E L B S - 10 LINE BREAK DETECTION SYSTEM INSTRUCTION HANDBOOK
|
|
- Scott Edwards
- 6 years ago
- Views:
Transcription
1 E L B S 10 LINE BREAK DETECTION SYSTEM INSTRUCTION HANDBOOK MDE135E2 REVISION LIST 2 18/05/2002 Fixed operating mode M.B. A.A. 1 18/07/2000 Update function of CN51 external power supply ( pag.12 ) 0 18/01/2000 Issue document M.B. A.A. Rev. Date Description Prepared Approved BIFFI ITALIA s.r.l. DIREZIONE, UFFICIO COMMERCIALE,,STABILIMENTO HEADQUARTER, SALES DEPARTMENT, FACTORY Fiorenzuola d'arda (Piacenza) Italy Tel. (0523) Telex Bifior.I Telecopier (0523) M.B. A.A i
2 CONTENTS 1. FORWARD WORKING PRINCIPLE TABLE OF OPERATING MODES GENERAL CHARACTERISTICS VALVE CONTROL ON PRESSURE DROP RATE VALVE CONTROL ON HIGH OR LOW PRESSURE VALVE CONTROL FOR SIMULATION TEST VALVE CONTROL DELAY LINE PRESSURE DATA ACQUISITION SOLENOID VALVE CONTROL OUTPUT POWER SUPPLY PACK LOCAL OPERATOR INTERFACE LOCAL COMMUNICATION PORT OUTPUT RELAYS PRESSURE TRANSDUCER EXAMPLE OF PRESSURE DROP RATE CONTROL ELBS10 ELECTRONIC CARDS DIPSWITCHES AND JUMPERS SETTING : TECHNICAL CHARACTERISTICS OF ELBS ELECTRICAL CONNECTIONS OF ELBS VIEW OF EEXD LINE BREAK CABINET MENU OF THE LOCAL OPERATOR INTERFACE OF ELBS PARAMETERS AND SETPOINTS LIST ALARMS AND WARNINGS LIST PARAMETERS LIST OF THE TEST FUNCTION INSTRUCTIONS FOR USING THE LOCAL OPERATOR INTERFACE LIBVIEW.EXE PROGRAM TO INSTALL THE LIBVIEW.EXE PROGRAM ON THE PC TO CONFIGURE THE ELBS10 LINE BREAK DETECTION MODULE TO SAVE ALL THE EVENTS DATA OF THE ELBS10 MODULE TO VISUALISE THE ELBS10 STATUS MAIN COMPONENTS OF EEXD LINE BREAK CABINET TYPICAL ELECTRICAL DIAGRAM TYPICAL OPERATING DIAGRAM START UP INSTRUCTIONS TO RESTORE THE VALVE CONTROL FUNCTION BATTERY MAINTENANCE ii
3 1. FORWARD The Line Break Detection System type ELBS10 is an electronic equipment, developed by Biffi, for monitoring the pipeline integrity. The ELBS10 continuously monitors the pressure in the line and in case of failure, it sends a command to the actuator so as to stroke the line valve to the fail safe position. The electrical power necessary for working, is supplied by a 7.2V lithium battery pack that allows the ELBS10 to work for at least one year. The ELBS10 is provided with a powerful local operator interface, made of one 2 lines / 16 characters LCD display and 3 pushbuttons, that allows to enter the configuration data and to visualise the values of variables or the status of the device. Moreover an RS232 serial communication port is provided for connection to a PC or LAP TOP, to carry out parameter configuration, or variables visualisation or to download the recorded event data for further analysis of pipeline behaviour. LCD display of local operator interface Example of cabinet equipped with ELBS 10 Pushbuttons of local operator interface, ' ', 'ENTER' pushbutton,' ', 'DEC' pushbutton,' ', 'INC' pushbutton The ELBS 10 was especially engineered for ON FIELD service, it means capability of working in the severest ambient conditions, as wide operating temperature range, vibrations, explosive atmosphere, etc. Particular care was taken to increase the level of immunity against the radio frequency disturbs
4 2. WORKING PRINCIPLE The ELBS10 samples cyclically the line pressure value, measured by the pressure transducer (PT) and memorises the sampled values in a temporary rolling memory, type FIFO (First in, First out). The rolling FIFO memory allows to store 256 samples and the sampling rate is programmable from 1 to 10 s. The pressure magnitude and pressure drop rate are continuously compared to the reference values, set by the user in the configuration memory. An event is defined as the condition that occurs when the measured pressure magnitude or pressure drop rate exceeds the customer setpoint for a configurable time. In case of event, the pressure magnitude values, present in the FIFO memory and relevant to 88 samples preceding the event and 168 samples after the event, are transferred to the data memory. Only one sample out of four is stored in the event data memory. So each event is recorded in the event data memory by 64 samples (22 samples preceding the event and 42 after the event). The event data memory can store up to 1000 events. The following drawing shows the block diagram of the ELBS10: ELBS10 External voltage supply 7 Vdc Solid state switch DC/DC converters Wakeup control Battery voltage monitor Opto Line voltage monitor Power supply Time keeper / wakeup circuit / watchdog circuit C P U Local operator interface LCD display: 2 lines / 16 char 3 pushbuttons: FIFO memory RAM/ROM memory Relay DC/DC converter Opto DC/DC converter 128Kx8 event data memory Relay RS 232 transceiver A to D converter: 12 bit / 2 channel 128Kx8 event data memory Relay Relay RS 232 serial communication line 12Vdc / 20mA 8Kx8 RAM memory External line voltage sensor Available inputs Emergency solenoid valve control LineBreak Alarm relay Valve Control : armed/not armed relay Line break Warning relay External supply voltage value input 020mA line pressure input +12V pressure transmitter voltage supply
5 The ELBS10 transfers into the event data memory the following type of EVENTS: EVENT 1 pressure value decreases of a preset amount (field configurable ) EVENT 2 pressure reaches the low value limit (field configurable) EVENT 3 pressure value increases of a preset amount (field configurable) EVENT 4 pressure reaches the high value limit (field configurable) EVENT 5 (only in ACQ mode) pressure drop exceeds the preset speed drop data acquisition (field configurable) EVENT 6 pressure drop exceeds the preset speed drop valve control (field configurable) The following configurable operating mode are available: data acquisition valve control sleep In data acquisition operating mode the pressure samples relevant to an event (1,2,3,4,5) are stored in the data memory but an event does not affect the valve position. In valve control operating mode the pressure samples relevant to an event (1,2,3,4,6) are not stored in the data memory but EVENTS 2,4 and 6, cause the valve to stroke to the failsafe position. The two operating mode can be used separately or simultaneously. In valve control + acquisition mode (ACQ+VC ), in case of pressure drop only EVENT 6, EVENT 1, 2,3,4 are recorded, while EVENT 5 is not recorded. The sleep operating mode is used to inhibit both data acquisition and valve control operating modes to puts out of service the ELBS10. In case of alarm or if valve control mode is chosen but the solenoid valve control is not armed, automatically, the ELBS10 enters in the slow sampling state. In the above state the valve control and acquisition functions are off, but the ELBS10 restores to normal operation when the cause disappears
6 The following figure shows the data acquisition area in function of the time. Pressure bar Max. pressure Data acquisition area Time Pressure drop in valve control Pressure drop in acquisition Min. pressure min. The below figure shows the above described types of EVENT that could be memorised during one year of pipeline data acquisition. The Event 1, happened in January, represents a pressure that pass through the values of 30 bar and 25 bar, causing the memorisation of the events in the event data memory ( Event 1.1 & Event 1.2).In February, April, May, July September and November the pipeline pressure does not generates any Event. The Event 3 represents a pump station startup, while the Event 5 is a pump station shut down that creates a pressure drop rate higher than the ELBS10 adjustment, so that the Event 5.1, 5.2, 5.3 and 5.4 are memorised into the event data memory. The Event 6 represents a Line Break that creates a pressure drop rate higher than the pipeline curve behaviour present in the ELBS10 memory. In this case the actuator is controlled in order to stroke the pipeline valve in the fail position. Pressure (bar) Pressure behaviour relevant to one year Jan. Feb. March April May June July Aug. Sept Oct. Nov. Dec EVENT 1 EVENT 2 EVENT 3 EVENT 4 EVENT 5 EVENT 6 HIGH PRESSURE VALUE EVENT LOW PRESSURE VALUE EVENT Time (hours)
7 All the Events are memorised in the event data memory. The following formula allows to calculate the duration of the recorded time corresponding to each event and the time between two recorded pressure data in each event: recorded time duration ( min. ) = sampling rate * 256 / 60 time between 2 data( sec. ) = sampling rate * 4 For example with sampling rate at 8 sec. the time duration of the recorded data is 8*256/60 = 34.1 min, and the time between two recorded pressure data is 8*4 = 32 sec. When the event data memory reaches 90% of its capability an alarm informs about the need to discharge the memory content in a portable PC in order to allow the ELBS10 to restart its pipeline survey. The content of the event data memory can be used to buildup the pipeline pressure curve relevant to one year of survey, as shown in the below figure. The pressure curve allows to calculate the typical values of pressure and pressure drop rate of the pipeline and to enter the correct setpoints in the ELBS10. Pressure curve obtained after one year of survey Pressure (Bar) EVENT 4 HIGH PRESSURE VALUE EVENT Event Event 3 Event Event 1 Event 2 LOW PRESSUR VALUE EVENT January February March April May June July August September October November Dicember
