Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break

Size: px
Start display at page:

Download "Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break"

Transcription

1 Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926 Technical Guide Load-break,

2 General Description The Drywell Current Limiting Fuse Cannister is a removable fuse assembly for use in single and three phase pad-mounted transformers. The fuse well assembly accepts general purpose current limiting fuses and is available in both load-break and dead-break designs. The combination of the drywell current limiting fuse cannister and the general purpose current limiting fuse provides a reliable, versatile and easily serviced current limiting protection system for transformers. Features and Advantages Test Proven Quality and Reliability The ABB Fuse Cannister has passed a series of design tests which offer verification of the design reliability. The tests are covered in TD and are listed below: 1. Switching Test 2. Fault Close Test 3. Dielectric Test 4. Short Time Current Test 5. Temperature Thermocycle Test 6. Safe Transit Test In addition to the design testing, the following production tests are done: 1: Audit - Dimension check to verify critical dimensions % - Seal test to verify sealing integrity. Current Limiting Capability The Drywell Current Limiting Fuse Cannister will accept general purpose current limiting fuses of the, ELX and GP variety. The current limiting fuse provides instantaneous Fuse Cannister Body Lower Probe Load-break Cannister Lower Contact Arc Quenching Insulators Loadbreak Contact Fuse Cannister Body No Lower Probe. Fuse Slides Into Lower Contact Deadbreak Contact Cannister Lower Contact protection for the system and transformer from faults within the interrupting rating of the fuse. Current limiting fuses offer faster response times and higher interrupting ratings than expulsion type fuses. Load-break Design The Load-break Current Limiting Fuse Cannister has an arc quenching device inside the cannister to permit load-break switching operations. The load make/load break capability of the fuse cannister provides the additional versatility and economy of load switching at the fuse itself without the need for additional switches. Design The dead-break design does not have arc stretching and quenching capability. If a transformer already has a high voltage switch, the dead-break design offers an economical method of providing current limiting fuse protection. The deadbreak design offers all the features of the load-break design except for the loadmake/loadbreak and fault close capability. Drawout The current limiting fuse is removed from the cannister at the front of the transformer using a standard hot stick. Once removed, the fuse can be inspected and/or replaced as necessary without disturbing the seal integrity of the transformer. Straight or Slant Mounting The ABB fuse cannister is available in both straight and slant mounting designs. The slant mounting is especially suited to single phase pad-mount transformer where the slanted design permits for shorter tank depth and a lower profile design. 2 ABB

3 Rugged Fuse The cannister is made up of two basic parts: the fuse cannister body assembly and the draw out assembly. All of the insulating parts are glass reinforced thermoset materials which are both arc and track resistant. Load-break Cannister Cutaway View The cannister body is assembled from glass wound epoxy tubing and a molded thermoset epoxy housing with brass electrical contacts. The upper draw out assembly is made from molded thermoset polyester and stainless steel hook eye and end cap. High Strength Contact Structure The fuse cannister contacts are brass to copper at the bushing lead connection and copper to brass at the cannister to winding connection. The combination of brass and copper provides the necessary conductivity and high strength for the internal lead connections. A spiral spring contact made of a silver plated copper alloy is used at the winding connection contact to insure consistent contact surface and balanced contact pressure. The contact to cannister interface is uniquely designed to provide transformer access to the contacts and yet maintain the seal integrity of the cannister. High Current Withstand Both the load-break and dead-break fuse cannisters are designed to withstand a 10 cycle, 60Hz current of amperes without damage to the cannister or contact structure. This design ensures that both the cannister and contact structure will withstand high current surges without impairing the cannister s ability to meet its functional requirements. Accessories End Cap Cover The end cap cover (451B806G02) is used to insulate the lower lead clamp and end cap assembly of the fuse cannister. The end cap cover is made from a black thermo-plastic polyester, and is designed to fit over the cannister end cap and lead clamp assembly. The end cap is supplied as standard equipment on load-break fuse cannisters. The end cap is not provided with dead-break fuse cannisters and must be ordered separately. Mounting Flange The mounting flange comes in two configurations; straight (5995A52G01), and slant.(5995a53g01). Both flanges are made from zinc plated steel with a yellow chromate sealer. On standard fuse cannisters, the mounting flange is supplied with the cannister as part of the mounting hardware. Cannister KV Rating Tag Hot Stick Eye Bolt Molded-in Gasket Seat Upper Probe Upper Contact Fuse Cartridge Lower Probe Arc Quenching Insulators Lower Contact 8.3 KV End Cap Cover ABB 3

