SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.
|
|
- Della Moody
- 6 years ago
- Views:
Transcription
1 S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS below. SPECIAL TO THIS PRODUCT: INCLUSIONS: Integral quick-make quick-break mechanism and antifriction bearings are featured in the built-in operating mechanism of the three-pole switches, which are furnished as complete units including direct-coupled, chain-coupled, or pipe-coupled handle; full-length interphase barriers; side barriers; and any other operatingmechanism components required by the specifications for any Standard Mounting Arrangement covered in S&C Data Bulletin Shaft extensions for Alduti-Rupter Switches with Power Fuses will be furnished if they are specified on orders, together with the dimension required. EXCLUSIONS: Switches do not include holders or refill units. The applicable holder is listed on the same horizontal line as the switch. Switches do not include connectors. Various connectors are available as listed in the table on page 5. Specify quantity and catalog number of connectors desired. SPECIFICATION DEVIATIONS: Switches cannot be provided with special insulators. Switches, regardless of voltage rating, cannot be supplied for back connection. Switches cannot be supplied less insulators. Higher or lower insulator voltage ratings for a switch of a given voltage rating are not available. Switches can be supplied with an operating mecha nism which conforms to the specifications of any minor modification of the Standard Mounting Arrangements listed in S&C Data Bulletin Switches can be supplied with an operating mecha nism which requires the preparation or re-use of a custom erection drawing of a special mounting arrange ment. Switches can be supplied with tin-plated terminal pads. To specify, add suffix -Z5 to the catalog number. WARRANTY QUALIFICATIONS: For the standard warranty contained in seller s standard conditions of sale (as set forth in Price Sheet 150) to apply to S&C Alduti- Rupter Switches with Power Fuses Type SM when installed in indoor, outdoor, or indoor-outdoor enclosures of other than S&C manufacture, the enclosures must be constructed in accordance with S&C s applicable mini mum construction specifications to be found in the following publication: DATA BULLETIN 792-: S&C Alduti-Rupter Switches with Power Fuses Indoor Distribution (4.8 kv and 13.8 kv) Minimum Construction Specifications for Metal Enclosures Indoor and Outdoor With respect to S&C Alduti-Rupter Switches with Power Fuses Type SM when installed in submersible enclosures of other than S&C manufacture, warranty does not apply unless enclosures are furnished by an approved supplier and are of watertight construction providing proper electrical clearances and proper space for fuse handling. a S&C Alduti-Rupter Switches with Power Fuses are manufactured in accordance with a quality system certified to ISO Supersedes Specification Bulletin dated s S&C ELECTRIC COMPANY ç2011 SPECIFICATION BULLETIN Page 1 of 10
2 S&C Alduti-Rupter Switches with Power Fuses Conditions of Sale Continued How to Order an Alduti-Rupter Switch with Power Fuses 1. Switch, accessories, and connectors: a. Obtain the catalog number of the desired switch from the tables on pages 3 and 4. b. Obtain the ED number of the desired mounting arrangement from S&C Data Bulletin If either a minor modification of a standard mounting arrangement or a special mounting arrangement is desired, see the Specification Deviations section on page 1. c. If tin-plated terminal pads are desired, add suffix -Z5 to the switch catalog number. d. If accessories or parts are desired, obtain the cata log number of the desired accessory or part from page 5. e. If connectors are desired, obtain the catalog number of the desired connector from page Fuse components: a. Obtain the catalog number of the applicable holder from the Holder column on pages 3 and 4, reading from the same line on which the switch catalog number is listed. b. Obtain the catalog number of the desired refill unit from the tables on pages 6 and 7, taking care to match the voltage rating to that of the switch. How to Order Handling Tools Obtain the catalog number of recommended handling tool(s) from the table on page SPECIFICATION BULLETIN Page 2 of 10 S&C ELECTRIC COMPANY s
