1 Construction Purchasing Department SW Merlo Road Beaverton, OR Phone: Fax: Date: March 4, 2016 SOLICITATION ADDENDUM NO. 5 ITB Cedar Park HVAC/Plumbing Upgrade THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED: This Addendum modifies the Invitation to Bid (ITB) document(s) only to the extent indicated herein. All other areas not changed or otherwise modified by this Addendum shall remain in full force and effect. This Addendum is hereby made an integral part of the ITB document. Bidder must be responsive to any requirements of this Addendum as if the requirements were set forth in the ITB. Failure to do so may result in Bid rejection. See the ITB regarding requests for clarification or change and protests of this Addendum, and the deadlines for the foregoing. This addendum is to be acknowledged in the space provided on the Bidder Certification form supplied in the solicitation document. Failure to acknowledge receipt of this addendum may be cause to reject your offer. The closing date REMAINS: March 9, 2016 at 2:00 PM CHANGES: The Substantial Completion date is changed to: August 26, 2016 See attached Specifications and Drawings for additional changes. Replace Section I Instructions to Bidders item 6.c. with the following: c. Controls: i. Johnson Controls (JCI) will be installed by a District approved contractor as outlined in BSD Technical Standard Division 23: HVAC. Currently, the following contractors are approved installers: Johnson Controls, Inc Northwest Control Contractors Controls will be installed at each unit or used to interface to each unit. The JCI system will be the BACnet version. The controls will be a complete package including graphics and will be part of the Districts Metasys ADS system. CLARIFICATIONS: If a substitution request was submitted to the district and it is included in any of the addenda it is considered acceptable. If a substitution request is not incorporated in an addenda it is considered rejected. District Goal: All students will show continuous progress toward their personal learning goals, developed in collaboration with teachers and parents, and will be prepared for post-secondary education and career success. The Beaverton School District recognizes the diversity and worth of all individuals and groups. It is the policy of the Beaverton School District that there will be no discrimination or harassment of individuals or groups based on race, color, religion, gender, sexual orientation, gender identity, gender expression, national origin, marital status, age, veterans' status, genetic information or disability in any educational programs, activities or employment.

2 Questions and Answers: Q: Unit Ventilators Please confirm that the unit ventilators have a single speed fan. UV spec and sequence of operations appear to show different requirements. A: Unit ventilators are specified as three speed units. The controls will operate the UV at the speed selected at the unit by the balancer to achieve specified airflow. There is not intention to operate the UV at more than one speed from the BAS. Q: Is there a sequence of operations for the multizone units/central exhaust serving the library? A: Same sequence as for the MZU serving the band area, see Q: Addendum 2 states all Johnson Controls in the boiler room to be replaced. Does this include the NAE? A: No reference is intended to indicate in Addendum 2 that All Johnson Controls in the Boiler Room are to be replaced. Please refer to section E of the specifications. END OF ADDENDUM Michael Mathews Construction Purchasing Manager 2

3 Cedar Park and Meadow Park Middle School 03/03/2016 Addendum Items 5 SPECIFICATIONS Note: Revised Additions are in bold, deletions have a strikethrough. SECTION ) Article 2.03, C, 1, 2, 3: Revise as follows. C. Showers 1. Chase Mounted SH-1 : Stainless steel wall panel shower assembly furnished complete with 2.0 gpm (maximum flow) shower head, pressure balance mixing valve with stops, supports and piping by the shower manufacturer. All mounting brackets, heads, valves, etc., shall be of vandal-proof construction. Upper wall concealed pipe chase cover with mounting clips, one piece 18 gauge min. 304 stainless steel panel. Provide recessed soap dish. Bradley WS-1WCA-HD-RSD series unit with stainless steel extension to ceiling. Shower valves shall conform to ASME A / CSA B Chase Mounted SH-2 : Stainless steel wall panel shower assembly furnished complete with fixed 2.0 gpm (maximum flow) shower head, hand shower and 60" hose with guide rail. Provide with quick disconnect, diverter valve, pressure balance mixing valve with stops, supports and piping by the shower manufacturer. All mounting brackets, heads, valves, etc., shall be of vandal-proof construction. Upper wall concealed pipe chase for top supply, mounting clips, one piece 16 gauge min. stainless steel panel. Provide fold down wall mount seat and grab bar with stainless steel extension to ceiling. Bradley HN250-HD. Shower valves shall conform to ASME A / CSA B Chase Mounted SH-3 : Stainless steel wall panel shower assembly furnished complete with 1.5 gpm shower head on slide bar, pressure balance mixing valve with stops, supports and piping by the shower manufacturer. All mounting brackets, heads, valves, etc., shall be of vandal-proof construction. Upper wall concealed pipe chase cover with mounting clips, one piece 18 gauge min. 304 stainless steel panel with stainless steel extension to ceiling. Bradley WS-1WCA-HD-SB-G-SHV- ST. Shower valves shall conform to ASME A / CSA B SECTION ) Article 1.03: Add new paragraph E as follows. E. Where drawings say to provide materials the subject materials are to be provided and installed. 3) Article 2.13: Add new article 2.13 as follows. Page 1 of 5