4 Cannister Type Load-break Load-break Load-break Load-break Fuse Type kv To Order Mounting Arrangement Specify Tank Gasket Two different tank gaskets are available depending upon the type of cannister installation. Both the straight (5994A60H01) and slant (5994A60H02) mounting gasket are made from Nitrile. The tank gasket is supplied with the hardware kit on all standard fuse cannisters. - BIL (kv) Continuous Current (Amperes) Style Short Time Current (1.3 asymmetry Factor in Amperes) Number 60 Hz Withstand Voltage (kv) # Load-make/ Load-break Operations at Amperes Style Number 8. 3 Straight A 608C617G Slant A 608C617G24 15 Straight A 608C617G51 15 Slant A 608C617G53 23 Straight A 608C617G35 23 Slant A 608C617G Straight C433G Slant C433G12 15 Straight C433G43 15 Slant C433G44 Printed in USA by Tennessee Industrial Printing Services, Inc. Garter Spring The contact garter springs (51D0562H07) are designed to provide electrical conductivity between the upper corona shield and the upper lead contact assembly and as a field shaper between the upper corona shield and tank wall. The spring is made from stainless steel and is provided as standard equipment on the fuse cannisters listed above. See DS page 14 for garter spring installation instructions. Lead Clamp & Hardware The upper and lower contact clamps are identical. They are made from tin plated steel to resist corrosion during transport and storage before assembly in the transformer. All standard fuse cannisters are provided with two lead clamp assemblies and the necessary mounting nuts, bolts, and washers. See DS pg. 12 (straight) or pg. 13 (slant) for ordering information. ABB Inc S. Cavalier Drive Alamo, TN 38001, USA Telephone: Fax: IZUA en Replaces TPL , May 0

5

6

7

8 Straight Flange Lower Probe (Loadbreak Cannister Only) Varies by Cannister Contact ABB Fuse (Not Included) 5.00 (127.0mm) Mounting Flat 3.90 (99.1mm) Diamter Mounting Hole After Painting Flange Pad 3A34303H02 Flange (Standard - Straight) 451B587H05 Upper Probe Varies by Cannister Contact ABB Cannister See appropriate DS: Loadbreak: DS pg 10 Deadbreak: DS pg 11 Mounting Stud (9.5mm) Diameter 1.00 (25.4mm) Long 4 Required on 6.00 (152.4mm) Bolt Hole Circle Cannister Tank Gasket (Standard - Straight) Straight: 5994A60H07 Spring Clip 1B11118H01 Mounting Nuts & Washers to match mounting studs on tank wall Torque to 60 inlbs. Garter Spring 2 Required 51D0562H13 Tank Wall Clamp Nut 2 Required 608C611H01 Standard items are included with cannister. Clamp Washer 4 Required 608C606H06 Lead Clamp 2 Required 2792A96H02 End Cap Cover (Loadbreak Cannister Only) 451B806G02 Clamp Bolt 2 Required 608C609H04 ABB Inc. Components & Insulation Material TITLE STRAIGHT FUSE CANNISTER INSTALLATION INSTRUCTIONS DIMENSION SHEET: PAGE: REVISION: DIMENSIONS ARE IN INCHES.

9 Fuse (Not Included) Flange (Standard-Slant) 451B587H06 Upper Probe Varies by Cannister Contact ABB Lower Probe (Load-break Cannister Only) Varies by Cannister Contact ABB Flange Pad 3A34303H01 Cannister See Appropriate DS Loadbreak: DS pg 10 Deadbreak: DS pg (3.4mm) Radius Mounting Tab 5.75 (146.1mm) Diameter Mounting Flat Tank Wall 4.34 (110.2mm) Diameter Mounting Hole After Painting Garter Spring 51D0562H13 Slant Flange Mounting Hole End Cap Cover (Loadbreak Cannister Only) 451B806G02 Lead Clamp (2-Standard) 2792A96H02 Mounting Nuts & Washers to match mounting studs on tank wall Torque to 60 inlbs. Spring Clip 1B11118H02 Cannister Tank Gasket (Slant) 5994A60H08 Mounting Stud (9.5mm) Diameter 1.00 (25.4mm) Long, 4 Required on 6.50 (165.1mm) Bolt Hole Circle Clamp Nut (2-Standard) 608C611H01 Clamp Washer (4-Standard) 608C606H06 Clamp Bolt (2-Standard) 608C609H04 ABB Inc. Components & Insulation Material TITLE SLANT FUSE CANNISTER INSTALLATION INSTRUCTIONS DIMENSION SHEET: PAGE: REVISION: DIMENSIONS ARE IN INCHES.