8 2.1. Table of operating modes Operating mode Valve Control ( V C ) (configurable) Acquisition ( ACQ ) (configurable) Valve Control + Acquisition ( V C + ACQ ) (configurable) Sleep ( SLEEP ) (configurable) Slow sampling ( SLOW ) (automatic, not configurable) Description No data acquisition, only valve control in case of EVENTS 2,4, 6. Valve control mode is active only if Solenoid valve control is armed. The ELBS10 switches to slow sampling mode if : solenoid valve control is not armed. if there is an alarm. after the valve control. Valve control not active. No valve control, only data acquisition on EVENTS 1, 2, 3, 4, 5. The ELBS10 switches to slow sampling mode if : the event data memory is full and not circular mode is set. if there is an alarm. in case of low pressure (EVENT 2). in case of high pressure (EVENT 4). Valve control on EVENTS 2, 4, 6, and data acquisition on EVENTS 1, 2, 3, 4, 6. Valve control + Acquisition is active only if Solenoid valve control is armed. The ELBS10 switches to slow sampling mode if : solenoid valve control is not armed. if there is an alarm. after the valve control. If event data memory is full and not circular mode is set, the data acquisition stops, but valve control is still active. No data acquisition and valve control. No pressure and voltage measurement. The local operator interface is still available. No data acquisition and valve control. The local operator interface is still available. The ELBS10 measures the voltage supply and the pressure with a time equal to slow sampling rate (see: parameters and setpoints list). The ELBS10 display show ' SLOW' The ELBS10 restores to normal operation when the cause disappears
9 3. GENERAL CHARACTERISTICS 3.1. Valve control on pressure drop rate When the pressure drop rate exceeds the drop rate setpoint (EVENT 6), the ELBS10 sends an electric command to the solenoid valve and the actuator stroke the line valve to the fail position Valve control on high or low pressure The ELBS10 sends an electrical signal to the solenoid valve in order to stroke the line valve to the fail safe position when the pressure value is lower than the low pressure setpoint ( EVENT 2 ), or is higher than the high pressure setpoint ( EVENT 4) Valve control for simulation test The ELBS10 is fitted with an hardware/software module that allows to enter a pressure drop rate in place of the pressure transducer values, in order to verify the output command signal to the solenoid valve and the correct operation of the device. The test function force the valve control (VC) mode. The simulated pressure will start to the high pressure limit and goes to 0 bar. The test function can be stopped by the ENTER push button. If the ELBS10 will close the pipeline valve the event will not be recorded Valve control delay The ELBS10 is fitted with a configurable time delay module that allows to delay the solenoid valve command. If the condition which causes the event (low pressure EVENT 2, high pressure EVENT 4, pressure drop rate EVENT 6), disappears during the delay time, the valve control signal will not be generated Line pressure data acquisition The ELBS10 temporary rolling memory (FIFO) is continuously recording 256 samples. When an event occurs, the FIFO memory data are stored, one out of four, in the event data memory. The event data memory capacity is of 1000 events. The following setpoint are used : low pressure setpoint (EVENT 2), high pressure setpoint (EVENT 4), drop rate setpoint in valve control mode (EVENT 6), pressure drop rate setpoint in acquisition mode (EVENT 5), pressure increases of preset amount (EVENT 3), pressure decreases of preset amount (EVENT 1). When more events occur during the data acquisition, the relevant event record will be marked whit the code of the first one. The data relevant to the events can be visualised by local operator interface or by PC via RS232 serial line. By PC, the user can builtup the line pressure behaviour
10 3.6. Solenoid valve control output The ELBS10 is provided with a 24Vcc/100mA output electric signal and one changeover dry contacts of a relay, suitable to drive the solenoid valve of the actuator. A timer module allows to set the duration of the solenoid valve control (solenoid control duration). The output is active if the ELBS10 operating mode is valve control (VC) or valve control + acquisition (VC+ACQ) and solenoid valve control is armed Power supply pack In this case the ELBS10 is fitted with a battery pack with 4 x 3.6V Lithium Thionyl Chloride, size D. The battery pack is installed in an explosion proof enclosure. The battery service life depends on the sampling rate. By selecting 8 sec. as sampling rate the minimum battery life is 1 year. A battery life survey function generates a Warning signal when the next change of battery is necessary ( see next maintenance on tab. 7.1) Local operator interface The ELBS10 is fitted with a 2 lines / 16 characters LCD display and 3 pushbuttons that allows to enter the configuration parameters or to visualise the working data., ' ', 'ENTER' pushbutton,' ', 'DEC' pushbutton,' ', 'INC' pushbutton Two pushbuttons 'DEC', 'INC' are used to move into the menu, while the third 'ENTER' is used to enter the selected information. To visualise the messages of the display, the operator can choose between two available languages (English or Italian). The following operations can be done: to visualise the: event data memory content pipeline present pressure value line valve control setpoints data acquisition setpoints battery voltage value status and alarm of the ELBS10 to configure all ELBS10 parameters and setpoints to arm the valve control output relay The configuration operation are protected by password. The operator can enter in the configuration menu and change the parameters or arm the solenoid valve control output, only after entering the appropriate password. The ELBS10 is supplied by BIFFI with the default password The customer can enter its own secret password of 4 alphanumerical characters. When the new password is entered, the default one is no longer valid
11 3.9. Local communication port The ELBS10 when is connected via RS232 to a portable computer it is possible to control and program all relevant parameters. The following operations can be done: to visualise the: event data memory content pipeline present pressure value line valve control setpoints data acquisition setpoints battery voltage value status and alarm of ELBS10 to configure all ELBS10 parameters and setpoints to download the event data memory content to arm the valve control output relay 3.10.Output relays One output relay with changeover, dry contacts is available for remote signalling of alarm of ELBS10. In alarm the ELBS10 stops working. (see: alarm and warning table ). One output relay with changeover, dry contacts is available for remote signalling of warning of ELBS10. In warning all functions of the ELBS10 are available, but some parameter or variable is not correct (see alarm/ warning table). One output relay with changeover, dry contacts is available for remote signalling of solenoid valve control not armed. When the status of the relay indicates armed, the ELBS10 is ready to control the valve if the pressure is lower than the setpoint, or the pressure is higher than the setpoint or the pressure drop rate exceeds the setpoint (EVENTS 2,4,6), when one of this events is detect the ELBS10 command the line valve to fail position and switch this relay. After valve control the relay remains in the status not armed. This relay will be reset when the ELBS10 is re ARMED. (see : how to arm solenoid valve control par.) Pressure transducer The pressure transducer is supplied with the ELBS10 and is installed on the line valve at valve maker / customer care, according to Biffi instructions. The pressure transmitter must be installed downstream the line valve and converts the pipeline pressure 0100 bar to a 020mA electrical signal
12 3.13. Example of pressure drop rate control The following figure shows the ELBS10 behaviour in presence of a continuous pressure drop rate. *Pressure drop greater than setpoint EVENT6 Pressure samples in FIFO memory tm Pressure curve tm Sampling rate tm (sec.) = 26 / pressure drop rate setpoint (bar/min.) t1 (sec.) = 4 * sampling rate (sec.) t2 (sec.) = valve control delay (sec.) t3 (sec.) = solenoid control duration Slow sampling rate Valve control mode, solenoid valve control armed, no alarm tm tm tm tm Valve control Time Time t0tm Present time* t0 Time t0+t1 Time t0+t1+t2 Time t0+t1+t2+t3 Valve control not armed, slow sampling rate Measuring time of pressure drop confirmation time Delay Solenoid control duration Note : Before than the valve control action takes place, it needs that the EVENT 6 condition is confirmed for the confirmation time and the pressure decreases during the delay time. The following figure shows the ELBS10 behaviour in presence of a temporary pressure drop rate. Pressure drop greater than setpoint EVENT 6 Pressure samples in FIFO memory Pressure curve tm Sampling rate Pressure drop smaller than setpoint Event condition cleared Valve control mode, solenoid valve control armed, no alarm tm tm tm tm tm No event, normal operation Time Time t0tm Present time t0 Time t0+t1 Time t0+t1+t2 Measuring time of pressure drop Event confirmation time Delay of valve stroking tm (sec.) = 26 / pressure drop rate setpoint (bar/min.) t1 (sec.) = 4 * sampling rate (sec.) t2 (sec.) = valve control delay (sec.)
