Liebert exm BDC. User Manual kVA, 60Hz

Size: px
Start display at page:

Download "Liebert exm BDC. User Manual kVA, 60Hz"

Transcription

1 Liebert exm BDC User Manual kVA, 60Hz

2 TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS GLOSSARY OF SYMBOLS LIEBERT EXM BDC Normal (UPS) Mode Maintenance Mode Locating the Cabinet Cable Installation Wiring Preparation Power Cable Installation Input/Output Wiring Accessory Fuses and Back-Feed Breaker Wiring Bolting Cabinets Together Floor Installation Cable Entry Optional Cabinets Liebert exm UPS Bypass Assembly Liebert exm BDC Interface INSTALLATION DRAWINGS SPECIFICATIONS Electrical Characteristics Torque Requirements FIGURES Figure 1 Single input UPS with external Liebert exm BDC with optional internal transformer Typical configuration Figure 2 Liebert exm BDC Access plate removed Figure 3 Accessory fuses Figure 4 Liebert exm BDC with distribution, single input Figure 5 Liebert exm BDC wiring, without transformer option, single input Figure 6 Liebert exm BDC wiring with transformer option, single input Figure 7 Wiring for LDMF with panelboard Figure 8 Wiring for LDMF with subfeed breakers Figure 9 Bolting Liebert exm UPS to a Liebert exm BDC Figure 10 Cabinet arrangement Figure 11 Liebert exm UPS bypass assembly connections Figure 12 Input dry contacts J Figure 13 Output dry contacts and EPO wiring Figure 14 Liebert exm BDC with 225A or 400A panelboards Main components Figure 15 Liebert exm BDC with two subfeed breakers Main components Figure 16 Liebert exm BDC with optional SKRU and transformer Figure 17 Busbars Liebert exm BDC with panelboard Figure 18 Busbars Liebert exm BDC Figure 19 Lineup arrangement, Liebert exm with Liebert exm BDC i

3 Figure 20 Outline drawing, Liebert exm BDC for Liebert exm, kVA Figure 21 Liebert exm BDC transformer location Figure 22 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC and panelboard Figure 23 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC, input isolation transformer and panelboard Figure 24 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC and two subfeed breakers Figure 25 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC, input isolation transformer and two subfeed breakers Figure 26 One-line diagram, 208V dual input kVA UPS with three-breaker Liebert exm BDC and panelboard Figure 27 One-line diagram, 208V dual input kVA UPS with three-breaker Liebert exm BDC and two subfeed breakers TABLES Table 1 Control wiring for Liebert exm to Liebert exm BDC Table 2 Liebert exm BDC interface Table 3 Output dry contact relays Table 4 Hardware torque values Table 5 Wiring for Liebert exm to Liebert exm BDC Table 6 Physical standards and parameters Table 7 Mechanical characteristics, Liebert exm BDC, kVA Table 8 Liebert exm BDC, kVA, mechanical characteristics Table 9 Liebert exm BDC heat dissipation Table 10 Liebert exm BDC input currents, single input, main, without transformer Table 11 Liebert exm BDC input currents, dual input, rectifier, without transformer Table 12 Liebert exm BDC output currents Table 13 Liebert exm BDC input currents, dual input, bypass, without transformer Table 14 Recommended lug sizes (compression type) M12, 1/2" bolt Table 15 Busbar torque for power wiring Table 16 Terminal block torque with compression lugs for control wiring Table 17 Breaker torque Table 18 Electrical data Liebert exm BDC, 480VAC input, 208VAC output, single input, with 480V:208V transformer Table 19 Electrical data Liebert exm BDC, 208VAC or 220VAC input, single input, with 208V:208V or 220V:220V transformer Table 20 Electrical data Liebert exm BDC, 600VAC input, 208VAC output, single input, with 600V:208V transformer ii

4 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of the Liebert exm BDC (bypass distribution cabinet). Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel. A properly trained and qualified electrical contractor should oversee the installation of the equipment. The Liebert exm BDC cannot be put into operation until it is commissioned by the manufacturer or authorized engineer. Otherwise, human safety may be endangered and damage to the UPS will not be covered by the warranty. The Liebert exm BDC is designed for commercial and industrial uses and cannot be used as life support equipment.! WARNING Risk of moving heavy equipment and electric shock. Can cause equipment damage, injury and death. Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The Liebert exm BDC s weight ranges from 660 to 1752 lb. (300 to 794kg). Determine the unit s weight and locate the center of gravity symbols before handling the Liebert exm BDC. Test lift and balance the cabinet before transporting it. Never tilt equipment more than 15 degrees from vertical. In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires. Extreme caution is required when performing maintenance. Be constantly aware that the UPS system contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters prior to making contact.! AVERTISSEMENT Risque lors du déplacement de l'équipement lourd et de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. Faites preuve d'une extrême prudence lors de la manutention des armoires ASC afin d'éviter de les endommager ou de blesser le personnel. Les armoires Liebert exm BDC pèsent de 660 à 1752 lb (de 300 à 794 kg). Déterminez le poids de l'unité et trouvez les symboles de centre de gravité avant de déplacer l'armoire Liebert exm BDC. Faites des essais de levage et d'équilibre avant de transporter l'armoire. N'inclinez jamais l'équipement à plus de 15 degrés à la verticale. En cas d'incendie associé à du matériel électrique, n'utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d'origine électrique. Les opérations d'entretien requièrent une extrême prudence. Soyez toujours conscient du fait que le système ASC contient des tensions c.c. et c.a. élevées. Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d'établir tout contact. 1 Liebert exm BDC

5 ! WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure even after input power has been disconnected. The risk of contact with these voltages is minimized as the live component parts are housed behind a metal panel. Further internal safety screens make the equipment protected to IP20 standards. Never remove panels or covers or open doors that will expose internal components to contact. Read and follow all warnings, cautions and safety and operating instructions to avoid serious injury or death from electric shock. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.! AVERTISSEMENT Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. À l'instar des autres types d'équipement haute puissance, des tensions dangereuses sont présentes à l'intérieur de l'armoire ASC et du châssis de batteries même après le débranchement de l'alimentation d'entrée. Le risque de contact avec ces tensions est diminué, car les parties de composants sous tension sont abritées derrière un panneau métallique. D'autres écrans de sécurité internes protègent l'équipement en conformité avec les normes IP20. Ne retirez jamais les panneaux ou les couvercles et n'ouvrez pas les portes donnant accès aux composants internes avec lesquels vous pouvez entrer en contact. Veuillez lire et suivre l'ensemble des avertissements, des mises en garde et des instructions de sécurité et de fonctionnement afin d'éviter des blessures graves, voire la mort, pouvant être causées par une décharge électrique. Il n'y a aucun risque pour le personnel lorsque l'équipement est utilisé normalement, en suivant les procédures de fonctionnement recommandées. Toutes les procédures de réparation et d'entretien de l'équipement exigent un accès à l'intérieur de l'armoire et devraient être menées uniquement par du personnel compétent. Liebert exm BDC 2

6 Ground Leakage Currents! WARNING Risk of electric shock from high leakage current. Can cause injury, property damage and death. EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. Earth leakage current exceeds 3.5 ma and is less than 1000 ma. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices. Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with the local electrical code of practice.! AVERTISSEMENT Risque de décharge électrique due à un courant de fuite élevé pouvant causer des blessures, des dommages matériels et même la mort. IL EST PRIMORDIAL D'ASSURER UNE CONNEXION DE TERRE AVANT DE BRANCHER L'ALIMENTATION D'ENTRÉE. La fuite à la terre est supérieure à 3,5 ma et inférieure à ma. Vous devez tenir compte des fuites de courant transitoires et permanentes à la terre, susceptibles de se produire au démarrage de l'équipement, lors de la sélection des dispositifs DDFT instantanés. Vous devez sélectionner des disjoncteurs différentiels de fuite à la terre (DDFT) sensibles aux impulsions unidirectionnelles c.c. (classe A) et insensibles aux impulsions de courant transitoires. Notez également que les courants de fuite à la terre de la charge seront acheminés par ce dispositif DDFT. Cet équipement doit être mis à la terre conformément au code national de l'électricité.! WARNING Risk of electric shock. Can cause injury, property damage and death. Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the internal batteries (internal batteries accommodated by the 10-40kVA frame only). Observe all safety precautions in this manual before handling or installing the UPS system as well as during all maintenance procedures. Observe all battery safety precautions before working on or near the battery. This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS. All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes. ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground). Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur. 3 Liebert exm BDC