10

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA 5321-100 Technical Guide Nut Mount Weld Mount General Description The ABB Type LBOR-II switch is a manually operated, two position, load make

More information

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA 5670-100 Technical Guide 15 kv, 23 kv, & 35 kv General Description The Protective link is an oil immersed, expulsion type, fuse

More information

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc. DO-III DO-III Fuse Holder TPL 44-835, May 2000, Page 1 of 4 General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder ABB Inc. General Description The ABB DO-III fuse holder is a draw

More information

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

LV Bushing Oil to Air Dry Insulation PTAB-SLV832 LV Bushing Oil to Air Dry Insulation PTAB-SLV832 Technical Guide 600 V, 30 kv BIL, 600-2500 A 5/8" Integral Flange Bushing 1.0" Integral Flange Bushing 1.25" Bushing General Description The ABB low voltage

More information

ABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4

ABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4 General Information: DT-100 DT-150 DV-100 DV-150 De-energized Switches TPL 44-816, July 1999, Page 1 of 4 Type DT-100 & DT - 150, Tap Changers; Type DV-100 & DV- 150, Dual Voltage Switches - General Information

More information

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION Fusing Equipment Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly Electrical Apparatus 40-40 GENERAL Cooper Power Systems Bay-O-Net Fuse Assemblies are used to protect transformers and distribution

More information

Low voltage bushings for pad-mounted distribution transformers Technical information guide

Low voltage bushings for pad-mounted distribution transformers Technical information guide Transformer components Low voltage bushings for pad-mounted distribution transformers Technical information guide ABB low voltage bushings terminate a transformer s internal low voltage leads at the tank

More information

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION Fusing Equipment Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly Electrical Apparatus 240-40 GENERAL Cooper Power Systems Bay-O-Net Fuse Assemblies are used to protect transformers and distribution

More information

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL Loadbreak Apparatus Connectors 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal Electrical Apparatus 500-10-7 GENERAL The Cooper Power Systems Loadbreak Elbow Connector is

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic

More information

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 35 kv Separable Insulated Connector (elbow) Bus Bar or Other Component Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other

More information

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 2 / 9 Table of contents 1 Description... 3 2 Ratings...

More information

Loadbreak Apparatus Connectors

Loadbreak Apparatus Connectors Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector

More information

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 35 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other

More information

CSP Circuit Breaker Three Phase

CSP Circuit Breaker Three Phase General Information : LR Breaker SQR Breaker LQR Breaker, HQR Breaker Wall-Mounting Type CSP Circuit Breaker Three Phase Three Phase CSP Circuit Breaker For Distribution Transformers General Information

More information

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 15 kv or 25 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic

More information

25 kv Apparatus Bushings

25 kv Apparatus Bushings Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation

More information

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage 1500 kva Padmount Transformer 12470 delta Primary Voltage 208Y/120 Secondary Voltage Cooper Power Systems Proposal Number: BED1096719 Date: January 4, 2010 Revision 00 Item Number: 00001 Item Details Customer

More information

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Equipment Connection Bus Bar, or Grounded Metal Equipment Plate F Series Mounting Holes ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric

More information

15 kv and 25 kv Thru-Bushings

15 kv and 25 kv Thru-Bushings Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation

More information

X-Limiter full-range current-limiting fuse

X-Limiter full-range current-limiting fuse Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal Loadbreak Connectors Catalog Data CA650062EN Supersedes June 2015 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal General Eaton s Cooper Power series

More information

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN OEM Equipment MN800008EN Effective February 2016 Supersedes S800-35-2 November 2013 COOPER POWER High-voltage primary bushings installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF

More information

25 kv class fused loadbreak elbow connector

25 kv class fused loadbreak elbow connector Loadbreak Connectors Catalog Data CA650070EN Supersedes 500-111 July 2012 COOPER POWER SERIES 25 kv class fused loadbreak elbow connector General Eaton combines a fully-shielded and insulated plug-in termination

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connectors Catalog Data CA650063EN Supersedes 500-10-7C November 2011 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General

More information

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connectors CA650101EN Supersedes 500-29-7C November 2011 COOPER POWER SERIES 200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