3 ALDUTI-RUPTER SWITCHES WITH POWER FUSES Three-Pole With Disconnect 458 Opening Silencer or Snuffler Fuses1 Style Fuse Holder Type and Max Amp kv Nom. Max BIL Cont. and Interr.2 Mom. (Asym.)2 Amperes, RMS Fault-Closing, Duty-Cycle,3 Two-Time24 Fuse Interrupting5 (Sym.) Switch (less Holders)6 Page Reference for Holder (Three Dimensional Required, Refill Information Units not Included) Main Contact at Top Handle on Right SM-4Z 200E l R R R2a 86632R2d 8 SM-5S l l R R R2a 86642R2d 1 Generally speaking, S&C Alduti-Rupter Switches with Power Fuses will perform any switching duty typically required of such devices. For specific switching capabilities, particularly with respect to capacitive current, refer to Specification Bulletin , S&C Alduti-Rupter Switches Indoor Distribution, where the Applications column on pages 5 and 6 together with explanatory tables on pages 2 and 3 provide the desired specific information for each voltage rating. 2 These ratings apply to switches. Fuse ratings are indicated in the second and ninth columns. 3 Duty-cycle fault-closing ratings define the ability to close the switch, in combination with the appropriate Type SM-5S Power Fuse, the specified number of times (one or two) against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and inter rupt rated continuous current. 4 The two-time duty-cycle fault-closing rating of the -ampere switches alone (unfused) is 40,000 amperes. The one-time duty-cycle fault-closing rating of the 4.8-kV, -ampere switches alone (unfused) is 61,000 amperes. 5 Symmetrical ratings assigned are based on available short-circuit current at locations where the X/R ratio is 15. The interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. Higher symmetrical ratings have been determined for these fuses where X/R 5 10 and X/R 5 5. These higher ratings as well as asymmetrical ratings are given in S&C Descriptive Bulletin Top and bottom front-connected. These switches cannot be supplied for back connection. These switches are furnished with S&C Cypoxy Insulators. l shown applies at 4.16 kv. At 4.8 kv, rating is 43,500 amperes RMS asymmetrical (27,000 amperes RMS symmetrical). a Rated 7.2 kv nominal, for use in listed 4.8-kV switches for system voltages through 4.8 kv, or in discontinued 7.2-kV switches for system voltages through 7.2 kv. d Rated 14.4 kv nominal, for use in listed 13.8-kV switches or in discontinued 14.4-kV switches. s S&C ELECTRIC COMPANY SPECIFICATION BULLETIN Page 3 of 10
4 S&C Alduti-Rupter Switches with Power Fuses ALDUTI-RUPTER SWITCHES WITH POWER FUSES Three-Pole With Non-Disconnect Super-Snuffler Fuses1 Style Fuse Holder Type and Max Amp kv Nom. Max BIL Cont. and Interr.2 Mom. (Asym.)23 Amperes, RMS Fault-Closing, Duty-Cycle,4 Two-Time2 Fuse Interrupting5 (Sym.) Switch (less Holders)6 Page Reference for Holder Dimensional (Three Required, Information Refill Units not Included) Main Contact at Top Handle on Right SM-5SS a d a R R2l 10 1 Generally speaking, S&C Alduti-Rupter Switches with Power Fuses will perform any switching duty typically required of such devices. For specific switching capabilities, particularly with respect to capacitive current, refer to Specification Bulletin , S&C Alduti-Rupter Switches Indoor Distribution, where the Applications column on pages 5 and 6 together with explanatory tables on pages 2 and 3 provide the desired specific information for each voltage rating. 2 This rating applies to the switch. Fuse ratings are indicated in the second and ninth columns. 3 This rating is based on limiting of the let-through current by the associated power fuses. 4 Duty-cycle fault-closing ratings define the ability to close the switch, in combination with the appropriate Type SM-5S Power Fuse, the speci fied number of times (one or two) against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and interrupt rated continuous current. 