4 Cedar Park and Meadow Park Middle School 03/03/2016 Addendum Items STARTERS AND SWITCHES A. Manufacturers: Cerus Industrial Model numbers are listed. General Electric, ABB, Allen Bradley, Schneider Electric, Eaton, are approved equal. Provide starters by same manufacturer throughout project. B. General: Provide each motor with starter or switch as approved and recommended by manufacturer of motor or equipment of which motor is a part. C. System Description 1. Single Phase Starter: Starters for 115VAC single phase motors less than 1 HP shall be capable of both manual and automatic operation. Refer to Section D for single phase starter requirements. 2. Magnetic Starters: Starters for 3-phase motors shall be magnetic starters. Refer to Section E for magnetic starter requirements. 3. Combination Starters: Provide combination magnetic starters for all motors requiring branch circuit protection or a line-of-sight disconnect. Refer to Section F for combination magnetic starter requirements. D. Enclosed Full Voltage Non-Reversing (FVNR) Single Phase Starter 1. Single Phase Motor Starter Control: The single phase motor starter shall consist of a manually operated quick-make toggle mechanism lockable in the Off position which shall also function as the motor disconnect. Additionally, the starter shall provide thermal overload protection, run status pilot light and fault pilot light. The starter must include the capability to operate in both manual and automatic control modes. In automatic mode, the starter shall have the capability to integrate with a building automation system by providing terminals for run input, run status output and fault output. All control terminals shall be integrated in the starter. At a minimum, each single phase starter shall include an interposing run relay and current sensing status output relay. Single phase motor starter shall be in a surface mount enclosure. 2. Approved manufacturer: Cerus Industrial, model BAS-1P or approved equal. E. Enclosed Full Voltage Non-Reversing (FVNR) Non-Combination Starter 1. Magnetic Motor Starters shall be enclosed in a general purpose electrical enclosure with the appropriate environmental rating. 2. Starters shall consist of a horsepower rated magnetic contactor with a minimum of 1NO and 1NC auxiliary contacts and solid state electronic overload relay. Overload relay shall protect all three phases with a wide range current setting and trip class to allow field adjustment for specific motor FLA. Overload relay shall provide phase failure, phase loss, locked rotor and stall protection. 3. Provide a manual reset pushbutton on the starter cover to restore normal operation after a trip or fault condition. 4. Each starter shall include an installed 50VA control power transformer (CPT) with protected secondary. The CPT must accept the available line voltage and the control voltage shall not exceed 120V. Page 2 of 5