More information

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated

More information

Eaton s Cooper Power Systems

Eaton s Cooper Power Systems Page: 1 of CERTIFIED TEST REPORT Eaton s Cooper Power Systems 600 Amp - 35 kv Class Deadbreak Bushing With Internal Ground Screen Design Qualification Tests December 17, 2013 Supersedes 10/20 2013 Eaton

More information

High-voltage primary bushings installation instructions

High-voltage primary bushings installation instructions OEM Equipment Effective November 2013 Supersedes April 2013 S800-35-2 High-voltage primary bushings installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and

More information

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze

More information

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connector CA650099EN Supersedes 500-28-7C November 2011 COOPER POWER SERIES 200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General Eaton

More information

INSTALLATION PRODUCTION TESTS

INSTALLATION PRODUCTION TESTS Deadbreak Apparatus Connectors 600 A 15/25 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-10 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class Bol-T Deadbreak Connector is used to terminate

More information

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254. 3 Loadbreak Elbows 200 Amp 5-15 kv Industrial pg. 252 Loadbreak Elbows 200 Amp 25 kv Industrial pg. 254 Loadbreak Elbows 200 Amp Industrial pg. 255 Loadbreak Elbows Accessories 3 Loadbreak Elbows 3M 200

More information

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications

More information

your Green Power WIND POWER SOLUTIONS only Greener

your Green Power WIND POWER SOLUTIONS only Greener your Green Power WIND POWER SOLUTIONS only Greener WIND POWER SOLUTIONS Thomas & Betts is committed to being your partner in power delivery by leading the industry in innovative wind power solutions and

More information

600 A 15 and 25 kv class Cleer grounding elbow

600 A 15 and 25 kv class Cleer grounding elbow Loadbreak/Deadbreak Connectors CA650013EN Supersedes March 2015 COOPER POWER SERIES 600 A 15 and 25 kv class Cleer grounding elbow General Eaton provides a visible ground on its Cooper Power series 600

More information

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation Elastimold solid dielectric switchgear agenda Compelling value Design principles Product overview Switchgear applications

More information

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv) S&C Loadbuster Disconnect Switches Outdoor Distribution ( kv through 34.5 kv) S&C s Loadbuster Disconnect Switches, when used with S&C s Loadbuster tool, provide the ultimate in distribution live-switching

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents

More information

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors Loadbreak/Deadbreak Connectors CA650079EN Supersedes 650-10 December 2005 COOPER POWER SERIES and 600 A, 15, 25, and 35 kv junction bars for General Eaton designs its Cooper Power series junction bars

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive

More information

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50 Deadbreak Apparatus Connectors 600 A 35 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-50 General The Cooper Power Systems 600 A, 35 kv Class Bol-T Deadbreak Connector is used to terminate

More information

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Powergrid Solution s Metal Enclosed Switchgear has many different customizable options and configurations. Customers

More information

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number: 15kV 200A Loadbreak Fuse Elbow Design Test Report Report Number: Date: RN-R2601 9/3/2015 Table of Contents 1. Partial Discharge Test Fuse Elbow... 2 2. AC Withstand Voltage Test - Fuse Elbow... 3 3. DC

More information

VacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components

VacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components Supersedes July 2002 Contents Page Procedure for identifying parts... 2 Customer ordering instructions.... 2 Distributor ordering instructions.... 2 Front panel components.... 3 Breaker pan assembly....

More information

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: 4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:

More information

Wind Power Solutions. Make Energy Renewable and Reliable!

Wind Power Solutions. Make Energy Renewable and Reliable! Wind Power Solutions Make Energy Renewable and Reliable! Reliable Thomas & Betts Products for Clean, Green, Thomas & Betts makes all the products that connect and protect a wind farm and its power distribution

More information

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed. City of Cartersville Electric System P.O. Box 1390 320 S. Erwin St. Cartersville, GA 30120 770-387-5631 March 2006 SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS This specification provides standardization

More information

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses Page 1 2016 EPMR-35-311S-R2/ESW-CM9 Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton s CPS LRTPs 50 Amp (Max) 27 kv Clip-Mounted NX Fuse Provisions 21.1/36.6 kv Grounded Wye Max Design, 150 kv

More information

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,

More information

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear Descriptive bulletin ReliaGear ND ANSI narrow frame metal-clad switchgear Table of contents Introduction...3 Vmax/A breaker...4 Instrument transformers...5 Potential transformers...6 15 kv potential transformers...6