5 The symmetrical rating assigned is based on available short-circuit current at locations where the X/R ratio is 15. The interrupting rating expressed in amperes RMS asymmetrical is 1.6 times the symmetrical rat ing listed. Higher symmetrical ratings have been determined for these fuses where X/R 5 10 and X/R 5 5. These higher ratings as well as asym metrical ratings are given in S&C Descriptive Bulletin Top and bottom front-connected. This switch cannot be supplied for back connection. This switch is furnished with S&C Cypoxy Insulators. a At hertz only; 55,000 amperes RMS asymmetrical (34, amperes RMS symmetrical) on 7.2/12.47Y-kV -hertz systems only. d The two-time duty-cycle fault-closing rating for the 13.8-kV switch in combination with the Type SM-5SS Power Fuse has not been established. The one-time duty-cycle fault-closing rating of the 13.8-kV switch in combination with the Type SM-5SS Power Fuse is 54,000 amperes, hertz only (55,000 amperes on 7.2/12.47Y-kV -hertz systems only). The two-time duty-cycle fault-closing rating of the 13.8-kV -ampere switch alone (unfused) is 40,000 amperes. l Rated 14.4 kv nominal, for use in listed 13.8-kV switch or in discontinued 14.4-kV switches SPECIFICATION BULLETIN Page 4 of 10 S&C ELECTRIC COMPANY s
5 ACCESSORIES AND PARTS Item Type For Use on Switches Rated, kv Catalog Number Interlock Key All a Spare or Replacement Interrupter Single-bolt 4.8 or or 14.4 SA-30817R2 SA-30818R4 Spare Spring-and-Cable Assembly For use with SM-4 Refill Unit For use with SM-5 Refill Unit 4.8 or or or or 14.4 FA-972 FA-973 FA-2341l FA-2342l Spare Silencer SM-4Z All FDA-1079 Spare Snuffler SM-4S SM-5S SM-5SS a Order by description. l For use only in holders carrying an arrow-shaped nameplate. Springand-cable assemblies for holders which do not carry an arrow-shaped All FA FDA-1065 FA f nameplate are no longer available so a new holder with the appropriate voltage rating must be ordered. f Not usable in disconnect style mounting. CONNECTORS Illustration Description Accommodating Conductor Catalog Number Aluminum-Alloy Body, Tin Plated. Includes two Z\x C\v0 Galvanized Steel Bolts No. 2 solid (33.6 mm 2 ) through 500 kc mil (335 mm 2 ) stranded copper or aluminum 4741R2d Aluminum-Alloy Body, Tin Plated. Includes two Z\x Z\v0 Galvanized Steel Bolts No. 2 solid (33.6 mm 2 ) through 500 kc mil (335 mm 2 ) stranded copper or aluminum 4746f Standard Bronze Pad Terminal, Four-Bolt, Tin Plated. Includes two Z\x Z\x0 galvanized steel hardware for attachment to terminal pads of switches No. 6 solid (13.3 mm 2 ) through 250 kc mil (168 mm 2 ) copper or aluminum 1/0 solid (53.5 mm 2 ) through 500 kc mil (335 mm 2 ) copper or aluminum 2/0 stranded (89 mm 2 ) through 800 kc mil (539 mm 2 ) copper or aluminum 4564R1-B 4565R1-B 4567R1-B d Not usable at lower terminal pads of switches with disconnect style SM-4Z or SM-5S Power Fuses. f Usable only at lower terminal pads of switches with disconnect style SM-4Z or SM-5S Power Fuses. Not usable on switch with non-disconnect style SM-5SS Power Fuse. HANDLING TOOLS Item For Removal and Installation of Holder Style Type Catalog Number Grappler 458 Opening Disconnect SM-4Z 4423 Large Clamp 458 Opening Disconnect SM-4Z or SM-5S 4410R3 Locking Prong Non-Disconnect SM-4Z, SM-5S, or SM-5SS 4404 Universal Pole Refer to Specification Bulletin s S&C ELECTRIC COMPANY SPECIFICATION BULLETIN Page 5 of 10
6 S&C Alduti-Rupter Switches with Power Fuses SM-4 REFILL UNITS (For Use in SM-4 and SML-4 Holders), Amperes 7.2 kv Nominal, 8.3 kv Max kv Nominal, 17.0 kv Max2 TCC TCC R R R R4 TCC S&C Slow TCC TCC S&C Slow TCC S&C Coord. TCC E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 210E R R R R R R R R R4 1210R R R R R R R R R R R R R4 2510R R R R R R R R R R R R R R R R R R4 1220R R R R R R R R R R R R R4 2520R R R R R R R R R R4f 1 Rated 7.2 kv nominal, for use in SM-4 Holders rated 7.2 kv when applied in listed switches rated 4.8 kv or in discontinued switches rated 7.2 kv. 2 Rated 14.4 kv nominal, for use in SM-4 Holders rated 14.4 kv when applied in listed switches rated 13.8 kv or in discontinued switches rated 14.4 kv. f This S&C Coordinating refill unit should be applied where the maximum continuous load current does not exceed 200 amperes and where all fault currents below 1000 amperes will be cleared by another fuse SPECIFICATION BULLETIN Page 6 of 10 S&C ELECTRIC COMPANY s