5 Cedar Park and Meadow Park Middle School 03/03/2016 Addendum Items 5 5. Installed accessories shall include Hand-Off-Auto operation switch with 22mm style operator interfaces. Include LED pilot light indicators for Hand, Off, Auto, Run and Overload conditions. All pilot devices shall be water tight and dust tight. 6. When remotely controlled by an automation system, the starter shall include remote run terminals which accept both a voltage input signal and a contact closure. The voltage run input shall accept both AC and DC signals including 24VAC, 120VAC, 24VDC and 48VDC to allow direct connection of the transistorized automation signal to the starter. 7. In applications where the motor is interlocked with a damper or valve, the actuator control must reside within the starter enclosure. The starter must provide a voltage output to operate the actuator to open the damper or valve without closing the motor circuit. The starter will only close the motor circuit and start the motor after it has received a contact closure from a limit or end switch confirming the damper or valve position. 8. Manufacturer shall provide and install tags with engraved white lettering to designate equipment served. F. Enclosed Full Voltage Non-Reversing (FVNR) Combination Starter / Disconnect. 1. Enclosed combination starters shall include all of the magnetic starter requirements in addition to a disconnecting method. Acceptable disconnects include: motor circuit protectors, UL 489 circuit breakers, or a fused disconnects. All disconnects shall include a lockout mechanism when in the off position. See Section E for other requirements. 2. The Motor Circuit protector shall be a UL listed 508 current limiting manual motor starter with magnetic trip elements only. The breaker shall carry a UL 508F rating (up to 100A frame size) which provides for coordinated short circuit rating for use with the motor contactor and provides a minimum interrupting rating of 30,000 AIC for the combination starter. 3. Fused disconnect shall be UL 98 suitable for service entrance protection. It shall accommodate time delay J-style fuses. 4. UL 489 breaker shall include thermal and magnetic trip mechanisms. G. Enclosed Starter Options: 1. Must provide over/under voltage and phase monitoring capability. Monitor shall be field adjustable for both over and under voltage levels and a delay time before returning to normal operation after a trip. 2. Starter must measure and display output current on the front cover. If necessary, install digital or analog ammeter. H. Quality Assurance 1. Manufacturer shall provide a five year warranty on the complete starter assembly. 2. The starter assembly shall be UL listed under UL 508A. 4) Article 3.02, D: Revise as follows. Page 3 of 5

6 Cedar Park and Meadow Park Middle School 03/03/2016 Addendum Items 5 D. Provide all starters for mechanical motors. Review Electrical Specifications and Drawings to determine which mechanical motor starters will be provided under the Electrical Specification Sections and provide all others. Adjust all starters as required for equipment loads and proper operation. SECTION ) Article 4.07: Revise as follows. 5. Demand Ventilation Control (DVC): During occupied mode the outside air dampers shall modulate to maintain return air CO2 levels at or below 1000 ppm (Adjustable). DVC shall occur when levels begin to exceed the CO2 set point. This sequence for units without terminal unit CO 2 sensors. SECTION ) Article 3.04: Revise heading as follows RESTORATION OF EXISTING HVAC OR REFURBISH EQUIPMENT DRAWINGS Cedar Park: 1. Revision Sheet A1.0 Add repair information for curb and sidewalk outside of boiler room for chiller piping trenching. 2. Revision Sheet M1.1_1.2_1.3_1.4_1.5_1.6_1.7 Add demolition coordination note for all demo sheets. 3. Revision Sheet M2.1 Revise Mechanical Plan Notes. Add information at admin area for controls of existing equipment, along with revising rtu note and adding ef note with tag. Add duct cleaning notes to several locations. Erase reference to stat near boiler room at janitor s office. Revise state information for Kitchen and Cafeteria/Platform. 4. Revision Sheet M2.3 Revise relief information at Fitness Center. Revise section cut at 2M2.3. Revise SA and RA ductwork at computer lab/mechanical loft. Revise stat information in B-14 and B-12. Revise all VAV stat references for RTU-3 VAV boxes from 2 series to 3 series to match RTU Revision Sheet M2.4 Revise stat in Classroom C-7/C Revision Sheet M2.5 Fix viewports, and add duct cleaning notes to mezzanine ductwork. Revise general note to add mezzanine ductwork cleaning. 7. Revision Sheet M2.6 Add information for Fan B-4 near Library. Add second relief for fitness room as shown on floor plan. Meadow Park: Page 4 of 5

7 Cedar Park and Meadow Park Middle School 03/03/2016 Addendum Items 5 8. Revision Sheets A1.0, M1.3, M1.6, M , M2.6, M2.7, M5.1, M6.1, M6.2 - Revise entire sheets. 9. Revision Sheets M6.3a, M6.3b, M6.4a, M6.4b, M6.4c, M6.5a, M6.5b, P2.1a Revise partial sheets. MFIA, Inc. Page 5 of 5

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL 13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

BAC Custom Engineered Controls

BAC Custom Engineered Controls BAC Custom Engineered Controls Product Detail Product Introduction......................................... K2 BAC Custom Engineered Controls Benefits....................................................

More information

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives. SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.

