SECTION U -- STANDBY ENGINE/ALTERNATOR SETS
|
|
- Stuart Williamson
- 5 years ago
- Views:
Transcription
1 SECTION U -- STANDBY ENGINE/ALTERNATOR SETS CONTENTS PAGE 1. GENERAL... U Introduction... U-1 2. REQUIREMENTS... U General... U Exhaust Requirements... U Alarms... U Grounding... U Connections... U Fuel System... U Guards, Labels and Nameplates... U Testing and Acceptance... U Batteries... U Radiator... U Emergency Shut Down... U-4 TABLE U-1 SUMMARY OF CHANGES IN SECTION U Revision Date Item Action Requirements Change Notification 07/01/ Modification ATT-TP GENERAL 1.1. Introduction The Installation Supplier shall ensure, as part of the evaluation of the installation, that all equipment added, rearranged or modified is properly installed and in conformance with AT&T installation specifications (ATT ) The Installation Supplier shall assure, as part of the evaluation of the installation, that all work is performed in accordance with the detail specifications or approved changes to the detail specifications (ATT JP) This section covers the general requirements for the installation of stand-by engine/alternator sets Changes in this issue of Section U are summarized in Table U For more detailed information refer to ATT and ATT JP. U-1
2 Revised July, 2016 AT&T January, REQUIREMENTS 2.1. General All exterior engines and associated support equipment shall be protected by bollards, covers, or other protective obstructions to prevent damage from vehicles or other traffic Only cabling directly associated with the Engine / Alternator and fuel system shall be run into and out of the Engine/Alternator room/enclosure. Examples of permitted cable includes, the grounding cable, telecommunication cables (commonly referred to as telephones), Alarm Cabling, Telemetry, power for Engine/Alternator accessories, and the AC output of the Engine / Alternator set Exhaust Requirements Exhaust piping and duct connection joints shall not be insulated until the on-site full load testing has been completed and the bolts have been re-tightened A critical grade exhaust silencer equipped with a condensation drain, companion flanges, and a stainless steel bellows type exhaust fitting shall be provided. The flexible stainless steel bellows type exhaust fitting shall be installed within 12 of the exhaust manifold (if possible) All exhaust components exposed to outside elements (module or building) shall be stainless steel Alarms The Installation Supplier shall extend and terminate all specified alarm leads as designated by the AT&T Equipment Engineer. The terminal blocks shall be stenciled per Section L All new standby engine/alternator sets shall have the capability of forwarding alarms via TCP/IP to the appropriate alarm center. The alarms specified shall be the AT&T minimum alarms and required equipment specific alarms per AT&T drawing ATT-P E Grounding The engine/alternator set base/skid, start battery racks, battery chargers, and fuel day tanks (when present and of metallic construction), shall be bonded to the Common Bonding Network (CBN) with stranded copper grounding conductors in conformance with ATT-TP The set mounted control cabinet, meter cabinet/panel, and engine/alternator shall be bonded to the engine/alternator metallic base/skid. When present, a factory installed bond is sufficient. Such bonds shall be made with conductors designed to withstand engine/alternator vibrations When multiple parallel conduits are used a full sized grounding conductor shall be run in each conduit Equipment grounding conductors shall terminate within the engine/alternator cabinet provided for termination of phase conductors. Termination shall be made directly to a non-insulated ACEG bus bar To provide grounding continuity between the entire engine/alternator set and the equipment grounding conductors, the engine/alternator cabinet shall be electrically connected to the set frame in one of the following manners: a) By attachment hardware U-2
3 b) By a bonding strap of cross-sectional area equal to that of the grounding conductor specified Connections All field wire and cable connections shall be made in accordance with TP76300 section K The installation vendor shall provide means to prevent field-installed connectors from turning at termination points The standby engine/alternator set output leads (either single or three phase) shall be connected to the transfer switch, building AC or within a junction box termination point in the following manner: a) The correct compression type splice connector shall be utilized when the conductors between the alternator and AC transfer switch are spliced or directly joined together. b) Two-hole compression terminals may be utilized with a bus bar arrangement in the junction box or AC transfer switch when this arrangement is specified. c) Split bolt type connectors, sometimes called kearnies, shall NOT be used. d) The splice or junction box shall not be mounted on the engine/alternator set due to vibration. e) Liquidtight Flexible Metal Conduit (LFMC) shall be used between the junction box and engine/alternator set due to vibration Fuel System The AT&T Power Equipment Engineer/Capacity Manager will outline basic requirements of the fuel system, such as tank size and the need for a day tank in the ATT JP. CRE will design and implement the fuel system based on those requirements