More information

Installation Instructions LINK---C

Installation Instructions LINK---C IS---LINK---C Page 1 of 10 Installation Instructions LINK---C DEADBREAK CAM LINK OPERABLE CONNECTOR SYSTEM The is a 600 amp, connector designed to: 1.) provide a fully shielded, fully submersible hot stick

More information

S&C Loadbuster Disconnects

S&C Loadbuster Disconnects S&C Loadbuster Disconnects Outdoor Distribution ( kv through 34.5 kv) With these outstanding features... Up to -ampere continuous ratings, 40,000-ampere RMS asymmetrical momentary ratings Designed for

More information

Disconnect & ByPass Switches

Disconnect & ByPass Switches Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class

More information

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector www.chardongroup.com IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector Application Chardon Front T-Body / Coupling (Rear) T-Body connectors are fully

More information

600 A 15 kv class T-OP II deadbreak connector

600 A 15 kv class T-OP II deadbreak connector Deadbreak Apparatus Connectors CA650017EN Supersedes 600-12 February 2010 COOPER POWER SERIES 600 A 15 kv class T-OP II deadbreak connector General Eaton terminates high-voltage underground cable to transformers,

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability 15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability Application The Chardon 15 kv Class Fused Loadbreak Elbow Connector combines a fullyshielded and insulated loadbreak elbow

More information

RBA Catalog Numbers and Information

RBA Catalog Numbers and Information 50 RBA s and Information Type RBA Expulsion Fuses for Use Indoors or in an Enclosure Ampere Rating Standard Speed (Fuse Refills) Curve Reference 36-635 Time-Lag (Fuse Refills) Curve Reference 36-635 Approx.

More information

Product Specifications for Aluminum Vertical Break Switches

Product Specifications for Aluminum Vertical Break Switches 1. General a) This specification covers the design, manufacture, and shipment of aluminum vertical break switches, both air-break and load-break configurations, for substation and transmission switching

More information

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

600 A 35 kv class BT-TAP deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector Supersedes 600-55 July 2014 600 A 35 kv class BT-TAP deadbreak connector General Eaton's Cooper Power Systems 600 A 35 kv Class BT-TAP deadbreak connector is used to terminate high-voltage underground

More information

Power IT Liquid Filled Single Phase Padmounted Transformers kva

Power IT Liquid Filled Single Phase Padmounted Transformers kva X62082-Brochure 8/15/03 10:09 AM Page 1 Power IT Liquid Filled Single Phase Padmounted Transformers 10-250 kva Industrial IT enabled X62082-Brochure 8/15/03 10:09 AM Page 2 X62082-Brochure 8/15/03 10:09

More information

A 1.2 kv class externally removable secondary bushing

A 1.2 kv class externally removable secondary bushing OEM Equipment Catalog Data CA800018EN Supersedes July 2015 COOPER POWER SERIES 3010-4515 A 1.2 kv class externally removable secondary bushing General Eaton s Cooper Power series 3010-4515 A externally

More information

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall

More information

Product Specifications for Phase Over Phase GOABS(r)

Product Specifications for Phase Over Phase GOABS(r) 1. General a) This specification covers the design, manufacture, and shipment of phase-over-phase, 1-way, 2-way, 3-way, and 4-way, gang-operated disconnecting switches, both air-break and load-break, for

More information

Westinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401

Westinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401 February 26, 1976 Supersedes PL 38-640 dated October 15,1974 Pages 1-8 Prices effective April 29, 1974 Subject to change without notice Selling Policy 38-000 Mailed to E, D, C/1991, 2430/ PL Standard Bill

More information

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary 14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching

More information

Power Fuses. > Power Fuses > BPA & HPA kv AMPs

Power Fuses. > Power Fuses > BPA & HPA kv AMPs The equipment described in this bulletin performs in accordance with NEMA standards publication SG2-1954, paragraphs SG2-5, SG2-5.10, and SG2-5.11 TYPE BPA Power Fuses 7.2-161 kv 100-200-300 400 AMPs The

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

C. System Design and Performance Requirements

C. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16361-E-E to 26 10 03, removed references to other section numbers A. Summary - mgl44 Change Approver

More information

Molded Current-Limiting Fuse

Molded Current-Limiting Fuse Molded Current-Limiting provide fullrange fault current protection using specially designed fuse elements, rated through 23kV line to ground and 50kA interrupting current. Construction is modular with