7 ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures, des dommages matériels et même la mort. Les précautions de sécurité habituelles suffisent lorsque le système ASC est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système ASC doit être exempte de flaques d eau, d humidité excessive et de débris. Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l installation et à l entretien du système ASC. Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d installer le système ASC, ainsi que pendant toutes les procédures d entretien. Cet équipement comporte plusieurs circuits à haute tension. Seuls des équipements d essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours des voltmètres c.a. et c.c. pour vérifier les tensions avant d établir un contact ou d utiliser des outils. Des tensions dangereusement élevées peuvent demeurer dans le système ASC même une fois l alimentation coupée. Tous les câbles d alimentation et de contrôle doivent être installés par un électricien qualifié. Tous les câbles d alimentation et de contrôle doivent être conformes au Code national de l électricité des États-Unis (NEC) et celui du Canada, ainsi qu aux codes locaux en vigueur. L entretien du système ASC ne doit être confié qu à des professionnels qualifiés. Les responsables de l entretien et l équipement d essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d équipement sous tension. Les responsables de l entretien doivent porter des chaussures isolantes pour prévenir tout contact direct avec le plancher. Ne travaillez jamais seul, même si toute l alimentation d entrée est coupée de l équipement. Une seconde personne devrait toujours être présente pour porter assistance ou chercher de l aide en cas d accident. NOTICE Risk of improper ground connection. Can cause equipment damage. Ground connection is essential before connecting the input supply. This equipment must be grounded in accordance with local electrical codes. Maximum load must not exceed that shown on the UPS rating label. NOTICE Risk of improper electromagnetic shielding. Can cause radio communication interference. This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting. Liebert exm BDC 4

8 GLOSSARY OF SYMBOLS Risk of electrical shock! Indicates caution followed by important instructions AC input AC output i Requests the user to consult the manual - + PbH2SO4 Indicates the unit contains a valve-regulated lead acid battery R Recycle DC voltage AC voltage Equipment grounding conductor Bonded to ground 5 Liebert exm BDC

9 Liebert exm BDC 1.0 LIEBERT exm BDC The Liebert exm BDC is designed to operate in UPS normal mode, static bypass mode and maintenance mode. The Liebert exm BDC offers kVA capacity to match the associated Liebert exm frame offerings. Each of the Liebert exm BDC capacities offer optional input 208V, 220V, 480V and 600V internal transformers as well as multiple output distribution selections. Figure 1 Single input UPS with external Liebert exm BDC with optional internal transformer Typical configuration BYPASS DISTRIBUTION CABINET * System AC Input 3 Wire + GND BIB MBB MIB (Optional) 54 Pole See Note 5 AC Output 208V 4 Wire + GND STATIC BYPASS Local Grounding Electrode See Note 1 UPS CABINET BATTERY NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. UPS system input and output cables must be run in separate conduits. 4. Control wiring must be run in separate conduits. 5. Optional 54-pole, 225A for 10-40kVA frame only or optional 54-pole 400A for kVA frame only. 6. Transformer available: 208, 220, 480, 600V input. BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring EXM1104 Rev Normal (UPS) Mode While the Liebert exm BDC is in Normal mode (MBB open; BIB/MIB closed), the UPS is supplying the connected load with continuous, high-quality AC power. In this mode of operation, the load is protected by the UPS. 1.2 Maintenance Mode When the Liebert exm BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS. Liebert exm BDC 6

10 1.3 Locating the Cabinet Liebert exm BDC This Liebert exm BDC may be mounted to the right of the UPS or installed as a stand-alone unit. Ensure that the unit is in a well-ventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes. When the BDC is ordered as a stand-alone cabinet, connecting cables are not included. 1.4 Cable Installation Wiring Preparation Be sure that the unit is not connected to any AC utility power source or UPS before installing any wiring to this unit. This Liebert exm BDC should be installed by a qualified / certified electrician.! WARNING Risk of electrical shock and arc flash. Can cause property damage, injury and death. Read this section thoroughly before attempting to install wiring to this unit. Read and comply with all warnings and cautions in this manual. Removing the Cover Plates Plates cover the input and output terminals on the front of the Liebert exm BDC (see Figure 2). Remove these and keep the screws and plates for reinstallation. Figure 2 Liebert exm BDC Access plate removed Power Cable Installation Refer to Table 42 when selecting cables. NOTE Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load. 7 Liebert exm BDC

11 Liebert exm BDC Input/Output Wiring Follow the steps below to connect the input wiring: NOTE Input wiring must be installed using conduit if cabinet is not mounted to the immediate right of the UPS. 1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the appropriate size hole for the size conduit being used. Pull the three/four input wires through it, allowing some slack for installation. For cabinets that are located to the immediate left of the UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that the edge guarding is installed and intact. 2. Secure the conduit to the access plate of the Liebert exm BDC. 3. Input power cables connect to the system input bus; refer to Figure 14 and to Table Connect the ground (earth) wire to the earth busbar and tighten it to 428 lb-in (48Nm) for M12 bolt. 5. Locate UPS input and output cables and access panel to UPS on lower right side. NOTE If the Liebert exm BDC is not to be bolted to the UPS, use either top or bottom access plate. 6. Connect the system ground cable between the Liebert exm BDC and UPS and tighten the connections to 428 lb-in (48Nm) for M12 bolt. 7. Connect the system input cables between the Liebert exm BDC UPS Input Busbars (A-B-C N terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 428 lb-in (48Nm) for M12 bolt. 8. Connect the system output cables between the Liebert exm BDC UPS Output Busbars (A-B-C N terminals) and UPS output busbars (A-B-C N terminals) and tighten the connections to 428 lb-in (48Nm) for M12 bolt. 9. Connect TB1 from the Liebert exm BDC to J23, J24 and J26 on the Liebert exm. NOTICE Risk of improper wiring connection. Can cause equipment damage. The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between bypass cabinet and UPS. NOTES 1. All interconnection hardware supplied by Emerson. 2. AC connections must be made to the UPS module before attaching Liebert exm BDC to UPS module. 3. All cabling will be field-supplied when a Liebert exm BDC is configured as a stand-alone cabinet. 4. Liebert exm BDC s must attach to the right side only of the Liebert exm UPS. 5. Refer to the individual drawing of each piece of equipment for additional details. Table 1 Control wiring for Liebert exm to Liebert exm BDC From Liebert exm UPS Bypass Module (X9 J23, J24 and J26) To Liebert exm BDC Terminal Strip (TB1) J24-3 TB1-7 FH1-B TB1-8 J26-15 TB1-6 J26-13 TB1-5 J26-11 TB1-4 J26-9 TB1-3 J23-4 TB1-11 J23-6 TB1-12 FH1-N J24-1 Refer to Figure 3 for the location of fuse block FH1 and to Figure 11 for the location of J23, J24 and J26 Liebert exm BDC 8

12 1.4.4 Accessory Fuses and Back-Feed Breaker Wiring Liebert exm BDC The back-feed breaker fuse block provides power to trip the BIB breaker. It is at the lower right of the input/output panel on the front of the Liebert exm UPS. See Figure 3 for fuse block locations. Figure 3 Accessory fuses Back-Feed Breaker Fuse Block, FH1 BDSUi Fuse Block, FH2 (optional for Alber battery monitoring feature) Fuse Blocks are on the front of the Liebert exm UPS. The back-feed breaker fuse block provides 120V and is connected to the UPS output (L-N). The fuse is rated for 8A. Figures 4, 5 and 6 show the back-feed breaker wiring; the connections are made to the static bypass assembly as shown in Table 1. For additional details about the FH1 fuse block refer to the Liebert exm UPS manuals, SL and SL The manuals ship with the UPS and are available at Liebert s Web site: 9 Liebert exm BDC

13 Liebert exm BDC Figure 4 Liebert exm BDC with distribution, single input Utility W07 W08 W09 MBB See Note 6 W04 W05 W06 BIB Detail A Detail B W85 W86 W87 AC Output on oa ob oc UPS Fuse A B C mn PE AC Input W88 W89 W90 MIB See Note Kirk Key K2 (2) Fuses 2A Output Neutral Ground to Unit Frame SKRU ØA ØB ØC AC Output Optional 54-Pole/Two Subfeeds See Note 3 Output Ground TB KO Optional Input Neutral Main Ground Busbar See Note 1 AC 120V Lamp Push Button SKRU - Solenoid Key Release Unit KO - Key Operator Ground to Unit Frame Notes 1. Customer-furnished electrode conductor must be installed in accordance with national and local electrical codes. 2. See installation manual for additional connection information. 3. Optional 54-pole, 225A for 10-40kVA frame only or optional 54 pole, 400A for kVA frame only. Or two 225A subfeeds for kVA only 4. Optional transformer: 208/220/480/600V input. 5. Overcurrent protection is based on 80% rated devices. 6. MBB auxiliary switch connections are on the normally closed and common positions. 7. MIB auxiliary switch connections are on the normally opened and common positions. 8. When the Liebert BDC is connected to UPS module, all control and power wiring is supplied by Emerson. When the Liebert BDC is remote from the UPS module, the cables between the Liebert BDC and UPS module must be supplied by others. Detail A AC Output on oa ob Detail B Field-Supplied Wiring Factory-Supplied Wiring EXM1405 Rev. 0 X9J24 MFP_D1 MFP_S3 MFP_C5 Main_obnl_O2 Main_obnl_S4 Main_obnl_C6 X9J23 BFP_O1 BFP_S3 BFP_C5 INV_D2 INV_S4 INV_C6 FH1 BLK oc FH2 UPS *Option Fuse X9J26 GND_DRY15 Q5_STATUS13 GND_DRY11 Q3_STATUS 9 Liebert exm BDC 10