Fuel systems shall meet all local, state and federal permitting requirements The installation of all fuel systems shall be reviewed by AT&T EH&S. Any time the fuel system (i.e., piping, day tank, fuel storage tank, etc.) from the standby engine/alternator set to any fuel tank supporting the engine/alternator set requires work, the Installation Supplier shall contact the AT&T Environmental Health & Safety at KNOW EHS before beginning work Fuel lines that are located outside the building and exposed shall be protected from being crushed Both the fuel and return lines shall have flexible sections connected to the engine/alternator set All field installed fuel hoses shall be of proper length without looping, sharp bends or excessive slack Pipe sealant shall be used on all fittings Day tanks, when required, shall be located in an engine room that serves as a spill containment room, or if the room does not serve as spill containment, shall be equipped with spill containment dams of adequate capacity to contain the contents of the day tank Guards, Labels and Nameplates All phase leads between the engine/alternator set and the control board shall be marked showing the phase rotation All piping shall be directionally labeled and isolation valves shall be position labeled. U-3
4 Revised July, 2016 AT&T January, Installation Supplier shall ensure that all high temperature warning labels, insulation, ventilation guards, and safety guards recommended by the manufacturer and provided in accordance with TP76400 section 16 are properly affixed All set screws, bolts, keys or keyways shall have no projecting or sharp edges or be suitably guarded. All in-running gears and sprockets shall be completely enclosed or provided with band guards around the face of the gear or sprocket. Working personnel shall not be able to touch any rotating part The engine/alternator set AC panel shall have the far end destination point labeled clearly Testing and Acceptance General testing and acceptance details are described in ATT-TP Engine/alternator set testing and acceptance details are described in ATT JP. The Installation Supplier shall follow the procedures and requirements set forth in these documents for testing and acceptance of engine/alternator sets The Installation Supplier shall verify the availability of lubricating oil and permanent antifreeze required for standby engine/alternator sets The Installation Supplier shall verify that the engine/alternator contains the proper levels of lubrication oils and water/antifreeze mixture before the initial test run All personnel working in the vicinity of operating engine/alternator sets shall wear ear and eye protection The engine/alternator set shall not be started until a manufacturer s representative has performed the initial start-up The Installation Supplier shall provide resistive type load bank(s) and connection cables capable of absorbing 110 % of the engine/alternator s rated output in kilowatts during shop test and on site load testing The Installation Supplier shall provide a representative to assist AT&T personnel in acceptance testing Start Batteries The engine starting batteries shall be chosen and sized per ATT , sections and Anti-corrosion coating such as NO-OX-ID-A shall be applied to all battery terminals and connections All battery cables shall be secured per section J to prevent chaffing The engine/alternator set start and control batteries shall be located so the cells are not exposed to excessive heat All batteries shall be contained in an appropriately grounded rack or other manufacturer recommended container that meets local seismic requirements Radiator U-4
5 Any radiator not located on the engine/alternator base/skid shall comply with all remote radiator requirements specified in ATT Radiator piping and AC conduit shall not be supported by the radiator stand All radiator piping shall be painted with a high temperature outside paint Radiator piping shall have braided stainless steel flexible lines with finished ends, flange coupled, at the engine/alternator set and radiator Emergency Shut Down Both the generator set control cabinet and the alarm annunciator panel shall be equipped with emergency shutdown switches. See , for details regarding the alarm annunciator panel The emergency shutdown switch for the engine shall be designated and covered to prevent accidental activation. [END OF SECTION] U-5
SPECIAL SPECIFICATION 8676 Solar Panel Power Supply System
2004 Specifications CSJ 2552-01-033 SPECIAL SPECIFICATION 8676 Solar Panel Power Supply System 1. Description. This work shall consist of furnishing and installing an integrated Solar Panel Power Supply
More information.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates
Issued 2005/06/01 Section 16239 Power Generation to 30 kw Page 1 of 7 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01355 Waste Management and Disposal..2 Section 01810 Commissioning..3 Section 03100 Concrete
More informationSpecification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings
Page 1 Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings I. General This specification covers the design requirements for a pad-mounted capacitor
More informationInstallation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries
RS-2046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES.
