Transient reactive power characteristics of HVDC during commutation failure and impact of HVDC control parameters
|
|
- Everett Griffin
- 5 years ago
- Views:
Transcription
1 The 6th International Conference on Renewable Power Generation (RPG) October 2017 Transient reactive power characteristics of HVDC during commutation failure and impact of HVDC control parameters Jingzhe Tu 1, Yan Pan 2, Jian Zhang 1, Bing Zeng 1, Junchuan Jia 1, Jun Yi 1 1 China Electric Power Research Institute, Beijing, People s Republic of China 2 C-EPRI Electric Power Engineering Co. Ltd, Beijing, People s Republic of China tujingzhe@epri.sgcc.com.cn Published in The Journal of Engineering; Received on 9th October 2017; Accepted on 1st November 2017 Abstract: HVDC commutation failure and recovery, the reactive power exchanged between HVDC and AC systems will change largely, showing the external characteristic of large capacity reactive impact load, so it is quite necessary to carry out studies on this problem. In this study, first, the HVDC sending-side and receiving-side reactive power equations in steady state and transient process are given. Second, the HVDC sending-side and receiving-side reactive power characteristics during commutation failure and recovery are analysed. Finally, the impact of the HVDC control system parameters is studied. All the contents are verified by simulation of the HVDC equivalent case system. 1 Introduction As the HVDC transmission projects are being continually commissioned, the strong DC and weak AC characteristic of the power system is becoming gradually apparent. HVDC has an advantage in large capacity and long distance, but will also bring security and stability problems. The converters on the sending side and receiving side both consume a large amount of reactive power in operation, usually, the reactive power consumed by the rectifier and inverter is and 40 60% of the active power, respectively [1 3]. Commutation failure is one of the most common contingencies in HVDC [4 6], which has a great impact on the stability of the sending-side and receiving-side AC systems [7 10]. During HVDC commutation failure and recovery, the reactive power consumed by converters and supplied by AC filters has a transient process. So the reactive power exchanged between HVDC and the sending-side/ receiving-side AC system will change largely, showing the external characteristic of large capacity reactive impact load which is harmful to the system. So far, there have been several papers studying the HVDC reactive power characteristic and its impact on system, mainly in two aspects: (i) HVDC reactive power characteristic in steady state and under small disturbances Zheng et al. [11, 12] analyse the dynamic reactive power trajectory characteristic of the rectifier and inverter, respectively. Xin et al. [13] propose an index of the multi-infeed HVDC generalised short-circuit ratio, which can precisely measure the supporting of the receiving-side AC system to the HVDCs. (ii) Impact of HVDC control on reactive power characteristic the authors of [14, 15] study the impact of a control mode of the rectifier and inverter on commutation failure, respectively. On the base of that Yang et al. [16] furtherly studies the overshoot problem during HVDC commutation failure. It can be seen that most studies are mainly concerned about local problems using simulation, but lacking integrated studies on HVDC transient reactive power characteristic during commutation failure and recovery. Therefore, it is quite necessary to carry out studies on this problem. In this paper, first, the differential-algebraic equations describing the HVDC sending-side and receiving-side reactive power characteristics in steady state and transient process are given. Second, the HVDC reactive power characteristic of the sending side and receiving side during commutation failures and recovery is analysed. Finally, on the base of those, the impact of the HVDC control system parameters on transient reactive power characteristic is studied. All the contents are verified by simulation of the HVDC equivalent case system. 2 HVDC reactive power equations in steady state and transient process 2.1 Steady state According to the HVDC quasi-steady state model [1, 2], the reactive power exchanged between HVDC and AC system (positive if absorbing reactive power from AC system, negative if sending reactive power to AC system) is shown as U r0 = 3 2 Nr T p r U r, U i0 = 3 2 Ni T p i U i (1) U dr = U r0 cos a 3 p N r X cr I d, U di = U i0 cos g 3 p N i X ci I d (2) U dr U di = R d I d (3) ( w r = arccos U ) ( dr, w U i = arccos U ) di r0 U i0 (4) P r = 2U dr I d, P i = 2U di I d (5) Q r = P r tan w r U 2 r B r, Q i = P i tan w i U 2 i B i (6) where U r0, U i0 denote the DC open-circuit voltage (subscript r, i denote the rectifier side and inverter side, the same hereinafter), N r, N i denote the number of 6-pulse converters (normally EHVDC with 2, UHVDC with 4), T r, T i denote the tap ratio of converter transformers, U r, U i denote the converter bus AC voltage, U dr, U di denote the DC voltage, a denotes the rectifier ignition angle, g denotes the inverter extinction angle, X cr, X ci denote the commutation reactance, I d denotes the DC current, R d denotes the