13 4. ELBS10 ELECTRONIC CARDS The ELBS10 consists of two electronic card ( mother board and display board). On the mother board are located the microprocessor, the A/D converter, the memories, the power supply stage and the input / output modules. On the display board are located the LCD display, the circuit necessary to control the 3 push buttons of the local operator interface and the RS 232 connector. The following figure shows the ELBS10 electronic cards. CN1 Output relays terminals Output relays ELBS10 2 lines / 16 char LCD display DISPLAY BOARD MOTHER BOARD CN2 Output relays terminals CN3 Terminals of local operator push buttons RS 232 connector CN4 Analog and digital input terminals CN5 External battery pack terminals 4.1 Dipswitches and Jumpers setting : Factory default : SW1 1= off, SW1 2= off J1 = open, J2 = open, J3 = 23 close, J5 = open, J6 =close
14 5. TECHNICAL CHARACTERISTICS OF ELBS10 Application: gas / liquids Ambient temperature: 20 / + 70 C Working pressure: from 0 to 300 bar Pressure drop rate: from 0.2 to 20 bar / min Pressure sampling rate: from 1 to 99 sec. adjustable Data memory capacity: 1000 events Valve stroke delay: from 0 to 999 sec. Valve stroke duration: from 0 to 255 sec. High/low pressure setpoints from 0 to 300 bar. Battery voltage: 4x3.6V,size D, Lithium Thionyl Chloride. Pressure transmitter supply: 12V / 20 ma Solenoid valve control output: 24V / 100mA PC connection: via optocoupled RS 232 serial port. 6. ELECTRICAL CONNECTIONS OF ELBS10 The following figure shows the terminals of the ELBS10 electronic cards ELBS10 cards enclosure Alarm relay: 1/2 closed (1/3 open) in case of no alarm Solenoid Valve Control Armed relay: 4/5 closed (4/6 open) when Armed Solenoid valve control relay: 1/2 closed (1/3 open) when controlling Warning relay: 4/5 closed (4/6 open) in case of no Warning Solenoid valve control +24 Vcc/100mA CN1 CN2 DISPLAY BOARD RS CN3 CN4 MOTHER BOARD CN ELBS10 CARDS V common + V battery A Line Monitor +Line Monitor + V battery B 020 ma pressure signal 0 V +12 V Diode D1 1N5821 Local operator interface controls +8 V 0 V EARTH Solenoid valve coil Pressure transmitter Optional external power supply (8V ) with external diode D
15 The following figure shows the layout of the line break protection system Battery Pack 2x3.6V Lithium Thionyl Chloride, size D battery pack A supply 7.2V + battery pack B supply 7.2V + + Alarm contacts Pushbuttons Alarm relay Local operator interface Display Warning relay ELBS10 RS 232 connector Warning contacts Voltage supply Solenoid valve control Solenoid control relay Armed relay Pressure 12V 0V signal Armed contacts close Solenoid valve Pressure transmitter Actuator Pipeline L = min. 10 D D = pipe diameter Flow Valve Flow
16 6.1 View of Eexd Line Break Cabinet. Battery Pack Eexd enclosure Line Break Eexd enclosure LCD display of local operator interface Pushbuttons of local operator interface Downstream pressure intake ELBS10 pressure transducer
17 7. MENU OF THE LOCAL OPERATOR INTERFACE OF ELBS10. Display message Push to wakeup the display functions Step 0 P XXX.X BAR SAMPLING NO ALA/WARN see: alarm list C XX.XX V XX.X OP.MODE ACQ+VC Step 1 SOLENOID CONTROL ARMED ENTER PASSWORD XXXX VALVE OPEN? NO YES Step 2 EVENTS XXX MEMORY XX % N XXX T hh:mm:ss E X.D ddmmyyyy S XX DT XXXX P XX.X BAR Step 3 PARAMETERS READ / WRITE CHANGE VALUES? YES ENTER PASSWORD XXXX NO See parameters list Step 4 TEST See test parameters list P=XXX.X BAR NORMAL TEST Step 5 SPECIAL FUNCTIONS LANGUAGE: XXXXXXXXXXXX Language list PASSWORD CHANGE ENTER PRESENT PASSWORD XXXX ENTER NEW PASSWORD XXXX MEMORY MANAGEMENT ENTER PASSWORD XXXX CLEAR? Push simultaneously to return at the step 0 of the menu
18 7.1. Parameters and setpoints list DISPLAY MESSAGE HIGH PRESSURE XXX.X BAR LOW PRESSURE XXX.X BAR VALVE CONTROL BAR / MIN XX.X ACQUISITION BAR / MIN. XX.X PRESSURE INC. XX.X BAR PRESSURE DEC. XX.X BAR DELAY XXX SEC DURATION XX SEC SAMPLING RATE XXX SEC TIME hh:mm:ss DATE ddmmyyyy OPERATING MODE ACQ + VC SLOW SAMPLING RATE XXX SEC. MEMORY MODE CIRCULAR ALARM 90 % ON OFF VOLTAGE X.X V ON VOLTAGE X.X V TRASMITTER 0mA XXX BAR TRASMITTER 20mA XXX BAR LAST MAINT. ddmmyyyy NEXT MAINT. ddmmyyyy SERIAL NUMBER XXXXXXXXXXXX DESCRIPTION ENG. RANGE ACTUAL UNIT VALUE High pressure limit ( EVENT 4 ) integer Low pressure limit ( EVENT 2 ) integer Pressure drop rate in VC valve control mode and in ACQ+VC mode ( EVENT 6 ) bar/min Pressure drop rate in ACQ acquisition mode bar/min ( EVENT 5 )see par.2 Pressure change in increase ( EVENT 3 ) bar Pressure change in decrease ( EVENT 1 ) bar Delay of the valve stroking sec Duration of the valve stroking sec Sampling rate sec Time hhmmss actual Date ddmm actual yyyy Operating mode: SLEEP, ACQuisition, Valve integer SLEEP,ACQ, VC Control, ACQuisition and Valve Control VC, ACQ+VC Slow sampling rate: sampling rate after sec valve stroking or in alarm status Event memory mode: circular / not circular boolean circ/not circular (note 1) circ Alarm when the event memory content boolean on/off off reaches 90% : ON / OFF Low voltage limit. Alarm when the supply V voltage fall down the above value. Off to on supply voltage. Min. voltage V needed to restore correct operation Pressure Transducer Zero bar Pressure Transducer Span bar Date of the last battery change Date of the next battery change Serial number ELBS ,,5 ddmm yyyy ddmm yyyy alphanum char max 12 char NEW VALUE Note 1. Circular = when the event memory is full the new event takes the place of the oldest (the first). The next one will take the place of the second, etc. Not circular = when the memory is full the acquisition function stops working. The clear memory control restarts the acquisition function. Valve control function remains active
19 7.2. Alarms and warnings list DISPLAY MESSAGE MEMORY ERROR MEMORY 90 % TRANSMITTER HIGH VOLTAGE LOW VOLTAGE TEMPERATURE SLEEP MAINTENANCE A W A A A W A W ALARM / WARNING RESET No error in CRC memory CLEAR memory control Transmitter signal < 20 ma Voltage value < 10 V Voltage value > "on voltage" Temperature value correct ACQ or VC operating mode Next maint. date > present date DESCRIPTION Alarm ( A )due to error in checking the CRC of the EEPROM memory Warning ( W )generated when the EEPROM memory reaches 90% of its capacity and if the relevant parameter is set to on. Alarm ( A )generated when the signal of the pressure transmitter is > 20.5 ma or the relevant A/D converter is blocked Alarm ( A )generated when the voltage supply is > 10 V Alarm ( A )generated when the supply voltage is lower than the relevant configured parameter( OFF VOLTAGE ) Warning ( W )generated when the temperature is higher than +75 C or lower than 20 C Alarm ( A )generated when " SLEEP " operating mode selected. Warning ( W )generated if present date is > than the configured " NEXT MAINT.ddmmyyyy " (see parameters and setpoint list) 7.3. Parameters list of the test function DISPLAY MESSAGE PRESSURE DROP XX.X BAR / MIN START TEST DESCRIPTION Pressure drop value used by the test function. START of the test function Note 1: the test function causes the valve control also if the data acquisition mode is configured. The test execution can be interrupted by pushing 'ENTER' ( or by pushing simultaneously 'DEC' and 'INC' ) of the local operator interface.see also par. 3.3 and how to launch test function
