VEEDER-ROOT COMPANY. Product Knowledge Session. Understanding Line Leak Detection Methods / Test Type / Certifying
|
|
- Erica Chambers
- 6 years ago
- Views:
Transcription
1 VEEDER-ROOT COMPANY Product Knowledge Session Understanding Line Leak Detection Methods / Test Type / Certifying
2 Veeder-Root / Red Jacket Line Leak Detection Methods > Pressurized Electronic Line Leak Detection (PLLD) > Mechanical Leak Detection (MLD)
3 Electronic Line Leak Detection Why use an ATG with Electronic Line Leak Detection Veeder-Root s patented measurement technology tests lines at full pump pressure for highly accurate 0.1 gph precision,0.2 gph and 3.0 gph gross testing. Wide range of piping types Compatible with TLS-350, TLS-450 and TLS-450PLUS systems Testing Frequencies - Automatic, Monthly and Repetitive for business convenience Meet s Federal, State and most local line leak detection regulations Benefits: Performs 3.0 GPH line testing that meets Federal line leak detection requirements. Can perform a 0.1 and 0.2 gph test to meet monthly and annual needs. No need for a separate annual test. Eliminates Slow Flow from thermal contraction Detects loss of pressure during dispensing activity
4 3.0 GPH PLLD Pressure Decay Test
5 0.2 and 0.1 GPH Pressure Line Testing
6 Electronic Line Leak Detection (ELLD) Applications Site Equipment STP, Piping Type and length determines application requirements for Electronic Line Leak Detection (ELLD) Line Leak Application Guide Provides detailed information for supported applications Application questions you may contact Veeder-Root Technical Support at M F 8am to 7pm
7 ATG Operability Testing Veeder-Root environmental monitoring systems installed in accordance with installation manual requirements are designed to detect and report conditions that inhibit proper operation. Veeder-Root systems self-diagnose essential components, and if a component failure is detected, will not complete and report tank and line tests. The system will issue an audible and visual alarm when a failed or disconnected sensor is detected. Veeder-Root recommends periodic operability testing on its leak detections systems at a minimum annually. Reference Manual # (H or Higher)
8 ATG Operability Testing 3 GPH testing utilizing the Red Jacket FTA 3 GPH testing utilizing the Red Jacket FX tester 3 GPH testing utilizing the KWA LS 2003 Leak Detector Tester Verification of 0.2 and 0.1 GPH Performance
9 Reports: Environmental
10 Line Leak Test Results
11 Mechanical Line Leak Detection (MLLD) Why use an Mechanical Leak Detector (MLD) Red Jacket proven reliability for 5 Plus decades Wide range of piping types Meet s Federal, State and most local line leak detection regulations Benefits: Performs 3.0 GPH line testing that meets Federal line leak detection requirements. Detects loss of pressure during dispensing activity Drawbacks Slow Flow from thermal contraction
12 Leak Detector Applications Leak Detectors can only find leaks downstream of the metering circuit in the valve Leak detectors cannot find leaks if the pump runs continuously. Three things need to happen for a test to be performed: The pump must turn off The pressure must fall The pump must start Red Jacket leak detectors must operate in clean product. Abrasives will degrade performance. Excessive additive concentrations may affect Elastomers Fuel Types. UL Cert: 100% Diesel (contains max 5% Bio per ASTM D975) 100% Gasoline Gasoline and up to 10% Ethanol Performance Guarantee All of the above and up to E-100 Red Jacket Leak detectors are designed for operation in submersible pumping systems in vehicle fueling operations Performance in centrifugal,suction pump systems cannot be guaranteed. Booster pump systems where a submersible pump boosts the pressure may present problems with pump interaction and are not recommended
13 How Do Mechanical Leak Detectors Work? When the dispenser is activated, product flows through the detector at a rate of 1.5 to 3.0 gallons per minute. This causes the pressure in the pipe to increase rapidly to 8-10 psi in the case of FX model Leak Detectors. This pressure increase actually pushes the valve in the leak detector toward a metering position, restricting the flow to a rate of 3 gallons per hour or greater. If there is a leak in the system of about 3 gal/h or greater at 10 psi, then the pressure will not increase further and the flow will remain restricted. If there is no leak or a leak of lesser magnitude, then the pressure will build slowly, though it will eventually reach full operating pressure. If the system is tight, then the pressure will increase rapidly. As the pressure goes above 10 psi, the valve is forced to it s fully open position and the system is in operation. The valve remains open until the submersible pump turns off and the pressure in the line drops below a static pressure.