14 Liebert exm BDC Figure 5 Liebert exm BDC wiring, without transformer option, single input AUX. C N/O N/C Refer to Table 1 DETAIL B Output Neutral MBB W04 AUX. C N/O N/C W05 W06 Detail A AC Output W88 W89 W90 MIB To Panelboard or Subfeed Refer to Table 1 UPS Fuse Detail B DETAIL A Utility Input Phase A Phase B Phase C Neutral Customer Main Input Busbars W07 W08 W09 BIB W85 W86 W87 Ground AC Input W83 W84 TB1 Customer Input Neutral Ground to Unit Frame NOTES 1. Wiring furnished by factory. 2. Customer-furnished grounding electrode conductor to be installed in accordance with National Electric Code Article Customer Main Ground Busbar Ground Electrode See Note 2 WIRING LEGEND Factory-Supplied Wiring Factory - or Field-Supplied Pg. 1, Rev Liebert exm BDC

15 Liebert exm BDC Figure 6 Liebert exm BDC wiring with transformer option, single input Utility Input A B C AUX. DETAIL A W01 W02 W03 H1 H2 H3 Isolation Transformer T X-A X-B X-C X0 Ground to Unit Frame NOTES 1. Wiring furnished by factory. 2. Customer-furnished grounding electrode conductor to be installed in accordance with National Electric Code Article W10 MBB W04 W05 W06 Detail A BIB W07 W08 W09 W85 W86 W87 W83 Customer Input Neutral Ground to Unit Frame W84 AUX. Output Neutral DETAIL B AC Output MIB W88 W89 W90 To Panelboard or Subfeed Detail B A B C mn PE AC Input Customer Main Ground Busbar Ground Electrode See Note 2 WIRING LEGEND Factory-Supplied Wiring Factory - or Field-Supplied Pg. 2, Rev. 3 C N/O N/C C N/O N/C Refer to Table 1 Refer to Table 1 G15, G61, G71, G81 G91, G93, G101 Only UPS Fuse Liebert exm BDC 12

16 Liebert exm BDC Figure 7 Wiring for LDMF with panelboard Rear View LEFT SIDE RIGHT SIDE 1. Wiring furnished by factory. 2. Customer-furnished grounding electrode conductor to be installed in accordance with National Electric Code, Article WIRING LEGEND Factory- or Field-Supplied Pg. 5, Rev Fuse 5A DB9 to Accent P9 (50 Pin) P8 (50 Pin) P15 (50 Pin) P16 (50 Pin) Rear View CT STRIP-1 50 Pin 50 Pin Ribbon Cable to P15 Ribbon Cable to P16 Ribbon Cable to P9 Ribbon Cable to P8 50 Pin 50 Pin CT STRIP-2 Load Line Pin 1 Pin 1 W508 (Black) W512 (Black) W511 (Black) W510 (Black) C-Phase B-Phase A-Phase W504 (Wht) W503 (Blk) W503 (Blk) W504 (Wht) W505 (Blk) W501 (Red) W502 (Blk) Panel Board Output Neutral CT1 CT2 CT3 CT4 Ground Busbar CT5 W507 Input Neutral Customer-Supplied Wiring Twisted Pair from LCD Ribbon Cable from LCD Factory-Supplied Wiring AC (N) AC (L) +Vout NC -Vout NC NC P38 (34 Pin) Liebert exm BDC

17 Liebert exm BDC Figure 8 Wiring for LDMF with subfeed breakers 88 DB9 to Accent P38 (34 Pin) 1. Wiring furnished by factory. 2. Customer-furnished grounding electrode conductor to be installed in accordance with National Electric Code, Article WIRING LEGEND Factory-Supplied Wiring Factory- or Field-Supplied P9 (50 Pin) P8 (50 Pin) P15 (50 Pin) P16 (50 Pin) Pg. 5, Rev. 2 Pin 1 Pin 1 W504 (Wht) W503 (Blk) W503 (Blk) 53834G P P P G2 A-Phase B-Phase C-Phase A-Phase B-Phase C-Phase Load Line W504 (Wht) W505 (Blk) Fuse 5A W501 (Red) W502 (Blk) Subfeed Breaker Front View Output Neutral J3 77 J1 Input Neutral Twisted Pair from LCD Ribbon Cable from LCD 76 AC (N) AC (L) +Vout NC -Vout NC NC 78 TB P6 (9 Pin) P5 (9 Pin) MBB MIB CB1 CB2 Ground Busbar Liebert exm BDC 14

18 Liebert exm BDC 1.5 Bolting Cabinets Together NOTE UPS wiring must be completed before the cabinets are bolted together. 1. Line up cabinets so that mounting holes are aligned. Figure 9 Bolting Liebert exm UPS to a Liebert exm BDC A Hex Head Bolt, M10 x 30mm Washer Split, M10 Washer Flat, M10 Place cabinets so mounting holes are aligned. A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet. DETAIL A 2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the UPS side or from the Liebert exm BDC side, whichever is more convenient.! WARNING Risk of heavy units tipping over while being moved. Can cause property damage, injury and death. The Liebert exm BDC and battery cabinets must be properly prepared and secured for lifting. Improper lifting may cause the cabinets to fall, causing equipment damage, personal injury and death. Emerson recommends lifting the units with one of the following methods: Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism. Placing suitable straps on the Liebert exm BDC or battery cabinet. The straps must go under the unit to be lifted. 15 Liebert exm BDC

19 1.5.1 Floor Installation Liebert exm BDC! AVERTISSEMENT Le centre de gravité élevé des appareils présente un risque de renversement lors des déplacements, pouvant entraîner des dommages matériels, des blessures et même la mort. If the Liebert exm BDC is to be placed on a raised floor, the UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the Liebert exm UPS manual, SL or SL-25650, to design this pedestal Cable Entry Les armoires Liebert exm BDC et de batterie doivent être correctement préparées et sécurisées avant d être levées. Un mauvais levage peut faire tomber les armoires, causant des dommages à l'équipement, des blessures, voire la mort. Emerson recommande de soulever les unités en suivant l'une des méthodes suivantes : En installant quatre anneaux de levage dans les ouvertures fabriquées en usine, avec un anneau dans chaque coin de l appareil, pour ensuite fixer les câbles ou sangles aux anneaux afin d'effectuer le levage à l'aide d'un mécanisme approprié. En plaçant des sangles convenables sur l'armoire Liebert ou de batterie. Les sangles doivent passer sous l'unité à soulever. Cables can enter the Liebert exm BDC from the top or bottom through removable metal plates. Some plates have factory-punched holes and others are designed to allow the personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS. The conduit size and wiring method must be in accordance with all local, regional and national codes and regulations, including NEC ANSI/NFPA 70. NOTE When installing the UPS, the customer must provide a disconnect with overcurrent protection at the output of the UPS Optional Cabinets The Liebert exm BDC must be bolted to right side of the Liebert exm (see Figure 10). The Liebert exm BDC must be cabled and bolted to the Liebert exm before the UPS and bypass distribution cabinet are moved into their final position. Connect input wiring to the Liebert exm BDC ONLY after the units are internally cabled and positioned. Battery cabinets may be bolted only to the left side of the Liebert exm; see Figure 10. Figure 10 Cabinet arrangement ALL UNITS VIEWED FROM ABOVE Liebert exm Bypass Distribution Cabinet Battery Cabinet Battery Cabinet Liebert exm Bypass Distribution Cabinet Liebert exm UPS connected only to Liebert exm BDC (The Liebert exm BDC must be on right side of the Liebert exm UPS) Liebert exm UPS connected to Liebert exm BDC and Battery Cabinets (BDC must be on right side of the Liebert exm) (Battery Cabinets must be on the left side of the Liebert exm UPS) Liebert exm BDC 16

20 Liebert exm BDC 1.6 Liebert exm UPS Bypass Assembly Figure 11 Liebert exm UPS bypass assembly connections J1 J19 J20 J21 J22 J26 J23 J24 J25 Liebert IntelliSlot Ready Switch Bays 1, 2, 3 The Static bypass assembly has three Liebert IntelliSlot interface card bays and connections for ancillary cabinets (Liebert exm BDC and battery) and for options Liebert exm BDC Interface The Liebert exm BDC interface is on the Auxiliary Terminal Block at J26. Refer to Figure 12 for circuit details. Table 2 Liebert exm BDC interface Position Name Description J26.1 Q1 STA Main input switch status signal J26.5 Q2 STA Bypass input switch status signal J26.9 Q3 STA External maintenance switch status signal J26, 3, 7, 9 GND Ground for dry contacts These contacts cannot be active unless they are set via software. 17 Liebert exm BDC

21 Liebert exm BDC Figure 12 Input dry contacts J26 J26 Q1 STATUS GND_DRY Q2 STATUS GND_DRY Q3 STATUS GND_DRY Q5 STATUS GND_DRY GND_DRY RESV2 RESV3 GND_DRY NC UT UT GND_MON GEN MODE GND_DRY TMP BATT IN +12V_DRY GND_DRY GND_DRY _ RESERVED ENV_DET CHG SHUT GND_DRY RESV1 GND_DRY NC UT UT NC NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively. NOTE Refer to Table 1 and Figure 4 for the Liebert exm BDC wiring. Figure 13 Output dry contacts and EPO wiring INV_O INV_S INV_C MAIN_O MAIN_S MAIN_C RESV_O RESV_S RESV_C J23 J24 J BFP_O BFP_S BFP_C MFP_O MFP_S MFP_C RESV_O RESV_S RESV_C Liebert exm BDC 18