More informationSECTION CENTRIFUGAL HVAC FANS
SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationDiesel Engines for Fire Protection Applications
Cincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for Fire Protection Applications Based on NFPA 20 2010 Edition www.clarkefire.com NFPA 20 Engine Type Diesel Engines for fire pump drive shall
More informationDARTMOUTH COLLEGE DESIGN February 15, 2006 & CONSTRUCTION GUIDELINES
PART 1 - DESIGN DIRECTIVES 1.1 SUMMARY SECTION 15160 PUMPS A. Related Sections: The following sections contain requirements that relate to this section: 1. DC Standards ELECTRICAL REQUIREMENTS FOR MECHANICAL
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationFiber Optic Above-Ground) Cross-Connect Enclosure (ACE) Model ACE-200DS Installation Guide)
Fiber Optic Above-Ground) Cross-Connect Enclosure (ACE) Model ACE-200DS Installation Guide) 13536-A Figure 1. ACE-200DS Enclosure With OCM-HD Panels Content Page INTRODUCTION... 2 1 PRODUCT DESCRIPTION...
More informationSECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems
COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationInstruction Manual. for Heating Cables and Cold Leads Type and Catalogue no and Hemstedt GmbH.
Instruction Manual for Heating Cables and Cold Leads Type 68994- and 68997- Catalogue no. 68994- and 68997- Hemstedt GmbH Schleicherweg 19 D-74336 Brackenheim-Botenheim Phone +49 (7135) 9898-0 Fax +49
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationVRLA Batteries. Battery Installation And Start up Guide
TECHNICAL MANUAL 41-7525 VRLA Batteries 26-206 Ampere-Hour Capacity Battery Installation And Start up Guide (For Rack Mounted Systems) 41-7525/0514/CD www.cdtechno.com Table of Contents 12V VRLA Battery
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationTechnical Summary of Battery Energy Storage Systems
Technical Summary of Battery Energy Storage Systems Based on the 2017 Massachusetts Electrical Code This document summarizes the new Article 706 in the Massachusetts Electrical Code (MEC). Article 706
More informationSPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.
City of Cartersville Electric System P.O. Box 1390 320 S. Erwin St. Cartersville, GA 30120 770-387-5631 March 2006 SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS This specification provides standardization
More informationSERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING
SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company
More informationMATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****
Page 1 of 8 ****Supercedes BECo Standard E2.12-2.12 and ComElectric Spec 6-0895**** 1.0 General Requirements SINGLE PHASE PAD-MOUNTED DISTRIBUTION TRANSFORMERS 1.1 These specifications cover single-phase
More informationICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical
ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements 1. PURPOSE sponsored by ABYC, BMF, ICOMIA, IMCI, and NMMA Author: Wieger de Wit Guideline Number 3 Electrical
More informationCellwatch Electrical Installation
Tech20081110-1-1 Cellwatch Electrical Installation Critical Distances...2 Typical Layout...3 Typical ibmu Placement...4 Typical Control Unit Placement...5 Physical Mounting and Location - General...6 CU
More informationCAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877
CAT-1 Series 3 Installation Guide The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 (203) 431-0262 (203) 431-0296 FAX tvg@cat-1.com Installation of Load Cells for CAT-1 Systems
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationTechnical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP
United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February
More informationPollution Prevention Training. Unit 4 Generating New Options