2 DC line resistance, w r, w i denote the power factor angle, P r, P i denote the DC active power, B r, B i denote the AC filter susceptance, Q r, Q i denote the reactive power exchanged between HVDC and AC system. Therefore, the reactive power exchanged between HVDC and AC system in steady state can be calculated by solving the algebraic equations shown in (1) (6), easy for a theoretical calculation. 2.2 Transient process Contingencies of HVDC itself or the sending-side/receiving-side AC system, will both make HVDC enter into a transient process [3]. In HVDC transient process, the main variables are the rectifier ignition angle a, the inverter ignition angle b (the extinction angle g), and the DC current I d. In which, a, b (g) are decided by the differential-algebraic equations of HVDC control system, I d is decided by differential equations of HVDC transmission line HVDC control system: The HVDC control system used in practical HVDC projects in China can be divided into ABB technology and Siemens technology, the main differences lie in the inverter-side control mode, but the HVDC transient regulation characteristics of the two are similar during commutation failure [15]. In this paper, ABB technology is taken as an example, the main structure of an ABB HVDC control system can be seen in Fig. 1. The ABB HVDC control system mainly includes three levels: the main control, the pole control, and the ignition control. The pole control mainly includes the DC current controller, the DC voltage controller, and the extinction angle controller. These three fundamental controllers all have independent proportional integral (PI) regulators, and the coordination method of magnitude limit, in turn, is applied. In the transient process after contingencies, according to the set logic, the HVDC control system will rapidly output the rectifier and inverter ignition angle a, b, g [17]. Because the HVDC control system is very complicated, in order to simplify analysis and illustration, the differential-algebraic equations describing the transient process of the HVDC control system are shown as dx r dt = f r (x r, U r, I d, a), dx i dt = f i (x i, U i, I d, g) (7) 0 = g r (x r, U r, I d, a), 0 = g i (x i, U i, I d, g) (8) where f r ( ) f i ( ) denote the state equation of rectifier and inverter HVDC control, g r ( ), g i ( ) denote the corresponding output equation, x r, x i denote the state variables of HVDC control system. It should be noted that the ABB inverter extinction angle control (AMAX) is a predictive open-loop control, so its Fig. 1 Main structure of ABB HVDC control system differential-algebraic equation will degenerate to the algebraic equation: 0 = g i (x i, U i, I d, g) HVDC transmission line: The differential equation of HVDC transmission line is shown as U dr U di = (L r + L i + L d ) di d dt + R d I d (9) where L r L i denote the reactance of smooth reactor, L d denotes the reactance of HVDC transmission line. In the transient calculation, (3) should be replaced by (9). Therefore, in the transient process, the reactive power exchanged between HVDC and AC system can be calculated by solving the differential-algebraic equations shown in (1) (9). Normally, the numerical integration method with the help of power system simulation software is needed. 3 HVDC receiving-side transient reactive power characteristic during commutation failure and recovery 3.1 HVDC receiving-side transient reactive power characteristic during commutation failure Under different short-circuit fault locations resulting in HVDC commutation failure, the reactive power absorbed by HVDC from the receiving-side AC system changes greatly, which can be divided into the following two conditions Fault near to the inverter: The short-circuit fault near to the inverter will result in HVDC commutation failure, the inverter bus AC voltage will drop to a low level (will drop to 0 after a fault on the inverter bus). The commutation failure prediction (CFPREV) will operate to decrease the inverter ignition angle, making the inverter DC voltage drop to nearly 0 (U i0 0 in (2)). Although the DC current will have a transient process of rapid increase (U di 0 in (9)), the reactive power consumed by the inverter during commutation failure is nearly 0 (P i tan w i 0 in (6)). The inverter bus AC voltage is very low during commutation failure, making the reactive power supplied by AC filters is nearly 0 (Ui 2 B i 0 in (6)). Therefore, during commutation failure, HVDC will absorb nearly 0 reactive power from the receiving-side AC system (the reactive power consumed by the inverter minus the reactive power supplied by AC filters) under nearby fault Fault distant from the inverter: The short-circuit fault distant from the inverter can also result in commutation failure, the inverter bus AC voltage will still remain at a high level (with enough voltage drop to cause commutation failure). CEPREV will operate to decrease the inverter ignition angle, and the inverter DC voltage can still remain above 0 (U i0. 0 in (2)). So the rapid increase of DC current during commutation failure (U di. 0 in (9)), will make the inverter consume a large amount of reactive power (P i tan w i very large in (6)). Although the inverter bus AC voltage can still remain during commutation failure, the reactive power supplied by AC filters is still much smaller than the reactive power consumed by the inverter (Ui 2 B i a little bit small in (6)). Therefore, during commutation failure, HVDC will absorb a large amount of reactive power from the receiving-side AC system under remote fault. 3.2 HVDC receiving-side transient reactive power characteristic during recovery Under different strength conditions of the receiving-side AC system, the relative recovery speed of the AC voltage and the DC power is different, the HVDC receiving-side transient reactive power characteristic varies, which can be divided into the following two conditions.