22 Liebert exm BDC Table 3 Output dry contact relays Port Pin Name Description 1 MFP_O Rectifier back-feed normally open contact. Open when there is no back-feed. J24 3 MFP_S Rectifier back-feed common contact. 5 MFP_C Rectifier back-feed normally closed contact. Closed when there is no back-feed. 2 INV_O Inverter state normally open contact. Open when the inverter is abnormal. J23 4 INV_S Inverter state common contact. 6 INV_C Inverter state normally open contact. Closed when the inverter is normal. 1 BFP_O Bypass back-feed normally open contact. Open when there is no back-feed. J23 3 BFP_S Bypass back-feed common contact. 5 BFP_C Bypass back-feed normally closed contact. Closed when there is no back-feed. 2 MAIN_O Rectifier input state normally open contact. Open when the rectifier is abnormal. J24 4 MAIN_S Rectifier input state common contact. 6 MAIN_C Rectifier input state normally closed contact. Closed when the rectifier is normal. 19 Liebert exm BDC

23 Installation Drawings 2.0 INSTALLATION DRAWINGS Figure 14 Liebert exm BDC with 225A or 400A panelboards Main components FRONT NOTES 1. Dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits. 3. All wiring must be in accordance with national and local electrical codes. 4. If bypass distribution cabinet is attached to the right side of the UPS, Emerson will supply the interconnection cables. See Figure 18. TOP BOTTOM 23.6" (600mm) 37.5" (953mm) Panelboard 78.5" (1994mm) MBB BIB MIB System Input Bus Neutral Bus Ground Bus LEFT SIDE Panel Removed FRONT Door Removed RIGHT SIDE Panel Removed Liebert exm BDC 20

24 Installation Drawings Figure 15 Liebert exm BDC with two subfeed breakers Main components NOTES 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits. 3. Copper cables only are recommended. 4. All wiring is to be in accordance with national and local electrical codes. 5. When the Liebert exm BDC is attached to the UPS, Emerson will supply the interconnection cables A panelboard for 10k-40kVA only. 400A panelboard for kVA only BOTTOM TOP 23.6" (600mm) 37.5" (953mm) Neutral Busbar Subfeed Breakers MBB BIB MIB System Input Bus Ground Busbar Neutral Bus LEFT SIDE Panel Removed FRONT Door Removed RIGHT SIDE Panel Removed EXM16013 Rev. 0 LDMF inside front door 21 Liebert exm BDC

25 Installation Drawings Figure 16 Liebert exm BDC with optional SKRU and transformer Key Operator Lamp LDB Kirk Keys MBB BIB Transformer Option for 208V, 220V, 480V or 600V Input MIB System Input Bus Neutral Bus Ground Bus FRONT VIEW With Covers FRONT VIEW Door Removed EXM15007 Rev. 0 RIGHT SIDE VIEW Panel Removed Liebert exm BDC 22

26 Installation Drawings Figure 17 Busbars Liebert exm BDC with panelboard 23.6" (600mm) 37.5" (953mm) Neutral Busbar Ground Busbar Panelboard MBB BIB MIB See Figure 18 for details about busbars LEFT SIDE FRONT Panel Removed Door Removed Notes: 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits. 3. All wiring is to be in accordance with national and local electrical codes. 4. Emerson will supply the interconnection cables when the Liebert exm BDC is attached to the UPS A panelboard for 10k-40kVA only. 400A panelboard for kVA only. RIGHT SIDE Panel Removed EXM16012 Rev Liebert exm BDC

27 Installation Drawings Figure 18 Busbars Liebert exm BDC UPS Bus Ø 0.44" (11mm) Typical System Input Bus See Detail B Input/Output Bus, Typical 1.5" x 8.9" (38mm x 227mm) Ø 0.44" (11mm) Typical 1.38" (35mm) 1.38" (35mm) 1.38" (35mm) 1.38" (35mm) Ø 0.56" (14mm) Typical Shown with Optional SKRU 2.44" (62mm) DETAIL A 2.44" (62mm) Ground Bus 5" x 4" (127mm x 102mm) Ø 0.56" (14mm) Typical Input Breaker Input Ground Bus Neutral Bus 5" x 8.9" (127mm x 227mm) Ø 0.44" (11mm) Typical 1.75" (44.5mm) Typical All Busbars System Input Busbar at Rear, Typical System Input Connections Neutral Input/Output Connections Ø 0.56" (14mm) Typical See Figure 14. DETAIL B Iso-View Front Left Corner Post Removed Liebert exm BDC 24

28 Installation Drawings Figure 19 Lineup arrangement, Liebert exm with Liebert exm BDC 47.6" (1208mm) 23.6" (600mm) 23.6" (600mm) 78.7" (2000mm) NOTES 1. Dimensions are in inches (mm) " (610mm) minimum clearance above unit. 36" (914mm) front access required for service. For seismic mounting only 5" (102mm) in rear for mounting brackets 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. Bypass distribution cabinet must be positioned on the right side of the UPS. UPS BDC FRONT VIEW EXM13028 Rev Liebert exm BDC

29 Installation Drawings Figure 20 Outline drawing, Liebert exm BDC for Liebert exm, kVA 11.5" (292mm) Outside Panel 6.5" (164mm) Outside Panel 23.7" (602mm) TOP VIEW Maximum Door Swing " (600mm) Cable Entry Area 11.4" x 13.2" (290 x 335mm) 34.6" 28.3" (870mm) (719mm) Bracket Centers 5.5" (140mm) BOTTOM VIEW 39.5" (1000mm) Cable Entry Area 6.2" x 13.2" (57 x 335mm) 6.5" (164mm) Outside Panel 6.4" (162mm) Outside Panel 78.7" (2000mm) 24" (609mm) FRONT Leveling Feet RIGHT SIDE 1. All dimensions are in inches (mm) " (610) minimum clearance above unit; 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Control wiring and power wiring must be run in separate conduits. 6. All wiring is to be in accordance with national and local electrical codes. UAM06008 Rev. 5 Liebert exm BDC 26

30 Installation Drawings Figure 21 Liebert exm BDC transformer location Transformer RIGHT SIDE REAR OF CABINET 27 Liebert exm BDC

31 Table 4 Wiring for Liebert exm to Liebert exm BDC See Figure 4 and Table 1 for additional details. Installation Drawings Run From To Conductors A Utility AC source BDC System Input Bus Phase A, B, C B Utility AC Source BDC System Input Bus Neutral C BDC Bypass Isolation Breaker UPS Main Input Phase A, B, C D BDC Bypass Isolation Breaker UPS Main Input Neutral E UPS Output Liebert exm BDC Maintenance Isolation Breaker Phase A, B, C F UPS Output Liebert exm BDC Maintenance Isolation Breaker Neutral G BDC Panelboard Load AC Connection Phase A, B, C H BDC Panelboard Load AC Connection Neutral I Utility AC Source All Ground Connections Ground J BDC Terminal Block TB1 UPS Static Bypass Module J23, J24 and J26 Wiring for KO on Liebert exm BDC NOTE Interconnection wiring between the UPS and bypass distribution cabinet is supplied by Emerson when the Liebert exm BDC and Liebert exm UPS are ordered as a system. Table 5 Hardware torque values Hardware Two Belleville Washers M10 (3/8") 240 lb-in. (27 Nm) M12 (1/2") 428 lb-in (48Nm) Liebert exm BDC 28

32 Installation Drawings Figure 22 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC and panelboard BYPASS DISTRIBUTION CABINET * System AC Input 4 Wire + GND BIB MBB MIB (Optional) 54 Pole See Note 6 AC Output 208V 4 Wire + GND STATIC BYPASS UPS CABINET BATTERY NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. A neutral is required from the system AC input source. 4. UPS system input and output cables must be run in separate conduits. 5. Control wiring must be run in separate conduits. 6. Optional 54 pole, 225A for 10-40kVA frame only or optional 54 pole 400A for kVA frame only. BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring EM11003 Rev Liebert exm BDC

33 Installation Drawings Figure 23 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC, input isolation transformer and panelboard BYPASS DISTRIBUTION CABINET * System AC Input 3 Wire + GND BIB MBB MIB (Optional) 54 Pole See Note 5 AC Output 208V 4 Wire + GND STATIC BYPASS Local Grounding Electrode See Note 1 UPS CABINET BATTERY NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. UPS system input and output cables must be run in separate conduits. 4. Control wiring must be run in separate conduits. 5. Optional 54-pole, 225A for 10-40kVA frame only or optional 54-pole 400A for kVA frame only. 6. Transformer available: 208, 220, 480, 600V input. BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring EXM1104 Rev. 0 Liebert exm BDC 30

34 Installation Drawings Figure 24 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC and two subfeed breakers BYPASS DISTRIBUTION CABINET LDB * System AC Input 4 Wire + GND BIB MBB MIB LDB (Optional) (2) 225A See Note 6 AC Output 208V 4 Wire + GND STATIC BYPASS UPS CABINET BATTERY NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended. 4.UPS system input and output cables must be run in separate conduits. 5. Control wiring must be run in separate conduits. 6. Optional (2) 225A LDB for kVA frame only. Optional single 225A LDB for 10-40kVA frame. LDB - Load Distribution Breaker BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring EXM11005 Rev Liebert exm BDC