14 Product Thermal Contraction Items that affect Thermal Contraction: Length of piping and pipe diameter (piping volume) Volume of freshly pumped product left cooling in the pipeline (gallons dispensed) Location of dispenser in piping system. Backfill around piping Season Burry depth of piping Daily temperature swings Time Interval from last pumping Basically a myriad of things make it hard to predict The resulting drop in pressure forces Leak Detectors to perform numerous leak tests. This, coupled with the possibility of opening times longer than the solenoid delay time, may cause increased nuisance tripping of leak detectors. The worst case scenario for thermal contraction is heavy pumping followed by a long idle time Note: a 17 F (about 10 C) temperature change will change the volume of gasoline about 1 %
15 Types of Red Jacket Leak Detector Annual Verifications The following testers may be used for any Red Jacket Leak Detectors AVO Functional Check (Apparatus to Verify Operation) Described in Red Jacket publication RJ 21 FX Tester Functional Check Described in Red Jacket publication
16 AVO Leak Detector Testing Functional Testing Ref: Red Jacket publication RJ 21 Functional Testing AVO (apparatus to Verify operation) testing is performed at the dispenser. Only section IV of RJ 21 is required to be performed for functionality test. Note that performance of the Simulated Leak Test set forth in Section IV will satisfy the minimum functionality check requirements for annual inspection of leak detectors. verified upon start-up and that testing of the leak detector be performed routinely at least annually.
17 FTA Leak Detector Testing Finite Testing Ref: Red Jacket publication RJ 20 Finite Testing allows a more consistent, accurate form of leak detector test Leak rates are measured and timed at 10 psi for more consistent results. Finite testing is required where local requirements demand 3 gph at 10 psi field tests.
18 FX Tester System- Functional Testing Snap- Tap Fittings FX Tester functional testing can be performed at the submersible pump on FX2 Model Leak Detectors. The tester may also be used to test other Leak detectors at the island by installing a Snap-Tap fitting on the test port of the impact valve for the duration of the test. Snap-Tap fittings allow fast, clean connection of the tester at the pump without shutting down product line.
19
20
General Issues of Line Leak Detection
Quality Petroleum Equipment Solutions for Over 20 Years ARM-4073 AST-4010 AST-4012 CFOSI FST-200 ISM-4080 ISM-4081 ISM-4080 MC LD-2000 LD-2000\E LD-2200 LD-2200\75 LD-3000 LD-3000\E LD-3000\FL LDT-890
More informationRelease Detection Challenges for High Throughput Facilities
Release Detection Challenges for High Throughput Facilities Typical High Throughput Fueling System Large tank size and number Large line size and number Numerous dispensers Large submersible turbine pumps
More informationNorth Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section
North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section To discover a release before a major contamination incident occurs Required
More informationContact Name: Company Name: Technician Name: Company Address: Company Phone: Company Fax: Address. Technician SSN:
Certification Exam Product Line & Leak Detector Testing COVER SHEET Contact : Company : Technician : Company Address: Company Phone: Company Fax: E-Mail Address Technician SSN: (Last 6 digits - ONLY!)