P2 Pollution Prevention Training Unit 4 Generating New Options Unit 4: Generating New Options Unit Outline How to Generate New Options How to Recommend a TO Change P2 Pollution Prevention Training Unit
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationINSTALLATION INSTRUCTIONS
TT-1079 9/95 INSTALLATION INSTRUCTIONS Original Issue Date: 9/95 Model: 20-60 kw (Detroit Diesel Powered) Market: Industrial Subject: Sound Shield Enclosure Kits PA-324742-SD, 324742-SD, PA-324743-SD,
More information1. General Requirements
Ge n e ra lre q u ire me n ts 2016 Electric Service Requirements, 3rd Edition Section 1 Section 1 General Requirements Directory Page 1.1 Manual Purpose and Scope 1 1.2 Customer and Power Company Defined
More informationP Original Series Cargo Van Lift Mounting Instructions Fullsize Ford Van present. Preparing the Gate
Fullsize Ford Van- 1992-present Preparing the Gate 1. Remove the mounting hardware which is banded to the liftgate. 2. Verify mounting kit (Figure 1 and Table 1). S-400-40 STRAP VAN MOUNTING EAR BENT BRACKET
More informationAUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-4800 BBS-4800E
AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-4800 BBS-4800E SENS part no: 101312 Document revision: K DCN No. 107455 Date 4/2/18 1840 Industrial Circle Longmont, CO 80501 Fax: (303) 678-7504
More informationSECTION AXIAL HVAC FANS
SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationPrecision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL
POWER CONVERSION/DISTRIBUTION Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL 3 Phase 15 kva - 225 kva 50 & 60 Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1
More informationTubeTrace Tubing Bundles
for Custom CEMS and Analytical Umbilicals English Units Receiving, Storing and Handling... 1. Inspect materials for damage incurred during shipping. Report damages to carrier for settlement. 2. Identify
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationSmartBoost 50 INSTALLATION INSTRUCTIONS & OWNER S MANUAL LT93 SMTBST50 1. Issue 1 Print 2 AUTOMATIC SHORELINE TRANSFORMER
SmartBoost 50 AUTOMATIC SHORELINE TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL 1 Contents INTRODUCING... THE SmartBoost 50............................................................ 3 Manual
More informationEMC INSTALLATION INFORMATION
EMC INSTALLATION INFORMATION For: SANYO DENKI Stepper Motors RTA Stepper Drives AUTOMATED MOTION SYSTEMS PTY.LTD. MAILING ADDRESS: P.O.BOX 1240 WANGARA DC W.A. 6947 PHONE: (08) 9309 1896 FAX: (08) 9309
More informationSPECIFICATION FOR. MAINTENANCE OF POWERED LIFTING PLATFORMS (for use by disabled persons)
SPECIFICATION FOR MAINTENANCE OF POWERED LIFTING PLATFORMS (for use by disabled persons) INDEX MAINTENANCE REPORTS MANUFACTURER S REQUIREMENTS PERMIT TO WORK CERTIFICATION GUIDANCE MINOR REPAIRS Platform
More informationOptimizing Emergency Power Systems for Health Care Applications
2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan
More informationMATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****
Page 1 of 8 ****Supercedes BECo Standard E2.12-2.14 and ComElectric Spec 7-0895**** THREE-PHASE DEADFRONT PAD-MOUNTED DISTRIBUTION TRANSFORMERS, LOOP & RADIAL FEED DESIGNS 1.0 General Requirements 1.1
More informationInstallation and Commissioning of Auxiliary Power Unit
Models PC6012 PC6013 PC6014 PC6015 PC6022 PC6023 PC6024 Installation and Commissioning of Auxiliary Power Unit 30-871-21 Rev. E Warning & Cautions Vehicles with longer wheel bases should have the APU mounted
More informationINSTALL INSTRUCTIONS DC C-EV. Installation Instructions: DC C-EV.
INSTALL INSTRUCTIONS DC6-48-60-0-8C-EV Installation Instructions: DC6-48-60-0-8C-EV INSTALL INSTRUCTIONS DC6-48-60-0-8C-EV Contents Section Description Page 1 Copyright 2 1.1 Disclaimer 2 1.2 Warnings
More information************************************************************************************************************* PART 1 GENERAL 1.