7 SM-5 REFILL UNITS (For Use in SM-5 Holders), Amperes 1E 2E 4.16 kv Nominal, 4.76 kv Max1 7.2 kv Nominal, 8.3 kv Max2 TCC R R4 TCC R R4 TCC R R R R R R R R R4 1300R R R R R R R R R R R4 130R4 S&C Slow TCC S&C Coord. TCC TCC R R R R R R R R R4 1310R R R R R R R R R R R4 131R4 S&C Slow TCC S&C Coord. TCC E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 250E 300E 410E 420E 225R4 230R4 240R4 250R4 2R4 275R4 2100R4 2125R4 2150R4 2200R4 2250R4 2275R4 2300R4 2400R4 2500R4 2R R4lf R4lf R R R R4 2610R R R R R R R R R R4 261R R4f R4f, Amperes 14.4 kv Nominal, 17.0 kv Max3 TCC R R4 1E 2E TCC S&C Slow TCC S&C Coord. TCC E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 250E 300E 410E 420E R R R R R R R R R4 1320R R R R R R R R R R R4 132R R R R R4 2620R R R R R R R R R R R4 262R R4f R4f 1 Rated 4.16 kv nominal, for use in SM-5 Holders rated 7.2 kv when applied in listed switches rated 4.8 kv for system voltages through 4.16 kv. 2 Rated 7.2 kv nominal, for use in SM-5 Holders rated 7.2 kv when applied in listed switches rated 4.8 kv for 4.8-kV system voltage only, or in discontin ued switches rated 7.2 kv for system voltages of 4.8 kv through 7.2 kv. 3 Rated 14.4 kv nominal, for use in SM-5 Holders rated 14.4 kv when applied in listed switches rated 13.8 kv or in discontinued switches rated 14.4 kv. s S&C ELECTRIC COMPANY l Catalog numbers are in italics because these are 7.2-kV refill units. Interrupting ratings are those listed in S&C Descriptive Bulletin for 7.2-kV SM-5S Power Fuses applied to systems rated 2.4/4.16Y kv. f These S&C Coordinating refill units should be applied where the maximum continuous load current does not exceed 400 amperes and where all fault currents below 3000 amperes (for s R4 and R4) and 4000 amperes (for s R4 and R4) will be cleared by another fuse. SPECIFICATION BULLETIN Page 7 of 10
8 S&C Alduti-Rupter Switches with Power Fuses Three-Pole Main Contact at Top With Disconnect 45 Opening SM Power Fuses Style Fuse Holder Type and Max Amp kv Nom. Max BIL Cont. and Interr. Mom. Amperes, RMS Fault-Closing, Duty-Cycle, Two-Time Fuse Interrupting, Symmetrical Switch (less Holders) Holder (Three Required) Main Contact at Top Handle on Right SM-4Z 200E SM-5S l R R7 345R R R R R R2 l shown applies at 4.16 kv. At 4.8 kv, rating is 43,500 amperes RMS asymmetrical (27,000 amperes RMS symmetrical) SPECIFICATION BULLETIN Page 8 of 10 S&C ELECTRIC COMPANY s
9 Dimensions in Inches A 1 A 2 B C D E F 1 F 2 H J K L M 1 M 2 N R W Net Wt., Lbs. 9Z\v 11C\v 9Z\v 11C\v 10Z\, 12B\, 10C\, 12M\, 5 7Z\x 5 7Z\x 38Z\x 46Z\x 38Z\x 46Z\x 8Z\x 10 8Z\x 10 7C\v 7C\v Z\x 20Z\x 16Z\x 20Z\x 19 24C\v 19 24C\v Z\, 6 7Z\, 34Z\x 42Z\x 34Z\x 42Z\x 26Z\x 33B\, 26Z\x 33B\, 29 34C\, 31 35C\v C\, 22M\, 16C\, 22M\, 29 34Z\v 29 34Z\v s S&C ELECTRIC COMPANY SPECIFICATION BULLETIN Page 9 of 10
10 S&C Alduti-Rupter Switches with Power Fuses Three-Pole Main Contact at Top With Non-Disconnect SM Power Fuses C\, Style Main Contact at Top Handle on Right Fuse Holder Type and Max Amp SM-5SS kv Nom. Max BIL Cont. and Interr. Mom. Amperes, RMS Fault-Closing, Duty-Cycle, Two-Time Fuse Interrupting, Symmetrical Switch (less Holders) Holder (Three Required) d R R2 546 d Two-time duty-cycle fault-closing rating for the 13.8-kV switch in combination with the Type SM-5SS Power Fuses has not been established. The one-time duty-cycle fault-closing rating of the 13.8-kV switch in combination with the Type SM-5SS Power Fuses is 54,000 amperes, hertz only (55,000 amperes on 7.2/12.47GrY-kV -hertz systems only). The twotime duty-cycle fault-closing rating of the 13.8-kV -ampere switch alone (unfused) is 40,000 amperes. Net Wt., Lbs SPECIFICATION BULLETIN Page 10 of 10 S&C ELECTRIC COMPANY s
Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.
