ADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017

Size: px
Start display at page:

Download "ADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017"

Transcription

1 ADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017 ITB Services: Subject: The purpose of this solicitation is to acquire sealed competitive bids from qualified Contractors. The Contractor will be required to provide all labor, and materials necessary to complete the required Fuel Storage Compliance Inspections. This Addendum contains questions submitted by prospective Respondents, Florida A&M University s answers and updates to the ITB language. Deletions are indicated by strikethrough or reference. Additions, updates or replacements are indicated by underscore, reference or highlighting. REFERENCE: DELETE: ADD: Pages 15-17, 2.0 TECHNICAL SPECIFICATIONS This sections in its entirety 2.0 TECHNICAL SPECIFICATIONS Bidders are required to meet or exceed the specifications below. 2.1 General Information Florida A&M University is soliciting bids to establish a contract for its Fuel Storage Tanks Compliance Inspections. Storage tanks covered by this document are located at the addresses given below: There are currently eleven (11) *Regulated underbelly generator storage tanks. The Vendor will Perform visual inspections of all tank components and leak detector test including interstitial monitoring (Monthly) for twelve (12) months at all facilities where applicable. All tank level gauges will require an Annual Operability test every twelve (12) months where applicable at all locations shown below. Plant Operations & Maintenance (POM) Wahnish Way Coleman Library Orr Drive School of Business North Gamble St Science Research Facility South MLK Blvd Perry-Paige Building tank # S MLK Blvd Perry-Paige Building tank # S MLK Blvd School of Architecture South MLK Blvd Teaching Gymnasium Wahnish Way Jones Hall MLK Blvd FAMU Village tank # Gamble Street FAMU Village tank # Gamble Street Tank Farm Wahnish Way Each bidder is invited to inspect each of these sites prior to submitting a bid. For visitation appointments, please contact Paul McKay, or Kendall Jones at or Stephanie Fisher, or Paul.McKay@famu.edu; Purchasing@famu.edu. Page 1 of 5

2 It is the University s intent that the vendor who is awarded this contract will provide all necessary parts and labor so that all items under Scope of Work will be fully operational at all times. 2.2 SCOPE OF WORK 1. Monthly Inspect/Maintenance: Maintain all physical apparatus including: All integral mechanical, electrical, and electronic parts of the fuel dispensers and replace as needed Maintain calibration (per state inspector) All assisted vapor recovery components Inspect and clean all sumps Inspect and clean fill man-ways and caps Inspect nozzles, hoses & breakaways and replace as needed Inspect all dispenser shear valves and replace as needed Test low level and high level alarms Test overfill alarm Check printer for proper operation Tank monitor system Check monitoring wells Underground and above ground tank equipment including Submergible pumps, check valves, O-rings, fill and vent caps, pressure vents, dry breaks, gage caps, gaskets, sump cover, lids, and bolts and fasteners. 2. Quarterly Maintenance: Replace all fuel filters or as needed 3. Yearly Certifications Provide Veeder root certification Provide Leak detection certification 4. Three Year Integrity test 2.3 SCHEDULE Monthly Inspection at all facilities shown below: Plant Operations & Maintenance (POM) Wahnish Way Inspection at Plant Operations and Maintenance Facility (POM) 2400 Wahnish Way Vendor will Perform visual inspection of all tank components and leak detector test (Monthly) for twelve (12) months at this Facility. Vendor will Perform inspection of all tank components and leak detector test at this Facility Annually, Vendor will perform hydrostatic Integrity test on three (3) below grade dispenser sumps every three years Vendor will perform hydrostatic integrity test on three (3) below grade pump sumps every three years Vendor will perform hydrostatic Integrity test on three (3) below grade single wall spill buckets Annually Vendor will perform Annual Operability Test at this facility per **DEP and manufacturer s requirements. Three underground submersible pumps in the sump wells Two underground 2500 gallon unleaded tanks Page 2 of 5

3 One 550 gallon underground diesel tank One 600 gallon belly generator diesel tank OPW fuel monitoring system FuelMaster key reader Coleman Library. 525 Orr Drive One 600 gallon diesel belly generator tank School of Business North 500 Gamble St One 600 gallon diesel belly generator tank Science Research Facility South MLK Blvd One 650 gallon diesel belly generator tank Perry-Paige Building tank 2 tanks S MLK Blvd One 850 gallon diesel belly generator tank. (Vendor will perform Annual Operability Test on this tank per DEP and manufacturer s requirements) One 1300 gallon diesel belly generator tank School of Architecture.1938 South MLK Blvd One 700 gallon diesel belly generator tank Alfred Lawson Teaching Gymnasium Wahnish Way One 650 gallon diesel belly generator tank Jones Hall. 530 MLK Blvd One 1000 gallon diesel belly generator tank FAMU Village tank 2 tanks Gamble Street One 600 gallon diesel belly generator tank in the East mechanical room Vendor will perform Annual Operability Test per DEP and manufacturer s requirements One 600 gallon diesel belly generator tank in the West mechanical room (Vendor will perform Annual Operability Test per DEP and manufacturer s requirements Tank Farm 1660 Wahnish Way One 60,000 gallon diesel tank Page 3 of 5

4 One 50,000 gallon diesel tank Containment wall and floor *Regulated tanks are those with storage capacities greater than 550 gallons. Page 4 of 5

