THREE PHASE PMT SINGLE PHASE PMT METHOD OF INSTALLING ARTIFICIAL IVY ON PADMOUNT CABINETS CO CITY OF ANAHEIM
|
|
- Shanon Snow
- 5 years ago
- Views:
Transcription
1 SCOPE: THIS STANDARD SHOWS THE METHOD OF INSTALLATION OF ON. A. TRANSFORMER PADMOUNT RISER NUMBER (EXAMPLE: RC892) (EXAMPLE: 1976) TRANSFORMER NUMBER 6" THREE PHASE PMT REV RISER NUMBER TRANSFORMER NUMBER (TYP) SINGLE PHASE PMT & LOCK ASSEMBLY METHOD OF INSTALLING ON SHEET 1 OF 8
2 B. AUTOMATIC TRANSFER SWITCH, PADMOUNT CIRCUIT IDENTIFICATION AUTO TRANSFER SWITCH (A.T.S.) DESIGNATION NUMBER XXXXXXXX XXXXXX ATS XXX 6" PREFERRED/EMERGENCY IDENTIFICATION CIRCUIT IDENTIFICATION (REFER TO CO 17) ATS (AUTOMATIC TRANSFER SWITCH) CO REV METHOD OF INSTALLING ATIFICIAL IVY ON SHEET 2 OF 8
3 C. 15KV 6 AMP PADMOUNT LIVE FRONT FUSE CABINET (PMH) COMPARTMENT IDENTIFICATION USE 1" NUMBERS CIRCUIT INTERRUPTER (CI) IDENTIFICATION 1 USE 2 2" LETTERS AND NUMERALS CLEARANCE STICKER. PADMOUNT CABINET IDENTIFICATION ON CENTER OF STREET SIDE - USE 2 1/2" LETTERS AND NUMERALS CO REV ADDED / REVISED TEXT ADDED / REVISED MATERIAL - REVISION KEYS: - METHOD OF INSTALLING ON SHEET 3 OF 8
4 D. SWITCHED CAPACITOR BANK, PADMOUNT (EXAMPLE: 1976) PSC NUMBER (EXAMPLE: PSC123) FRONT SIDE CO REV BACK SIDE PSC (PADMOUNTED SWITCHED CAPACITOR) METHOD OF INSTALLING ON SHEET 4 OF 8
5 E. 15KV 6 AMP DEAD FRONT SWITCH (VFI), PADMOUNT (EXAMPLE: 1976) PMV NUMBER (EXAMPLE: PMV 123) CO REV PMV (PADMOUNTED VFI SWITCH) METHOD OF INSTALLING ON SHEET 5 OF 8
6 F. DISTRIBUTION FUSE CABINET LIFTING LUGS COVER SIDES & BACK IF ACCESSIBLE XXX FRONT VIEW DFC (DISTRIBUTION FUSED CABINET) FUSE CABINET NUMBER (EX. DFC-1) LIFTING EARS REMOVABLE RADIO ANTENNA OPTIONAL CO REV COVER SIDES & BACK IF ACCESSIBLE W/ PAD LOCK PROVISIONS * FRONT VIEW AC (AUTOMATION CABINET) METHOD OF INSTALLING ON SHEET 6 OF 8
7 WIRE TIE MOUNT GRID LINES (NOTE 15) 12" MAX (TYP) 12" MAX (TYP) FRONT SIDE TYPICAL WIRE-TIE-MOUNT APPLICATION ITEM# DESCRIPTION QTY. MANUFACTURER STOCK CODE CU MFR MODEL 1 AS NEEDED IVY-IT WIRE TIE MOUNT AS NEEDED WELD MOUNT SYSTEM* ---- AT-5 (BLACK) 3 ADHESIVE AS NEEDED WELD MOUNT SYSTEM* ---- AT-21 CO REV * METHOD OF INSTALLING ON SHEET 7 OF 8
8 NOTES: 1. SHOULD BE INSTALLED USING NON-INTRUSIVE MATERIAL, AND SHOULD LEAVE NO OR MINIMAL RESIDUE AFTER REMOVAL FROM EQUIPTMENT SURFACE. THE RESIDUE SHOULD BE REMOVABLE AND CLEANABLE WITHOUT LEAVING ANY MARK OR DAMAGE TO EQUIPMENT CABINET. 2. INSTALL ONLY ON SURFACES VISIBLE TO THE PUBLIC, UNLESS OTHERWISE APPROVED BY THE UTILITY INSPECTOR. INCLUDE TRANSFORMER OUTSIDE FINS. 3. DOOR SEAMS SHOULD NOT BE COVERED AND INSIDE OF CABINET SHOULD BE ACCESSIBLE FOR OPERATING AND AINING EQUIPMENT. 4. OF EQUIPMENT IF EQUIPMENT IS SHORTER THAN 4 FEET OR TOP IS REACHABLE FOR APPLYING GRAFFITI. 5. USE NYLON TIE WRAP WITH UV RATING TO INSTALL TO WIRE TIE MOUNT. 6. WASH EQUIPTMENT OFF OF LOOSE DIRT /SOOT ETC. (IF EQUIPMENT HAS RUST, HOLES, SHOWS ANY SIGNS OF OIL LEAKAGE, OR ANY OTHER DAMAGE OF ANY SORT REPORT IT TO CITY REPRESENTATIVE IMMEDIATELY). 7. PAINT OVER GRAFFITI MARKINGS WITH MUNSELL GREEN 7GY3.29/1.5 PAINT AS NEEDED. 8. APPLY/REPLACE ALL EQUIPMENT IDENTIFICATION MARKINGS, WARNING STICKERS, AND ANY OTHER LABELS THAT ARE REQUIRED. 9. PRIOR TO IVY INSTALLATION USE INFRA-RED GUN TO TAKE TEMPERATURE READINGS. 1. APPLY WIRE-TIE-MOUNT TO EACH OF THE FOUR SIDES AND TOP OF THE EQUIPMENT LESS THAN 12" APART AS NEEDED (THE NUMBER OF TABS VARIES DEPENDING ON THE SIZE OF THE EQUIPMENT). USE THE TWO PART EPOXY GLUE RECOMMENDED BY THE TAB MANUFACTULRER TO ADHERE TABS TO THE EQUIPMENT. 