S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set
More informationSpecifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order
S&C Alduti-Rupter Switchesa Indoor Distribution ( kv through kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 0 apply. SPECIAL TO THIS PRODUCT:
More informationwww. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003
Types SM-4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through kv) Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet apply, except as modified under
More informationSpecifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)
S&C Power Fuses Types SM- 4, SM-5, SMD-0, and SMD-40 Outdoor Distribution (4.16 kv through kv) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: The seller s standard
More informationSpecifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)
Outdoor Distribution (4.4 kv through 46 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 50 apply, except as modified under WARRANTY QUALIFICATIONS
More informationSPECIFICATION BULLETIN
SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS on page 3. SPECIAL TO THIS PRODUCT:
More informationSpecifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles
Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified
More informationSpecifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)
Outdoor Distribution (4.16 through 25 ) Specifications Conditions of Sale STANDAD: Seller s standard conditions of sale set forth in Price Sheet 153 apply, except as modified under WAANTY QUALIFICATIONS
More informationS&C Recloser Bypass Disconnects
S&C Recloser Bypass Disconnects Outdoor Distribution (14.4 kv through 34.5 kv) Application S&C Recloser Bypass Disconnects are station-type devices used to bypass and isolate automatic circuit reclosers
More informationSpecifications. S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv)
Outdoor Distribution ( kv and kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WAR- RANTY QUALIFICATIONS
More informationSpecifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale
S&C Omni-Rupter Switches Outdoor istribution (14.4 kv and 5 kv) Specifications Conditions of Sale STNR: Seller s standard conditions of sale as set forth in Price Sheet apply. SPECIL TO THIS PROUCT: INCLUSIONS:
More informationSpecifications. S&C Source-Transfer PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT Control. Conditions of Sale
Outdoor Distribution ( kv and kv) With Micro-AT Control Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WAR-
More informationS&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size.
S&C Mini-Rupter es Indoor Distribution (4.16 kv through 25 kv) Selecting Standard Mounting Arrangements for Manually Operated Styles Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter
More informationCleaning Flooded Gear
S&C Manual Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding
More informationSpecifications. S&C Switch Operators Types AS-1A and AS-10a. Conditions of Sale
a Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Switch Operators Types AS-1A and AS-10 are
More informationS&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection
More informationS&C Manual PME Pad-Mounted Gear
S&C Manual PME Pad-Mounted Gear Outdoor Distribution,. kv and 5 kv S&C Manual PME Pad-Mounted Gear... Featuring Elbow-Connected Encased Components. S&C Manual PME Pad-Mounted Gear brings in-air insulation,
More informationSpecif ications. S&C Positrol Fuse Links. Outdoor Distribution
S&C Positrol Fuse Links Outdoor Distribution Specif ications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: SPECIFICATION
More informationCleaning Flooded Gear
S&C Manual PMX Modular Metal-Enclosed Switchgear Outdoor Distribution (13.8 kv and 25 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding
More informationWestinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401
February 26, 1976 Supersedes PL 38-640 dated October 15,1974 Pages 1-8 Prices effective April 29, 1974 Subject to change without notice Selling Policy 38-000 Mailed to E, D, C/1991, 2430/ PL Standard Bill
More informationS&C Circuit-Switcher Mark VI Outdoor Transmission (69 kv through 138 kv)
Outdoor Transmission (69 kv through 138 kv) Construction Guide This publication sets forth the data required for the user to design a support structure or pedestals for a Mark VI Circuit-Switcher; the
More informationPAD-MOUNT SWITCHGEAR 15kV 25kV 35kV
PAGE 1 TYPE PSI PAD-MOUNT SWITCHGEAR 15kV 25kV 35kV INSTRUCTIONS For Installation and Operation INTRODUCTION... 1 Receiving... 1 Handling... 1 Storage... 1 GENERAL DESCRIPTION... 1 SAFETY FEATURES... 1
More informationINSTRUCTIONS Ç CAUTION Ç IMPORTANT
Type SM, SML, and SME j Indoor Distribution INSTRUCTIONS For Installation GENERAL Ç CAUTION The equipment covered by this publication must be selected for a specific application and it must be installed,
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Vertical-Break Style Reciprocating Operating Mechanism 25/34.5 kv and 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section
More informationTYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV
Cutler Hammer SECTION PB-1A-110 PAGE 1 Replaces April, 1996 TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV The PSI/II Padmount is the second generation of switchgear in the PSI switchgear family. The PSI/II
More informationS&C Switch Operators Types AS-1A and AS-10
S&C Switch Operators Types AS-1A and AS-10 Page 1 of 11 S&C Switch Operators - Types AS-1A and AS-10 Types AS-1A and AS-10 Switch Operators are high-speed operators expressly designed for power operation
More informationSpecif ications. Minimum Surge Arrester Rating, kv
&C Fault amer Fuse Limiter Outdoor Distribution ( kv through kv) For Overhead Pole-op ransformers pecif ications Conditions of ale ADAD: eller s standard conditions of sale set forth in Price heet 0 apply.
