUIPMENT DATA SHEET DELUGE VALVE DATA SHEET JOB NO. : RFQ. NO. : ISSUE : SHEET OF 01 CUSTOMER : ITEM NO. : 02 PROJECT : QUANTITY : 03 LOCATION : SERVICE : FIRE WATER AND / OR FOAM SYSTEM

More information

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION Page 1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

Instructions for Installation, Operation Care and Maintenance

Instructions for Installation, Operation Care and Maintenance Model A Dry Pipe Valve Bulletin 353 Rev.K Bulletin 353 Rev.K Instructions for Installation, Operation Care and Maintenance 2 1 2 (65mm) Valve With Model A Trim Listed by Underwriters Laboratories, Inc.

More information

Q= C v P S. Flow control valve Model j-2 Halar coated

Q= C v P S. Flow control valve Model j-2 Halar coated October 22, 2010 Flow Control 507a 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can

More information

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

Model DDX Deluge Valves 4 (100 mm), 6 (150 mm) and 165 mm Sizes Features 1. Differential-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot sprinklers Dry pilot actuators Solenoid valves 3. Drop in seat &

More information

Model DDX Deluge Valve 8 (200mm) Features

Model DDX Deluge Valve 8 (200mm) Features Model DDX Deluge Valve 8 (200mm) Bulletin 514 Bulletin 514 Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot

More information

Features 1. Differential Latch-type, lightweight, dependable

Features 1. Differential Latch-type, lightweight, dependable Bulletin 516 Rev. B Model DDX-SS Deluge Valve (100mm), (150mm) & (200mm) Bulletin 516 Rev. B Features 1. Differential Latch-type, lightweight, dependable construction. 2. Easily trimmed for releasing by:

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve, Limited Space Valve Cabinet General Description The TYCO DV-5 Remote-Resetting, Pressure-Reducing Deluge Valve,

More information

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50 Instructions for Installation, Operation, Care and Maintenance Model AGCX Deluge Valve (50 mm), ½ (65 mm), 3 (80 mm), 4 (00 mm), 6 (50 mm), 8 (00 mm) Wet Pilot Line, Dry Pilot Line, and Electric Actuation

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev. D Bulletin 507 Rev. D Instructions for Installation, Operation, Care and Maintenance 1 1 / 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim Actuated Valve with LPCB Approved Preaction Trim 104g/01 with: - Electric Activation with Redundant Solenoid Valve - Electric Activation with Redundant Solenoid Valve and AutoConvert Dry Trim - Double

More information

Technical Data. UL Listing is based on the following criteria:

Technical Data. UL Listing is based on the following criteria: Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN1 and DN15) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water

More information

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications Page 1 of 11 1. DESCRIPTION The Viking Model F-2 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching

More information

MODEL UMC UNIVERSAL MANIFOLD CHECK ASSEMBLY

MODEL UMC UNIVERSAL MANIFOLD CHECK ASSEMBLY 077 irpark Dr. Standish, MI 88 989-8-8 www.globesprinkler.com Technical Support 989--00 techservice@globesprinkler.com MODEL UMC UNIVERSL MNIFOLD CHECK (With or Without Control Valve) ¼", ½", ", ½", 7.mm,

More information

Instructions for Installation, Operation, Care, and Maintenance

Instructions for Installation, Operation, Care, and Maintenance Bulletin 750 Rev. B Model DDX Double Interlock Preaction System Type D 2 (50 mm), 2½ (65 mm), 3 (80 mm), 76 mm, 4 (00 mm), 6 (50 mm), 65 mm & 8 (200 mm) Bulletin 750 Rev. B Instructions for Installation,

More information

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 inch to inch (DN40 to DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11 Page 1 of 11 1. DESCRIPTION The Viking Model F-1 Dry Pipe Valve is a latching differential valve used to separate the water supply from the dry pipe sprinkler system. The valve combines a positive latching

More information

TotalPac 3 Deluge, Electric release Remote controlled system

TotalPac 3 Deluge, Electric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

TECHNICAL DATA 2-1/2-8 (dn65 - dn200) 1 of 13 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual

More information

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150)

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150) 1 of 12 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The Flow Control Valve can be used to facilitate manual

More information

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date MEA: 248-98-E CSFM: 7770-0531-117 The patent-pending Victaulic Series 769 FireLock NXT controls the water supply entry into the deluge system piping and open sprinklers. The Series 769 is a low differential,

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Model H Deluge Riser Assembly Bulletin 507 Rev.C Bulletin 507 Rev.C Instructions for Installation, Operation, Care and Maintenance 1 1 2 (40mm) Size Electric Actuation The Reliable Automatic Sprinkler