More informationUNDERGROUND STORAGE TANK (UST) INSTALLATION & MAINTENANCE
SUBJECT: FIRE DEPARTMENT INSTALLATION & MAINTENANCE Fire Department 955 Sonoma Avenue Santa Rosa, CA 95404 Phone: (707) 543-3500 Fax: (707) 543-3520 http://ci.santa-rosa.ca.us/fd/ Bulletin Number: 010
More informationUNDERGROUND STORAGE TANK INSPECTION CHECKLIST
UNDERGROUND STORAGE TANK INSPECTION CHECKLIST Facility Name: Inspector will mail copy of this inspection report to the tank owner at: General Requirements A. Site Administration 1. Submit/revise Facility
More informationSTP-MLD. Installation and Owner s Manual
The Leader in Submersible Technology Mechanical Leak Detector STP-MLD STP-MLD-D STP-MLD-E Gasoline Diesel Flexible Pipe STP-MLD STP-MLD Installation and Owner s Manual 4805 Voges Rd., P.O. Box 139 McFarland,
More informationLorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA
Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary
More informationTest Date: 3/30/2018 Order Number: Dear Regulator, Enclosed are the results of recent testing performed at the following facility:
11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 4/17/2018 STATE OF NEW HAMPSHIRE-DES HARDING SCHOFIELD Upload to website https://www2.des.state.nh.us/onestopdataproviders/deslogin.aspx
More informationANNUAL UST SYSTEM INSPECTION CHECKLIST
APPENDIX A-3: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST Page 1 ANNUAL UST SYSTEM INSPECTION CHECKLIST Facility ID# Facility Name/Address Qualified Technician Signature Date
More informationSTP-MLD+ Installation and Owner s Manual. Manual # Revision Date Changes from previous revision
STP-MLD+ Installation and Owner s Manual Manual # Revision Date Changes from previous revision 400439002 3 Sept. 2014 Changed MLD+AG description to 85% ethanol Franklin Fueling Systems 3760 Marsh Rd. Madison,
More informationFranklin Fueling Systems
Franklin Fueling Systems SOLUTIONS YOU CAN TRU S T CATALOG Table of Contents Franklin Fueling Systems has contributed many innovative product designs to the petroleum industry, including the highest performing
More informationSubmersible Pumping Systems. Product Catalog
Submersible Pumping Systems Product Catalog SUBMERSIBLE PUMPING SYSTEMS Table of Contents Submersible Pumping Systems Franklin Fueling Systems has contributed many innovative product designs to the petroleum
More information(Addendum to the March 1994 Evaluation) March 11, 1999
Evaluation of the Red Jacket Fx1DV and Fx2DV Installed in the Big-Flo Diaphragm Valve (BFDV) for Hourly Testing on Flexible Pipelines Containing Diesel Fuel (Addendum to the March 1994 Evaluation) PREPARED
More informationSUBMERSIBLE PUMPING SYSTEMS SUBMERSIBLE TURBINE PUMPS
Variable Speed Submersible Turbine Pumps Introduced in 1995, FE Petro brand variable speed submersible turbine pumps (STPs) were the first of their kind for the petroleum equipment industry. With faster
More informationElectronic Line Leak Detectors
Manual No: 577013-465 Revision: W Electronic Line Leak Detectors Application Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied
More informationSTP-MLD Installation and Owner s Manual
STP-MLD Installation and Owner s Manual 2006 400439001 Rev. 6 Franklin Fueling Systems 3760 Marsh Rd. Madison WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
More informationInspector's Initials: Tank Owner or Agent Signature: Title: Date:
STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF UNDERGROUND STORAGE TANKS 4 TH Floor, L & C Tower 401 Church Street Nashville, TN 37243-1541 UST OPERATIONS INSPECTION Mo /Day
More informationIST INTELLIGENT SUBMERSIBLE TURBINE
INTELLIGENT SUBMERSIBLE TURBINE IST The FIRST Submersible Pump Ever Designed For High Volume Retailers. The NEW 4HP 4" Diameter Variable Speed Turbine. When FAST Fueling Means MORE Sales. THE IST... NOW
More informationINSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES
INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES SYSTEM CONCEPT When not transferring fuel, the pressure in the underground closed piping system of a gasoline station may fall due
More informationGeneral information about underground storage tank (UST) fueling systems in every day language.
What this document contains: General information about underground storage tank (UST) fueling systems in every day language. What you need to know about Texas Commission on Environmental Quality (TCEQ)
More informationFIXED SPEED SUBMERGED TURBINE PUMPS STP
FIXED SPEED SUBMERGED TURBINE PUMPS STP MagShell SETS A NEW STANDARD FOR SUBMERSIBLE PUMP PERFORMANCE SUBMERGED TURBINE PUMPS Since the mid 190 s, FE Petro s parent company, Franklin Electric, has been
More informationKWA. Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines.
Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines (Addendum to the August 20, 1993 Evaluation of the Vaporless LD 3000 and
More informationFINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit
FINAL UNDERGROUND STORAGE TANK RULE CHANGES Heather Peters UST Compliance and Technology Unit Regulation Changes Federal Rule Based Changes Federal Regulations finalized in July 2015 Federal Rules effective
More informationPhase-Two Water Detector
Phase-Two Water Detector Frequently Asked Questions Sections: Background on Phase Separation Fuel Compatibility Equipment Compatibility Phase-Two Operability Background on Phase Separation 1. What is phase
More informationOverview of an Underground Storage Tank Inspection
Overview of an Underground Storage Tank Inspection PURPOSE OF INSPECTION Protect drinking water, lakes, streams, etc. Education. Protect property value. TECHNICAL ASSISTANCE INSPECTIONS Technical Assistance
More information(Please type or use black ink)
(Please type or use black ink) PNIPUG ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT NOTICE OF PROPOSED UST NEW INSTALLATION OR UPGRADE (Use a separate form for each separate place of operation) Date of
More informationUnderground Storage Tank. City of Burbank UST Owners & Operators
Underground Storage Tank City of Burbank UST Owners & Operators Created by: Kern County Environmental Health CUPA, Edited by: Burbank Fire Department for the Burbank Fire Department s use Burbank Fire
More informationManual No: Revision: J. FXV Leak Detectors. Installation Instructions
Manual No: 042-106-1 Revision: J FXV Leak Detectors Installation Instructions Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied
More informationNew UST Installation Inspection Checklist
Nebraska State Fire Marshal Fuels Division - FLST Section 246 South 14 TH Street - Lincoln, NE 68508-1804 (402) 471-9466 New UST Installation Inspection Checklist (Petroleum or Hazardous Substances) Inspection
More information6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section
6. Tanks - Leak Detection NCDENR Division of Waste Management Underground Storage Tank Section Why conduct Leak Detection? Required for regulated systems: EXCEPTIONS: Temporarily closed tanks Emergency
More informationPennsylvania DEP: Maintaining UST Compliance and Regulation Updates. NISTM 8 th Annual Pennsylvania Storage Tank Conference May 18, 2017
Pennsylvania DEP: Maintaining UST Compliance and Regulation Updates NISTM 8 th Annual Pennsylvania Storage Tank Conference May 18, 2017 Presented by: Randy Martin Solid Waste Program Specialist, Supervisor
More informationAutomatic Business Inventory Reconciliation
JKccu-FL Meter Service Ltd. /SP Automatic Business Inventory Reconciliation Technical Description of the Veeder-Root TLS-350R /^ P/N 577013-366 Rev A 13219 July, 1995 Veoder-Roofs TLS-350R The TLS-350R
More informationEarthsafe Systems, Inc. Page 1
ESS.WP.531. YQA Fuel Transfer Your Questions Answered (47) Fuel Transfer Systems earth safe Fuel Systems for Critical Power. 5.1 What types of pumps are used for fuel transfer? Fuel transfer pumps are
More informationUST General Requirements Inspection Checklist
UST General Requirements Inspection Checklist Inspection Date: Inspector s Name: Facility ID#: I. Ownership of s II. Location of s Owner's Name (Corporation, Individual, Public Agency, or other entity):
More informationP.O. Box 435 Saratoga Springs, NY 12866
Petroleum Storage Equipment Design, Installation & Maintenance September 7, 2016 As a family- and employee-owned business that owns its real estate, Stewart s puts a tremendous investment into our high
More informationFrequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania
Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania NISTM 6 th Annual Pennsylvania Storage Tank Conference April 9, 2015 Presented by: Randy Martin Solid Waste Program
More informationLOW LEVEL SUMP TESTING ORIGINS
LOW LEVEL SUMP TESTING ORIGINS Bruce Garrett Volta Oil Company/Dependable Petroleum Service One Roberts Road Plymouth, MA 02360 508-747-6238 bgarrett@dependablecompany.com Who is PMAA PMAA member associations
More informationMonthly Walkthrough Inspections
This form must be used to document the monthly walkthrough inspections. Only complete the sections that apply to your facility. Inspect the applicable items below for your site. If an item is not applicable,
More informationSubmersible Pumping Systems
Submersible Pumping Systems Global Product Catalogue Effective May 1, 2013 Table of Contents The Total System Solution 5 Standard of Pressure Pumping 8 Submersible Turbine Pumps 9 Submersible Turbine
More informationSwitching To Ethanol?