5 Questions and Answers ITB # Question: The bid sheet starting on page 15 does not clarify how many tanks are at each address and what type underground or above ground (Base Tank for Generator). Also, there is no indication as to the size or fuel type ex. diesel or gasoline. It also states on page 16 Monthly Leakage inspections on 12 regulated fuel tanks, and gives the site locations for those 12. From a current contract Ring Power is working on the campus with now we know that there are more than 12 tanks from the sites listed. There should be roughly 15 from the list given. POM has 3 tanks for example just at that one site 2 unleaded and 1 diesel. Answer: Corrections: There are eleven (11) Regulated underbelly generator tanks currently. 2. Question: It's noted on page 17 annual operability testing specifically for FAMU Village and Perry Paige. Are the other facilities not included. It appears from the wording on page 16 that the operability testing needs to be on all locations. It would be helpful if this was clarified. Answer: above. Annual Operability testing will be conducted at the aforementioned facilities 3. Question: Clarification on what the University is looking for with regard to Operability Testing (scope of testing). Answer: More information on Annual Operability testing can be found at FDEP Tank resources links below: Question: Monthly leak inspections and monthly visual inspections on the pricing attachment sheet A Page 18 have it listed as separate. Can these services be completed on the same day for each tank. The same goes for the annual operability testing and the integrity testing. There are two lines to separate the pricing for each. Answer: When required All services should be completed on the same day barring any unforeseen contingencies. ACKNOWLEDGEMENT OF ADDENDUM When Addendums are issued by the University, proposers are required to acknowledge them by signing below. SIGNATURE DATE Page 5 of 5

North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section

North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section To discover a release before a major contamination incident occurs Required

More information

Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania

Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania NISTM 6 th Annual Pennsylvania Storage Tank Conference April 9, 2015 Presented by: Randy Martin Solid Waste Program

More information

Understanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety

Understanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Understanding the Colorado Annual Compliance Package William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Overview Required Documentation: UST / AST Annual Compliance Package Release

More information

P.O. Box 435 Saratoga Springs, NY 12866

P.O. Box 435 Saratoga Springs, NY 12866 Petroleum Storage Equipment Design, Installation & Maintenance September 7, 2016 As a family- and employee-owned business that owns its real estate, Stewart s puts a tremendous investment into our high

More information

(Please type or use black ink)

(Please type or use black ink) (Please type or use black ink) PNIPUG ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT NOTICE OF PROPOSED UST NEW INSTALLATION OR UPGRADE (Use a separate form for each separate place of operation) Date of

More information

COUNTY OF FRESNO ADDENDUM NUMBER: ONE (1) RFQ NUMBER: FUEL SITE REPAIRS, MAINTENANCE, TESTING AND TANK MONITORING UPGRADES

COUNTY OF FRESNO ADDENDUM NUMBER: ONE (1) RFQ NUMBER: FUEL SITE REPAIRS, MAINTENANCE, TESTING AND TANK MONITORING UPGRADES COUNTY OF FRESNO ADDENDUM NUMBER: ONE (1) RFQ NUMBER: 992-5390 FUEL SITE REPAIRS, MAINTENANCE, TESTING AND TANK MONITORING UPGRADES Issue Date: IMPORTANT: SUBMIT QUOTATION IN SEALED PACKAGE WITH QUOTATION

More information

County of Yolo UNDERGROUND STORAGE TANK PROGRAM INSTALLATION/MODIFICATION/REPAIR APPLICATION

County of Yolo UNDERGROUND STORAGE TANK PROGRAM INSTALLATION/MODIFICATION/REPAIR APPLICATION April Meneghetti, REHS Environmental Health Divison Manager County of Yolo DEPARTMENT OF COMMUNITY SERVICES Environmental Health Division 292 West Beamer St., Woodland, CA 95695 PHONE - (530) 666-8646

More information

ANNUAL UST SYSTEM INSPECTION CHECKLIST

ANNUAL UST SYSTEM INSPECTION CHECKLIST APPENDIX A-3: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST Page 1 ANNUAL UST SYSTEM INSPECTION CHECKLIST Facility ID# Facility Name/Address Qualified Technician Signature Date

More information

Massachusetts Department of Environmental Protection Underground Storage Tank Program

Massachusetts Department of Environmental Protection Underground Storage Tank Program Massachusetts Department of Environmental Protection Underground Storage Tank Program Tom DeNormandie, Chief Underground Storage Tank and Stage I/II Branch 2016 New England Storage Tank Conference Westborough,

More information

SAN ANTONIO WATER SYSTEM P. O. BOX 2449 SAN ANTONIO, TEXAS TABULATION OF BIDS

SAN ANTONIO WATER SYSTEM P. O. BOX 2449 SAN ANTONIO, TEXAS TABULATION OF BIDS DELIVERY A. Parts available for pickup 10 days 7 days 2 days B. Restocking orders placed Mon.-Fri. Monday Mon. & Thur. 8:00 a.m. 8:00 a.m. 8:00 a.m. 5:00 p.m. 5:00 p.m. 5:00 p.m. C. Business Hour Mon.-Fri.