More information

TotalPac 3 Firecyle III Wet pipe Remote controlled system

TotalPac 3 Firecyle III Wet pipe Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications June 24, 2011 Flow Control 504a 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The Flow Control Valve can

More information

Wet pipe low flow foam/water manifold system

Wet pipe low flow foam/water manifold system December 6, 2010 Foam 15a 1. Description With the Wet Pipe Low Flow Foam/Water Manifold System, multiple risers can be supplied from a single proportioning device. A riser manifold is installed with various

More information

TotalPac 3 Deluge system Pneumatic release

TotalPac 3 Deluge system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE 1 of 13 1. DESCRIPTION Viking Deluge Valves are quick opening, differential diaphragm flood valves with one moving part. The Viking Model E-2 Halar Coated Deluge Valve is identical to the Viking Model

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4 Page 1 of 5 Model F Dry Valve with Trim Valve Size Part Number 3 13764PTR 4 13765PTR 6 13766PTR Standard Trim Sets include galvanized nipples and fittings. 4 Dry Valve Shown General Notes: Notes: For use

More information

Series 769 FireLock NXT Deluge Valve

Series 769 FireLock NXT Deluge Valve IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 79 FireLock NXT Deluge Valve With Deluge Trim Grooved X Grooved 30.81 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT DESCRIPTION The patent-pending

More information

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description Worldwide Contacts www.tyco-fire.com Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description The TYCO Model QRS Electronic Accelera tor is a quick

More information

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation Single Interlock Electric Release Preaction System 8 (200 mm) Size

More information

Series 758 FireLock Actuated System Valve

Series 758 FireLock Actuated System Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 58 FireLock Actuated System Valve With Deluge Trim Grooved X Grooved and Flanged X Grooved 30.04 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT

More information

CJ=TN=- FRONT DELUGE VALVE, EXTERNAL RESETTING. MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) a P il

CJ=TN=- FRONT DELUGE VALVE, EXTERNAL RESETTING. MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) a P il DELUGE VALVE, EXTERNAL RESETTING MODEL F470 MULTIMATIW - 4 and 6 INCH (100 and 150 mm) The 4 and 6 inch (100 and 150 mm), Model F470 External Resetting Multimatic Deluge Valves are differential latch type

More information

Easy Riser swing check valve Models E-1 & F-1

Easy Riser swing check valve Models E-1 & F-1 Page 1 of 7 1. DESCRIPTION The Viking Easy Riser Swing Check Valve is a general purpose rubber-faced approved for use in fire service systems. The valve is for use in wet system risers, preaction system

More information

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS. Page 1 of Telephone: 29-95-9501 Technical Services: 877-38-5 Fax: 29-818-180 Email: techsvcs@vikingcorp.com 1. GENERAL DESCRIPTION The Halar Coated Concentrate Control (CCV) is utilized in Viking foam

More information

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system (Optional) Description This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE August 31, 2006 Check Valve 815a 1. PRODUCT NAME Viking Easy Riser Swing Check Valve Model E-1: Available since 1992 Model F-1: Available since 1994 2. MANUFACTURER The Viking Corporation 210 N. Industrial

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 727 Rev. G Single Interlock Preaction System 4 (00mm), 6 (50mm) & 65mm Sizes Bulletin 727 Rev. G Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,4 bar) Pneumatic Supervising

More information

Section M Dry Pipe Systems

Section M Dry Pipe Systems Section M Dry Pipe Systems TABLE OF CONTENTS Dry Pipe System (Model G)... M-1 Dry Pipe System (Model F)... M-2 Accelerators / Air Maintenance Devices... M-3 Accessories and Components... M-4 Notes 1. Refer

More information

TotalPac 3 Non interlock Preaction system Pneumatic release

TotalPac 3 Non interlock Preaction system Pneumatic release (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description The TYCO Aluminum Bronze DV-5 Deluge Valves are available to provide an alternative material

More information

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in.

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in. August 19, 2003 Flow Control 504 a 1. PRODUCT NAME Viking Model H-2 Halar Coated Flow Control Valve 2" (50mm), 3" (80mm), 4" (100mm), 6" (150mm) Halar Coating Manufactured 1994-2. MANUFACTURER THE VIKING

More information

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Series 756 FireLock Dry System Check Valve

Series 756 FireLock Dry System Check Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series FireLock Dry System Check Valve Grooved X Grooved and Flanged X Grooved 0.0 VICTAULIC IS AN ISO 900 CERTIFIED COMPANY PRODUCT DESCRIPTION The Victaulic

More information

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date VNIIPO ME: 248-98-E CSFM: 7770-0531-117 The patent-pending Victaulic Series 769 FireLock NXT Preaction Valve controls the water supply entry into the Preaction system piping and sprinklers. The Preaction

More information

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology Technical Bulletin TB-ACV-LFF11RFP_SentryPlus LEAD FREE * LFF11RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology Installed upstream of Reduced Zone Backflow Preventer.