11. TRIM IVY TO DESIRED LENGTHS AND SHAPES TO EXPOSE ALL WARNING LABELS AND EQUIPMENT MARKINGS. 12. TRIM IVY FOR S AND TO ALLOW DOORS TO OPEN AND CLOSE WITHOUT INTERFERENCE. 13. APPLY BY CABLE TYING TO WIRE-TIE-MOUNTS APPLIED IN STEP 1, USING UV RATED CABLE TIES. CO REV 14. AFTER INSTALLATION OF IVY IS COMPLETE, TAKE ADDITIONAL TEMPERATURE READING ON ALL FOUR SIDES OF THE EQUIPMENT, RECORD READINGS. 15. TO PLACE WIRE-TIE-MOUNTS ACCURATELY IDENTIFY THEIR LOCATIONS BY DRAWING GRIDLINES AS SHOWN ON PAGE 6. * METHOD OF INSTALLING ON SHEET 8 OF 8
MDS Dead-front Padmount Switchgear Style Guide 1VAM SG May 2010 Revision D
MDS Dead-front Padmount Switchgear Style Guide 1VAM224804-SG May 2010 Revision D The MDS style guide aids in the proper selection of your style number. When ordering the MDS, the style number must be given
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 10/03/17 Specifications for Residential Construction Revision List REVISION Date Page No. Description 8/18/09 T.O.C., 8.1-8.1.5 &
More information35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses
Page 1 2016 EPMR-35-311S-R2/ESW-CM9 Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton s CPS LRTPs 50 Amp (Max) 27 kv Clip-Mounted NX Fuse Provisions 21.1/36.6 kv Grounded Wye Max Design, 150 kv
More informationSolid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER
Solid Dielectric Load Break Switch SPECIFICATION 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED VACUUM LOAD INTERRUPTING
More informationThermoLite 110W-330W Solar Panel Installation Instructions
ThermoLite 110W-330W Solar Panel Installation Instructions INSTALL APPLICATIONS SUPPORTED BY THIS GUIDE: 1. Trailer Roof Top Mounted 2. Bus Roof Top Mounted 3. Tractor Fairing Mounted 40W and 110W Replacement
More informationSERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES
SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 04/25/18 Specifications for Residential Construction Revision List REVISION Date Page No. Description 03/20/00 6.1-6.2 Added Armorcast
More informationINDEX Welcome 1.2 Contacting Powergrid Solutions, Inc. 1.3 Terms Of Usage 1.4 Product Codes and Descriptions
INDEX SECTION 1 INTRODUCTION 1.1 Welcome 1.2 Contacting Powergrid Solutions, Inc. 1.3 Terms Of Usage 1.4 Product Codes and Descriptions SECTION 2 PADMOUNTED ENCLOSURES/CABLE SWITCHING/TERMINATING GEAR
More informationSPECIFICATIONS FOR COMMERCIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR COMMERCIAL CONSTRUCTION REVISED 06/28/18 Commercial Construction Specifications Revision List REVISION Date Page No. Description 03/01/00 4.2-4.3 Changed leveling
More informationSpecification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings
Page 1 Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings I. General This specification covers the design requirements for a pad-mounted capacitor
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationFEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation
FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation Elastimold solid dielectric switchgear agenda Compelling value Design principles Product overview Switchgear applications
More information15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch
Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and
More informationOPERATION AND MAINTENANCE OF TRAYER 4000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER
OPERATION AND MAINTENANCE OF TRAYER 4000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER 1) INTRODUCTION 2) CAUTIONS 3) RECEIVING A) UNPACKING B) INSPECTION C) HANDLING D) STORAGE 4) INSTALLATION A) PRE-INSTALLATION