20 7.4. Instructions for using the local operator interface, ' ', 'ENTER' pushbutton,' ', 'DEC' pushbutton,' ', 'INC' pushbutton How to move in the ELBS11 menu If the display is off, push ' ' to wakeup the display control and put it in the step 0 of the menu. The display shows the following information: pressure value, ELBS11 status (normal, alarm, event, sampling), valve control output status ( = armed, fl = not armed, fi = valve control in progress ) If the display shows the message Sleep, see the procedure relevant to sleep status. Use ' ', ' ' to move into the menu and ' ' to select the variable to be visualised and the operation to be done. Push simultaneously ' ', ' ' to return at the step 0 of the menu The display automatically switches off one minute later the end of the last operation with the ELBS11 local operator interface How to change a setpoint or parameter If the display is off, push ' ' to wakeup the display control. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ', ' '. The display shows the message Parameters read / write ( step 3 ) Push ' '. The display shows the message Change values?. Push ' '. The display shows the message Enter password. Enter the password (see the relevant procedure) and then push ' ' or ' ' to select the parameter or setpoint to be changed. The display shows the present value. Push ' ' and then push ' ' or ' ' until the display shows the desired new value. Push ' ' to enter the new value. The display will show the new present value. Push ' ' or ' ' to select another parameter or setpoint to be changed and repeat the procedure. Push simultaneously ' ', ' ' to return at the step 0 of the menu How to arm/disarm the solenoid valve control If the display is off, push ' ' to wakeup the display control. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu. The solenoid valve control output status is indicated on the display by the following symbol: = armed, fl = not armed, fi = valve control in progress Check the operating mode (see: parameters and setpoints list). If the operating mode is ACQ or SLEEP (acquisition, or sleep), the solenoid valve control can not be armed or disarmed. Check the alarm / warning list. If there is an alarm or a warning eliminate the cause of the malfunction. Push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' '. The display shows the status of the solenoid valve control parameter ( step 1 ). The display message is : solenoid control armed/not armed. Push ' '. The display shows the message Enter password. Enter the password (see the relevant procedure). The ELBS10 ask you if the pipeline valve is open. If yes, push ' ' to arm the valve control.if not, or if you want to disarm the solenoid valve control push ' ' and the solenoid valve control will be disarmed. The display shows the status of the parameter. Push simultaneously ' ', ' ' to return at the step 0 of the menu How to enter the password If the display shows the message Enter password, enter the default password 0000 or the secret password (if the default one was changed) as follows: Push ' ' or ' ' to select the first character Push ' ' to enter the value Repeat the procedure to enter the second, third, and fourth characters If the password is correct the display shows the message Password correct for 2 seconds and then the display shows the message relevant to the next step of the menu. If the password is wrong the display shows the message Password wrong for 2 seconds and then the display shows the message relevant to the previous step of the menu
21 How to see the alarm/warning list If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ' and then ' ', ' ' to see the list of the present alarms ( A ) and warnings ( W ) Push simultaneously ' ', ' ' to return at the step 0 of the menu How to select a new language If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ', ' ', ' ', ' '. The display shows the message Special functions ( step 5 ) Push ' '. The display shows the present language. Push ' ' and then ' ' or ' ' to select the new language. Push ' ' to enter the new selected value. Push simultaneously ' ', ' ' to return at the step 0 of the menu How to clear the event data memory If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ', ' ', ' ', ' '. The display shows the message Special functions ( step 5 ) Push ' ' and then ' ', ' '. The display shows the following message Memory management. Push ' '. The display shows the following message Enter password. Enter the password (see the relevant procedure) Push ' '. The display shows the following message Clear?. Push ' ' to clear the event data memory. Push simultaneously ' ', ' ' to return at the step 0 of the menu How to enter a new password The ELBS11 is supplied with the default password 0000 to protect the configured data from undesired changes. It is possible to change the default password in a different secret password of 4 alphanumerical characters. When the new password is entered, the default password is not longer valid, so DO NOT FORGET THE NEW SECRET PASSWORD. Proceed as follows: If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ', ' ', ' ', ' '. The display shows the message Special functions ( step 5 ) Push ' ' and then ' '. The display shows the message Password change. Push ' ' and then enter the default password 0000 or the secret password (if the default one was changed). When the display shows the message Enter new password, enter the new desired secret password as follows: 1. Push ' ' or ' ' to select the first character 2. Push ' ' to enter the value 3. Repeat the procedure to enter the second, third, and fourth characters The display will show the message password changed for 2 seconds Push simultaneously ' ', ' ' to return at the step 0 of the menu How to read a setpoint or parameter If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ', ' '. The display shows the message Parameters read / write ( step 3 ) Push ' '. The display shows the message Change values?. Push ' ' and then push ' ' or ' ' to move into the parameters and setpoints list. The display shows the present value of the setpoints and of the parameters. Push simultaneously ' ', ' ' to return at the step 0 of the menu
22 How to leave the SLEEP status If the display is off, push ' ' to wakeup the display control. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu. The display shows the message SLEEP Push ' ', ' ', ' '. The display shows the message Parameters read / write ( step 3 ) Push ' '. The display shows the message Change values?. Push ' '. The display shows the message Enter password. Enter the password (see the relevant procedure) and then push ' ' to select the parameter operating mode. The display shows the message operating mode sleep. Push ' ' and then push ' ' or ' ' until the display shows the desired operating mode. Push ' ' to enter the new value. The display will show the new present value. Push simultaneously ' ', ' ' to return at the step 0 of the menu How to enter the SLEEP status If the display is off, push ' ' to wakeup the display control. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu. The display shows the message SLEEP Push ' ', ' ', ' '. The display shows the message Parameters read / write ( step 3 ) Push ' '. The display shows the message Change values?. Push ' ' The display shows the message Enter password. Enter the password (see the relevant procedure) and then push ' ' to select the parameter operating mode. The display shows the present operating mode. Push ' ' and then push ' ' or ' ' until the display shows the message operating mode sleep. Push ' ' to enter the new value. The display will show the new present value. Push simultaneously ' ', ' ' to return at the step 0 of the menu How to launch the test function How to see the event data memory content If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ' to enter in the step 2 of the menu. The display shows the number of events stored in the memory. Push ' ' and then ' ', ' ' to see number (N), type (E), time (T), and date (D) of each event in the memory. Push ' ' to select the event and then push ' ' or ' ' to see the values of the data relevant to the 64 sample of the event. The display shows the following data: 1) number ( S ) of the pressure sample in the event 2) time ( DT ) of the pressure sample before or later the time of the event ( time T ) 3) value ( P ) of the pressure sample Push simultaneously ' ', ' ' to return at the step 0 of the menu If the display is off, push ' ' to wakeup the display function. If the display is on, push simultaneously ' ', ' ' to return at the step 0 of the menu Push ' ', ' ', ' ', ' ' to enter in the step 4 of the menu. The display shows the message test Push ' ' to perform test. the display shows the message Enter password. Enter the password (see the relevant procedure). the display show "pressure drop 3.0 bar/min" Push ' ' or ' ' to select the desired pressure drop speed for the test. Push ' ' to enter the value. the display show "START TEST?". Push ' ' to start the test or ' ' to abort the test function. When the test operation starts, the display show the simulated pressure and the ELBS10 status. The test function force the valve control (VC) mode.the simulated pressure will start to the high pressure limit and goes to 0 bar. The test function can be stopped by the ' ' push button. If the ELBS10 will close the pipeline valve the event will not be recorded. Push simultaneously ' ', ' ' to return at the step 0 of the menu