35 Installation Drawings Figure 25 One-line diagram, 208V single input kVA UPS with three-breaker Liebert exm BDC, input isolation transformer and two subfeed breakers BYPASS DISTRIBUTION CABINET LDB * System AC Input 3 Wire + GND BIB MBB MIB LDB (Optional) (2) 225A See Note 5 AC Output 208V 4 Wire + GND Local Grounding Electrode See Note 1 STATIC BYPASS UPS CABINET BATTERY NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. UPS system input and output cables must be run in separate conduits. 4. Control wiring must be run in separate conduits. 5. Optional (2) 225A LDB for kVA frame only. Optional single 225A LDB for 10-40kVA frame. 6. Transformer available: 208, 220, 480, 600V input. LDB - Load Distribution Breaker BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring EXM11006 Rev. 0 Liebert exm BDC 32

36 Installation Drawings Figure 26 One-line diagram, 208V dual input kVA UPS with three-breaker Liebert exm BDC and panelboard BYPASS DISTRIBUTION CABINET * Bypass AC Input 4 Wire + GND BIB MBB MIB (Optional) 54 Pole See Note 6 AC Output 208V 4 Wire + GND STATIC BYPASS * Rectifier AC Input 4 Wire + GND See Note 7 UPS CABINET BATTERY NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. 4. Bypass and rectifier inputs and output cables must be run in separate conduits. 5. Control wiring must be run in separate conduits. 6. Optional 54-pole, 225A for 10-40kVA frame only or optional 54-pole 400A for kVA frame only. 7. Customer must supply shunt trip breaker with 120V coil. 8. Remove bypass jumper busbars inside the UPS to configure a dual input system. BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring See Tables 12 and 13 for details. EXM11007 Rev Liebert exm BDC

37 Installation Drawings Figure 27 One-line diagram, 208V dual input kVA UPS with three-breaker Liebert exm BDC and two subfeed breakers BYPASS DISTRIBUTION CABINET LDB * Bypass AC Input 4 Wire + GND BIB MBB MIB LDB (Optional) (2) LDB AC Output See Note 6 208V 4 Wire + GND STATIC BYPASS * Rectifier AC Input 4 Wire + GND See Note 7 UPS CABINET BATTERY Notes 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conuctors are recommended. 4. Bypass and rectifier inputs and output cables must be run in separate conduits. 5. Control wiring must be run in separate conduits. 6. Optional (2) 225A LDB for kVA frame only. 7. Customer must supply shunt trip breaker with 120V coil. 8. Remove bypass jumper busbars inside the UPS to configure a dual input system. LDB - Load Distribution Breaker BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection By Others Field-Supplied Wiring See Tables 12 and 13 for details. EXM11008 Rev. 0 Liebert exm BDC 34

Specification Grade Contemporary Wall Mount/Technical Installation Data

Specification Grade Contemporary Wall Mount/Technical Installation Data AVAILABLE CONFIGURATIONS RECESSED MOUNT SURFACE MOUNT MOUNTING REQUIREMENTS A. Recessed Mount: Minimum 4-Gang Box, 1-5/8 in. Deep (72.8 Cubic Inches) with 4-Gang Box Cover (20.3 Cubic Inches) B. Surface

More information

LIEBERT BATTERY INTERFACE BOX : UPSBIBX, UPSBIBN AND UPSBIBR

LIEBERT BATTERY INTERFACE BOX : UPSBIBX, UPSBIBN AND UPSBIBR LIEBERT BATTERY INTERFACE BOX : UPSBIBX, UPSBIBN AND UPSBIBR Product Specification/Installation SheetLiebert EXL, Liebert EXL S, Liebert NX -6 and Liebert NXL SAVE THESE INSTRUCTIS This manual contains

More information

Captivate Illuminated Mirror Light

Captivate Illuminated Mirror Light ENGLISH WARNINGS & SAFETY INFORMATION: PLEASE READ CAREFULLY FRANÇAIS MISES EN GARDE ET SÉCURITÉ: SE IL VOUS PLAÎT LIRE ATTENTIVEMENT WARNING: RISK OF FIRE OR ELECTRIC SHOCK. LUMINAIRE WIRING AND ELECTRICAL

More information

INSTALLATION INSTRUCTIONS LED Canopy Retrofit Kit

INSTALLATION INSTRUCTIONS LED Canopy Retrofit Kit INSTALLATION INSTRUCTIONS LED Canopy Retrofit Kit TRMUNV065ECxyyZ TRAUNV065ECxyyZ Installation Instructions subject to change without notice. Page 1 of 8 1.0 INSTALLATION WARNINGS 1. 2. 3. 4. 5. 6. "THIS

More information

Albeo TM LED Luminaire Heavy Industrial High Bay Lighting (ABR1-Series)

Albeo TM LED Luminaire Heavy Industrial High Bay Lighting (ABR1-Series) GE Lighting Installation Guide Albeo TM LED Luminaire Heavy Industrial High Bay Lighting (ABR1-Series) Features UL 1598 Suitable for Wet Locations IP66 Rated Ingress Protection BEFORE YOU BEGIN Read these

More information

Lumination TM LED Luminaire RC/LRC/RX/LRX Series - New Construction Frame

Lumination TM LED Luminaire RC/LRC/RX/LRX Series - New Construction Frame Installation Guide Lumination TM LED Luminaire RC/LRC/RX/LRX Series - New Construction Frame BEFORE YOU BEGIN Read these instructions completely and carefully. RISK OF ELECTRIC SHOCK Turn power off before

More information

INSTALLATION INSTRUCTION Bollard Light 12V

INSTALLATION INSTRUCTION Bollard Light 12V Bollard Light 12V 6611/6621/6631/6641/6651 SAFETY INSTRUCTION IMPORTANT: NEVER attempt any work without shutting off the electricity. Read all instructions before installing. System is intended for installation

More information

IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following:

IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: ZR-RK Series LED Retrofit Troffer Kit Includes: ZR22RK and ZR24RK Standard and Emergency Luminaires IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed

More information

Instruction Sheet ERK-XXXXKD SERIES KNOCKDOWN STANDALONE RACK

Instruction Sheet ERK-XXXXKD SERIES KNOCKDOWN STANDALONE RACK Instruction Sheet ERK-XXXXKD SERIES KNOCKDOWN STANDALONE RACK C UL R US LISTED THANK YOU Thank you for purchasing the ERK-XXXXKD Series Knockdown Standalone Rack. Please read these instructions thoroughly

More information

CSD Series Current Devices Split Core

CSD Series Current Devices Split Core CSD Series Current Devices Split Core Installation Instructions CSD-CF0A0-1 CSD-CF0J0-1 CSD-CA1G0-1 Part. 24-10345-34, Rev. D Issued March 31, 2014 Supersedes April 5, 2013 Applications The Current Switch

More information

Fan Relay Board (FRBii) Assembly

Fan Relay Board (FRBii) Assembly Fan Relay Board (FRBii) Assembly Installation, Operation, and Maintenance Instructions PK-FCU030-0, PK-FCU050-0 Part No. 24-10143-1221, Rev. A Issued February 2017 Application Refer to the QuickLIT website

More information

Electric Vehicle Supply Equipment

Electric Vehicle Supply Equipment Electric Vehicle Supply Equipment By Control Module Inc, EVSE LLC State of the Art EVSE with Cable Management Electrician EVSE Tester Model 3840-001 User Guide Model 3840-001 Electrician EVSE Tester Patents

More information

Wet Rated Batten LED Luminaire

Wet Rated Batten LED Luminaire Installation Guide Wet Rated Batten LED Luminaire LED Lighting System BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING / AVERTISSEMENT RISK OF ELECTRIC SHOCK Turn power off before

More information

Lumination TM LED Luminaires LAL Series - Continuous Run Option

Lumination TM LED Luminaires LAL Series - Continuous Run Option GE Lighting Installation Guide Lumination TM LED Luminaires LAL Series - Continuous Run Option BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING/AVERTISSEMENT RISK OF ELECTRIC

More information

UB-2 2 Universal Button

UB-2 2 Universal Button UB-2 2 Universal Button UB-2/LTUL Universal Button with Latching Timer ADA Compliant For UB-2/LTUL the enclosed timer is to be used and installed per the enclosed LT-1UL installation sheet. For access

More information

LST Solid-State Starter User s Manual TB WOOD S INCORPORATED

LST Solid-State Starter User s Manual TB WOOD S INCORPORATED Form 1276A TM LST Solid-State Starter User s Manual TB WOOD S INCORPORATED Chambersburg, Pennsylvania TRADEMARK NOTICE TB Wood s and are registered trademarks of TB Wood s Incorporated. is a trademark

More information

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. DANGER RISK OF SHOCK DISCONNECT POWER BEFORE INSTALLATION

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. DANGER RISK OF SHOCK DISCONNECT POWER BEFORE INSTALLATION UR Series LED Upgrade Kit Includes: 24" Linear Option IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND FOLLOW ALL

More information

Eaton 9395 High Performance* Sync Installation Controland Operation Manual

Eaton 9395 High Performance* Sync Installation Controland Operation Manual Eaton 9395 High Performance* Sync Installation Controland Operation Manual Installation and Operation Manual *Referenced throughout as 9395P Eaton 9395 High Performance* Sync Installation Controland Operation

More information

VA-4233-AGx Series Electric Valve Actuators

VA-4233-AGx Series Electric Valve Actuators Installation Instructions VA-4233 No. 1 Issue Date June 30, 2014 VA-4233-AGx Series Electric Valve Actuators Installation Refer to Figures 2 through 4 for proper actuator orientation before attempting

More information

LAL SERIES LED LUMINAIRE

LAL SERIES LED LUMINAIRE INSTALLATION, OPERATION & MAINTENANCE DATA SHEET LAL SERIES LED LUMINAIRE CAUTION: LAL SERIES LED LUMINAIRE Before installing, make sure you are compliant with area classifications, failure to do so may

More information

Cable Cubby 1202 and 1402 Installation Guide

Cable Cubby 1202 and 1402 Installation Guide Cable Cubby 0 and 40 Installation Guide IMPORTANT: Go to www.extron.com for the complete user guide, installation instructions, and specifications. This guide provides instructions for an experienced technician

More information

INSTALLATION INSTRUCTIONS LED RETROFIT ASSEMBLY (LRA) Rev F

INSTALLATION INSTRUCTIONS LED RETROFIT ASSEMBLY (LRA) Rev F SAFETY S IMPORTANT SAFETY INFORMATION SUITABLE FOR DRY OR DAMP LOCATIONS. NOT FOR USE WITH PHASE CUT DIMMERS. Risk of shock. Disconnect power before installation. DANGER CONVIENT AUX EMPLACEMENTS HUMIDES.