16620 STANDBY EMERGENCY ELECTRICAL GENERATOR (CNG/LPG) ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number:
More informationSPECIAL SPECIFICATION 6894 Communication Cabinet
2004 Specification CSJ 0353-04-085, etc. SPECIAL SPECIFICATION 6894 Communication Cabinet 1. Description. Furnish and install communication cabinet to include the installation of the foundation, cabinet,
More informationExpert Design...Trusted Power
Expert Design...Trusted Power 350 750 kva Range Performance I Durability I Serviceability A new power standard has arrived. The 350 750 kva range from FG Wilson is designed by our expert engineers to
More information5. Contractor Information 3M Model 2300 Series System Layout Checklist
5. Contractor Information 3M Model 2300 Series System Layout Checklist This checklist contains the information necessary to provide the environment required to successfully install your new Model 2300
More informationAutomatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit
Instruction Sheet 10-2004 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch.
More informationSPECIAL SPECIFICATION 1788 Surveillance Cabinet
1993 Specifications CSJ 2266-02-095 SPECIAL SPECIFICATION 1788 Surveillance Cabinet 1. General. This Item shall govern the furnishing and installation of Surveillance Cabinet to include the installation
More informationDefinitions. Scope. Customer Generation Interconnection Requirements
Updated 02/1 Page 1 Scope The purpose of this document is to describe Idaho Power s requirements for the installation and testing of Customer Generation acilities that are interconnected with Idaho Power
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Acceptance Inspection Date of Review / / BLD20 - Project Address: Project Name: Numbers following worksheet comments represent an NFPA
More informationc. Single battery installations must comply with the 18 inch envelope for dielectric
1. Which of the following is a true statement? a. Multiple battery installations must comply with the 12 inch envelope for dielectric shielding when required. b. Multiple battery installations must comply
More informationInstallation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries
RS02046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES.
More informationINSTALLATION MANUAL CRYSTALLINE SOLAR MODULES
Sapphire Solar Pty Ltd Phone: 1300 308 751 Email: customerservice@sapphire-solar.com 4/320 Lorimer Street, Port Melbourne VIC Australia 3207 TABLE OF CONTENTS 1. ABOUT THIS MANUAL... 3 2. DISCLAIMER OF
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationThermoLite 110W-330W Solar Panel Installation Instructions
ThermoLite 110W-330W Solar Panel Installation Instructions INSTALL APPLICATIONS SUPPORTED BY THIS GUIDE: 1. Trailer Roof Top Mounted 2. Bus Roof Top Mounted 3. Tractor Fairing Mounted 40W and 110W Replacement
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationInfinity 1U 19 Converter Shelf Models: J L224-48V to +24V, L V to -48V
GE Critical Power Quick Start Guide Infinity 1U 19 Converter Shelf Models: J5964803 L224-48V to +24V, L225 +24V to -48V Edge Controller example Outputs RTNs Inputs RTNs Refer to Infinity Converter Brochure
More informationINTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY
INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application
More informationKD1E Range Potential Indicators
KD1E Range Potential Indicators Operating Instructions 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Limited Warranty & Limitation
More informationCHAPTER 10 ELECTRICAL. Notes:
CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic
More informationBULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven
BULLETIN 456 July 1997 VANEAXIAL FANS Type W Direct Drive/Belt Driven Model VW Direct Drive Model VWBD Belt Driven Aerovent certifies that the Type W Vaneaxial Fans shown herein are licensed to bear the
More informationGENERAL FEATURES / SPEC M&H AWWA C502 FIRE HYDRANTS Style 929 Traffic Model 250 PSI Working Pressure 500 PSI Hydrostatic Test AWWA UL / FM Approval Type: Compression type, opening against line pressure.
More informationThermal Wraps. GT Exhaust Accessories Installation and Operation Manual. Rev. A. Copyright 2012 GT Exhaust, Inc. All Rights Reserved
Thermal Wraps GT Exhaust Accessories Installation and Operation Manual Rev. A Copyright 2012 GT Exhaust, Inc. All Rights Reserved Published: December 20, 2012 NOTICE The instructions herein must be expressly
More informationTable of Contents 1. SCOPE Toronto Hydro Requirements Enclosed Switchgear Ontario Electrical Safety Code SI Units..