More information

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x. Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,

More information

Enclosures. See Section Typical Description

Enclosures. See Section Typical Description January 00 Sheet 1187 Motor Starters & Contactors Low Voltage Enclosures General Individual Enclosed, ac Full Voltage.7- Combination Starters Maximum 00 hp, Volts Application Size 1, NEMA 1, Enclosed Magnetic

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK PART 1 - GENERAL 1.1 GENERAL: SECTION 15150 MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK A. The Mechanical Contractor shall furnish to the Electrical Contractor for installation,

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Self-protected Combination Starters System PKZ 2-SP

Self-protected Combination Starters System PKZ 2-SP Self-protected Combination Starters System PKZ 2-SP 03/035 PKZ 2/ZM/S-SP motor starters: a higher level of protection and versatility : The PKZ 2/ZM/S-SP is a self-protected starter, the first motor controller

More information

Designed for ease of integration with automation systems

Designed for ease of integration with automation systems BAS, 200 ~ 600V, 1/2-30HP BUILDING AUTOMATION STARTER SMARTER AND MORE VERSATILE THAN EVER Smartstart Equipped with advanced I/O including Fireman s Override and damper control, the BAS was designed from

More information

HVW701 HVAC Drive with By-Pass

HVW701 HVAC Drive with By-Pass s Automation Energy Transmission & Distribution Coatings HVW701 HVAC with By-Pass Designed Especially for HVAC Systems US.HVW701.By-Pass.07/2017 www.weg.net WEG HVAC-R Products WEG, a leading supplier

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

Submittal Data Information

Submittal Data Information Effective: NOVEMBER 3, 2014 JOB CONTRCTOR ITEM NO. Submittal Data Information TS - Taco dvanced Starter ENGINEER REP. 301-2690 Supersedes: NEW TS - Taco dvanced Starter 1Ø, 120-230V, 1/10-30HP 3Ø, 200-600V,

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

3. Coils shall be of molded construction

3. Coils shall be of molded construction .7-4 Motor Starters & Contactors Low Voltage Enclosures General Non-Combination Starters January 00 Sheet 8 0 7 8 9 4 Non-Combination Starters Maximum hp, Volts Typical Non-Combination Starter Application

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

INVITATION TO BID FUEL PRODUCTS

INVITATION TO BID FUEL PRODUCTS INVITATION TO BID FUEL PRODUCTS Notice is hereby given that the Aberdeen School District is accepting fuel bids and propane bids for the following: 1. Regular, unleaded and diesel fuels for district buses

More information

EPS-ECONOMY PUMP STARTER

EPS-ECONOMY PUMP STARTER EPS-ECONOMY PUMP STARTER NEMA 1 & 3R ENCLOSURES franklinwater.com EPS-ECONOMY PUMP STARTER - 1 & 3 PHASE, 50/60HZ, 200-600 VAC, 1-80A The enhanced Franklin Electric Economy Pump Starter (EPS) provides

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

HVAC Drives Lenze AC Tech MCH Series Price Book May US Dollars

HVAC Drives Lenze AC Tech MCH Series Price Book May US Dollars HVAC Drives Lenze AC Tech MCH Series Price Book May 2015 - US Dollars Document: pcmchusd-0515_a MCH Series Drives: Model Number Designation Code The MCH Series drives are rated for variable torque applications,

More information

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories Manual motor protectors Manual motor protectors Manual motor Protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certified

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Submittal Data Information

Submittal Data Information Effective: NOVEMBER 3, 2014 JOB CONTRACTOR ITEM NO. Submittal Data Information TDX - Taco Duplex Starter ENGINEER REP. 301-2693 Supersedes: NEW TDX - TACO DUPLEX STARTER 1Ø, 230V, 1/10-15HP 3Ø, 200-460V,

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

1. GENERAL BIDDING: For clarification, the sealed bids shall be marked as follows:

1. GENERAL BIDDING: For clarification, the sealed bids shall be marked as follows: Addendum Santa Fe College Y Building Learning Commons Renovations and Remodel Gainesville, Florida Project 18-24-22 October 22, 2018 SF Project Number Date 1763 Page 1 of 2 and 3 Attachments Architect

More information

Metasys Zoning Package Overview

Metasys Zoning Package Overview Technical Bulletin Issue Date August 26, 2002 Metasys Zoning Package Overview Metasys Zoning Package Overview...2 Introduction... 2 Key Concepts... 3 Related Information... 3 Metasys Zoning Package Components...