More information34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE
4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationNEW Solutions for Underground System Growth
NEW Solutions for Underground System Growth Cooper s Single-Phase Voltage Regulator Improved Power Quality More Economical Improved System Reliability Increased Safety Better Aesthetics Lower Maintenance
More informationOPERATION AND MAINTENANCE OF TRAYER 3000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER
OPERATION AND MAINTENANCE OF TRAYER 3000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER 1) INTRODUCTION 2) CAUTIONS 3) RECEIVING A) UNPACKING B) INSPECTION C) HANDLING D) STORAGE 4) INSTALLATION A) PRE-INSTALLATION
More informationPan & Tilt Kit (REV-C)
PANDORA Pan & Tilt Kit (REV-C) www.dpcav.com The items shown in the photo below are provided in the kit. Be sure to check for missing parts BEFORE your start assembly. Figure 2, Kit Contents The following
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before
More informationA. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.
1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall
More informationGENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17
GENERAL INFORMATION SECTION GUIDE SECTION 10 PAGE 1 DESCRIPTION SECTION NUMBER GENERAL INFORMATION... 10 POLE MOUNT TRANSFORMER SINGLE PHASE... 15 PAD MOUNT TRANSFORMER SINGLE PHASE..... 16 POLE MOUNT
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115 PADMOUNTED TRANSFORMERS 12kV AND DUAL VOLTAGE, RADIAL FEED STAINLESS STEEL NOVEMBER 2011 Specification:ELE_115_R1 Page
More informationElastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters
Underground Distribution Switchgear Molded Vacuum Switches and Fault Interrupters MVS Molded Vaccum Switches Spring-energy, load-switching devices that make, carry and interrupt load currents through 600
More information29048, 29049, 29050, 29051, 29052, 29053, 29054,
April 15, 2014 Lit. No. 29225, Rev. 11 29048, 29049, 29050, 29051, 29052, 29053, 29054, 29400 5 HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM w/2 PLUG SYSTEM HARNESSES Installation Instructions Read
More informationTOYOTA tc HANDS FREE BLU LOGIC Preparation
TOYOTA tc 2011- HANDS FREE BLU LOGIC Preparation Part #: PT923-00111 Conflicts: JBL Audio, Factory Navigation NOTE: Part number of this accessory may not be the same as the part number shown. Kit Contents:
More informationSTANDARD SPECIFICATION FOR PAD-MOUNTED CAPACITOR BANKS FOR 15kV or 25kV APPLICATIONS
A. General 1. Product The pad-mounted capacitor banks shall be in accordance with the applicable plans, drawings, and one-line diagrams and shall conform to these specifications. 2. Assembly The outdoor
More informationINSTALLATION INSTRUCTIONS TRAILER HITCH MAIN HARNESS KIT
PART NUMBER: 0000-89-N30 GENUINE ACCESSORIES INSTALLATION INSTRUCTIONS TRAILER HITCH MAIN HARNESS KIT APPLICABLE MODELS: 2016 > CX-9 PACKAGE CONTENTS: INSTALLATION INSTRUCTIONS QTY 1 CABLE TIE MOUNT QTY
More informationPRODUCT INSTALLATION GUIDE
PRODUCT INSTALLATION GUIDE PRODUCT CODE: PRODUCT DESCRIPTION: 4WDXHDSFK 4WD EXTREME HEAVY DUTY 6 COUPLER SYSTEM SELF FIT KIT KIT CONTENTS: QTY PRODUCT QTY PRODUCT QTY PRODUCT 1 Couplertec Module 3 Black
More informationInstallation Instructions PowerBoard Automatic Retracting Running Board
Installation Instructions PowerBoard Automatic Retracting Running Board Vehicle Application Dodge Ram Quad Cab Pickup 2002-2008 : 75101-15 Dodge Ram Mega Cab Pickup 2006-2009 : 75118-15 www.bestop.com
More informationDISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS
Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.
More information15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor
Page 1 2015 Heavy-duty 11-gauge steel enclosure is all-welded construction for long life Clear polycarbonate removable safety barrier separates upper and lower compartment (supplied only with internally
More informationSWITCHGEAR DIVISION PRODUCT PROFILES
SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,
More informationUNSIGNED HARDCOPY NOT CONTROLLED
Subject: APPROVED BY STATUS PURPOSE AFFECTED FUNCTIONS Flat Braid Cables Manager, Hardware Engineering Maintenance Revision Establishes the requirements for the fabrication of special-purpose electrical
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More informationInstallation Instructions PowerBoard Automatic Retracting Running Board
Installation Instructions PowerBoard Automatic Retracting Running Board Vehicle Application Dodge Ram Quad Cab Pickup 2002-2008 Part Number: 75101-15 Dodge Ram Quad Cab Pickup, 2500 / 3500 / HD 2003-2009
More informationFORM: C 01/06
Accessory Color Document # 3802 REVISION B 01/09/06 Part Number: 00016-21910 Accessory Code:YQ4 Kit Contents Item # Quantity Reqd Description 1 1 MPX Security Module 2 1 Shock Sensor 3 1 LED Valet Switch
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationAUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS
AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS The original TOMMY GATE hydraulic lift Assembling the Auxiliary Battery Box 1. Remove the cover from the auxiliary battery box by removing the two nuts and
More informationOnboard. Onboard RTU270 Installation Manual
Onboard Onboard RTU270 Installation Manual Contents Parts Checklist 3 Pre-installation considerations 4 Installation 5 Status LEDs 7 Completing Installation 8 2 Onboard RTU270 Installation Parts Check
More informationsolutions RUS accepted
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting
More informationRevised: April 2018 ¹ SERVICE TO WIRELESS DEVICE ANTENNA ATTACHMENTS ON CUSTOMER SERVICE POLES (SHEET 1) CUSTOMER: 1. An overcurrent protective device including a disconnect switch shall
More information35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor
Page 1 2016 EPM-PCS-35-320P-R2/ESW-GCM6-2S-SA Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton's CPS LRTPs 35 kv Elliott Air-Insulated SuperWell Bushings 21.1/36.6 kv Grounded Wye Max Design, 150
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationREARSIGHT PART NUMBER: Code: MC1 RECOMMENDED SEQUENCE OF APPLICATION
Document # 3848 REVISION A 1/26/06 2006 TOYOTA TACOMA REARSIGHT PART NUMBER: 00016-00050 Code: MC1 RE V I S I O N A KIT CONTENTS ITEM QTY DESCRIPTION 1 1 MIRROR/MONITOR 2 1 REAR CAMERA ASSEMBLY 3 1 CAMERA
More informationOutdoor Padmount Switching Products
Outdoor Padmount Switching Products Live-front & Dead-front 15 & 25 kv Switchgear, Fused Sectionalizing Enclosures, Metering and Capacitor Enclosures Rugged Outdoor Construction Safety and Security Features
More informationInstallation Instructions
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting
More informationSTANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General
Page 1 STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General 1. Product The pad-mounted switchgear shall be in accordance with the applicable plans, drawings,