More information

600 A 25 kv class BT-TAP deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector Deadbreak Connectors Catalog Data CA650001EN Supersedes January 2015 600 A 25 kv class BT-TAP deadbreak connector COOPER POWER SERIES General Eaton terminates high-voltage underground cable to transformers,

More information

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to

More information

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses) .7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous

More information

Section 1 Introduction to the Presentation

Section 1 Introduction to the Presentation 2007 Thomas & Betts Section 1 Introduction to the Presentation Introduction of T&B Hi-Tech Fuses and our products Expulsion fuses vs. Current-Limiting fuses Hi-Tech s fuse construction & design features

More information

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor 35-kV Safefront 2 Amp SuperWell 5-33 Page 1 216 EPM-PMS-35-311P-R2/ESW Three Phase Two Ways per Phase 2 Amp 35 kv Class Eaton's CPS LRTPs NEMA Standard Outdoor Instrument Transformer Provisions 21.1/36.6

More information

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor Page 1 2015 Heavy-duty 11-gauge steel enclosure is all-welded construction for long life Clear polycarbonate removable safety barrier separates upper and lower compartment (supplied only with internally

More information

FX Full-Range Current-Limiting Fuse

FX Full-Range Current-Limiting Fuse Hi-Tech FX Full-Range Current-Limiting Fuses Trans-Guard FX Full-Range Current-Limiting Fuse Patented damage sensor significantly reduces the risk of fuse failure should the fuse be subjected to an element-damaging

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Elastimold & Hi-Tech Fuse Products

Elastimold & Hi-Tech Fuse Products In this section... Elastimold & Hi-Tech Fuse Products Elastimold & Hi-Tech Fuse Products Overview...H-62 Elastimold Fused Loadbreak Elbows (FLE)... H-63 H-67 Elastimold Molded Current-Limiting Fuses (MCLF)...

More information

M-Force three-phase switch

M-Force three-phase switch Supersedes K-SEC 926 December 2012 M-Force three-phase switch Description The M-Force switch from Eaton's Cooper Power Systems is a distribution-class, gangoperated, factory unitized three-phase overhead

More information

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E Supersedes PL.44B.04.P.E Dated September 1998 600 Volts AC Maximum 200 ka, RMS Sym. Short Circuit Maximum 800-5000 Amps Continuous Effective: October 1999 Page 1 Index Page Table Description/Application...

More information

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv) S&C Power Fuses Types SM- 4, SM-5, SMD-0, and SMD-40 Outdoor Distribution (4.16 kv through kv) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: The seller s standard

More information

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number: 25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.

More information

Product Selection Guide

Product Selection Guide Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility

More information

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor Page 1 2016 EPM-PCS-35-320P-R2/ESW-GCM6-2S-SA Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton's CPS LRTPs 35 kv Elliott Air-Insulated SuperWell Bushings 21.1/36.6 kv Grounded Wye Max Design, 150

More information

Single Phase Padmounted Transformers kva

Single Phase Padmounted Transformers kva Single Phase Padmounted Transformers 10-250 kva Introduction to ABB ABB is a global leader in power and automation technologies that enable utility and industry customers to improve their performance while

More information

M-Force three-phase switch

M-Force three-phase switch Switches and Disconnects CA008004EN Supersedes May 2015 COOPER POWER SERIES M-Force three-phase switch Description Eaton's Cooper Power series M-Force switch is a distribution-class, gang-operated, factory

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses) .7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous

More information

Boric Acid Fuse Links

Boric Acid Fuse Links Boric Acid Fuse Links BBU Fuse Link Mount Construction Bird proof design insulator provides insulation characteristics higher than ANSI distribution cut-out standards and equal in most cases to ANSI switch

More information

GROUP D. Switch & Protective device.

GROUP D. Switch & Protective device. GROUP D Switch & Protective device PYUNGIL Bldg., 147-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-0~3 FAX : 82-31-424-7300 www.pyungil.com Pole-mounted SF Insulated

More information

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035 Instruction Bulletin 4402-997-0 February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker

More information

Reliable liquid or simulated winding indication at eye level

Reliable liquid or simulated winding indication at eye level qualitrol 104/TR6000 Remote mount thermometers Reliable liquid or simulated winding indication at eye level Rugged construction and corrosion resistant materials for life-long function Wide array of options

More information