3 3.2.1 Strong receiving-side AC system: If the receiving-side AC system infeed by HVDC is strong (the effective short-circuit ratio ESCR. 3), the recovery speed of the AC voltage is normally faster than that of the DC power (measured by the time from fault cleared to AC voltage/dc power recovered to 90% of the prefault steady-state value). After fault cleared, the AC voltage will rapidly recover to the steady-state value. Because the voltagedependent current order limit (VDCOL) restricting current increase has a time delay, the DC power recovery has some time lag. After fault cleared and before DC power recovered, the reactive power supplied by AC filters is much larger than the reactive power consumed by the inverter (P i, steady state value and U i steady state value in (6)), HVDC will send a large amount of reactive power to the receiving-side AC system. After HVDC recovered to the rated power, because of the overshoot effect of the PI controller [16], the DC power will continually increase exceeding the rated value and then decrease. During the short period after HVDC recovered, the reactive power consumed by the inverter will be larger than the reactive power supplied by AC filters (P i. steady state value and U i steady state value in (6)), HVDC will absorb some reactive power from the receiving-side AC system. Therefore, during commutation failure recovery, HVDC will firstly send a large amount of reactive power to the receiving-side AC system and then absorb some reactive power from the receiving-side AC system under strong system conditions Weak receiving-side AC system: If the receiving-side AC system infeed by HVDC is weak (ESCR, 3), the recovery speed of the AC voltage may be slower than that of the DC power. The receiving-side AC system lacks dynamic reactive power support because of small short-circuit capacity, the AC voltage recovery after fault cleared is slow, making the reactive power supplied by AC filters is small. If HVDC has already got rid of the restriction of VDCOL making the DC power recover normally at that time, the reactive power consumed by the inverter may be always larger than the reactive power supplied by AC filters (P i steady state value and U i, steady state value in (6)). Therefore, during commutation failure recovery, HVDC may continually absorb some reactive power from the receiving-side AC system under weak system conditions. 3.3 Case system analysis Comparison of electromagnetic simulation and electromechanical simulation: Simulations are performed on the detailed electromagnetic model and the simplified electromechanical model [17] of a practical UHVDC applying the electromagnetic program PSCAD and the electromechanical program PSD-BPA, respectively (fault clearance time is 0.1 s). During HVDC commutation failure and recovery, the electromagnetic and electromechanical caparison curves of the reactive power exchanged between HVDC and the receiving-side AC system (positive if absorbing reactive power from AC system, negative if sending reactive power to AC system) are shown in Figs. 2 and 3. It can be seen from Figs. 2 and 3, the simulation results of the simplified electromechanical model are almost the same as the detailed electromagnetic model, which can precisely reflect the HVDC receiving-side transient reactive power characteristic during commutation failure and recovery. Therefore, the electromechanical program of PSD-BPA is used as the simulation tool in the following case system analysis HVDC receiving-side transient reactive power characteristic simulation (nearby fault): Simulation analysis is performed on the HVDC equivalent case system (ideal power source with series impedance) applying PSD-BPA. During HVDC commutation failure Fig. 2 Comparison curves of the reactive power exchanged with the receiving-side AC system (nearby fault) Fig. 3 Comparison curves of the reactive power exchanged with the receiving-side AC system (remote fault) resulted by inverter nearby fault, the simulation curves of reactive power consumed by HVDC, reactive power supplied by AC filters, and reactive power exchanged with the receiving-side AC system are shown in Fig. 4. It can be seen from Fig. 4, during HVDC commutation failure resulted by nearby fault, the reactive power consumed by HVDC is nearly 0, the reactive power supplied by AC filters is also nearly 0, so the reactive power absorbed by HVDC from the receiving-side AC system is nearly 0. After fault cleared and HVDC entered into recovery process, the reactive power supplied by AC filters instantly increases from 0 to 3600 Mvar (strong receiving-side system), and after a time delay of 40 ms, the reactive power absorbed by HVDC increases from 0 to 4600 Mvar in 50 ms, then gradually recovers to the steady-state value 3500 Mvar. Therefore, the reactive power absorbed by HVDC from the receiving-side AC system reaches the maximum value 1400 Mvar in 90 ms after fault cleared HVDC receiving-side transient reactive power characteristic simulation (remote fault): During HVDC commutation failure Fig. 4 Reactive power curves of the HVDC receiving side (nearby fault)