More information

Underground Storage Tank Annual Compliance Inspection (Revised 1/2015)

Underground Storage Tank Annual Compliance Inspection (Revised 1/2015) Colorado Department of Labor and Employment Division of Oil and Public Safety Compliance Section 633 17 th Street, Suite 500 Denver, CO 80202-3610 Phone: 303-318-8525 Fax: 303-318-8518 Email: cdle_oil_inspection@state.co.us

More information

6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section

6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section 6. Tanks - Leak Detection NCDENR Division of Waste Management Underground Storage Tank Section Why conduct Leak Detection? Required for regulated systems: EXCEPTIONS: Temporarily closed tanks Emergency

More information

PROJECT: Springhill & Canal Development (1950 E. Springhill Drive, Terre Haute, IN 47802)

PROJECT: Springhill & Canal Development (1950 E. Springhill Drive, Terre Haute, IN 47802) July 20, 2017 Architectural Project #1702 Springhill & Canal Development ADDENDUM NO. 1 PROJECT: Springhill & Canal Development (1950 E. Springhill Drive, Terre Haute, IN 47802) THIS LETTER CONSTITUTES

More information

Underground Oil Storage Tanks Annual Inspection Report

Underground Oil Storage Tanks Annual Inspection Report Underground Oil Storage Tanks Annual Inspection Report Rev 3/26/2018 Form Instructions To Installers and Inspectors: This electronic document (the overall workbook and each individual inspection worksheet)

More information

Changes to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017

Changes to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Changes to Chapter 62-761, Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Rule Organization The rule sections are reorganized a bit with separate sections now for:

More information

Compliance Strategies and Benefits

Compliance Strategies and Benefits Compliance Strategies and Benefits NISTM St. Louis Conference October 17, 2012 Brad Walls Director, Central Division Welcome Agenda Introduction Proposed Revisions to Federal Regulations Best Practices

More information

General information about underground storage tank (UST) fueling systems in every day language.

General information about underground storage tank (UST) fueling systems in every day language. What this document contains: General information about underground storage tank (UST) fueling systems in every day language. What you need to know about Texas Commission on Environmental Quality (TCEQ)

More information

New Tank Installations. Peter Rollo

New Tank Installations. Peter Rollo New Tank Installations Peter Rollo New Tank Installations What tanks are regulated? All tanks with a capacity greater than 1,100 gallons Commercial tanks, other than heating fuel tanks, with a capacity

More information

PEI/RP Recommended Practices for the Inspection and Maintenance of UST Systems

PEI/RP Recommended Practices for the Inspection and Maintenance of UST Systems PEI/RP900-08 Recommended Practices for the Inspection and Maintenance of UST Systems Recommended Practices for the Inspection and Maintenance of UST Systems CONTENTS Foreword...iii SECTIONS 1. Introduction

More information

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com

More information

Pennsylvania DEP: Maintaining UST Compliance and Regulation Updates. NISTM 8 th Annual Pennsylvania Storage Tank Conference May 18, 2017

Pennsylvania DEP: Maintaining UST Compliance and Regulation Updates. NISTM 8 th Annual Pennsylvania Storage Tank Conference May 18, 2017 Pennsylvania DEP: Maintaining UST Compliance and Regulation Updates NISTM 8 th Annual Pennsylvania Storage Tank Conference May 18, 2017 Presented by: Randy Martin Solid Waste Program Specialist, Supervisor

More information

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com

More information

FINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit

FINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit FINAL UNDERGROUND STORAGE TANK RULE CHANGES Heather Peters UST Compliance and Technology Unit Regulation Changes Federal Rule Based Changes Federal Regulations finalized in July 2015 Federal Rules effective

More information

Central Florida Regional Transportation Authority d.b.a.

Central Florida Regional Transportation Authority d.b.a. Central Florida Regional Transportation Authority d.b.a. 455 N. Garland Avenue Orlando, FL 32801 AMENDMENT OF SOLICITATION MANUFACTURE OF COMMERICAL STYLE BUS SHELTERS 1. AMENDMENT NO: 2. SOLICITATION

More information

Winning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac

Winning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac Minimum Specifications/Questionnaire Bid Results for One (1) New Fuel Dispensing System-Larrabee Shop Winning Bid PERMIT FEES, FORMS, PLANS and NOTIFICATIONS Secure all necessary state and local permits

More information

ADDENDUM NO. 1 Kansas City Area Transportation Authority 1350 E. 17 th Street Kansas City, Missouri 64108

ADDENDUM NO. 1 Kansas City Area Transportation Authority 1350 E. 17 th Street Kansas City, Missouri 64108 ADDENDUM NO. 1 Kansas City Area Transportation Authority 1350 E. 17 th Street Kansas City, Missouri 64108 INVITATION FOR BIDS (IFB) #17-5036-33 BI-FUEL SHUTTLE BUSES FOR PARATRANSIT SERVICES Issue Date:

More information

Mark S. Morgan, Regulatory Counsel

Mark S. Morgan, Regulatory Counsel SUBJECT: ISSUE: PMAA CONTACT: EPA UST Regulations Final UST Rules Mark S. Morgan, Regulatory Counsel mmorgan@pmaa.org DATE: November 16, 2015 U.S. EPA FINAL UNDERGROUND STORAGE TANK REQUIREMENTS: I. BACKGROUND

More information

Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities

Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities Connecticut Department of Energy and Environmental Protection Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities May 15, 2015 Peter Zack, Assistant