More informationSolid Dielectric, Single Phase Reclosers
Solid Dielectric, Single Phase Reclosers Providing electronic overcurrent protection for single phase operation on systems rated through 38kV, 800A continuous current,12.5ka symmetrical interrupting Reliable
More informationFigure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES
Voltage Regulators Single-Phase Pad-mounted Step GENERAL McGraw-Edison Single-Phase Padmounted Voltage Regulators add a dimension to underground system planning. They provide system planners freedom to
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vst14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting
More informationInstallation Instructions PowerBoard Automatic Retracting Running Board
Installation Instructions PowerBoard Automatic Retracting Running Board Vehicle Application Toyota Tundra Double Cab 2007 Current Part Number: 75136-15 Toyota Tundra CrewMax 2007 Current Part Number: 75137-15
More informationSTOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION
CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.
More informationMounting Instructions Welded Coupling Mounting Instructions Welded Coupling
Mounting Instructions Welded Coupling Rev.08 (2014.06) OL Page 1 of 11 Table of contents I. STRUCTURE OF THE MANUAL / CLARIFICATION... 3 II. SAFETY AND HEALTH CONCERNS... 4 1 INTRODUCTION... 5 2 GENERAL
More informationMeter Installation. -and- Padmount Transformer Guide
Meter Installation -and- Padmount Transformer Guide Feb. 2016 METERING REQUIREMENTS The following information shall be used as a guide for installing metering equipment. A self-contained meter has all
More informationIVTM Installation Manual
Integrated Vehicle Tire Pressure Monitoring IVTM Installation Manual 2nd edition Copyright WABCO 2006 Vehicle Control Systems An American Standard Company The right of amendment is reserved Version 002/06.06(us)
More information29048, 29049, 29050, 29051, 29052, 20953, 29054,
July 15, 2008 Lit. No. 29225, Rev. 06 29048, 29049, 29050, 29051, 29052, 20953, 29054, 29400-2 HARNESS KIT 3-PORT ISOLATION MODULE LIGHT SYSTEM w/2-plug SYSTEM HARNESSES Installation Instructions Read
More information35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor
35-kV Safefront 2 Amp SuperWell 5-33 Page 1 216 EPM-PMS-35-311P-R2/ESW Three Phase Two Ways per Phase 2 Amp 35 kv Class Eaton's CPS LRTPs NEMA Standard Outdoor Instrument Transformer Provisions 21.1/36.6
More informationSOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS
SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial
More informationOVERHEAD SERVICE. Items to consider
OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must
More informationCobra-S. Catalog Cobra-S
Cobra-S Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5/16kA symmetrical interrupting Control
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,
More informationSolid Dielectric, Three Phase Reclosers Catalog O-vs18
Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance
More informationSPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.
City of Cartersville Electric System P.O. Box 1390 320 S. Erwin St. Cartersville, GA 30120 770-387-5631 March 2006 SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS This specification provides standardization
More informationINSTALLATION INSTRUCTIONS: P/N: / D
INSTALLATION INSTRUCTIONS: P/N: 75-5104 / 75-5104D 15461 SLOVER AVE., FONTANA, CA 92337 PH: 909.947.0015, FAX: 909.947.0603 WWW.SBFILTERS.COM Thank You! for purchasing your new S&B Filters intake kit.