Switching To Ethanol? Guidelines for Conversion of Retail Service Station Tanks from Gasoline to Ethanol - Blended Gasoline Central Illinois Manufacturing Co. 201 N. Champaign St. Bement, IL 61813 Ph 217.678.2511
More informationPEI/RP Recommended Practices for the Inspection and Maintenance of UST Systems
PEI/RP900-08 Recommended Practices for the Inspection and Maintenance of UST Systems Recommended Practices for the Inspection and Maintenance of UST Systems CONTENTS Foreword...iii SECTIONS 1. Introduction
More informationCPT Controller. Installation and Operation. Marley Pump Company. Is ISO 9001 Certified
CPT Controller Installation and Operation Marley Pump Company Is ISO 9001 Certified CPT Controller Manual: Installation and Operation RE260-240 Rev. I June 99 Certifications and Listings The Marley Pump
More informationLEAD FREE * LFF113RFP Flood Protection Shut Down Valve
Technical Bulletin TB-ACV-LFF11RFP LEAD FREE * LFF11RFP Flood Protection Shut Down Valve Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when continuous discharge from
More informationAutomated Control Electronics (ACE ) System Operation and Diagnostics
Commercial Products Automated Control Electronics (ACE ) System Operation and Diagnostics PART NO. 98962SL This page is intentionally blank. Table of Contents Introduction... 1 Controller Operation and
More informationRed Jacket Submersible Turbine Pumps. Pressure technology for the modern service station.
Red Jacket Submersible Turbine Pumps Pressure technology for the modern service station www.veeder.com Red Jacket Submersible Turbine Pumps Pressure technology for the modern service station Pressure technology
More informationReliable Temperature Compensation is Critical to CNG Vehicle Safety
Reliable Temperature Compensation is Critical to CNG Vehicle Safety August 18, 2014 This Technical Bulletin addresses the potential hazards created by failure of compressed natural gas (CNG) dispensers
More informationChanges to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC
Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com
More informationOperating And Maintaining Underground Storage Tank Systems UPDATED Practical Help And Checklists. Printed on Recycled Paper
UPDATED 2016 Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists EPA 510-K-16-001 Printed on Recycled Paper EPA wrote this booklet for owners and operators of underground
More informationUnderground Oil Storage Tanks Annual Inspection Report
Underground Oil Storage Tanks Annual Inspection Report Rev 3/26/2018 Form Instructions To Installers and Inspectors: This electronic document (the overall workbook and each individual inspection worksheet)
More informationKen Wilcox Associates, Inc.
Evaluation of the INCON Tank Sentinel ATG with SCALD 2.0 As a Continuous In-Tank Leak Detection System (Models: TS-750, TS-1000, TS-1001, TS-2000, and TS-2001 With Probe TSP-LL2) Final Report PREPARED
More informationEssential Elements of a Successful Preventive Maintenance Program
Essential Elements of a Successful Preventive Maintenance Program OCTOBER 19, 2015 PRESENTED BY: ROBBIE L. SARLES RLS & ASSOCIATES, INC. Why Be Concerned with Preventive Maintenance Required by FTA Required
More informationCONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR
Environmental Health - UST Program CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR As part of our inter-local contract with the Nevada Division of Environmental
More informationPurging Air From Divider Block Lubrication Systems
FROST ENGINEERING SERVICE Purging Air From Lubrication Systems A D I V I S I O N O F G E C S E Y S A L E S & S E R V I C E DESCRIPTION Divider block lubrication systems operate correctly only when all
More informationSAN ANTONIO WATER SYSTEM P. O. BOX 2449 SAN ANTONIO, TEXAS TABULATION OF BIDS
DELIVERY A. Parts available for pickup 10 days 7 days 2 days B. Restocking orders placed Mon.-Fri. Monday Mon. & Thur. 8:00 a.m. 8:00 a.m. 8:00 a.m. 5:00 p.m. 5:00 p.m. 5:00 p.m. C. Business Hour Mon.-Fri.