More information

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran 4 Project:_ Engineer:_ Mitsubishi Electric Automation, Inc. (MEAU) Variable Frequency Drives - HVAC System Submittal Summary Data Form NEMA 1 Bypass Systems Architect:_ Contractor:_ Submitted by: Date:

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS www.igcaire.com SINGLE DUCT TERMINAL UNITS Direct Digital Control, Pressure Independent FEATURES 22 Gauge Galvanized Steel Casing Construction with a 20 Gauge Casing Option that Provides Strength and Product

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

Overview V10-T1-2 V10-T1-2 V10-T1-3 V10-T1-4 V10-T1-5 V10-T1-6 V10-T1-7 V10-T1-7 V10-T1-8

Overview V10-T1-2 V10-T1-2 V10-T1-3 V10-T1-4 V10-T1-5 V10-T1-6 V10-T1-7 V10-T1-7 V10-T1-8 Enclosed Control. Welcome............................................... Eaton Corporation........................................ Eaton Support and Service Center Capabilities.................. Technical

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

Standard Materials Bodies and covers: copper-free aluminum.

Standard Materials Bodies and covers: copper-free aluminum. -26 AEB Series: Bolted Combination and Non-Combination Full Voltage Motor Starters: Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection. Application Combination and

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q 14/03/08 A136 Relay - General Purpose 90-293Q Enclosed fan relays used for switching single or two speed fan motors, solenoids, relays, resistive loads, heating and cooling applications and general purpose

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

Motors Automation Energy Transmission & Distribution Coatings. UMBW UL489 and UL1077 Thermal-Magnetic MCB

Motors Automation Energy Transmission & Distribution Coatings. UMBW UL489 and UL1077 Thermal-Magnetic MCB Motors Automation Energy Transmission & Distribution Coatings UMBW UL489 and UL1077 Thermal-Magnetic MCB UL489 AND UL1077 Circuit Protection Overview: Single pole and multi-pole thermal-magnetic minature

More information

HUNTLEY COMMUNITY SCHOOL DISTRICT #158 Addendum No. 1 to Bid Specifications for HVAC Preventative Maintenance Services Bid #

HUNTLEY COMMUNITY SCHOOL DISTRICT #158 Addendum No. 1 to Bid Specifications for HVAC Preventative Maintenance Services Bid # HUNTLEY COMMUNITY SCHOOL DISTRICT #158 Addendum No. 1 to Bid Specifications for Bid # 2017-44 8-15-17 Dear Bidders; Following is Addendum No. 1 for Bid Specification for Bid # 2017-44 for Huntley Community

More information

XT IEC Power Control Manual Motor Protectors

XT IEC Power Control Manual Motor Protectors May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted

More information

MaxPak Plus Analog DC V S Drive

MaxPak Plus Analog DC V S Drive Three-Phase 3-600 HP non-regenerative and 5-150 HP regenerative drives Designed to accommodate a wide range of industrial requirements, the DC V S Drive has been widely applied worldwide. Selected ratings

More information

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE 201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

Daikin McQuay. VAV Air Terminal Unit MQ FCI6, FVI5, THI5. Replacement Parts List No Revision J 07/2017

Daikin McQuay. VAV Air Terminal Unit MQ FCI6, FVI5, THI5. Replacement Parts List No Revision J 07/2017 Replacement Parts List No. 700020000 Revision J 07/2017 Daikin McQuay VAV Air Terminal Unit MQ FCI6, FVI5, THI5 To find your Daikin Applied parts distributor, call 1-800-377-2787 or visit www.daikinapplied.com

More information

SELECTRIC, INC. Selectric (PA) Autotransformer Type Motor Control Panel Installation And Operation Manual

SELECTRIC, INC. Selectric (PA) Autotransformer Type Motor Control Panel Installation And Operation Manual SELECTRIC, INC. Selectric (PA) Autotransformer Type Motor Control Panel Installation And Operation Manual Table of Contents I. Description of Equipment Page 3 II. Description of Operation 3 III. Installation

More information

4 - Miniature controls

4 - Miniature controls Index -....1.22 Selection Contactors for connection to PLCs, B6S & B7S, 3 phase...6 Contactors, Interface, B6 & B7, 3 phase...5 Contactors, features...1 Contactors, mechanically interlocked, B6 & B7, 3

More information

3.1. NEMA Manual Starters. Contents Description Types B230, B330, Switches... MS Series, Single-Phase Starters...

3.1. NEMA Manual Starters.   Contents Description Types B230, B330, Switches... MS Series, Single-Phase Starters... Product Description The B100 Manual Motor Starters can be used in single-phase applications rated hp at 240 Vac or 2 hp at 20 Vdc. The starter can also be rated for three-phase applications up to 10 hp

More information

Phase 1 Remodeling for New State s Attorney Office Facility Will County Court Annex 57 N. Ottawa St & 57 W. Jefferson St.