23 8. LIBVIEW.exe PROGRAM The communication between ELBS10, line break detection module, and PC is done via RS232 digital serial line. The program LIBVIEW.exe, to be installed on the PC, runs under WINDOWS 95 operating system is supplied as an option. The program LIBVIEW.exe allows the following : to visualise the event data memory content, present pressure value, date, voltage supply value, setpoints and all internal parameters to configure the setpoints and the internal parameters The following diagram shows the electrical diagram of the cable for connecting the PC to ELBS10. DB9 Female DB9 Male SHELL 2 5 SHELL to female 9poles connector on ELBS10 line break detection module cable length max. 6.0 m. to RS 232 9poles male connector of PC 8.1. To install the LIBVIEW.exe program on the PC Insert the diskette in the floppy disk driver A and then proceed as follows: Click on START. Click on RUN. Digit the name of the program: A:\Setup.exe. Click on OK and then follow the instructions on the screen of the computer Double click on the icon LIBVIEW to open the program Alternatively: Create a new directory in C: Copy Libview.exe in the new directory Run the program Libview.exe Click on Option to select the communication port
24 8.2. To configure the ELBS10 Line Break Detection Module Click on LIBVIEW icon Click on configuration Click on OBJECT LIST Click on the to see the variable list Click on the variable name that will be configured Click on READ to see the present value Click on the value and introduce the new one Click on WRITE Click on READ to check that the new value has been entered Operating mode Sampling rate Pressure drop rate (in valve control) High pressure Low pressure Pressure increase (in acquisition mode) READ WRITE OBJECT NAME: sampling rate RANGE: 0100 E. U.: sec. VALUE: 8 Cancel
25 8.3. To visualise the event data of the ELBS10 module Click on LIBVIEW icon Click on configuration Click on events data Click on the to see the events list Click on the event number. Click on READ to see the event data on the screen Click on CLEAR ALL EVENTS to clear the event memory of the ELBS10 READ CLEAR ALL EVENTS Cancel EVENTS LIST: # 1 # 2 # m # n EVENT DATA #m: time date number of samples: sampling rate time between samples type of event battery voltage sample sample sample 1 22 sample 0 23 sample +1 sample +2 sample +3 sample to exit: Click on Cancel Click on File Click on Exit
26 To save the single event on disk : Click on File Click on save 8.4. To save all the events data of the ELBS10 module Click on configuration Click on events data To save all the events on disk : Click on File Click on Download 8.5. To visualise the ELBS10 status Click on LIBVIEW icon Click on configuration Click on read I / O Click on X Click on File Click on Exit ELBS10 status sampling, normal, sleep valve control on acquisition on event in progress event recorded ESD completed Input / Output Valve control relay SOV control Armed/not Arm. relay Alarm relay Warning relay Line pressure Battery voltage Ambient temperature Warnings Event memory 90% Temperature over range Battery maintenance FIFO status Events low pressure high pressure delta pressure increase delta pressure decrease pressure drop for data acquisition pressure drop for valve control loss of external power supply Alarms EEPROM memory failure pressure transmitter failure high voltage low voltage
27 9. Main Components of Eexd Line Break cabinet Some internal views of Eexd cabinet : Line Break Card Battery pack
28 10. TYPICAL ELECTRICAL DIAGRAM
29 11. TYPICAL OPERATING DIAGRAM
30 12. START UP INSTRUCTIONS WARNING: if the actuator is located in hazardous area a hot permit must be obtained before opening the explosion proof enclosures. Moreover the area must be cleaned from explosive mixture since batteries handling could generate electrical spark and cause explosion. See the operating diagram and the wiring diagram. The 4 batteries are supplied separately, so the first of all it needs to install the batteries in the actuator enclosure. Proceed as follows: open the actuator battery pack enclosure and put the batteries inside the battery holders. Be careful at the battery polarity, since the reversed polarity causes fast batteries discharge. See the drawing, in battery maintenance paragraph, to correctly install the batteries. by a multimeter measure the voltage on the terminals + and. The voltage should be about 7.2Volt. press the pushbutton ' ' to wakeup the display. enter the desired operating mode, VC valve control, ACQ data acquisition, or VC+ACQ valve control + data acquisition ( see: How to leave the SLEEP status procedure ) and then enter the desired values of setpoints and parameters (see: Parameters and setpoint list and relevant procedures). The default password is enter present TIME, and DATE. Enter LAST MAINT = present date enter NEXT MAINT = present date + 1 year (with Lithium batteries) to set the date of the warning signal and maintenance request. use the local operator interface to check that all parameters and setpoints are in the correct range. use the local operator interface to check the pressure value, the alarm / warning list, the voltage and temperature values (see: step 0 of the menu ). If there is any alarm or warning, use the display messages to findout the cause of the malfunction. if everything is correct and valve control operating mode is configured, launch the test function (see relevant procedure). At the end of the test open the valve. BE CAREFUL, the test function can causes the actuator to close the valve, so do not perform the test function if valve closure is not allowed. if the valve is open and if valve control operating mode is selected, arm the solenoid valve control output (see: How to arm the solenoid valve control procedure ). Wait until the display switches off
31 13. TO RESTORE THE VALVE CONTROL FUNCTION In valve control operating mode (VC) and after a solenoid valve control due to EVENTS 2, 4, or 6, the ELBS10 close the pipeline valve and enters in the slow sampling state and the pipeline survey functions are inhibited. To reopen the valve and restore the survey functions it needs to rearm the solenoid valve control as follows: rearm the valve 681 (pneumatic pilot / hand return valve) see operating diagram open the pipeline valve see Instructions for using the local operator interface: how to arm the solenoid valve control. 14. BATTERY MAINTENANCE To change battery pack proceed as follows: use the local operator interface to put the ELBS 10 in solenoid valve control output not armed (see: How to arm the solenoid valve control output) and then in SLEEP mode (see: How to enter the SLEEP status). open the actuator battery pack enclosure. put the new battery inside the battery holders. Be careful at the battery polarity, since the reversed polarity causes fast batteries discharge. See the below drawing to correctly install the batteries. WARNING: if the actuator is located in hazardous area a hot permit must be obtained before opening the explosion proof enclosures. Moreover the area must be cleaned from explosive mixture since batteries handling could generate electrical spark and cause explosion. by a multimeter measure the voltage on the terminals + and. The voltage should be about 7.2Volt. see STARTUP INSTRUCTIONS to restart with line survey operations. +VB1: + of multimeter +VB2: + of multimeter 0V : of multimeter Battery pack: 4 x 3.6 V Lithium Thionyl Chloride batteries, D size, high drain capability (for example type SAFT LSH 20) 0V :To CN5,6 of ELBS10 card +VB1: To CN5,5 of ELBS10 card +VB2: To CN5,2 of ELBS10 card
32 BIFFI ITALIA s.r.l. DIREZIONE, UFFICIO COMMERCIALE,,STABILIMENTO HEADQUARTER, SALES DEPARTMENT, FACTORY Fiorenzuola d'arda (Piacenza) Italy Tel. (0523) Telex Bifior.I Telecopier (0523)
ECU1000 ELECTRONIC CONTROL UNIT
An advanced electronic system capable to be integrated in a SMART Electro Hydraulic System for heavy modulating, stepping, PST, diagnostic and ESD/BDV actions FEATURES GENERAL APPLICATION is a control
More informationKEMKRAFT ENGINEERING, INC. MODEL KEI-234 STEERING WHEEL TORQUE/INCLINOMETER TESTER
INSTRUCTION MANUAL STEERING WHEEL TORQUE/ INCLINOMETER SYSTEM MODEL KEI-234 W / INTERNAL BARCODE SCANNER REVISION DATE: 17-AUG-1999 1 GENERAL DESCRIPTION... 3 INSTALLATION... 3 SYSTEM SETUP... 4 To change
More informationBRAKE TESTER DECELEROMETER
OC3010_GBM_21009 BRAKE TESTER DECELEROMETER OWNER S MANUAL Version 8.++ ORBIT CONTROLS AG Zürcherstrasse 137 CH-8952 Schlieren/ZH Tel: + 41 44 730 2753 Fax: + 41 44 730 2783 info@orbitcontrols.ch www.orbitcontrols.ch
More informationECONOMISER SERIES E2T USER MANUAL
TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014
More informationCLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16
User Manual CLA-VAL Europe www.cla-val.ch cla-val@cla-val.ch 1 - LIN072UE - 04/16 Table of Contents 1 Introduction... 3 1.1 Precautions Before Starting... 3 1.2 Troubleshooting... 3 1.3 General Disclaimer...