More information

UNDERGROUND STORAGE TANK (UST) INSTALLATION & MAINTENANCE

UNDERGROUND STORAGE TANK (UST) INSTALLATION & MAINTENANCE SUBJECT: FIRE DEPARTMENT INSTALLATION & MAINTENANCE Fire Department 955 Sonoma Avenue Santa Rosa, CA 95404 Phone: (707) 543-3500 Fax: (707) 543-3520 http://ci.santa-rosa.ca.us/fd/ Bulletin Number: 010

More information

Public Works Department

Public Works Department Public Works Department SUBJECT: Consideration of two Resolutions concerning replacement of the Village s fuel system. AGENDA ITEM: 9.b.iii MEETING DATE: July 20, 2015 VILLAGE BOARD REPORT TO: Village

More information

Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida (813) Addendum No. 1

Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida (813) Addendum No. 1 Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida 33620 (813) 974-2481 Invitation to Bid No.: 18-12-YH Entitled: Opening Date: Bulk Fuel Delivery (PATS) November 14, 2017 at 3:00 p.m.

More information

Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations. Storage Tank Advisory Committee Harrisburg, PA September 1, 2015

Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations. Storage Tank Advisory Committee Harrisburg, PA September 1, 2015 Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations Storage Tank Advisory Committee Harrisburg, PA September 1, 2015 Why is EPA making changes to the UST regulations? The Energy

More information

KENDALL COUNTY HIGHWAY DEPARTMENT

KENDALL COUNTY HIGHWAY DEPARTMENT KENDALL COUNTY HIGHWAY DEPARTMENT NOTICE TO BIDDERS INSTRUCTIONS TO BIDDERS SPECIFICATIONS BID FORM For BULK FUEL November 4, 2016 10:00 A.M NOTICE TO BIDDERS Kendall County Highway Department will accept

More information

New Regs Get Ready for Containment Testing if You Haven t Done So Already!

New Regs Get Ready for Containment Testing if You Haven t Done So Already! New Regs Get Ready for Containment Testing if You Haven t Done So Already! Edward S. Kubinsky Jr. CROMPCO, LLC Director of Regulatory Affairs, Training and Certification ed.kubinsky@crompco.com NISTM Conference

More information

Compliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012

Compliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012 Compliance Strategies and Benefits Brian Derge Tanknology Inc. December 6, 2012 Welcome Introduction Tanknology Proposed Revisions to Federal Regulations What we have learned over 15 years of testing Sump

More information

7. UST Piping Corrosion Protection. NCDENR Division of Waste Management Underground Storage Tank Section

7. UST Piping Corrosion Protection. NCDENR Division of Waste Management Underground Storage Tank Section 7. UST Piping Corrosion Protection NCDENR Division of Waste Management Underground Storage Tank Section 1 Where piping connects to tank Piping Corrosion Protection 2 Main run of piping 3 Where piping connects

More information

FUEL DISPENSING AND STORAGE EQUIPMENT FORM 1306 (See Form 1306 Requirements and Instructions) Form 1300 must accompany this application.

FUEL DISPENSING AND STORAGE EQUIPMENT FORM 1306 (See Form 1306 Requirements and Instructions) Form 1300 must accompany this application. North Coast Unified Air Quality Management District 707 L Street Eureka, CA 95501 (707) 443-3093 FUEL DISPENSING AND STORAGE EQUIPMENT FORM 1306 (See Form 1306 Requirements and Instructions) Form 1300

More information

New UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most.

New UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most. New UST Regulations The long awaited UST regulations were released by the EPA on June 22, 2015 and soon will be published in the Federal Register. The new regulations will go into effect 90 days after

More information

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary

More information

New UST Installation Inspection Checklist

New UST Installation Inspection Checklist Nebraska State Fire Marshal Fuels Division - FLST Section 246 South 14 TH Street - Lincoln, NE 68508-1804 (402) 471-9466 New UST Installation Inspection Checklist (Petroleum or Hazardous Substances) Inspection

More information

Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information

Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information Papillion/La Vista Fire Marshal s Office Fuels Division FLST Section 146 rth Adams Street Papillion, NE 68046 (402) 829-1398 Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous

More information

City of Hammond Purchasing Department RFP # General Maintenance and Repair Service Contract City Generators

City of Hammond Purchasing Department RFP # General Maintenance and Repair Service Contract City Generators 1 City of Hammond Purchasing Department RFP # 15-33 General Maintenance and Repair Service Contract City Generators Proposals Shall Be Received by the Purchasing Department, City of Hammond 310 East Charles

More information

Inspector's Initials: Tank Owner or Agent Signature: Title: Date:

Inspector's Initials: Tank Owner or Agent Signature: Title: Date: STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF UNDERGROUND STORAGE TANKS 4 TH Floor, L & C Tower 401 Church Street Nashville, TN 37243-1541 UST OPERATIONS INSPECTION Mo /Day

More information

State of New Jersey. Department of Environmental Protection Air Quality Permitting

State of New Jersey. Department of Environmental Protection Air Quality Permitting State of New Jersey Department of Environmental Protection Air Quality Permitting General Permit (GP-004B) for Fuel Dispensing Facility Equipped with a Phase I Vapor Recovery Control System This General

More information

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL On January 26, 2005, the Maryland Department of the Environment (the Department) implemented, in the Code of Maryland Regulations (COMAR) 26.10,

More information

OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS

OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS PO BOX 52000 OKC, OK 73152-2000 www.occeweb.com Created on 10/1/2008

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 3/14) UNDERGROUND STORAGE TANKS SUMMARY OF REGULATORY REQUIREMENTS Underground storage tanks (UST) are defined as tanks containing petroleum or other regulated substances