Phase 1 Remodeling for New State s Attorney Office Facility Will County Court Annex 57 N. Ottawa St & 57 W. Jefferson St. DOCUMENT 00 91 13 - ADDENDA ADDENDUM NO.1: DATE: April 14, 2015 PROJECT: ARCHITECT/ ENGINEER: PROJECT NO.: Phase 1 Remodeling for New State s Attorney Office Facility Will County Court Annex 57 N. Ottawa

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Enclosed Full-Voltage Starters

Enclosed Full-Voltage Starters GE Energy Connections Made in USA Enclosed Full-Voltage Starters * www.geindustrial.com/products/starters GE Global Offer & Warranty starters utilize globally-rated IEC components which make it ideal for

More information

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you

More information

EPS-ECONOMY PUMP STARTER

EPS-ECONOMY PUMP STARTER EPS-ECONOMY PUMP STARTER 1 & 3 Phase, 50/60Z, 200-600 VAC, 1-80A The enhanced Franklin Electric Economy Pump Starter (EPS) provides a simple and dependable starting option with a wide electronic overload

More information

TDX - Taco Duplex Starter with

TDX - Taco Duplex Starter with Energy Management TDX - Taco Duplex Starter with Smartstart The TDX extends the life of your pumps by alternating control. It comes standard with underload protection, a enhanced class 10 electronic overload

More information

Enclosed Full-Voltage Starters

Enclosed Full-Voltage Starters GE Energy Connections Made in Canada Enclosed Full-Voltage Starters * ca.geindustrial.com/products/starters GE Global Offer & Warranty starters utilize globally-rated IEC components which make it ideal

More information

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL ed and

More information

Applications. Housings: copperfree (4/10 of 1%) aluminum Shaft, bushings and exposed hardware: stainless steel Standard Finishes

Applications. Housings: copperfree (4/10 of 1%) aluminum Shaft, bushings and exposed hardware: stainless steel Standard Finishes AE Threaded Combination and Non-Combination Full Motor Starters Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection. Class I, Division and, Groups C, D Class II, Division

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Instruction Bulletin. Enclosed ALTISTART 46 Controller Supplemental Instruction Bulletin Class 8638 and 8639 INTRODUCTION

Instruction Bulletin. Enclosed ALTISTART 46 Controller Supplemental Instruction Bulletin Class 8638 and 8639 INTRODUCTION Instruction Bulletin Bulletin No. 0006-39-03 May 997 Raleigh, NC, USA Enclosed ALTISTART 6 Controller Supplemental Instruction Bulletin Class 8638 and 8639 INTRODUCTION This bulletin is a supplement to

More information

Enclosures for hazardous areas EBMX clamped enclosures. Clamped EBMX. NEMA 7 classifi ed enclosures

Enclosures for hazardous areas EBMX clamped enclosures. Clamped EBMX. NEMA 7 classifi ed enclosures Enclosures for hazardous areas clamped enclosures Clamped NEMA 7 classifi ed enclosures Clamped : NEMA 7 classified enclosures Safer. Faster. Easy access, lower risk and less downtime. Creative thinking

More information

4.1. Definite Purpose Contactors and Starters. Contents

4.1. Definite Purpose Contactors and Starters. Contents . Definite Purpose and Starters Product Overview and Starters Definite Purpose and Starters Contents Description Page 20 0A, Compact Single- and Two-Pole C25................................ V5-T- 5 360A,

More information

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarters. Softstarters Type SSM Medium voltage ,800V 1 Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION

More information

SIGNAL WORDS QUALIFIED PERSON

SIGNAL WORDS QUALIFIED PERSON SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Overload Relays.................... C440/XT

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

CONTROL UNITS VEHICLE EXHAUST GASES. Pure advantages

CONTROL UNITS VEHICLE EXHAUST GASES. Pure advantages CONTROL UNITS VEHICLE EXHAUST GASES Movex s control s offers a good working environment, adapted to all types of facilities. The right choice of control s is energy-saving and provides the lowest possible

More information

CONTROL UNITS LOCAL EXTRACTORS LOCAL EXTRACTORS. Pure advantage

CONTROL UNITS LOCAL EXTRACTORS LOCAL EXTRACTORS. Pure advantage CONTROL UNITS LOCAL EXTRACTORS Fumex s control unit offers a good working environment, adapted to all types of facilities. The right choice of control units is also very energy-saving and provides the