More informationOperations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL
Operations Manual Automated Fuel Maintenance System FTI-10A & 20A FUEL TECHNOLOGIES INTERNATIONAL Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 07/15/2015 Rev E Fuel Technologies
More informationADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017
ADDENDUM NO. #1 ITB #0003-2018 FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017 ITB Services: Subject: The purpose of this solicitation is to acquire sealed competitive bids
More informationTLS-450PLUS Console Intelligent Pump Control
Manual No: 577014-361 Revision: A TLS-450PLUS Console Intelligent Pump Control Installation and Setup Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not
More informationUnderstanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety
Understanding the Colorado Annual Compliance Package William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Overview Required Documentation: UST / AST Annual Compliance Package Release
More informationIMILV01 Carry out routine light vehicle maintenance
IMILV01 Carry out routine light vehicle maintenance Overview This NOS is about conducting routine maintenance, adjustment and replacement activities as part of the periodic servicing of light vehicles.
More informationNCDEQ Underground Storage Tank Section
NCDEQ Underground Storage Tank Section Operation And Maintenance Manual Revised 10/30/2015 i Table of Contents CHAPTER 1. INTRODUCTION... 1 A. Why an Operation and Maintenance Manual?... 1 B. Benefits
More informationCompliance Strategies and Benefits
Compliance Strategies and Benefits NISTM St. Louis Conference October 17, 2012 Brad Walls Director, Central Division Welcome Agenda Introduction Proposed Revisions to Federal Regulations Best Practices
More informationUnderground Storage Tank Annual Compliance Inspection (Revised 1/2015)
Colorado Department of Labor and Employment Division of Oil and Public Safety Compliance Section 633 17 th Street, Suite 500 Denver, CO 80202-3610 Phone: 303-318-8525 Fax: 303-318-8518 Email: cdle_oil_inspection@state.co.us
More informationLV Bushing Oil to Air Dry Insulation PTAB-SLV832
LV Bushing Oil to Air Dry Insulation PTAB-SLV832 Technical Guide 600 V, 30 kv BIL, 600-2500 A 5/8" Integral Flange Bushing 1.0" Integral Flange Bushing 1.25" Bushing General Description The ABB low voltage
More informationRED JACKET SUBMERSIBLE TURBINE PUMPS
RED JACKET SUBMERSIBLE TURBINE PUMPS Optimise flow, maximise profits Building Better Business Why Red Jacket? Red Jacket from Gilbarco Veeder-Root unsurpassed expertise to help sites optimise fuel flow.
More informationRULE 449 TRANSFER OF GASOLINE INTO VEHICLE FUEL TANKS
RULE 449 TRANSFER OF GASOLINE INTO VEHICLE FUEL TANKS Adopted 2-5-75 (Amended 9-15-75, 6-1-76, 8-3-77, 9-29-87, 12-17-91, 2-2-95, 4-3-97, 09-26-02, 02-26-09) INDEX 100 GENERAL 101 PURPOSE 102 APPLICABILITY
More informationEvaluation of the Highland Tank Periodic Interstitial Vacuum Test Procedure for Double-Wall Underground Tanks (Titan, STi-P3,ACT-100U and HighGuard )
Evaluation of the Highland Tank Periodic Interstitial Vacuum Test Procedure for Double-Wall Underground Tanks (Titan, STi-P3,ACT-00U and HighGuard ) Final Report Prepared for: Highland Tank and Manufacturing
More informationRelay Contact Ratings. Operating Temperatures. Life Expectancy. Humidity Tolerance Enclosure Mounting Weight
Multi-Function Moisture Sensing Liquid Level Control INGRAM P R O D U C T S, I N C. Part No. : MSRP4A, MSRP0A The Ingram Multi-function Moisture Sensing Relay (MSR) saves you time and money. No more time
More informationNOW UL LISTED. Patented
NOW UL LISTED Patented Ø1.730 Ø 1.765 Ø.922 4.15 8.71 TOP VIEW 1.50 2" NPS THRDS. BOTTOM VIEW 2.13 2.14 SIDE VIEW 2.000 CLAY & BAILEY MFG. CO. 2" FILL SHUT OFF VALVE DATE:10/25/05 01228-03-2200 2" X 4"
More informationCompliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012
Compliance Strategies and Benefits Brian Derge Tanknology Inc. December 6, 2012 Welcome Introduction Tanknology Proposed Revisions to Federal Regulations What we have learned over 15 years of testing Sump