More information

M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators

M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators 34-636- 1360, Rev. C Installation Instructions M9109-GGx-5 Issue Date March 2016 M9109-GGx-5 Series Proportional Electric Non-spring Return Actuators Installation IMPORTANT: Use this M9109-GGx-5 Series

More information

Tetra minimax. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide

Tetra minimax. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide Installation Guide Volt Tetra minimax LED Lighting System GEMMRD-W, GEMMGL-W, GEMMBL-W BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING/AVERTISSMENT RISK OF ELECTRIC SHOCK Turn

More information

AC Power For Business-Critical Continuity. Liebert NXL. Installation Manual kVA, 60Hz, Three-Phase, Single-Module

AC Power For Business-Critical Continuity. Liebert NXL. Installation Manual kVA, 60Hz, Three-Phase, Single-Module AC Power For Business-Critical Continuity Liebert NXL Installation Manual 250-400kVA, 60Hz, Three-Phase, Single-Module CONTACTING EMERSON NETWORK POWER FOR SUPPORT To contact Emerson Network Power Liebert

More information

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT SITE PLANNING DATA LIEBERT EXM 3-PHASE : 10-100KVA/K, 60HZ, 208-480VAC, SINGLE INPUT MAINTENANCE BYPASS CABINET Busbar * System 3 ire + GND BIB MBB MIB Note 6 AC 208V 4 ire + GND Static Bypass Local Grounding

More information

INSTALLATION INSTRUCTION Aether 2 Shallow Recessed Housing

INSTALLATION INSTRUCTION Aether 2 Shallow Recessed Housing SAFETY INSTRUCTIONS IMPORTANT: NEVER attempt any work without shutting off the electricity. Read all instructions before installing. System is intended for installation by a qualified electrician in accordance

More information

INSTALLATION INSTRUCTION Aether 3.5 Color Tunable LED Downlight

INSTALLATION INSTRUCTION Aether 3.5 Color Tunable LED Downlight SAFETY INSTRUCTION IMPORTANT: NEVER attempt any work without shutting off the electricity. Read all instructions before installing. System is intended for installation by a qualified electrician in accordance

More information

System 350 S350C Temperature Slave Stage Module

System 350 S350C Temperature Slave Stage Module FANs 930, 930.5, 125, 121 Product/Technical Bulletin Issue Date April 8, 2014 System 350 Temperature Slave Stage Module The Temperature Slave Stage Module is used in conjunction with the A350 Temperature

More information

INSTALLATION DATA ETC SINGLE Stage

INSTALLATION DATA ETC SINGLE Stage INSTALLATION DATA ETC SINGLE Stage Electronic Temperature Control - NEMA TYPE 4X The Ranco ETC is a microprocessor based electronic temperature control designed to provide on/off control for commercial

More information

INSTALLATION INSTRUCTIONS MOONRING 1 LP1/MR1

INSTALLATION INSTRUCTIONS MOONRING 1 LP1/MR1 INSTALLATION INSTRUCTIONS MOONRING 1 LP1/MR1 Suspended, Ceiling LED n A 1035 22nd Avenue, Unit 1 Oakland, CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com Safety & Warnings! 1. Read all instructions.

More information

VWM SERIES U L R. Instruction Sheet. Vertical Wall Mount Rack LISTED

VWM SERIES U L R. Instruction Sheet. Vertical Wall Mount Rack LISTED Instruction Sheet VWM SERIES Vertical Wall Mount Rack C U L R LISTED US THANK YOU Thank you for purchasing the VWM Series. Please read these instructions thoroughly before installing or assembling this

More information

MAXLITE RKT LED Retrofit Kit

MAXLITE RKT LED Retrofit Kit MAXLITE RKT LED Retrofit Kit Description and Intended Use The RKT LED Retrofit Kit is a high performance LED Fixture upgrade kit designed to replace the original components inside 2 x2 and 2 x4 fluorescent

More information

WARNING/AVERTISSEMENT. Coupez l alimentation électrique à la boîte de fusibles ou au disjoncteur avant servicing or installing product.

WARNING/AVERTISSEMENT. Coupez l alimentation électrique à la boîte de fusibles ou au disjoncteur avant servicing or installing product. Tetra Contour LS LED Lighting System GEXNLBL-1, GEXNLGL-1, GEXNLRD-1, GEXNL65-1, GEXNL32-1 Installation Guide 24 Volt BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING/AVERTISSEMENT

More information

INSTALLATION DATA ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

INSTALLATION DATA ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL INSTALLATION DATA ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL The Ranco ETC is a microprocessor based family of electronic temperature controls, designed to provide on/off control for commercial heating,

More information

Installation Instructions

Installation Instructions PART NUMBER: CPLPCONV007A00 60,000---130,000 BTU/HR 2TO5TONS SMALL PACKAGED PRODUCTS GAS HEATING/ELECTRIC COOLING UNITS HIGH ALTITUDE ONLY 2001---6000 FT PROPANE CONVERSION KIT Installation Instructions

More information

ASTAT XB USER MANUAL. 1 Caution Statements

ASTAT XB USER MANUAL. 1 Caution Statements ASTAT XB USER MANUAL 1 Caution Statements Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read

More information

MOONRING 1.5 MOONRING 3

MOONRING 1.5 MOONRING 3 INSTALLATION INSTRUCTIONS MOONRING 1.5 MOONRING 3 MR1.5 & MR3 Suspended, Ceiling LED n A 1035 22nd Avenue, Unit 1 Oakland, CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com Safety & Warnings!

More information

Electric Vehicle Supply Equipment

Electric Vehicle Supply Equipment Electric Vehicle Supply Equipment By Control Module Inc, EVSE LLC State of the Art EVSE with Cable Management Electrician EVSE Tester Model 3840-001 Model 3840-001 Electrician EVSE Tester Patents Pending

More information

LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA

LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA BYPASS DISTRIBUTION CABINET (Optional; see Note 7) The UPS must be fed from a solidly grounded wye or delta

More information

ELV1abbccd-e. Color Temperature: 30 = 3000K White 35 = 3500K White 40 = 4000K White 45 = 4500K White 50 = 5000K White

ELV1abbccd-e. Color Temperature: 30 = 3000K White 35 = 3500K White 40 = 4000K White 45 = 4500K White 50 = 5000K White GE Lighting Immersion TM Elite LED Refrigerated Display Lighting End Mullion Lights for Vertical Cases Installation Guide ELV1abbccd-e Prefix: EL = Elite V = Vertical FD = French Door 1 = Generation Light

More information

Troubleshooting Guide

Troubleshooting Guide Troubleshooting Guide Current Revision: June 2009 Table of Contents PAGE IMPORTANT NOTES ------------------------------------------------------------------- 3 20T Main Electrical System --------------------------------------------------------------

More information

INSTALLATION INSTRUCTIONS SUPERPLANE 2.5. Suspended. A nd Avenue, Unit 1 Oakland, CA P E W alwusa.

INSTALLATION INSTRUCTIONS SUPERPLANE 2.5. Suspended. A nd Avenue, Unit 1 Oakland, CA P E W alwusa. INSTALLATION INSTRUCTIONS SUPERPLANE 2.5 Suspended A 1035 22nd Avenue, Unit 1 Oakland, CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com SP2.5S - Safety & Warnings! 1. Read all instructions. 2.