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

JEFFERSON COLLEGE COURSE SYLLABUS HRA101 ELECTRICITY FOR HVAC. 5 Credit Hours. Prepared by: William Kaune. Revised Date: March 17, 2014

JEFFERSON COLLEGE COURSE SYLLABUS HRA101 ELECTRICITY FOR HVAC. 5 Credit Hours. Prepared by: William Kaune. Revised Date: March 17, 2014 JEFFERSON COLLEGE COURSE SYLLABUS HRA101 ELECTRICITY FOR HVAC 5 Credit Hours Prepared by: William Kaune Revised Date: March 17, 2014 Dena McCaffrey, Ed.D., Dean, Career & Technical Education HRA101 Electricity

More information

HVAC-R Drive Products

HVAC-R Drive Products Motors Automation Energy Transmission & Distribution Coatings HVAC-R Drive Products Designed Especially for HVAC Systems US.HVAC-R Drive.Products.01/2017 www.weg.net/us WEG HVAC-R Products WEG, a leading

More information

ICG Switchgear Price List 2009

ICG Switchgear Price List 2009 ICG Switchgear Price List 2009 Section 1 Control Gear Page Contactors (AC,DC & Modular) 2,3 Overload Relays 4 Product Accessories 4,5 Starters-DOL, Star-Delta, Fan/Vibrators, Reversing/Twin 6,7 Section

More information

Variable Air Volume Dampers

Variable Air Volume Dampers OVAV 2000 SERIES OPTIMA VAV DAMPERS Overview OPTIMA make Variable Air Volume (OVAV) box is a part of an Air Conditioning system. It is located inside the duct work. VAV Dampers are designed to control

More information

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both

More information

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes: SECTION 15970 HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Thermostats, temperature transmitters, controllers, automatic valves, dampers, damper operators, pneumatic/ electric

More information

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

Product guide. Enclosed NEMA starters. Answers for industry.

Product guide. Enclosed NEMA starters. Answers for industry. Product guide Enclosed NEMA starters Answers for industry. The right choice for applications that demand the best Siemens NEMA combination and non-combination starters for industrial and construction applications

More information

Product Guide. enclosed NEMA STARTERS

Product Guide. enclosed NEMA STARTERS Product Guide enclosed NEMA STARTERS The Right Choice for Applications that Demand the Best. Siemens NEMA Combination and Non- Combination Starters for Industrial and Construction Applications Rugged,

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

CONTRA COSTA COMMUNITY COLLEGE DISTRICT

CONTRA COSTA COMMUNITY COLLEGE DISTRICT ADDENDUM #1 CONTRA COSTA COMMUNITY COLLEGE DISTRICT Date: 11/15/2018 D 4014 Warehouse Demolition Project Diablo Valley College 321 Golf Club Road, Pleasant Hill, CA 94523 NOTICE TO ALL CONTRACTORS: You

More information

REVISIONS App PC. App Sud. App Thom TC 2014/03/25

REVISIONS App PC. App Sud. App Thom TC 2014/03/25 /9 Rev Description Document format and number changed. Previous number 543-0.0.30 Rev n by TC 204/03/25 Sud TC 204/03/25 REVISIONS PC Thom VB LH Clyd r Act Issue Date YYYY/MM/DD Pending Pending Pending

More information

CTi Automation - Phone: Fax: Web:

CTi Automation - Phone: Fax: Web: CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net The control & protection you expect in an innovative soft starter design... Flexibility

More information

Bussmann series Quik-Spec Power Module Switch elevator disconnect

Bussmann series Quik-Spec Power Module Switch elevator disconnect Supersedes January 2016 Agency information UL 98 enclosed and dead-front switch - Guide WIAX, WIAX7 (Canada), File E182262 culus, NEMA 1, UL 50, Listed enclosure cul per Canadian Standards C22.2, No. 0-M91-CAN/

More information

NEMA Contactors & Starters (Freedom)

NEMA Contactors & Starters (Freedom) Page 1 February, 1 Supersedes TIP AN1, AN, CN1, CN Pages 1-0, Dated 1/1/4 ECN01, ECN0, ECN0, ECN0, ECN0 AN1, AN, CN1 & CN Sizes 00-, 00V Max. Non-Reversing & Reversing NEMA Type Enclosures 1, R, 4X & 1

More information