More information

Model RM-1 Riser Manifold Commercial and Residential General Description

Model RM-1 Riser Manifold Commercial and Residential General Description Worldwide Contacts www.tyco-fire.com Model RM- Riser Manifold Commercial and Residential General Description The TYCO commercial and residential Model RM- Riser Manifold provide the necessary waterflow

More information

Series 751 FireLock European Alarm Check Valve Stations

Series 751 FireLock European Alarm Check Valve Stations R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series FireLock European Alarm Check Valve Stations Grooved X Grooved 0.0 VICTAULIC IS AN ISO 00 CERTIFIED COMPANY PRODUCT DESCRIPTION The Victaulic Series

More information

ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE

ALARM CHECK VALVE 3, 4 & 6 MODEL H-1 FLANGE/FLANGE 3 & 4 MODEL H-2 GROOVE/GROOVE 3, 4 & 6 MODEL H-3 FLANGE/GROOVE DESCRIPTION AND OPERATION The Globe Model H-1, H-2 and H-3 Alarm Check Valves are used in wet pipe fire sprinkler systems. They primarily serve a dual purpose in that they prevent a reverse flow of water

More information

PRESSURE RELIEF / SUSTAINING CONTROL VALVES

PRESSURE RELIEF / SUSTAINING CONTROL VALVES PROJECT NAME LOCATION PRESSURE RELIEF / SUSTAINING CONTROL VALVES INTRODUCTION This specification covers the design, manufacture, and testing of 1 in. (25 mm) through 36 in. (900 mm) Control Valves PART

More information

January 2007 Approval Guide Fixed Extinguishing Systems 5-57

January 2007 Approval Guide Fixed Extinguishing Systems 5-57 Fixed Extinguishing Systems 5-57 CHEMETRON Fire Systems, 4801 Southwick Dr, 3rd Floor, Matteson IL 60443 High Pressure System Equipment. Automatic Actuator. 1-026-02, -0250. Alarm. 1-003-0033, -0070, -0071,

More information

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Frame Style Spray Nozzles are small, directional spray nozzles for use on water spray systems. They are thermosensitive glass bulb style nozzles, however they may be ordered

More information

Section P Flow Control and Pressure Regulation

Section P Flow Control and Pressure Regulation Section P TABLE OF CONTENTS Flow Control System... P-1 P-2 Pressure Regulation System... P-3 Alarm Devices... P-4 Pilot Operated Pressure Control Valves / Trim... P-5 P-6 Special Valves and Trim (Halar

More information

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P MANUAL NUMBER P-EFS-1 MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P TRAC Regulator Company Inc. 160 South Terrace Avenue Mount Vernon, New York USA 10550-2408 Phone: (914)

More information

Section L Wet Pipe Systems

Section L Wet Pipe Systems Section L TABLE OF CONTENTS Easy Riser System... L-1 Alarm Check Valve / Trim... L-2 Special Valves and Trim (Halar coated valves, brass trim, etc.)... L-3 Components and Accessories... L-4 Alarm Devices...

More information

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve Technical Bulletin TB-ACV-LFF11RFP LEAD FREE * LFF11RFP Flood Protection Shut Down Valve Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when continuous discharge from

More information

Val-Matic Air / Oil Hydraulic Panel Pump Control System. Operation, Maintenance and Installation Manual

Val-Matic Air / Oil Hydraulic Panel Pump Control System. Operation, Maintenance and Installation Manual Manual No. 5AOP-OM1-2 Val-Matic Air / Oil Hydraulic Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION...

More information

Colt Series C400, C500

Colt Series C400, C500 Colt Series C400, C500 RP/IS-A-C400/C500 C400 OSY Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies Sizes: 2 1 2" 10" (65 250mm) Installation Service Repair Kits Maintenance For other

More information

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , , Table 5.1.1.2 Summary of Sprinkler System Inspection, Testing, and Maintenance Item Frequency Reference Inspection Gauges (dry, preaction, and deluge systems) Quarterly 5.2.4.2, 5.2.4.3, 5.2.4.4 Control

More information

CIRCLE SEAL CONTROLS

CIRCLE SEAL CONTROLS CIRCLE SEAL CONTROLS ATKOMATIC SOLENOID VALVES INSTALLATION, MAINTENANCE, AND OPERATION INSTRUCTIONS 3000 SERIES Bronze, Normally Closed, Direct Lift Installation Instructions WARNING: These instructions