More information

PRODUCT DESCRIPTION SPECIFICATIONS

PRODUCT DESCRIPTION SPECIFICATIONS PRODUCT DESCRIPTION The Ranco ETC is a microprocessor based electronic temperature control designed to provide on/off control for commercial heating, ventilating, air conditioning and refrigeration. The

More information

LUNERA VERTICAL E26 LED FLOODLIGHT LED Replacement for E26 Medium Base Floodlights Type B Ballast Bypassed

LUNERA VERTICAL E26 LED FLOODLIGHT LED Replacement for E26 Medium Base Floodlights Type B Ballast Bypassed Installation Guide LUNERA VERTICAL E26 LED FLOODLIGHT LED Replacement for E26 Medium Base Floodlights Type B Ballast Bypassed Installation Description The LUNERA VERTICAL E26 LED FLOODLIGHT is a line driven

More information

M Remote Mounting Kit

M Remote Mounting Kit M9203-100 Remote Mounting Kit M9203-100 Part No. 34-636-2308, Rev. A Issued August 29, 2014 Applications IMPORTANT: Use this M9203-100 Remote Mounting Kit only to control equipment under normal operating

More information

WASP-P PRESSURE SENSOR

WASP-P PRESSURE SENSOR WASP-P PRESSURE SENSOR USER MANUAL VERSION 03.22 15/03/2016 WASP is a registered trademark owned by BossPac Engineering & Technology WASP is a PATENT PENDING technology owned by BossPac Engineering & Technology

More information

OWNER S MANUAL OM F

OWNER S MANUAL OM F OWNER S MANUAL OM-2606 96 030F May 2004 Cool Runner 3X. Specifications Recirculating Coolant System For Water-Cooled GTAW Torches And GMAW Guns Use With Guns/Torches Rated Up To 600 Amperes 3 gal (.4 L)

More information

- Wiring Brochure Zone Manager 335

- Wiring Brochure Zone Manager 335 - Wiring Brochure W 335 12/08 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications Rough-in Wiring Rough-in wiring instructions 3 4 Wiring

More information

Have a Bright Day! Nicholas Harmon President, Verilux, Inc.

Have a Bright Day! Nicholas Harmon President, Verilux, Inc. VF02 Dear Customer, Thank you for purchasing the Verilux EasyFlex Deluxe Natural Spectrum Floor Lamp. You have received a quality product, backed by a one year limited warranty. As a Verilux customer,

More information

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz. 103158 March 9, 2011 FOR INDOOR USE ONLY Detex Corporation, 302 Detex Drive, New Braunfels, Texas 78130-3045 (830)629-2900 / 1-800-729-3839 / Fax (830)620-6711 E-MAIL: detex@detex.com INTERNET: www.detex.com

More information

PowerXL Series VFD. Installation manual. Effective February 2018 Supersedes September 2016

PowerXL Series VFD. Installation manual. Effective February 2018 Supersedes September 2016 PowerXL Series VFD Installation manual Effective February 2018 Supersedes September 2016 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions, and safety

More information

INSTALLATION DATA ETC SINGLE STAGE ELECTRONIC TEMPERATURE CONTROL

INSTALLATION DATA ETC SINGLE STAGE ELECTRONIC TEMPERATURE CONTROL INSTALLATION DATA ETC SINGLE STAGE ELECTRONIC TEMPERATURE CONTROL The Ranco ETC is a microprocessor-based family of electronic temperature controls, designed to provide on/off control for commercial heating,

More information

Cable Cubby 650 UT Installation Guide

Cable Cubby 650 UT Installation Guide e NT: RTA.com for thtion O P IM tron talla w.ex uide, ins ations. o ww Go t te user g specific nd ple com ctions, a u instr Cable Cubby 650 UT Installation Guide This guide provides instructions for an

More information

Spun Bay Installation Standard Version (non dimmable), Hook Mount

Spun Bay Installation Standard Version (non dimmable), Hook Mount Spun Bay Installation Standard Version (non dimmable), Hook Mount WARNING: Make sure that all power is turned off while installing fixture. Do not turn power on until fixture is completely installed. Turn

More information

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

VA2202-xxx-2 Series Electric Spring Return Valve Actuators *4344D* 4-344-, Rev. D VA222-xxx-2 Series Electric Spring Return Valve Actuators Installation Instructions Part No. 4-344-, Rev. D Issued October 27 Applications IMPORTANT: Use this VA222 Series Spring

More information

- Wiring Brochure Zone Manager 336

- Wiring Brochure Zone Manager 336 - Wiring Brochure W 336 12/08 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in 4 Wiring Brochure Wiring

More information

SOLA SM and SOLA SM 365 Light Engine Instruction Manual

SOLA SM and SOLA SM 365 Light Engine Instruction Manual SOLA SM and SOLA SM 365 Light Engine Instruction Manual Lumencor, Inc. Document Number 57-10003, Rev. A www.lumencor.com Regulatory Models Lumencor utilizes regulatory model names for all certified and

More information

Cable Cubby 500 and 700 Installation Guide

Cable Cubby 500 and 700 Installation Guide e NT: R.com for thtion O P IM tron talla w.ex uide, ins ations. o ww Go t te user g specific nd ple com ctions, a u instr 500 and 700 Installation Guide This guide provides instructions for an experienced

More information

INSTALLATION INSTRUCTIONS LIGHTPLANE 3.5. LP3.5 Suspended LED. A nd Avenue, Unit 1. CA P E W alwusa.

INSTALLATION INSTRUCTIONS LIGHTPLANE 3.5. LP3.5 Suspended LED. A nd Avenue, Unit 1. CA P E W alwusa. Oakland, INSTALLATION INSTRUCTIONS LIGHTPLANE 3.5 LP3.5 Suspended LED A 1035 22nd Avenue, Unit 1 n CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com Safety & Warnings! 1. Read all instructions.

More information

RAPID SHUTDOWN COMBINER

RAPID SHUTDOWN COMBINER RAPID SHUTDOWN COMBINER Installation and Operation Guide Revision B 2017, Yaskawa Solectria Solar IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS 1. General Safety Information This manual contains

More information

2-WAY REMOTE STARTING SYSTEM WITH 1 BUTTONS FOR AUTOMATIC TRANSMISSION RED301-2WAY / ANT-2WDSS. User Guide For Key

2-WAY REMOTE STARTING SYSTEM WITH 1 BUTTONS FOR AUTOMATIC TRANSMISSION RED301-2WAY / ANT-2WDSS. User Guide For Key 2-WAY REMOTE STARTING SYSTEM WITH 1 BUTTONS FOR AUTOMATIC TRANSMISSION RED301-2WAY / ANT-2WDSS User Guide For Key This equipment complies with the FCC RF radiation exposure limits set forth for an uncontrolled

More information

MNBE-8D2x2 INSTRUCTIONS

MNBE-8D2x2 INSTRUCTIONS MNBE-8D2x2 INSTRUCTIONS MNBE-8D2x2 OUTDOOR 3R ENCLOSURE MNBE-8D2x2 Battery Enclosure with locking door and one shelf. Outdoor 3R rain type design. Powder coated aluminum and stainless steel construction.

More information

OmniAire Omnitec Design, Manufacturing Air Purification Equipment Since 1988

OmniAire Omnitec Design, Manufacturing Air Purification Equipment Since 1988 OmniAire 18000 Omnitec Design, Manufacturing Air Purification Equipment Since 1988 For your larger projects the OmniAire 18000 is the right tool. The modular design of this system allows for ease of transport

More information

Assembly and Operation Manual

Assembly and Operation Manual Adjustable Base Assembly and Operation Manual Table of Contents Safety Precaution and Usage Guide...2 To decrease the risk of electronic shock... 2 Adjustable base performance... 3 Restrictions of your

More information

GETTING STARTED WITH IN-WALL DIMMER SWITCH

GETTING STARTED WITH IN-WALL DIMMER SWITCH GETTING STARTED WITH IN-WALL DIMMER SWITCH This document is the property of Webee L.L.C. The data contained here, in whole or in part, may not be duplicated, used or disclosed outside the recipient for

More information

Cable Cubby 1200 and 1400 Installation Guide

Cable Cubby 1200 and 1400 Installation Guide e NT: R.com for thtion O P IM tron talla w.ex uide, ins ations. o ww Go t te user g specific nd ple com ctions, a u instr 00 and 400 Installation Guide This guide provides instructions for an experienced

More information

Installation Instructions

Installation Instructions at :: rangehoods. com Call 1-800-667-8721 anywhere in the US and Canada - www.rangehoods.com Installation Instructions ZV950 36" Stainless Steel Vent Hood Monogram. We bring good things to life. GE Monogram

More information

CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440

CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440 CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440 APPLICATION SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE CSR compact fused interlocked ARKTITE

More information

SF 10C SUB Subwoofer Setup Guide

SF 10C SUB Subwoofer Setup Guide SF 10C SUB Subwoofer Setup Guide This guide provides instructions for an experienced installer to install the Extron SF 10C SUB subwoofer and to make all connections. The subwoofer typically is installed

More information

WARNING / AVERTISSEMENT

WARNING / AVERTISSEMENT TM Arize LED Lighting System Lynk & Life Installation Guide BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING / AVERTISSEMENT RISK OF ELECTRIC SHOCK RISQUES DE DÉCHARGES ÉLECTRIQUES

More information

VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators

VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators FIG:mntpos_H2O_app VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators Installation Instructions VA9104-AGA-3S, VA9104-GGA-3S, VA9104-IGA-3S Applications The VA9104 Series Actuators are direct-mount,

More information

100A 225A 400A PATENT PENDING

100A 225A 400A PATENT PENDING HomeRun Combiner Boxes Installation and Operation Manual 100A 225A 400A PATENT PENDING TABLE OF CONTENTS 1.0 Overview 2.0 Introduction 3.0 Important Safety Instructions 4.0 Disconnecting Combiner Box Electrical