More informationCOSASCO TWO-INCH SYSTEM
COSASCO TWO-INCH SYSTEM INSTALLATION, OPERATION, & MAINTENANCE MANUAL SAND PROBES Rohrback Cosasco Systems 11841 East Smith Ave. Santa Fe Springs, CA 90670 Tel: (1) 562-949-0123 Fax: (1) 562-949-3065 E-mail:
More informationPRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS SUBMERSIBLE PUMPING SYSTEMS
PRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS SUBMERSIBLE PUMPING SYSTEMS 1 TABLE OF CONTENTS ABOUT US 5 Total System Solution 6 Submersible Pumping Systems 8 4" Submersible Pumps 9 Variable Speed 11 Intelligent
More informationINSTALLATION INSTRUCTIONS B-375-D Fiberglass DoubleWall Spill Bucket
INSTALLATION INSTRUCTIONS B-375-D Fiberglass DoubleWall Spill Bucket S. Bravo Systems, Inc. 2929 Vail Ave. - Commerce, CA 90040 (323) 888-4133 - FAX: (323) 888-4123 www.sbravo.com Written by Jonathan Smith
More informationMark S. Morgan, Regulatory Counsel
SUBJECT: ISSUE: PMAA CONTACT: EPA UST Regulations Final UST Rules Mark S. Morgan, Regulatory Counsel mmorgan@pmaa.org DATE: November 16, 2015 U.S. EPA FINAL UNDERGROUND STORAGE TANK REQUIREMENTS: I. BACKGROUND
More informationOn Board Diagnostics II A PCED
Page 1 of 8 HX18 DTC P0446 OR P1450: CHECK FOR VISUAL CAUSES OF EXCESSIVE FUEL TANK VACUUM Continuous Memory Diagnostic Trouble Code (DTC) P0446 or P1450 indicates that Self-Test has detected the Evaporative
More information6.7L Diesel Fuel System Service Tips
General Service Bulletin (GSB): This GSB targets the diagnosis, inspection and repair of the 6.7L diesel fuel system. Some 6.7L diesel vehicles may experience drivability concerns due to fuel system failures.
More informationThe Red Jacket Submersible Turbine Pump
Manual No: 577013-830 Revision: D The Red Jacket Submersible Turbine Pump Installation, Service, & Parts lists Notice Veeder-Root makes no warranty of any kind with regard to this publication, including,
More informationOperating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper
Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists Printed on Recycled Paper Contents How to Use This Booklet...1 Section 1 Identifying The Equipment At Your UST Facility...3
More informationOperating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper
Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists Printed on Recycled Paper Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists
More informationOKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS
OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS PO BOX 52000 OKC, OK 73152-2000 www.occeweb.com Created on 10/1/2008
More informationTHE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS
THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS Presented by: Joyce A. Rizzo President JD2 Environmental, Inc. 800 East Washington Street West Chester, PA 19380 www.jd2env.com
More informationApplication for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information
Papillion/La Vista Fire Marshal s Office Fuels Division FLST Section 146 rth Adams Street Papillion, NE 68046 (402) 829-1398 Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous
More information2016 PRICE LIST TOTAL SYSTEM SOLUTIONS
2016 PRICE LIST TOTAL SYSTEM SOLUTIONS Effective February 1, 2016 Submersible Pumping Systems 1 Submersible Turbine Pumps 1 Variable Speed Submersible Turbine Pumps 1 Intelligent Submersible Turbine Pumps
More informationChanges to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC
Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com
More informationveeder-root TLS-450 automated compliance and site management
veeder-root TLS-450 automated compliance and site management At Veeder-Root, we ve delivered over 200,000 times worldwide. With our TLS-450 platform, the same promises apply, along with new benefits that
More informationLPP-M PUMP THE SOLUTION YOU VE BEEN LOOKING FOR
LPP-M PUMP THE SOLUTION YOU VE BEEN LOOKING FOR LAROX PERISTALTIC PUMPS FOR METERING The innovative Larox Peristaltic Pumps for Metering (LPP-M) set a new industry standard for peristaltic pump technology.