More information

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC Jacking Bolts Outlet Connection to Release (dry pilot line) Connection to Alarm Line ANGUS GW DELUGE VALVE VALVE 2 Drain Port Note: All Other Connections ½ Inlet External resetting of clapper via hand

More information

PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE

PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE PROJECT NAME LOCATION PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE INTRODUCTION This specification covers the design, manufacture, and testing of 2-1/2 in. (65 mm) through 18 in. (450 mm) Control

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 13, 2007 Spray Nozzle 31a 1. DESCRIPTION Viking Frame Style Spray Nozzles are small, directional spray nozzles for use on water spray systems. They are thermosensitive glass bulb style nozzles, however

More information

Section P Flow Control and Pressure Regulation

Section P Flow Control and Pressure Regulation Section P TABLE OF CONTENTS Flow Control System...P-1 P-2 Pressure Regulation System... P-3 Alarm Devices... P-4 Pilot Operated Pressure Control Valves / Trim...P-5 P-6 Special Valves and Trim (Halar coated

More information

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm. Model RPHBM Hydrant Backflow Meter Installation Testing Maintenance Instructions CAUTION: Installation of Backflow Preventers must be performed by qualified, licensed personnel. The installer should be

More information

Cla-Val. Service Training Manual. Simple solutions plus learning with a purpose

Cla-Val. Service Training Manual. Simple solutions plus learning with a purpose Cla-Val Service Training Manual Simple solutions plus learning with a purpose 5 Application Series Section General Identify What Valve You Have 5-1 Rate of Flow 40 Series 5-2 Pressure Relief 50 Series

More information

200 Series - Plastic Hydraulic/Electric Control Valves. Water Control Solutions

200 Series - Plastic Hydraulic/Electric Control Valves. Water Control Solutions - Plastic Hydraulic/Electric Control Valves Water Control Solutions Plastic Hydraulic/Electric Control Valves for residential, commercial and agricultural irrigation systems. The BERMAD plastic control

More information

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d April 15, 2011 Deluge Trim 227a Order Deluge Valve Separately This Trim Chart is for use with the following Viking Trim Sets Valve Size Galvanized Trim Part No. Brass Trim Part No. 3 (DN80) 14631-1 14631-2

More information

2 ½ 12. Model RP 4A Model RPDA 4A Model RPDA2 4A. Installation, Operation, and Maintenance Manual

2 ½ 12. Model RP 4A Model RPDA 4A Model RPDA2 4A. Installation, Operation, and Maintenance Manual BFMM4ARPLBF 08/10 Model RP 4A Model RPDA 4A Model RPDA2 4A Installation, Operation, and Maintenance Manual 2 ½ 12 Reduced Pressure Principle Backflow Preventer Reduced Pressure Detector Assembly Conbraco

More information

FireFlex DUAL Single Interlock, Remote controlled system

FireFlex DUAL Single Interlock, Remote controlled system FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated single interlock Electric release preaction automatic sprinkler system combined with a clean agent fire extinguishing

More information

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE Technical Data SD 4011 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE A SERIES AIR ADJUSTED PILOT PRINTED IN U.S.A. SD 4011/9504 Type A or A83 (wt 6 lb) Type A53 or A 85

More information

model E Spray nozzles vk810 - vk817

model E Spray nozzles vk810 - vk817 Page 1 of 10 1. DESCRIPTION Viking Model E, 3D Spray Nozzles are open type spray nozzles designed for directional spray applications in fixed fire protection systems. They have an open design only (nonautomatic)

More information

NYLON & PVC VALVES MINING DIVISION PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE PVC NYLON

NYLON & PVC VALVES MINING DIVISION PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE PVC NYLON MINING DIVISION NYLON & PVC VALVES PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE NYLON For Gold Mines DESCRIPTION The valve maintains a preset downstream pressure, regardless of upstream pressure

More information

BRAKE E

BRAKE E 8-1 GENERAL...8-2 SPECIFICATIONS...8-6 COMPONENTS...8-7 FRONT BRAKE...8-12 DISASSEMBLY INSPECTION REASSEMBLY (Pn1, Cu2 3 TON SERIES)...8-12 DISASSEMBLY INSPECTION REASSEMBLY (Pn2 3 TON SERIES)...8-17 BRAKE

More information

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A WATTS INDUSTRIES, INC. Technical Data SD 4512A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 PRINTED IN U.S.A. SD 4512A/9806 T124/T134 PILOT FRONT VIEW 2 1 /16 F 5 7 /8 2 3

More information