Section Table of Contents Page 1. SCOPE 1 1.1 Toronto Hydro Requirements 1 1.2 Enclosed Switchgear.. 1 1.3 Ontario Electrical Safety Code.. 1 1.4 SI Units.. 1 2. PURPOSE. 1 3. DEFINITIONS. 2 4. EXTENT
More informationRequirements for the Design & Construction of Customer-Owned High-Voltage Substations
Table of Contents 1. SCOPE... 7 1.1 Toronto Hydro Requirements... 7 1.2 Enclosed Switchgear... 7 1.3 Ontario Electrical Safety Code and Ontario Building Code... 7 1.4 SI Units... 7 2. PURPOSE... 8 3. DEFINITIONS...
More informationEclipse Hermetic Gas Boosters
Information Guide 620 12/1/2008 Eclipse Hermetic Gas Boosters Series HB & HBLC Version 1 Applications Eclipse Inc., produces a line of single stage, centrifugal type, hermetically sealed gas boosters for
More informationTPD2250H6.3 TECHNICAL DATA
TECHNICAL DATA DIESEL GENERATING SET TONTEK POWER LIMITED GREEN POWER SUPPLIER 50HZ www.tontekpower.com Page: 1/10 Specifications may change without Notice TPD2250H6.3 2250KVA/1800KW POWERED BY CUMMINS
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 23 30 00 - HVAC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical
More informationSECTION FUEL-OIL DISTRIBUTION (APPLIES TO FUEL TANKS FOR GENERATORS)
SECTION 02554 - FUEL-OIL DISTRIBUTION (APPLIES TO FUEL TANKS FOR GENERATORS) 1.1 SUMMARY A. Storage tanks, fuel oil, tank accessories, piping, valves, and specialties for fuel-oil distribution inside and
More informationINSTRUCTION MANUAL FOR PC63 CAGE
INSTRUCTION MANUAL FOR PC63 CAGE CPN106833 ISSUE DATE: 15689-12/02 ECN/DATE 106 BRADROCK DRIVE DES PLAINES, IL. 60018 (847) 299-1188 FAX: (847) 299-3061 16816-6/05 INSTRUCTION DRAWING NUMBER: P25-LPC63-1
More informationSOLAR HEATING SYSTEM
SECTION 13600 SOLAR HEATING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07600 - Flashing and Sheet Metal. 2. 07900 - Joint Sealers. 3. 15260 - Thermal Insulation (Plumbing). 4. 15410 - Piping
More informationME 463 Electronics Design
ME 463 Electronics Design Following this procedure will help the e-shop personnel assist you to (1) improve the quality and viability of the electrical part of your project, and (2) increase the safety
More informationACI Hoist & Crane. Festoon System. 689 S.W. 7th Terrace Dania, FL (954) Fax (954) Toll Free A-HOIST ( )
ACI Hoist & Crane Festoon System 689 S.W. 7th Terrace Dania, FL 33004 (954) 921-1171 Fax (954) 921-7117 Toll Free 1-888-4-A-HOIST (1-888-424-6478) www.acihoist.com 2 Standard Duty C-Track Index 1. General
More informationWARNING. Murphy W-Series Engine Panels General Installation Instructions. Installation Accessories
Murphy W-Series Engine Panels General Installation Instructions WS-93002N Revised 04-06 Section 30 (00-02-0191) Read the following information before installing. These installation instructions are typical
More informationREVISIONS. App Thom. App Sud. App PC T.C. 2013/10/01
REQUIREMENTS / REVISIONS Rev Description Rev n by Sud PC Thom VB LH Clyd Act Issue Date YYYY/MM/DD Standard Created T.C. 203/0/0 T.C. 203/0/0 Pending Pending Pending Pending Pending Pending 203/0/0 Sud
More informationELECTRICAL AREA CONTROLLED ACCESS PROCEDURE SP-18 NATIONAL HIGH MAGNETIC FIELD LABORATORY NHMFL FLORIDA STATE UNIVERSITY SAFETY PROCEDURE SP-18
NATIONAL HIGH MAGNETIC FIELD LABORATORY NHMFL FLORIDA STATE UNIVERSITY SAFETY PROCEDURE SP-18 CONTROLLED ACCESS PROCEDURE HEAD of MAGNET OPERATIONS Bryon Dalton EH&S MANAGER Angela Sutton HEAD OF FACILITIES
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More informationWARNING. Murphy W-Series Engine Panels General Installation Instructions. Installation Accessories
Murphy W-Series Engine Panels General Installation Instructions WS-93002N Revised 08-02 Section 30 (00-02-0191) Read the following information before installing. These installation instructions are typical
More informationSECTION 8. WIRING INSTALLATION INSPECTION REQUIREMENTS
9/8/98 AC 43.13-1B SECTION 8. WIRING INSTALLATION INSPECTION REQUIREMENTS 11-96. GENERAL. Wires and cables should be inspected for adequacy of support, protection, and general condition throughout. The
More informationTable of Contents 1. SCOPE... 5
Table of Contents 1. SCOPE... 5 1.1 Toronto Hydro Requirements... 5 1.2 Enclosed Switchgear... 5 1.3 Ontario Electrical Safety Code and Ontario Building Code... 5 1.4 SI Units... 5 2. PURPOSE... 6 3. DEFINITIONS...