More information

UST Compliance Assistance Handbook

UST Compliance Assistance Handbook UST Compliance Assistance Handbook O N E I D A E N V I R O N E N T A L, H E A L T H A N D S A F E T Y D I V I S I O N Oneida Tribe of Indians of Wisconsin P.O. Box 365 Oneida, WI 54155 Created by the Oneida

More information

Overview of an Underground Storage Tank Inspection

Overview of an Underground Storage Tank Inspection Overview of an Underground Storage Tank Inspection PURPOSE OF INSPECTION Protect drinking water, lakes, streams, etc. Education. Protect property value. TECHNICAL ASSISTANCE INSPECTIONS Technical Assistance

More information

CITY OF PORTSMOUTH PURCHASING DEPARTMENT PORTSMOUTH, NEW HAMPSHIRE. Annual Fuel Bid - #01-18 INVITATION TO BID

CITY OF PORTSMOUTH PURCHASING DEPARTMENT PORTSMOUTH, NEW HAMPSHIRE. Annual Fuel Bid - #01-18 INVITATION TO BID CITY OF PORTSMOUTH PURCHASING DEPARTMENT PORTSMOUTH, NEW HAMPSHIRE Annual Fuel Bid - #01-18 INVITATION TO BID The City of Portsmouth is soliciting bids for our primary supply and emergency supply of fuel.

More information

NEIWPCC-Defender Spill Containment. Interstice Monitoring-Testing - Maintenance

NEIWPCC-Defender Spill Containment. Interstice Monitoring-Testing - Maintenance NEIWPCC-Defender Spill Containment Interstice Monitoring-Testing - Maintenance DISCLAIMER Only certified contractors should perform maintenance on and/or install the products shown in this presentation.

More information

2018 UST Regulation Revision Comment Worksheet

2018 UST Regulation Revision Comment Worksheet Comment # Commenter Section Comment DEM Response 1 Overall NECSEMA requests that UST system compliance or installation testing that results in an inconclusive finding be given period of time for investigation

More information

Provide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext.

Provide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext. UNDERGROUND STORAGE TANK SYSTEM INSTALLATION/UPGRADE SUPPLEMENT For use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire (CFC); Chapter 6.7, Health

More information

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. New Jersey Fuel Dispensing Facilities Compliance Calendar

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. New Jersey Fuel Dispensing Facilities Compliance Calendar NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM New Jersey Fuel Dispensing Facilities Compliance Calendar 2014 Welcome The New Jersey Small Business Environmental Assistance Program developed

More information

SECTION VEHICLE FUEL DISPENSING EQUIPMENT

SECTION VEHICLE FUEL DISPENSING EQUIPMENT SECTION 23 10 13 PART 1 GENERAL 1.01 SUMMARY A. Provide vehicle fuel storage and dispensing equipment, including but not necessarily limited to: 1. Two compartment above ground gasoline and diesel tank.

More information

ROCK RIVER WATER RECLAMATION DISTRICT ADDENDUM NO. 1 TO THE INVITATION TO BID UNLEADED GASOLINE AND DIESEL FUELS SUPPLY ITB #

ROCK RIVER WATER RECLAMATION DISTRICT ADDENDUM NO. 1 TO THE INVITATION TO BID UNLEADED GASOLINE AND DIESEL FUELS SUPPLY ITB # ROCK RIVER WATER RECLAMATION DISTRICT ADDENDUM NO. 1 TO THE INVITATION TO BID UNLEADED GASOLINE AND DIESEL FUELS SUPPLY ITB #15-201 March 3, 2015 AD1-1 Notice This Addendum No. 1, dated March 3, 2015,

More information

Test Date: 3/30/2018 Order Number: Dear Regulator, Enclosed are the results of recent testing performed at the following facility:

Test Date: 3/30/2018 Order Number: Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 4/17/2018 STATE OF NEW HAMPSHIRE-DES HARDING SCHOFIELD Upload to website https://www2.des.state.nh.us/onestopdataproviders/deslogin.aspx

More information

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. New Jersey Fuel Dispensing Facilities Compliance Calendar

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. New Jersey Fuel Dispensing Facilities Compliance Calendar NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM New Jersey Fuel Dispensing Facilities Compliance Calendar 2018 Welcome The New Jersey Small Business Environmental Assistance Program developed

More information

BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION

BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION Page 3 Federal law requires the Division of State Fire Marshal, Bureau of Underground Storage Tank Regulations (BUSTR) to inspect

More information

INSTALLATION INSTRUCTIONS B-375-D Fiberglass DoubleWall Spill Bucket

INSTALLATION INSTRUCTIONS B-375-D Fiberglass DoubleWall Spill Bucket INSTALLATION INSTRUCTIONS B-375-D Fiberglass DoubleWall Spill Bucket S. Bravo Systems, Inc. 2929 Vail Ave. - Commerce, CA 90040 (323) 888-4133 - FAX: (323) 888-4123 www.sbravo.com Written by Jonathan Smith

More information

COUNTY OF BERKS Purchasing Department Berks County Services Center, 633 Court Street, Reading, PA Tel: Fax:

COUNTY OF BERKS Purchasing Department Berks County Services Center, 633 Court Street, Reading, PA Tel: Fax: COUNTY OF BERKS Purchasing Department Berks County Services Center, 633 Court Street, Reading, PA 19601 Tel: 610-478-6168 Fax: 610-478-6206 Kelly A. Laubach, Purchasing Manager NOTICE TO BIDDERS Amendment

More information

Date. Director c/o Petroleum Storage Program Manitoba Conservation and Water Stewardship 1007 Century Street Winnipeg, MB R3H 0W4

Date. Director c/o Petroleum Storage Program Manitoba Conservation and Water Stewardship 1007 Century Street Winnipeg, MB R3H 0W4 Date Director c/o Petroleum Storage Program Manitoba Conservation and Water Stewardship 1007 Century Street Winnipeg, MB R3H 0W4 To the Attention of the Director: Re: Insert Company Name Request for Variance

More information

State of New Jersey. Department of Environmental Protection Air Quality Permitting. General Permit (GP-004A) For FUEL DISPENSING FACILITIES

State of New Jersey. Department of Environmental Protection Air Quality Permitting. General Permit (GP-004A) For FUEL DISPENSING FACILITIES State of New Jersey Department of Environmental Protection Air Quality Permitting General Permit (GP-004A) For FUEL DISPENSING FACILITIES This General Permit allows for the construction, installation,

More information

Audit Follow-up. Fleet Fuel Operations (Report #0801, Issued October 18, 2007) As of March 31, Summary. Report #0811 June 20, 2008

Audit Follow-up. Fleet Fuel Operations (Report #0801, Issued October 18, 2007) As of March 31, Summary. Report #0811 June 20, 2008 Audit Follow-up As of March 31, 2008 Sam M. McCall, CPA, CGFM, CIA, CGAP City Auditor Fleet Fuel Operations (Report #0801, Issued October 18, 2007) Report #0811 June 20, 2008 Summary This is the first

More information

Page 1 of 6 ADDENDUM NO. 1. January 11, Shuttle Bus Service RFP # H General

Page 1 of 6 ADDENDUM NO. 1. January 11, Shuttle Bus Service RFP # H General ADDENDUM NO. 1 January 11, 2018 Shuttle Bus Service RFP # H18-0002 1. This addendum revises RFP documents. This addendum is issued to respondents of record prior to execution of contract, and forms a part

More information

Notice is hereby given of the following changes and questions and answers to the above referenced Bid:

Notice is hereby given of the following changes and questions and answers to the above referenced Bid: FLORIDA DEPARTMENT OF TRANSPORTATION Procurement Office Joyce Plummer Joyce.plummer@dot.state.fl.us 605 Suwannee Street, MS 20 Tallahassee, Florida 32399-0450 Phone: (850) 414-4568 ADDENDUM NO. 3 DATE:

More information

Underground Storage Tank. City of Burbank UST Owners & Operators

Underground Storage Tank. City of Burbank UST Owners & Operators Underground Storage Tank City of Burbank UST Owners & Operators Created by: Kern County Environmental Health CUPA, Edited by: Burbank Fire Department for the Burbank Fire Department s use Burbank Fire

More information

UST Compliance Review

UST Compliance Review UST Compliance Review Certificate Dispenser Card Reader Annular probe Spill bucket Fill pipe Tank sump Veeder Root Line Files Tank probe Dispenser sump Note: pumps are either submersible (in tank) or suction

More information

Rockwood School District Diesel Fuel Bid. BIDS DUE ON June 17, 2013 AT 11:00 A.M. CDT

Rockwood School District Diesel Fuel Bid. BIDS DUE ON June 17, 2013 AT 11:00 A.M. CDT Rockwood School District Diesel Fuel Bid BIDS DUE ON June 17, 2013 AT 11:00 A.M. CDT GENERAL SPECIFICATIONS It is the intent of these specifications to furnish the Rockwood School District with the aforementioned

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division COUNTY OF ROCKLAND Department of General Services Purchasing Division Title: Contract Period: Sludge Hauling and Disposal November 8, 2016 through November 7, 2017 with 2 one-year options, Extended through

More information

ADDENDUM NO. I. Penny Owens, Assistant Purchasing Agent, City of Knoxville. December 1, 2017 ** (see below) at 11:00:00 a.m.

ADDENDUM NO. I. Penny Owens, Assistant Purchasing Agent, City of Knoxville. December 1, 2017 ** (see below) at 11:00:00 a.m. DATE: November 27, 2017 ADDENDUM NO. I TO: FROM: SUBJECT: BIDS TO BE OPENED: All Potential Bidders Penny Owens, Assistant Purchasing Agent, City of Knoxville Addendum No. I to the ITB for Bulk Fuel December

More information

EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON

EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON 20 th ANNUAL NATIONAL TANKS CONFERENCE March 17-19, 2008 ATLANTA, GEORGIA SPILL BUCKETS: OPW 1 PETRO STOPPING CENTER JACKSON, MS Six 20,000

More information

Management of Underground Storage Tanks

Management of Underground Storage Tanks Management of Underground Storage Tanks Course No: C03-049 Credit: 3 PDH Mark Rossow, PhD, PE, Retired Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800

More information

UNDERGROUND STORAGE TANK INSPECTION CHECKLIST

UNDERGROUND STORAGE TANK INSPECTION CHECKLIST UNDERGROUND STORAGE TANK INSPECTION CHECKLIST Facility Name: Inspector will mail copy of this inspection report to the tank owner at: General Requirements A. Site Administration 1. Submit/revise Facility