More informationRESISTIVE LOAD XP300C
RESISTIVE LOAD XP300C Via della Torricella, 22 50012 ANTELLA (FI) - Italy Tel. +39 055 620508 Fax +39 055 620338 e-mail: marelita@tin.it www.marelweb.it INDEX GENERAL...3 OPERATION AND USE...3 WARNINGS...3
More informationHIGH POWER SOLENOID DRIVER 1
Elactis SA Switzerland Phone : Fax : E-mail : Web : +41 22 364 65 85 +41 22 364 65 87 info@elactis.com http://www.elactis.com HIGH POWER SOLENOID DRIVER 1 ADRV1012K 1 This datasheet is a preliminary description.
More informationKEMKRAFT ENGINEERING, INC. MODEL KEI-434 STEERING WHEEL TORQUE TESTER
INSTRUCTIONAL MANUAL STEERING WHEEL TORQUE SYSTEM MODEL KEI-434 REVISION DATE: 14-JANUARY-1998 47650 CLIPPER DR. PLYMOUTH MICHIGAN 48170 (313)414-6500 1 GENERAL DESCRIPTION The KEMKRAFT Model KEI-434 Steering
More informationService Manual BLACK DIAMOND SERVICE MANUAL. V.160 November
BLACK DIAMOND SERVICE MANUAL V.160 November 2011 www.montrealchargeur.com www.battelec.ca www.doctorfleet.com Page 1/30 1. SAFETY PRECAUTIONS 1 Before to start using the Black Diamond Charger, read these
More informationINSTALLATION AND OPERATION INSTRUCTION
INSTALLATION AND OPERATION INSTRUCTION ATi Max 2-1/2-6, 65-150mm Install the ATi Max valve either in the supply or return pipework for the unit. It is recommended that a strainer be installed prior to
More informationInstallation Instructions & Users Manual
Installation Instructions & Users Manual UTILITY/ BUILDING INPUT 120 VAC ( OPTION) 15-20A N L CONTROL BOARD G SECURITY LIGHTING POWER SUPPLY (OPTION) CHARGER- POWER SUPPLY ASSBY XFMR (OPTION) CBM MODEL
More informationDIESEL Engine Fire Pump Controllers Features
1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status
More informationREVISION HISTORY REVISION HISTORY
FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim
More informationOPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets
Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599
More informationMODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM
MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...
More informationCURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING
AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital
More informationBe2K-Plus AMF panel control wiring --
Be2K-Plus OEM's Manual V200 - August - 014 page 1 Be2K-Plus AMF panel control wiring -- Consult Section 17.0 for software upgrades & revisions The information in this document may be subject to change
More informationTECHNICAL MANUAL FOR ELECTRONIC SPEEDOMETER STR-RIEJU MATRIX 2
FOR ELECTRONIC SPEEDOMETER STR-RIEJU MATRIX 2 Rel. 4.0 3.0 2.0 1.0 0.0 Release Disposal Aim Modifications on chapter 8 and 13 Deleted automatic and manual test procedure General modifications Added par.
More informationSection 55 Chapter 6
Section 55 Chapter 6 REMOTE HYDRAULICS CONTROLLER Calibration and Fault Codes 6-12880NH TABLE OF CONTENTS REMOTE HYDRAULICS CONTROLLER CALIBRATION... 55-5 Requirements For Calibration... 55-5 Aux Set Main
More informationAutomatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list
OPERATOR'S MANUAL Automatic Genset Controller, AGC-4 Display readings Push-button functions handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com
More informationObserve all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary
More informationMB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR
MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside
More informationLingenfelter NCC-002 Nitrous Control Center Quick Setup Guide
Introduction: Lingenfelter NCC-002 Nitrous Control Center Quick Setup Guide The NCC-002 is capable of controlling two stages of progressive nitrous and fuel. If the NCC-002 is configured only for nitrous,
More informationINSTALLATION GUIDE Table of Contents
CT-3100 Automatic transmission remote engine starter systems. What s included..2 INSTALLATION GUIDE Table of Contents Door lock toggle mode..... 4 Notice...2 Installation points to remember. 2 Features..2
More informationOPERATING INSTRUCTIONS ECON-M
OPERATING INSTRUCTIONS ECON-M INDEX 1.0 Introduction 2.0 Salient features, Protection & Supervision 3.0 Display/ Front Panel 4.0 Switches Description 5.0 LED Annunciations Description 6.0 Lamp Test 7.0
More informationGENERAL INFORMATION MECHANICAL INSTALLATION PRESSURE INDEPENDENT VALVES 2-1/2"-10" MVP INSTALLATION & OPERATION INSTRUCTIONS UNION CONNECTIONS
GENERAL INFORMATION INSTALLATION & OPERATION INSTRUCTIONS 1. Clean the lines upstream of valve particles larger than 1/16" diameter (welding slag, pipe scale and other contaminants). Griswold Controls
More informationCurveMaker DFS v2.0 Dyna FS Ignition Programming Software
CurveMaker DFS v2.0 Dyna FS Ignition Programming Software Contents Dynatek 164 S. Valencia St. Glendora, CA 91741 phone (626)963-1669 fax (626)963-7399 page 1) Installation 1 2) Overview 1 3) Introduction
More informationEnergy Division
Energy Division http://energy.tycoelectronics.com Installation and Operating Manual GEN-TRANS Automatic Generator Transfer Switch Controller with Metering Tyco Electronics UK Limited Crompton Instruments
More informationLAMBDA SENSOR CONTROLLER
LAMBDA SENSOR CONTROLLER INSTALLATION & PROGRAMMING MANUAL version : V1.77 -V1.79 Manufacturer: AC Spółka Akcyjna. 15-182 Białystok, ul. 27 Lipca 64, Poland tel. +48 85 7438148, fax +48 85 653 8649 www.ac.com.pl,
More informationStarting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F
Starting System DS-102 Series 200 Elmatik AS P.O.Box 309 NO-3471, Slemmestad T - +47 31 28 37 83 F - +47 31 28 37 93 www.elmatik.no post@elmatik.no CONTENT 1. INTRODUCTION 3 2. TECHNICAL SPECIFICATIONS
More informationEFS EFS 2000 Electric failsafe actuators
EFS 2000 Electric failsafe actuators EFS 2000 Electric failsafe actuators A world of experience Biffi has been a leading manufacturer of valve actuators for more than 50 years. As one of the few manufacturers
More informationFuel Level FL1. FL1 - User s manual. Rev Revision#2.0, 28/11/2014 For firmware version 1.2
Fuel Level FL1 Revision#2.0, 28/11/2014 For firmware version 1.2 FL1 - User s manual Page intentionally left blank SECTIONS MECHANICAL INSTALLATION ELECTRICAL INSTALLATION OPERATING INSTRUCTIONS INSTRUMENT
More informationMEGA WAY LCD PAGER ALARM WITH REMOTE ENGINE STARTER. Operation Manual MEGATRONIX CHATSWORTH, CA U.S.A. MEGA 2700 OPERATE 1
MEGA 2700 2-WAY LCD PAGER ALARM WITH REMOTE ENGINE STARTER Operation Manual MEGATRONIX CHATSWORTH, CA U.S.A. MEGA 2700 OPERATE 1 2 WARNINGS: As with any product that performs automatic functions, there
More informationBe-K3 OEM s Manual --
Be-K3 OEM's Manual V200 - July - 010 page 1 Be-K3 OEM s Manual -- Consult Section 17.0 for software upgrades & revisions The information in this document may be subject to change without notice. No part
More informationMICROPROCESSOR BASED CONTROLLER
MICROPROCESSOR BASED CONTROLLER Electronic Controller for Bus HVAC Front Box Units FrontAIRE II SERVICE MANUAL TK 53337-3-MM (Rev. 0, 09/06) 2006 THERMO KING Table of contents 1. General Information...