More information

5300 Series Installation Guidelines

5300 Series Installation Guidelines 1-800-443-4859 5300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER

More information

Installation Instructions

Installation Instructions KGANP54011SP Gas Conversion Kit Natural --- to --- Propane for Low---Capacity Gas Furnace 26,000 BTUH Only NOTE: Installation Instructions CERTIFIED Read the entire instruction manual before starting the

More information

M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators

M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions M9203-AGA-2, M9203-AGB-2, M9203-AGA-2Z, M9203-AGB-2Z Applications The M9203-AGx-2(Z) Series On/Off

More information

INSTALLATION INSTRUCTION Vanities & Wall Sconce WS-85618

INSTALLATION INSTRUCTION Vanities & Wall Sconce WS-85618 WS-85618 WARNING IMPORTANT: NEVER attempt any work without shutting off the electricity. - Read all instructions before installing. - System is intended for installation by a qualified electrician in accordance

More information

poollux Power plx-pw60 & plx-pw100

poollux Power plx-pw60 & plx-pw100 poollux Power plx-pw60 & plx-pw100 ETL LISTED Conforms to UL STD 379; Certifi.ed.to.CSA.STD.C22.2.#218.1 5005508 Installation Instructions Read all instructions before attempting to perform installation

More information

M Remote Mounting Kit

M Remote Mounting Kit M9208-250 Remote Mounting Kit Installation Instructions M9208-250 Part No. 34-636-2200, Rev. A Issued August 29, 2014 Applications IMPORTANT: Use this M9208-250 Remote Mounting Kit only to control equipment

More information

Have a bright day! Nicholas Harmon President, Verilux, Inc.

Have a bright day! Nicholas Harmon President, Verilux, Inc. Model: VF02 Dear Customer, Thank you for purchasing the Verilux EasyFlex Deluxe Natural Spectrum Floor Lamp. You have received a quality product, backed by a one year limited warranty. As a Verilux customer,

More information

Palomino BATTERY CHARGERS. Installation and Operating Instructions. One Technology Place Caledonia, New York The Power of Excellence

Palomino BATTERY CHARGERS. Installation and Operating Instructions. One Technology Place Caledonia, New York The Power of Excellence Palomino BATTERY CHARGERS Installation and Operating Instructions One Technology Place Caledonia, New York 14423 The Power of Excellence FM1320 REV - B IMPORTANT SAFETY INSTRUCTIONS INSTRUCTIONS IMPORTANTES

More information

Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL

Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL POWER CONVERSION/DISTRIBUTION Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL 3 Phase 15 kva - 225 kva 50 & 60 Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1

More information

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators 34-636- 1484, Rev. B Installation Instructions M9109-GGx-4 Issue Date March 2016 M9109-GGx-4 Series Proportional Electric Non-Spring Return Actuators Installation IMPORTANT: The M9109-GGx-4 Series Electric

More information

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators

M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators M9106-GGx-4 Series Proportional Electric Non-Spring Return Actuators 34-636- 1468, Rev. B Installation Instructions M9106-GGx-4 Issue Date March 2016 Installation IMPORTANT: The M9106-GGx-4 Electric Actuator

More information

Acme Conduit Entry. String Combiner/Pass-Through. FOR PHOTOVOLTAIC INSTALLATION Installation Manual

Acme Conduit Entry. String Combiner/Pass-Through. FOR PHOTOVOLTAIC INSTALLATION Installation Manual Acme Conduit Entry String Combiner/Pass-Through FOR PHOTOVOLTAIC INSTALLATION Installation Manual Table of Contents Important Safety Instructions -----------------------------------------------------------------------------------------------------------

More information

Parent s Guide. This guide contains important information. Please keep it for future reference US

Parent s Guide. This guide contains important information. Please keep it for future reference US Parent s Guide This guide contains important information. Please keep it for future reference. 91-003324-000 US INTRODUCTION The Stack & Tumble Elephant TM provides a silly twist on the classic ring stacker.

More information

LS1 SERIES IMPORTANT: READ ALL INSTRUCTIONS THOROUGHLY AND CAREFULLY PRIOR TO INSTALLATION OF LINEAR SERIES FIXTURES AND RETAIN FOR FUTURE REFERENCE.

LS1 SERIES IMPORTANT: READ ALL INSTRUCTIONS THOROUGHLY AND CAREFULLY PRIOR TO INSTALLATION OF LINEAR SERIES FIXTURES AND RETAIN FOR FUTURE REFERENCE. The LS1 Series of commercial and industrial LED fixtures is designed to be used in utility strip applications using suspension or surface mount installation. The LS1 Series is designed for use in 120 277V,

More information

BT300 Variable Frequency Drive Bypass

BT300 Variable Frequency Drive Bypass Document No. DPD01375 BT300 Variable Frequency Drive Bypass Product Description The Siemens BT300 Bypasses are companion packages for the family of BT300 HVAC Variable Speed Drives. Product Numbers BTC

More information

M9203-Bxx-2(Z) Series On/Off Electric Spring Return Actuators

M9203-Bxx-2(Z) Series On/Off Electric Spring Return Actuators *34179124D* Applications The M9203-Bxx-2(Z) Series On/Off Electric Spring Return Actuators are direct-mount actuators that operate on AC 24 V power at /60 Hz, DC 24 V power, or AC 85 to 264 V power at

More information

1. Caution Statements System Design Electrical Installation Adjustments Troubleshooting... 16

1. Caution Statements System Design Electrical Installation Adjustments Troubleshooting... 16 CSXi RIGHT FROM THE START Contents 1. Caution Statements... 2 2. System Design... 4 3. Electrical Installation... 11 4. Adjustments... 14 5. Troubleshooting... 16 The examples and diagrams in this manual

More information

50 AMP TRANSFER RELAY DELAY - DUAL INPUT GENSET

50 AMP TRANSFER RELAY DELAY - DUAL INPUT GENSET R 50 AMP TRANSFER RELAY DELAY - DUAL INPUT GENSET Transfer Relay Delay 00-00803-400 Dual Input Genset INDUSTRIAL CONTROL EQUIPMENT TYPE 1 Shore Power Rating: 120/240VAC 60HZ 1 Phase 50A/Pole Generator

More information

INSTALLATION INSTRUCTION Bliss - Vanities & Wall Sconces WS-79622

INSTALLATION INSTRUCTION Bliss - Vanities & Wall Sconces WS-79622 WS-79622 WARNING IMPORTANT: NEVER attempt any work without shutting off the electricity. - Read all instructions before installing. - System is intended for installation by a qualified electrician in accordance

More information

Safety, Installation and Operating Instructions Instructions importantes concernant la sécurité

Safety, Installation and Operating Instructions Instructions importantes concernant la sécurité Safety, Installation and Operating Instructions Instructions importantes concernant la sécurité Manual for the Following Battery Discharger: BD6812QUAD 022118-70329 IMPORTANT NOTICE: Please save and read

More information

Installation Instructions

Installation Instructions Installation Instructions If you have questions, call 800.GE.CARES or visit our website at: www.monogram.com ZV950 36" Stainless Steel Vent Hood Safety Information BEFORE YOU BEGIN Read these instructions

More information

Record Plus. Molded Case Circuit Breaker Accessories. Plug In Base. DEH40915 Installation Instructions

Record Plus. Molded Case Circuit Breaker Accessories. Plug In Base. DEH40915 Installation Instructions DEH40915 Installation Instructions g Plug In Base Congratulations and thank you for choosing the Record Plus TM family of current-limiting circuit breakers. This UL-listed Plug-In Mounting Plate accessory

More information

Certification Exhibit FCC ID: SK9OW1 IC: 864G-OW1. FCC Rule Part: IC Radio Standards Specification: RSS-247. ACS Project Number:

Certification Exhibit FCC ID: SK9OW1 IC: 864G-OW1. FCC Rule Part: IC Radio Standards Specification: RSS-247. ACS Project Number: Certification Exhibit FCC ID: SK9OW1 IC: 864G-OW1 FCC Rule Part: 15.247 IC Radio Standards Specification: RSS-247 ACS Project Number: 16-0295 Manufacturer: Itron, Inc. Model: OW1 Manual 5015 B.U. Bowman

More information

Powerware Vdc Extended Battery Cabinet User s Guide.

Powerware Vdc Extended Battery Cabinet User s Guide. Powerware 9125 48 Vdc Extended Battery Cabinet User s Guide www.powerware.com FCC Part 15 Class A EMC Statements NOTE This equipment has been tested and found to comply with the limits for a Class A digital

More information

MNSOB Shut Off Box Instructions

MNSOB Shut Off Box Instructions MNSOB Shut Off Box Instructions MNSOB4X-4P MNSOB3R-4P The MNSOB Shut off boxes provide a Rapid System Shutdown as required by NEC 690.12. This Manual covers the following models: MNSOB4X-2P MNSOB4X-4P

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 6400 Vehicle Dock INSTALLATION INSTRUCTIONS " " " " " " " " " " " " " " " " " " " " " " " " " " " " PN: 962-020-006 Revision B August 1998 " NOTICE The information contained herein is proprietary and is

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INDIGO-CLEAN TECHNOLOGY RETROFIT KIT INSTALLATION INSTRUCTIONS 1 IMPORTANT SAFETY INFORMATION Risk of shock. Disconnect power before installation. DANGER- RISQUE DE CHOC- COUPER L ALIMENTATION AVANT L

More information