More informationCOLORADO DEPARTMENT OF LABOR AND EMPLOYMENT DIVISION OF OIL AND PUBLIC SAFETY STATISTICAL INVENTORY RECONCILIATION (SIR) GUIDANCE DOCUMENT
BILL OWENS Governor VICKIE L. ARMSTRONG Executive Director JEFFREY M. WELLS Deputy Executive Director RICHARD O. PIPER Acting Director of Oil and Public Safety DEPARTMENT OF LABOR AND EMPLOYMENT DIVISION
More informationAPPENDIX B. DYNAMIC PRESSURE PERFORMANCE TEST (taken from BAAQMD test procedure ST-27)
3745-21-10, Appendix B 1 APPENDIX B DYNAMIC PRESSURE PERFORMANCE TEST (taken from BAAQMD test procedure ST-27) 1. APPLICABILITY 1.1 This procedure is used to verify compliance with the applicable dynamic
More informationQ= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications
1 of 9 1. DESCRIPTION The Viking Flow Control Valve is a quick opening, differential diaphragm flood valve with a spring loaded floating clapper. The Flow Control Valve can be used to facilitate manual
More informationVSPS PACKAGE BOOSTER SYSTEM (END SUCTION PUMP DESIGN) FEATURES T Y P E
PACKAGE BOOSTER SYSTEM (END SUCTION PUMP DESIGN) PACKAGED PUMP SYSTEM WITH CAPACITIES TO 300GPM, PRESSURE BOOST TO 100PSI* WITH UP TO 25HP ON EACH PUMP AVAILABLE IN DUPLEX, AND TRIPLEX CONFIGURATION, AND
More informationHGM-MZ Multi-Zone Monitor Annual Maintenance And Troubleshooting Guide
HGM-MZ Multi-Zone Monitor Annual Maintenance And Troubleshooting Guide Service, Testing and Maintenance procedures BACHARACH Inc. HGM-MZ Routine Annual Maintenance And Operating Parameter Verification
More informationLeak Prevention Building Tighter Systems with Enhanced Leak Detection. Service Provided by CGRS, Inc.
Leak Prevention Building Tighter Systems with Enhanced Leak Detection Service Provided by CGRS, Inc. Everything Leaks! It s up to the user to determine what leak rate is acceptable. Service Provided by
More informationEPA UST Regulations Update May 22, 2018
EPA UST Regulations Update May 22, 2018 Founded in 1988, Tanknology has grown to become one of the largest testing and inspection service companies in the world. Our fleet of 150 vehicles provides service
More informationFLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)
FLOOD PROTECTION SHUT DOWN VALVE ( and smaller) 01/10 2 6 To Floor Drain L X JB11 4 FS99 5 Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when discharge from RPZ Relief
More informationDC400 Dispensing Cutoff System
DC400 Dispensing Cutoff System Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com Important
More informationDigital III Fueling Vehicle Control System
SM64335-2 April 2005 Aerospace Group Conveyance Systems Division Carter Brand Ground Fueling Equipment Applicable additional manuals: SM64335-1 Setup & Calibration User s Manual Digital III Fueling Vehicle
More informationWater Valve Shutoff. WVS Water Valve Shutoff
Water Valve Shutoff Monitors flooding from leaking or broken water line Automatic control of main water supply line Form C Relay output for external monitoring devices Visual and audible status indicators
More informationPROTECT YOUR BUSINESS WITH INSITE360
PROTECT YOUR BUSINESS WITH INSITE360 Wetstock Management Solutions from Gilbarco Veeder-Root Building Better Business Why Insite360? Insite360 protects your most valuable asset, your wetstock, and keeps
More information11 OPERATION AND VERIFICATION
11 OPERATION AND VERIFICATION Section Page 11.1 PREPARATION FOR A FIRST TIME START... 11-3 11.2 STARTING THE ENGINE... 11-9 11.3 RUNNING THE ENGINE... 11-12 11.4 STOPPING THE ENGINE... 11-14 (Rev. 3/04)
More informationLeak Detector, Red Jacket #FX1V
ITEM 1 SUBMERSIBLE REMOTE PUMPS A. 2. Manufacturer EACH Red Jacket Red Jacket 4. Effective date of schedule EACH Oct. 3, 2005 July 1, 2006 B. Red Jacket Equipment 1. Leak Detector, Red Jacket #FX1V 215.00
More information