More informationThe Standard Mounting Arrangements for S&C Omni-Rupter Switches
S&C Omni-Rupter Outdoor Distribution (14.4 kv and 25 kv) Selecting Standard Mounting Arrangements The Standard Mounting Arrangements for S&C Omni-Rupter S&C Omni-Rupter for outdoor distribution are offered
More informationTypical Specification
Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,
More informationS&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)
S&C Loadbuster Disconnect Switches Outdoor Distribution ( kv through 34.5 kv) S&C s Loadbuster Disconnect Switches, when used with S&C s Loadbuster tool, provide the ultimate in distribution live-switching
More informationS&C Loadbuster Disconnects
S&C Loadbuster Disconnects Outdoor Distribution ( kv through 34.5 kv) With these outstanding features... Up to -ampere continuous ratings, 40,000-ampere RMS asymmetrical momentary ratings Designed for
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Three-Pole Side-Break Heavy-Duty Style Reciprocating Operating Mechanism 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section Page Section Page INTRODUCTION
More informationDisconnect & ByPass Switches
Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class
More informationThe Standard Mounting Arrangements for S&C Alduti-Rupter Switches
S&C Alduti-Rupter Switches Outdoor Distribution (14.4 kv through 69 kv) The Standard Mounting Arrangements for S&C Alduti-Rupter Switches Three-pole S&C Alduti-Rupter Switches for outdoor distribution
More informationINSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET
S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3 Outdoor Transmission Mountings Rated 34.5, 46, and 69 kv INSTRUCTIONS For Field Assembly and Installation TABLE OF CONTENTS Section Page Number INTRODUCTION........................................1
More informationWARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation
PAGE 1 TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV QUALIFIED PERSONS...1 SAFETY INFORMATION...2 INTRODUCTION...3 Receiving...3 Handling...3 Storage...3 GENERAL DESCRIPTION...3
More informationINSTRUCTIONS Ç CAUTION. S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) For Installation TABLE OF CONTENTS
INSTRUCTIONS For Installation TABLE OF CONTENTS Section Page Number INTRODUCTION....................................... 1 INSPECTION AND HANDLING Packing.............................................. 3
More informationS&C Alduti-Rupter Switches. Outdoor Distribution, 14.4 kv through 69 kv
S&C Alduti-Rupter Switches Outdoor Distribution, 14.4 kv through 69 kv Application S&C Alduti-Rupter Switches, rated 14.4 kv through 69 kv, 600 amperes or 1200 amperes continuous and live switching, provide
More informationIntroduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)
S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) Inspection Recommendations for Switchgear with Type AT-3 Source- Transfer Controls Table of Contents Section
More informationT YPE MZ DISTRIBUTION S TANDARD CUTOUT
T YPE MZ DISTRIBUTION S TANDARD CUTOUT Page 1 of 7 The Fuse Cutout type MZ was developed to operate in overhead distribution systems rated at 15, 27 and 38 kv grounded systems with 100 or 200 A nominal
More informationCLEAVELAND / PRICE INC. Type RL-C Side Break Switch kv A. Bulletin DB-104E12
Bulletin DB-104E12 Type RL-C Side Break Switch 7.2-69 kv 600-2000 A. CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Type RL-C
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More information15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses
Page 1 2015 Heavy duty 11-gauge steel enclosure is all-welded construction for long life Corrosion proof nameplate is located to provide easy access for the operator Glass reinforced barriers meet NEMA
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationIntroduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)
S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) Inspection Recommendations for Switchgear Equipped with Type AT-2 Source-Transfer Controls Table of Contents
More information15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch
Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and
More informationSWITCHGEAR DIVISION PRODUCT PROFILES
SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Description: Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies
More informationUltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout
Fusing Equipment Catalog Data CA132035EN Supersedes November 2015 COOPER POWER SERIES UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Description Eaton has set a standard
More informationFusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses
Technical Data1019 Supersedes July 2013 Fusetron FRN-R Class RK5 250Vac/125Vdc Catalog symbols: FRN-R-_ (non-indicating) FRN-R-_ID (indicating) Description: Eaton Bussmann series advanced protection, energy
More informationUnit Substation Transformers 5 and 15 KV Class
Transformers 5 and 15 KV Class 85 General Information Description Federal Pacific unit substation transformers are available in a wide variety of types and ratings to provide reliable and versatile electrical
More informationPROTECTION AND CONTROL
B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationS&C Type XS Fuse Cutouts
S&C Type XS Fuse Cutouts Outdoor Distribution 4.16 kv through 25 kv Application An Unexcelled Cutout S&C Type XS Fuse Cutouts, when fused with S&C Positrol Fuse Links provide full-fault-spectrum protection
More informationINSTRUCTIONS For Installation
S&C Mini-Rupter@Switches ndoor Distribution (4.16 kv through 25 kv) NSTRUCTONS For nstallation NTRODUCTON CAUTON: The equipment covered by this publication mustbeselected for a specific application and
More informationCL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES
SERIES E-RATED / MEDIUM VOLTAGE FUSES 5kV AND 15kV CLIP-LOCK MOUNTED FUSES Amp-trap E-rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,
More informationNX indoor current-limiting fuses
Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground
More informationFigure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating
Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection
More informationVersaRupter 5-38 kv Load Interrupter Switch. Technical Guide
VersaRupter 5-38 kv Load Interrupter Switch Technical Guide NOTICE Components in this catalog are intended for use by switchgear assemblers engaged in original equipment manufacturing. All sales are subject
More informationSWITCHGEAR DIVISION PRODUCT PROFILES
SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,
More informationA. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.
1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall
More informationMica Element Support. Compacted Quartz Sand. Length B
Construction A Tin-Plated Brass Caps Dimensional Information for Trans-Guard s NOMINAL 5.5 Resin-Rich Filament Wound Glass/Epoxy Body 3 75 80 200 3 50 5 80 5 125 3 50 5 5 100 23.0 50 Low Current Interruption
More informationDEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV
TYPE PSE MANUAL DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV Figure 1 Federal Pacific Dead-Front PSE (available as UL Listed) contains an integrated system of fuses and switches with access control features
More informationS&C Trans-Rupter II Transformer Protector Outdoor Transmission (69 kv through 138 kv)
S&C Trans-Rupter II Transformer Protector Outdoor Transmission (69 kv through 138 kv) Construction Guide This publication sets forth the data required for the user to design a support structure for the
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationBUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352
8.3kV E-Rated Description: E-Rated, current-limiting, medium voltage fuses for feeder circuit, switchgear and transformer protection. Supersedes pril 2015 USSMNN SERIES Medium voltage fuses for feeder
More informationTYPE V CENTER BREAK SWITCH
TYPE V CENTER BREAK SWITCH 3-PHASE, GROUP-OPERATED (SUBSTATION AND TRANSMISSION APPLICATIONS) *Available in Copper Horizontal upright, vertical or underhung mounting 15KV through 230KV 600A through 4000A
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationInstallation. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Table of Contents
S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons.............................. 2 Read this
More informationSTANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General
Page 1 STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General 1. Product The pad-mounted switchgear shall be in accordance with the applicable plans, drawings,
More informationPT Medium voltage fuses for potential and small power transformers
Technical Data 6002 BUSSMANN Supersedes December 2017 SERIES PT Medium voltage fuses for potential and Description: Bussmann series Indicating and nonindicating E-Rated, current-limiting, medium voltage
More informationS&C Type XS Fuse Cutouts
S&C Type XS Fuse Cutouts Outdoor Distribution (4.16 kv through 25 kv) S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection Descriptive Bulletin 351-30 August 25, 2003 Supersedes
More informationPSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.