More informationSECTION SOLAR ENERGY ELECTRICAL POWER GENERATION SYSTEM
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 30 05 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // --- // if not applicable to project. Also, delete any other item or paragraph
More informationSECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS
SECTION 08350 HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1
More informationBID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR
BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR Bid Specifications for 300 kw Standby Generator Compliance CITY OF GENEVA PUBLIC WORKS DEPARTMENT ENGINE In-Line Six Cylinder, turbocharged ATAAC aspirated,
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More informationVD0C06N908C July 1998 Raleigh, NC, USA. Instruction Bulletin ALTIVAR 66, ALTIVAR 58, ALTIVAR 18. Dynamic Braking Resistor Kit User s Manual
Instruction Bulletin VD0C06N908C July 1998 Raleigh, NC, USA ALTIVAR 66, ALTIVAR 58, ALTIVAR 18 Dynamic Braking Resistor Kit User s Manual DANGER HAZARDOUS VOLTAGE Read and understand this bulletin in its
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 23 2123 - PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More information60 Hz FEATURES. Exclusively from your Caterpillar dealer
D I E S E L G E N E R A T O R S E T S STANDBY PRIME 60 Hz 60-100 kw 54-90 kw Model Standby Prime kw (kva) kw (kva) D60P4S* 60 (60) 54 (54) D75P3 75 (93.8) 68 (85) D80P4* 80 (100) 72 (90) D75P1S 75 (75)
More informationScope of Supply / Major Bill of Materials
Scope of / Major Bill of Materials The following table summarizes major scope of supply for this project. The tables also include a list of major parts that will be provided by customer/others. Additional
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationSECTION 8. WIRING INSTALLATION INSPECTION REQUIREMENTS
9/8/98 AC 43.13-1B SECTION 8. WIRING INSTALLATION INSPECTION REQUIREMENTS 11-96. GENERAL. Wires and cables should be inspected for adequacy of support, protection, and general condition throughout. The
More informationAP59-6. Model Name AP59-6 Frequency / PF 60Hz, 1800 rpm, 0.8pf. Engine Make & Model Perkins 1103A-33TG1 Alternator Make Stamford
AKSA Power Generation has been producing industrial generator sets with an innovative compact design and excellence in quality for over 30 years. AKSA has been providing reliable power through three main
More informationMODEL ELC-12/40-CVM-D BATTERY CHARGER
NATIONAL RAILWAY SUPPLY MODEL ELC-12/40-CVM-D BATTERY CHARGER Installing, Operating and Service Instructions for the ELC-12/40-CVM-D Solid State Charger PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING
More informationK25000 & KD25000 Series
K25000 & KD25000 Series Fire Alarm Power Supplies Installation, Commissioning and Operating Manual Man-1128 Issue 14 January 2016 Man-1128_K25400_series_Power_Supply_Manual_14 Page 1 of 20 Section Page
More informationAVOIDING ELECTROCUTION HAZARDS
Print AVOIDING ELECTROCUTION HAZARDS MODULE DESCRIPTION This module will provide information that helps you recognize and avoid common electrocution hazards in your work environment. OBJECTIVES After completing
More informationINSTALLATION INSTRUCTIONS AND OPERATION MANUAL
INSTALLATION INSTRUCTIONS AND OPERATION MANUAL FS Series Rolling Fire Door Operators UL325-2010 Compliant Restricted Duty Operators CORPORATION IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the
More information