More informationDKG-109 AUTOMATIC MAINS FAILURE UNIT
Tel: +90-216-466 84 60 Fax: +90-216 364 65 65 datakom@datakom.com.tr http://www.datakom.com.tr DKG-109 AUTOMATIC MAINS FAILURE UNIT FEATURES Automatic mains failure Engine control Generator protection
More informationWarnings and Cautions. Precision Flow Insertion Mass Flow Meter. Instruction Manual BULLETIN F-41-PFS FR# R
Table of Contents Warnings and Cautions Warning! Agency approval for hazardous location installations varies between flow meter models. Consult the factory for specific flow meter approvals before any
More informationMEGA WAY LCD 4-CHANNEL CAR ALARM SECURITY SYSTEM. Operation Manual MEGATRONIX CALIFORNIA, USA MEGA 2500 OPERATE 1
MEGA 2500 2-WAY LCD 4-CHANNEL CAR ALARM SECURITY SYSTEM Operation Manual MEGATRONIX CALIFORNIA, USA MEGA 2500 OPERATE 1 OPERATION: A. TRANSMITTER OPERATION: Transmitter Button System Function Remark Lock
More informationEZ SDI-1 TM. Installation and Operating Manual. Distributed By:
EZ SDI-1 TM Installation and Operating Manual Manual Revisions i EZ SDI-1 TM Automated Silt Density Index Test System Installation and Operating Manual Copyright 2014 NOTICE This manual is protected by
More informationFlight Systems. Replacement for KASSEC DESCRIPTION
DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most
More informationUser Manual Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...
More informationTe 803 Electronic Controller. Service, Operation & Technical Information Manual
Te 803 Electronic Controller Service, Operation & Technical Information Manual WARNING! Technical descriptions and data given in this document are accurate, to the best of our knowledge, but can be subject
More informationApplication Engineering
Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the
More informationREV F2.0. User's Manual. Hydraulic ABS (HABS) Hydraulic Power Brake (HPB) Page 1 of 28
REV F2.0 User's Manual Hydraulic ABS (HABS) Hydraulic Power Brake (HPB) Page 1 of 28 Table of Contents INTRODUCTION...4 Starting TOOLBOX Software... 5 MAIN MENU...6 System Setup... 6 Language... 7 Select
More informationApplication Engineering
Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor
More informationFactory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide
Factory Packaged Controls OE377-26-00058 (AAON Part No. V12090) MODGAS-X Controller Table of Contents GENERAL INFORMATION... 3 Overview...3 Features...3 INSTALLATION & WIRING... 4 Supply Air Temperature
More informationGE Energy. The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline
GE Energy The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline DNGP with Modbus Communication protocol features ZERO Bleed * technology and control logic designed for natural gas control valves
More informationEAOM-10.2 AUTOMATIC TRANSFER SWITCH & START UNIT FOR DIESEL GENERATORS
AUTOMATIC TRANSFER SWITCH & START UNIT FOR DIESEL GENERATORS Designed for diesel generators Long life membrane front key pad EEPROM internal memory 1 GENERAL INFORMATION EAOM-102 Automatic Transfer Unit
More informationDigital Diesel Control Remote control panel for GENVERTER GV4 and GV7i
OPERATING MANUAL Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i Art. nr. 40200801 WHISPER POWER BV ENGLISH: PAGE 1 Kelvinlaan 82 9207 JB Drachten NEDERLANDS: PAGINA 41 Netherlands
More informationCurveMaker HD v1.0 2Ki Programmable Ignition programming software
Contents CurveMaker HD v1.0 2Ki Programmable Ignition programming software Dynatek 164 S. Valencia St. Glendora, CA 91741 phone (626)963-1669 fax (626)963-7399 page 1) Installation 1 2) Overview 1 3) Programming
More informationINSTALLATION GUIDE. FCC ID NOTICE
REV.5 RS. ADVANCED REMOTE STARTER INSTALLATION GUIDE www.security.soundstream.com FCC ID NOTICE This device complies with Part 5 of the FCC rules. Operation is subject to the following conditions:. This
More informationP445 Series Electronic Lube Oil Control
FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with
More informationPF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016
PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication
More informationUSERS MANUAL MCD REMOTE OPERATOR
USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3
More informationHSC940 Genset Controller CONTENTS 1 OVERVIEW PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION KEY FUNCTIONS...
CONTENTS 1 OVERVIEW... 4 2 PERFORMANCE AND CHARACTERISTICS... 5 3 SPECIFICATION... 7 4 OPERATION... 8 4.1 KEY FUNCTIONS... 8 4.2 INDICATOR LIGHT... 9 4.3 AUTO START/STOP OPERATION... 10 4.4 MANUAL START/STOP
More informationIdle Timer Controller - A-ITC620-A Chevrolet Express/GMC Savana
Introduction An ISO 9001:2015 Registered Company Idle Timer Controller - A-ITC620-A1 2009-2019 Chevrolet Express/GMC Savana Contact InterMotive for additional vehicle applications The A-ITC620-A1 is an
More informationSPREADER SYSTEM. Proportional three function. 1. Features and Specifications. User Manual 12 INPUTS 12 OUTPUTS CONNECTIVITY MAIN FEATURES
User Manual SPREADER SYSTEM Proportional three function 12 INPUTS 3 interrupt digital inputs. 3 digital inputs for engine control (alternator, accelerator, oil alarm). 1 digital input for tachometer (squared,
More informationTe 804 Electronic Controller. Service, Operation & Technical Information Manual
Te 804 Electronic Controller Service, Operation & Technical Information Manual WARNING! Technical descriptions and data given in this document are accurate, to the best of our knowledge, but can be subject
More informationSmartON / SmartON+ Installation and Use Manual
SmartON / SmartON+ Installation and Use Manual Rev. Date Ver. Ver. Notes document document SmartON SmartViewII 1.0 06/04/2007 3.08 2.30 Pre-release 1.01 10/04/2007 3.08 2.30 Release 1.02 04/10/2007 3.09
More informationA U T O M A T I C T R A N S M I S S I O N M U L T I - C H A N N E L T W O - W A Y L C D R E M O T E S T A R T E R AS-2510 TW.