4 rectifier (Ur 2 B r not vary a lot in (6)). Therefore, during commutation failure, HVDC will absorb large amount of reactive power from the sending-side AC system in the stage of current increase. Fig. 5 Reactive power curves of the HVDC receiving side (remote fault) resulted by inverter remote fault, the simulation curves of reactive power consumed by HVDC, reactive power supplied by AC filters, and reactive power exchanged with the receiving-side AC system are shown in Fig. 5. It can be seen from Fig. 5, during HVDC commutation failure resulted by remote fault, the reactive power consumed by HVDC first increases to the maximum value 4200 Mvar in 30 ms and then decreases, the reactive power supplied by AC filters is kept at 1200 Mvar, so the reactive power absorbed by HVDC from the receiving-side AC system reaches the maximum value 3000 Mvar in 30 ms after fault. After the fault cleared and HVDC entered into the recovery process, which is almost the same as the nearby fault, the reactive power absorbed by HVDC from the receivingside AC system reaches the maximum value 1400 Mvar in 90 ms after fault cleared. Therefore, the simulation results show that, the threat of commutation failure on the receiving-side AC system is mainly the voltage instability resulted by large amount of reactive power absorbed by HVDC. 4 HVDC sending-side transient reactive power characteristic during commutation failure and recovery HVDC commutation failure is caused by incomplete recovery of the inverter thyristors blocking capability, so the rectifier will not have commutation failure [1 3, 18]. However, the HVDC control of the two sides is coupled with each other, so HVDC commutation failure of the receiving side will also result in transient reactive power variation of the sending side. 4.1 HVDC sending-side transient reactive power characteristic during commutation failure After HVDC commutation failure, the control system will decrease the DC current order, making the DC current have the transient process of firstly increase and then decrease, which can be divided into the following two stages DC current decrease stage: As the rectifier ignition angle continually increases, the DC current will reach the maximum value and then rapidly decrease, finally reaching the VDCOL restricted minimum value (U dr decrease rapidly in (9)). As the DC current rapidly decreases to the minimum value, the reactive power consumed by the rectifier will also rapidly decrease to nearly 0 (P r tan w r very small in (6)). But the reactive power supplied by AC filters still does not vary a lot due to small fluctuations of bus voltage, much larger than the reactive power consumed by the rectifier (U 2 r B r not vary a lot in (6)). Therefore, during commutation failure, HVDC will send large amount of reactive power to the sending-side AC system in the stage of current decrease. 4.2 HVDC sending-side transient reactive power characteristic during recovery As the same as the HVDC receiving side, after the DC power recovered to the rated value, the overshoot effect of the PI controller will make the reactive power consumed by the rectifier be larger than the reactive power supplied by AC filters in a short period. Therefore, during commutation failure recovery, HVDC will absorb some reactive power from the sending-side AC system. 