More informationSingle-phase pad-mounted step voltage regulator
Voltage Regulators Catalog Data CA225002EN Supersedes February 2015 COOPER POWER SERIES Single-phase pad-mounted step voltage regulator General Eaton's Cooper Power series single-phase pad-mounted voltage
More information/ CABLE TIES & WIRE FASTENERS /
Standard Self-locking Cable Ties information INFO Melting point: 265 C (509 F) Brittleness temperature: -112 C (-169 F) at 2% water Provide up to 50% more tensile strength and 15% larger bundle diameters
More informationMATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****
Page 1 of 8 ****Supercedes BECo Standard E2.12-2.12 and ComElectric Spec 6-0895**** 1.0 General Requirements SINGLE PHASE PAD-MOUNTED DISTRIBUTION TRANSFORMERS 1.1 These specifications cover single-phase
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationDISTRIBUTION TRANSFORMERS SPECIFICATION #
DISTRIBUTION TRANSFORMERS SPECIFICATION #1212.01 12.47kV Grd Wye Padmount & Polemount Bid No. 16-93 Exhibit I Page 1 of 19 TABLE OF CONTENTS 1 SCOPE... 3 2 STANDARDS... 3 3 EVALUATION AND AWARD... 3 4
More informationSS1066HF Jeep JK Wrangler Left Hand Drive CRDI4 2.8Litre-I4 Diesel Engine and EGHV6 3.8Litre V6 Gasoline Engine
SS1066HF Jeep JK Wrangler Left Hand Drive CRDI4 2.8Litre-I4 Diesel Engine and EGHV6 3.8Litre V6 Gasoline Engine Installation Guide Safari SS1066HF Page - 1 of 12 6/10/2009 ITEM PART NO DESCRIPTION QTY
More informationMP ES/ED. Toll Free Phone, (US & Canada): (800) Toll Free Fax, (US & Canada): (800)
MP ES/ED Toll Free Phone, (US & Canada): (800) 427-6668 Toll Free Fax, (US & Canada): (800) 361-7745 http://www.garland-group.com MOISTURE + (Electric) MP-ES/ED-10 INDEX DESCRIPTION PAGE Deluxe Control
More informationPadmount Solid Dielectric Switchgear Catalog
Padmount Solid Dielectric Switchgear Catalog p G&W headquarters in Bolingbrook, IL USA Company Profile Since 1905, G&W Electric has helped energize the world with innovative power system solutions. With
More informationINSTALLATION INSTRUCTIONS 89551
INSTALLATION INSTRUCTIONS 89551 For Rancho Suspension System RS66551B: Ford F250, F350 Super Duty 4x4 DIESEL ONLY (Single Rear Wheels Only With or Without Auxiliary Spring). (WILL NOT WORK ON GAS ENGINES
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Part# 69-0717 AIR IT UP 4 Tire On Board Installed Air Delivery System with Rear Mounted Controller (Requires External Air Source) For the most up-to-date instructions please visit
More information3-5 Hours Professional installation recommended
I N S T A L L A T I O N G U I D E APPLICATION LENGTH MODEL YR PART # Chevrolet Colorado / GMC Canyon - Crew Cab 72 2015-2016 76153-01A Chevrolet Colorado / GMC Canyon - Extended Cab 65 2015-2016 76153-01A
More informationP Original Series Cargo Van Lift Mounting Instructions Fullsize Ford Van present. Preparing the Gate
Fullsize Ford Van- 1992-present Preparing the Gate 1. Remove the mounting hardware which is banded to the liftgate. 2. Verify mounting kit (Figure 1 and Table 1). S-400-40 STRAP VAN MOUNTING EAR BENT BRACKET
More information650 Series Cargo Van Lift Mounting Instructions Fullsize Ford 1992-Present
TOMMY GATE OWNER'S / OPERATOR'S MANUAL 650 Series 650 LB Capacity 650 Series Cargo Van Lift Mounting Instructions Fullsize Ford 1992-Present Installing the Base Plate 1. Examine the interior and exterior
More informationINSTALLATION INSTRUCTIONS 97 FORD EXPEDITION
INSTALLATION INSTRUCTIONS 97 FORD EXPEDITION 1. Read the instructions completely and carefully before you begin. Check the kit for proper contents (refer to the part s list and the picture diagrams). Before
More information15-kV Live Terminal 200 Amp Mini-Switch Source-Isolated Pad-Mounted Switchgear 40 Amp (Max) Arc-Strangler NX Fuses
Page 1 2015 Heavy duty 11-gauge steel enclosure is all-welded construction for long life Door safety barrier removal instructions Safety latches on the door safety barriers, front and rear, are insulating