A U T O M A T I C T R A N S M I S S I O N M U L T I - C H A N N E L T W O - W A Y L C D R E M O T E S T A R T E R S Y S T E M AS-2510 TW User Guide Transmitter Part Number and Module Serial Number...2
More information2 WAY REMOTE STARTER & ALARM SYSTEM INSTALLATION GUIDE FCC ID NOTICE
REV. ARS. WAY REMOTE STARTER & ALARM SYSTEM INSTALLATION GUIDE FCC ID NOTICE This device complies with Part 5 of the FCC rules. Operation is subject to the following conditions:. This device may not cause
More informationST Wiring diagram. Product description. Temperature controller. Order number
ST7-31.3 Temperature controller Order number 9154.12 Wiring diagram Product description The switching exits of the thermostatic controller can be programmed as -two-point controller with alarm -three-point
More informationTOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES
TOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES Touchscreen PLS and Graphical Operator Interface in One Unit Five Screen Sizes Available: 5" Color, 6" Monochrome, 8" Color, 9" Monochrome
More informationTWO-WAY LCD AUTOMATIC TRANSMISSION REMOTE STARTER. User Guide
TWO-WAY LCD AUTOMATIC TRANSMISSION REMOTE STARTER User Guide A note concerning the battery inside the transmitter: Depending on your usage of the transmitter, the battery can last anywhere between 3 to
More informationEZECU - EzFi Starter ECU Standalone 3D Programmable Fuel Injection Computer for BOSCH Compliant EFI Systems
EZECU - EzFi Starter ECU Standalone 3D Programmable Fuel Injection Computer for BOSCH Compliant EFI Systems User s Manual January, 2012 Version 2.00 Copyright Copyright IC Leader Technology Corporation,
More informationHGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL
HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951/67992952
More informationINDEX 1 Introduction 2- Software installation 3 Open the program 4 General - F2 5 Configuration - F3 6 - Calibration - F5 7 Model - F6 8 - Map - F7
SET UP MANUAL INDEX 1 Introduction 1.1 Features of the Software 2- Software installation 3 Open the program 3.1 Language 3.2 Connection 4 General - F2 4.1 The sub-folder Error visualization 5 Configuration
More informationHGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL
HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL SMARTGEN ELECTRONICS Smartgen Electronic Equipment Co., Ltd No.12 Dongqing Street Zhengzhou Henan Province P.R.China Tel : (0086)-371-67992951
More informationOverview. References TEST SPECIFICATION FORT WORTH, TEXAS TROTTER CONTROLS REPORT X TS-0005 A MODEL ORDER TITLE BY CHK D. Tests
Rev A, 5/26/2009 1 26 Overview This document describes the use of the Maintenance System. This test is a built in diagnostic feature of the GEN II System and provides maintenance personnel with a diagnostic
More informationVC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL
1. INTRODUCTION VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down DC-DC Converter has a digitally adjustable output in 0.2V increments. This
More informationCM4200 and CM1000S Starter Control Module Installation Manual
Version Final - VF CM4200 and CM1000S Starter Control Module Installation Manual This manual is for authorized CompuStar dealers. Please thoroughly review this manual before beginning installation. If
More informationRVS-DN Digital Reduced Voltage Motor Starter
RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationPowerJet Sequential Injection INDEX. 1 Introduction 1.1 Features of the Software. 2- Software installation
INDEX 1 Introduction 1.1 Features of the Software 2- Software installation 3 Open the program 3.1 Language 3.2 Connection 4 Folder General - F2. 4.1 The sub-folder Error visualization 5 Folder Configuration
More informationQuick Setup Guide for IntelliAg Model YP Air Pro
STEP 1: Pre-Programming Preparation: The Quick Guide assumes the Virtual Terminal, Master Switch, Working Set Master, Working Set Member, and all sensors have been connected and properly installed. Reference
More informationBMS24. Thanks for your purchasing the BMS24 for your vehicle.
BMS24 for 2S-24S LiPo & LiFe Low power consumption High accuracy 2.8 TFT LCD display Programmable Thanks for your purchasing the BMS24 for your vehicle. Read the ENTIRE instruction manual to become familiar
More informationEco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0
Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n 107065-01 Revision 0 May 20, 2016 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical
More informationBMS16. Thanks for your purchasing the BMS16 for your vehicle.
BMS16 BMS for 2S-16S LiPo & LiFe Low power consumption High accuracy 2.8 TFT LCD display Programmable Thanks for your purchasing the BMS16 for your vehicle. Read the ENTIRE instruction manual to become
More informationAxpert-CSS AMTECH DRIVES Axpert-CSS Amtech
The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the
More informationGRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/
GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/98800750 English (GB) English (GB) Installation and operating instructions Original installation
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A
ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE 012945A0 040906 1 MAIN FEATURES Power supply 230V~ ±10% 50Hz Backlit alphanumeric LCD display Management of 5 output
More informationSmarTire TPMS Maintenance Hand Tool. Revision User Manual
SmarTire TPMS Maintenance Hand Tool Revision 1.04 User Manual Page 2 Table of Contents FCC Compliance Label... 4 User Interface Illustration... 4 Introduction... 5 Testing Tire Sensors... 5 Main Menu...
More informationIssue 2.0 December EPAS Midi User Manual EPAS35
Issue 2.0 December 2017 EPAS Midi EPAS35 CONTENTS 1 Introduction 4 1.1 What is EPAS Desktop Pro? 4 1.2 About This Manual 4 1.3 Typographical Conventions 5 1.4 Getting Technical Support 5 2 Getting Started
More informationQuick Setup Guide for IntelliAg Model YP40 20 Air Pro
STEP 1: Pre-Programming Preparation: The Quick Guide assumes the Virtual Terminal, Master Switch, Working Set Master, Working Set Member, and all sensors have been connected and properly installed. Reference
More informationMANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS
MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS This manual provides General Information, Installation, Operation, Maintenance and System Set-Up Information for METRON Model FD-4 Engine Driven Fire Pump Controllers.
More information4.1 Functional diagram FM100 fume hood monitor... 4 Functional description FM Interfaces Terminal diagram FM100...
2.0 LabSystem Fume hood monitors Table of contents Section Title Page 1.1 Introduction..................................... 2 2.1 Functional description............................. 2 2.1.1 Actual value
More informationHigh Quality Starter and Alarm Systems
High Quality Starter and Alarm Systems We sincerely appreciate you purchasing our vehicle starter and alarm systems. Our starter and alarm systems are produced with strict quality control and international
More informationTROUBLESHOOTING TP. Index
TROUBLESHOOTING TP Index E1 POWER CUT DETECTED... 2 E2 LOCK ERROR... 3 E3 DRAINAGE FAILURE / WATER IN TUB... 6 E4 MAXIMUM WATER LEVEL REACHED... 6 E5 FAULT WATER INLET... 6 E6 HEATING FAULT... 6 E7 MAXIMUM
More informationHGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic
HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 4 3. SPECIFICATIONS... 5 4. OPERATION... 6 5. PROTECTION...
More informationPV Charge Controller SBC-6108 / 6112 / 6120 / 6130
PV Charge Controller SBC-6108 / 6112 / 6120 / 6130 User's Manual Table of Contents Precautions and Specifications 1 1. Introduction 2 2. Control and Indicator 2 3. Installation and Indication 3 3.1 Connection
More informationInlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00
Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION
More informationQuick Setup Guide for IntelliAg Model 3PYP 12 Row Single Row Air Pro
STEP 1: Pre-Programming Preparation: Power on vehicle via ignition switch to activate Virtual Terminal (VT). Main menu will display pre-programmed default settings. If errors are detected (e.g., failed
More informationPowerView PV380-R2 Mechanical Configuration
PowerView PV380-R2 Mechanical Configuration Operations Manual *Products covered in this document comply with European Council electromagnetic compatibility directive 2004/108/EC and electrical safety directive
More informationPOLE STAR PRO. Installation and instruction manual.
POLE STAR PRO Installation and instruction manual. POLE STAR PRO is an automatic chrono and rev counter with a LED bar and Shift light which can be set, an indispensable instrument for drivers of: Go Karts
More informationGenerator Sets Controller 210. Operation Manual. Ver1.0
Generator Sets Controller 210 Operation Manual Ver1.0 Note This information could include technical inaccuracies or typographical error. Manufacturer may make improvements and/or changes in the product(s)
More informationACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery
More informationPANEL FOR CONTROL AND PROTECTION OF IRRIGATION MOTOR PUMPSET
PANEL FOR CONTROL AND PROTECTION OF IRRIGATION MOTOR PUMPSET INSTRUCTION AND USER MANUAL TYPE CEM-256 MADE TO: COMPLETE OF GSM TELEPHONE ANNUNCIATOR AND COMMAND SYSTEM Notifies up to 3 users via SMS message
More informationZoneTouch V2 Zone Control System Installation Manual
ZoneTouch V2 Zone Control System Installation Manual www.polyaire.com.au 2014 Polyaire Pty Ltd TABLE OF CONTENTS 1) Application 2 2) Features 2 3) Components 3 4) Configuration 4 5) Pre-Installation 6
More informationUser manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.
Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI
More information3200NT Timer Service Manual
Service Manual Valve Serial Number Valve Position 1-LEAd 2-LAg 3-LAg 4-LAg IMPORTANT: Fill in pertinent information on page 3 for future reference. Table of Contents Job Specifications Sheet.....................................................................
More information