More informationX-Limiter full-range current-limiting fuse
Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting
More informationSTANDARD SPECIFICATION FOR LIVE-FRONT 15KV AND 25KV PSI/II PAD-MOUNTED SWITCHGEAR
STANDARD SPECIFICATION FOR LIVE-FRONT 15KV AND 25KV PSI/II PAD-MOUNTED SWITCHGEAR A. General 1. Product The pad-mounted switchgear shall be PSI/II design as manufactured by Federal Pacific and shall conform
More informationDetail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order
Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2
More informationDescriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications
Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter
More informationType L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description
Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution
More informationCS-3 SERIES E-RATED/MEDIUM VOLTAGE FUSES
SERIES E-RATED/MEDIUM VOLTAGE FUSES 5kV, 8kV and 15.5kV FERRULE MOUNTED FUSES Amp-trap E-rated 5kV 8kV and 15kV fuses have 2 or 3 inch diameter barrels with ferrules and are mounted in spring reinforced
More informationHUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary
Catalog 14B January 2015 HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch.
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationProduct Selection Guide
Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility
More informationSERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES
SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationAluminum Vertical Break Switch kv A.
Bulletin DB-C106AA05 Type V2-CA Aluminum Vertical Break Switch 7.2-69 kv 600-2000 A. Designed for Simplicity V2-CA APPLICATION The Cleaveland/Price V2-CA is a three pole, group operated, aluminum vertical
More informationFaulted Circuit Interrupting Tests on Type CMU Power Fuses
CP No.: CP0509 Rev.01 Page: 1 of 9 CERTIFIED TEST REPORT Faulted Circuit Interrupting Tests on Type CMU Power Fuses REV. 01 DATE: August 10, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems,
More informationMagnetic Overload Relays
Magnetic Overload Relays Series N147 Series N147 Overload Relays are of the magnetically operated self reset type, designed for use on or motor starters and controllers for Navy Service A applications.
More information35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses
Page 1 2016 Heavy duty 11-gauge steel enclosure is all-welded construction for long life 11-gauge steel equipment plate is rigid for easier elbow operation Parking stands for the upper two phases extend
More informationOutdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter
Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles
More informationType NR oil switch installation and operation instructions
Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationOVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)
1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165
More informationAluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A A.
Bulletin DB-106AEH11 Type V2-CA Aluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A.- 3000 A. Designed for Simplicity Testing of the 345 kv V2-CA to IEEE Standards. The Cleaveland/Price 345 kv V2-CA
More informationT CLASS T FUSE BLOCKS
Ferraz Shawmut Fuse Blocks accommodate fuses up to 600A. Insulators are either of durable, glassfilled polycarbonate (GFPC) or phenolic with verified dielectric strength in excess of 2500V. Ferraz Shawmut
More informationCatalog 14A January 2013
Catalog 14A January 2013 Page 1 January 2013 Type AR (Automation-Ready) Switch 14.4kV, 25kV or 34.5kV 900 Amperes Continuous/Interrupt Description The Hubbell unitized Type AR switch is a distribution-level,
More informationS&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)
S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles
More informationType M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary
14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching
More information600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:
Issue Date: 07/17/2017 Page: 1 of 5 PSS- K656LR Elbow Connector (with Test ) Applications: The Elastimold K656LR (with test point) is designed to provide fully shielded, dead-front submersible cable connections
More informationFaulted Circuit Interrupting Tests on Type CMU Power Fuses
CP No.: CP0508 Rev. 01 Page: 1 of 9 CERTIFIED TEST REPORT Faulted Circuit Interrupting Tests on Type CMU Power Fuses REV. 01 DATE: August 10, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems,
More information600 A 35 kv class BT-TAP deadbreak connector
Supersedes 600-55 July 2014 600 A 35 kv class BT-TAP deadbreak connector General Eaton's Cooper Power Systems 600 A 35 kv Class BT-TAP deadbreak connector is used to terminate high-voltage underground
More informationشركة كهرباء محافظة القدس المساهمة المحدودة
Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories
More information