More information

New Amendment to Executive Orders VR-203-N & VR-204-N

New Amendment to Executive Orders VR-203-N & VR-204-N February 12, 2013 003 Technical Service Bulletin New Amendment to Executive Orders VR-203-N & VR-204-N EMCO Balance Models A4005EVR Nozzle and A4119EVR Safebreak Valve Receive CARB EVR Approval for Use

More information

PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843

PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843 BID ADDENDUM NO. 1 PROJECT: PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843 LABELLA PROJECT NO: 2160128 DATE: FEBRUARY 11, 2016 FROM: LaBella

More information

NYS DEPARTMENT OF ENVIRONMENTAL CONSERVATION CLASS C OPERATOR TRAINING

NYS DEPARTMENT OF ENVIRONMENTAL CONSERVATION CLASS C OPERATOR TRAINING NYS DEPARTMENT OF ENVIRONMENTAL CONSERVATION CLASS C OPERATOR TRAINING Presented by: The New York State Association of Service Stations and Repair Shops AT LEAST ONE TRAINED C OPERATOR MUST BE ON DUTY

More information

ROCKLIN UNIFIED SCHOOL DISTRICT ADDENDUM NUMBER 1 TO THE BID DOCUMENTS Amendment Date: January 25, 2019

ROCKLIN UNIFIED SCHOOL DISTRICT ADDENDUM NUMBER 1 TO THE BID DOCUMENTS Amendment Date: January 25, 2019 ROCKLIN UNIFIED SCHOOL DISTRICT ADDENDUM NUMBER 1 TO THE BID DOCUMENTS Amendment Date: January 25, 2019 E-rate Year 22 RFP 2019-115 Cabling Fiber Optic Infrastructure, 4 Sites A. This Amendment shall be

More information

CITY AND COUNTY OF SAN FRANCISCO. SPECIFICATION FOR Copier Lease Agreement Last revision 03/03/2016

CITY AND COUNTY OF SAN FRANCISCO. SPECIFICATION FOR Copier Lease Agreement Last revision 03/03/2016 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 SECTION 1 GENERAL EQUIPMENT SPECIFICATIONS: SPECIFICATION OUTLINE: SFMTA is

More information

NCDEQ Underground Storage Tank Section

NCDEQ Underground Storage Tank Section NCDEQ Underground Storage Tank Section Operation And Maintenance Manual Revised 10/30/2015 i Table of Contents CHAPTER 1. INTRODUCTION... 1 A. Why an Operation and Maintenance Manual?... 1 B. Benefits

More information

Dinwiddie County Administration Office

Dinwiddie County Administration Office Dinwiddie County Administration Office 14016 Boydton Plank Road Phone: (804) 469-4500 Fax: (804) 469-4503 E-Mail: hcasey@dinwiddieva.us ADDENDUM #1 Date: August 21, 2017 Invitation For Bids # 17-081017

More information

Monthly Walkthrough Inspections

Monthly Walkthrough Inspections This form must be used to document the monthly walkthrough inspections. Only complete the sections that apply to your facility. Inspect the applicable items below for your site. If an item is not applicable,

More information

Syracuse University Petroleum Bulk Storage Tank Program Manual

Syracuse University Petroleum Bulk Storage Tank Program Manual Syracuse University Petroleum Bulk Storage Tank Program Manual August 23, 2017 Prepared by: Syracuse University Environmental Health & Safety Services Division of Campus Safety and Emergency Services 029

More information

This handbook is provided as a general guide. https://floridadep.gov/waste/permitting-compliance- assistance/content/storage-tank-compliance

This handbook is provided as a general guide. https://floridadep.gov/waste/permitting-compliance- assistance/content/storage-tank-compliance This handbook is provided as a general guide. For specific regulatory requirements refer to the underground and aboveground storage tank systems rules (Chapters 62-761 and 62-762, Florida Administrative

More information

ADDENDUM NO. 2 DATE: March 3, BID TITLE: Replacement of Two (2) Twenty Ton Overhead Crane Hoists, Trolley Packages, and Associated Equipment

ADDENDUM NO. 2 DATE: March 3, BID TITLE: Replacement of Two (2) Twenty Ton Overhead Crane Hoists, Trolley Packages, and Associated Equipment FLORIDA DEPARTMENT OF TRANSPORTATION Procurement Office 605 Suwannee Street, MS 20 Tallahassee, Florida 32399-0450 Phone: (850) 414-4381 Fax: (850) 414-4951 ADDENDUM NO. 2 DATE: March 3, 2016 RE: BID #:

More information

PURPOSE RESPONSIBILITY

PURPOSE RESPONSIBILITY PAGE 1 OF 6 PURPOSE This Standard Operating Procedure (SOP) provides guidance and methods for Underground Storage Tank (UST) inventory control at Massachusetts Department of Transportation, Highway Division

More information

CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR

CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR Environmental Health - UST Program CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR As part of our inter-local contract with the Nevada Division of Environmental

More information

INVITATION TO BID FUEL PRODUCTS

INVITATION TO BID FUEL PRODUCTS INVITATION TO BID FUEL PRODUCTS Notice is hereby given that the Aberdeen School District is accepting fuel bids and propane bids for the following: 1. Regular, unleaded and diesel fuels for district buses