More informationU L T I M A T E R A D A R / L A S E R D E F E N S E S Y S T E M
S m a r t e r Q u i e t e r M o r e A c c u r a t e U L T I M A T E R A D A R / L A S E R D E F E N S E S Y S T E M Installation Manual PASSPORT 9500ci Comes Complete Front Radar Receiver Miniature weatherproof
More informationGreenRoad Installation Document (GRID) Document Number: VWR10
GreenRoad Installation Document (GRID) Document Number: VWR10 Chassis: Volvo B10BLE Version Created By Date Body: Wright Renown 1.0 JP 15/06/2011 Year: 1998/2000 Configuration: Single Deck Bus Adherence
More information2010+ Victory Cross Country / Cross Roads Installation Guide Nov 2014
2010+ Victory Cross Country / Cross Roads Installation Guide Nov 2014 125 Industrial Drive Spearfish, SD 57783 Toll Free 888.3WHEELS w w w. l e h m a n t r i k e s. c o m UNDERSTANDING SAFETY LABELS &
More informationFIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z
PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification
More informationSolid Dielectric, Single Phase Recloser
Solid Dielectric, Single Phase Recloser Catalog O-vsp17 Viper-SP Viper-SP solid dielectric, single phase recloser combines the time-proven reliability of electronically controlled, vacuum fault interrupters
More informationMetering and Service Installation:
Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...
More informationMODEL ELC-12/60-D BATTERY CHARGER
*32198* NATIONAL RAILWAY SUPPLY Installing, Operating and Service Instructions for the 12/60 Solid State Charger MODEL ELC-12/60-D BATTERY CHARGER PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS
More information15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses
Page 1 2015 Heavy duty 11-gauge steel enclosure is all-welded construction for long life Corrosion proof nameplate is located to provide easy access for the operator Glass reinforced barriers meet NEMA
More informationINSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL
Photovoltaic (PV) Residential Page 1 of 10 Revision Date: 07/18/2018 INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL INSPECTION CODE: 703 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,
More informationINSTALLATION INSTRUCTIONS FOR COZY CAB A-1 AIR CONDITIONING KIT
INSTALLATION INSTRUCTIONS FOR COZY CAB A-1 AIR CONDITIONING KIT 05-11 INSTALLATION INSTRUCTIONS A-12235 Air Conditioner Kit Cab set up instructions; This air conditioning kit is designed to be used with
More information29048, 29049, 29050, 29051, 29052, 29053, 29054,
April 15, 2014 Lit. No. 29206, Rev. 11 29048, 29049, 29050, 29051, 29052, 29053, 29054, 29400 5 HARNESS KIT 3 PORT ISOLATION MODULE LIGHT SYSTEM w/3 PLUG SYSTEM HARNESSES Installation Instructions Read
More informationTechnical Specification for Pole Mounted Capacitor Rack
Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationPump Gas Instructions for Polaris And 800 Models. Important Information before Installing This System:
Pump Gas Instructions for Polaris 600 700 And 800 Models Important Information before Installing This System: Before you begin your turbo install, read through these instructions to determine if you are
More informationSYSTEM PROTECTION SYSTEM PROTECTION. Underground Electric Distribution Standards I. FUSE COORDINATION
I. FUSE COORDINATION I.1. GENERAL I.1.1. The purpose of protective coordination is to provide isolation of a fault as close to the fault as possible so that a minimum of customers will be affected. The
More informationFig A ADDICTIVE DESERT DESIGNS. Preparation: Removal: Release these clips
Preparation: Disconnect the negative battery terminal. Park the vehicle on level ground and set the emergency brake. We recommend reading through the installation instructions in whole before performing
More informationSolar Power Switchgear & Energy Storage Renewable Energy Systems
7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH
More information