More information

ADDENDUM NO. 1. April 6, Project: Gas and Diesel Bid for School System Stations

ADDENDUM NO. 1. April 6, Project: Gas and Diesel Bid for School System Stations Livingston Parish Public Schools Excellence in Education! 13909 Florida Boulevard P.O. Box 1130 Livingston, Louisiana 70754-1130 Phone: (225) 686-7044 Fax: (225) 686-3052 Website: www.lpsb.org John Watson

More information

CONTRACT TERM: APRIL 28, 2018 THROUGH APRIL 27, 2020 RES. NO

CONTRACT TERM: APRIL 28, 2018 THROUGH APRIL 27, 2020 RES. NO CONTRACT AWARD AB2018-04 SLUDGE AND SEPTAGE REMOVAL AND SEWER LINE CLEANING FOR THE COUNTY OF MERCER FOR A PERIOD OF TWO (2) YEARS BID OPENING DATE: APRIL 5, 2018 CONTRACT TERM: APRIL 28, 2018 THROUGH

More information

SAN ANTONIO WATER SYSTEM PURCHASING DEPARTMENT

SAN ANTONIO WATER SYSTEM PURCHASING DEPARTMENT SAN ANTONIO WATER SYSTEM PURCHASING DEPARTMENT Issued By: Joseph Ramon Date Issued: July 29, 2014 BID NO.: 14-5053 FORMAL INVITATION FOR BIDS ANNUAL CONTRACT FOR PUMP REPAIRS SUBMERSIBLE TRAINS AND CENTRIFUGAL

More information

CITY OF TACOMA ENVIRONMENTAL SERVICES DEPARTMENT

CITY OF TACOMA ENVIRONMENTAL SERVICES DEPARTMENT CITY OF TACOMA ENVIRONMENTAL SERVICES DEPARTMENT ADDENDUM NO. 2 DATE: March 30, 2017 REVISIONS TO: Request for Bids Specification No. ES17-0020F METAL SOLID WASTE AND RECYCLING CONTAINERS NOTICE TO ALL

More information

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT 06045-0191 ADDENDUM NO. 1 For BID NO. 17/18-36 GENERATOR MAINTENANCE, REPAIR AND EMERGENCY SERVICES 1.

More information

The attached pre-qualification application should be submitted with your bid, in a separate sealed envelope.

The attached pre-qualification application should be submitted with your bid, in a separate sealed envelope. BL098-17 October 9, 2017 INSPECTION, MAINTENANCE AND REPAIR OF HOISTS AND CRANES ON AN ANNUAL CONTRACT ADDENDUM #1 BL098-17 The following should be added to the above-referenced bid. The attached pre-qualification

More information

SAN JOAQUIN VALLEY UNIFIED AIR POLLUTION CONTROL DISTRICT DRAFT STAFF REPORT

SAN JOAQUIN VALLEY UNIFIED AIR POLLUTION CONTROL DISTRICT DRAFT STAFF REPORT DRAFT STAFF REPORT Draft Amendments to Rule 4621 (Gasoline Transfer into Stationary Storage Containers, Delivery Vessels, and Bulk Plants) and Rule 4622 (Gasoline Transfer into Motor Vehicle Fuel Tanks)

More information

UST Program Overview. NISTM Conference June 17, Mark Barolo EPA, Office of Underground Storage Tanks

UST Program Overview. NISTM Conference June 17, Mark Barolo EPA, Office of Underground Storage Tanks UST Program Overview NISTM Conference June 17, 2014 Mark Barolo EPA, Office of Underground Storage Tanks Release Prevention Recent Trends Updating Regulations Biofuels and other Emerging Fuels Energy Policy

More information

NOTICE OF SALE. The City of Sioux Falls, SD, requests formal bids for the sale of Surplus Crown Victoria Sedans.

NOTICE OF SALE. The City of Sioux Falls, SD, requests formal bids for the sale of Surplus Crown Victoria Sedans. PUBLISH: November 27 and December 4, 2009 NOTICE OF SALE The City of Sioux Falls, SD, requests formal bids for the sale of Surplus Crown Victoria Sedans. Sealed bids shall be received by Purchasing, 3rd

More information

NYSDEC PBS REGULATIONS Heating Oil Tanks

NYSDEC PBS REGULATIONS Heating Oil Tanks 1 NYSDEC PBS REGULATIONS Heating Oil Tanks Central Office/Region 2 Division of Environmental Remediation Bulk Storage Compliance Program NISTM 2017 New York Storage Tank Conference Saint Francis College,

More information

THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS

THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS Presented by: Joyce A. Rizzo President JD2 Environmental, Inc. 800 East Washington Street West Chester, PA 19380 www.jd2env.com

More information

4 FEET HIGH CHAIN LINK FENCE AND GATE. TO INCLUDE TOP RAIL AND ALL OTHER HARDWARE, POSTS, ETC. NOT INCLUDED BELOW.

4 FEET HIGH CHAIN LINK FENCE AND GATE. TO INCLUDE TOP RAIL AND ALL OTHER HARDWARE, POSTS, ETC. NOT INCLUDED BELOW. 4 FEET HIGH CHAIN LINK FENCE AND GATE. TO INCLUDE TOP RAIL AND ALL OTHER HARDWARE, POSTS, ETC. NOT INCLUDED SIGNED BID / SIGNED ADDENDUM Yes / Yes Yes / Yes Yes / Yes YEARS EXPERIENCE 25 Years 24 Years,

More information