4.3 Case system analysis Comparison of electromagnetic simulation and electromechanical simulation: During HVDC commutation failure and recovery, the electromagnetic and electromechanical caparison curves of the reactive power exchanged with the sending-side AC system are shown in Fig. 6. It can be seen in Fig. 6, the simulation results of the simplified electromechanical model are almost the same as the detailed electromagnetic model, which can precisely reflect the HVDC sendingside transient reactive power characteristic during commutation failure and recovery. Therefore, the electromechanical program of PSD-BPA is used as the simulation tool in the following case system analysis HVDC sending-side transient reactive power characteristic simulation: Simulation analysis is performed on the HVDC equivalent case system. During HVDC commutation failure, the simulation curves of reactive power consumed by HVDC, reactive power supplied by AC filters, and reactive power exchanged with the sending-side AC system are shown in Fig. 7. It can be seen from Fig. 7, during HVDC commutation failure, the reactive power consumed by HVDC increases from 3600 Mvar to the maximum value 11,600 Mvar in 30 ms, then gradually decreases to the minimum value 0 in 50 ms. The reactive DC current increase stage: After HVDC commutation failure and before fault cleared, the inverter DC voltage remains at a low level. Under the function of VDCOL, the DC current order will be restricted at the minimum value (0 0.3 p.u.). In order to decrease the DC current to the VDCOL restricted minimum value after commutation failure, the function of current control (CCA) will rapidly increase the rectifier ignition angle to above 90. Because the control system has some time delay, at the early stage of the ignition angle increase, the DC current will still increase continually (U di very small in (9)). Because both of the DC current and the rectifier ignition angle increase rapidly, the rectifier will consume large amount of reactive power (P r tan w r very large in (6)). However, the reactive power supplied by AC filters does not vary a lot due to small fluctuations of bus voltage, much smaller than the reactive power consumed by the Fig. 6 Comparison curves of the reactive power exchanged with the sending-side AC system
5 Table 1 Maximum output reactive power of the HVDC sending side under different VDCOL parameters U dhigh Q I omin Q T U dtdn Q Table 2 Maximum input reactive power of the HVDC receiving side under different VDCOL parameters Fig. 7 Reactive power curves of the HVDC sending side power supplied by AC filters fluctuates in the range of Mvar. Therefore, the reactive power sent by HVDC to the sending-side AC system reaches the maximum value 3600 Mvar in 80 ms after a fault. HVDC will enter the recovery process after fault cleared, which is almost the same as the receiving side. Therefore, the simulation results show that the threat of commutation failure on the sending-side AC system is mainly the transient overvoltage resulted by a large amount of reactive power sent by HVDC. 5 Impact of control parameters on HVDC sending-side and receiving-side reactive power characteristics 5.1 VDCOL parameters VDCOL is normally installed both on the HVDC rectifier side and the inverter side [19]. When the DC voltage drops resulted by AC/ DC contingencies, VDCOL will limit the DC current order of the main control. The VDCOL characteristic curves under different parameters are shown in Fig. 8. In which, U dlow denotes the VDCOL start voltage, U dhigh the denotes VDCOL quit voltage, I omin denotes the VDCOL minimum current order. It can be seen from Figs. 8b d, increasing U dlow, increasing U dhigh, and decreasing I omin of the inverter-side VDCOL, can decrease the reactive power absorbed by HVDC from the receivingside AC system during commutation failure and recovery. U dhigh Q I omin Q T U dtup Q Decreasing U dlow, decreasing U dhigh, and increasing I omin of the rectifier-side VDCOL, can decrease the reactive power sent by HVDC to the sending-side AC system during commutation failure. Moreover, increasing the voltage drop filtering time constant T U dtdn of the rectifier-side VDCOL can decrease the reactive power sent by HVDC to the sending-side AC system during commutation failure. Increasing the voltage rise filtering time constant T U dtup of the inverter-side VDCOL can decrease the reactive power absorbed by HVDC from the receiving-side AC system HVDC commutation failure recovery. The simulation results are shown in Tables 1 and CFPREV parameters CFPREV is normally installed on the HVDC inverter-side applying ABB technology [20]. When the inverter bus voltage drop exceeding the threshold is detected, CFPREV will operate and rapidly decrease the inverter ignition angle, in order to increase the commutation margin. In CFPREV, increasing the commutation failure prediction gain G cf and the angle reduce the time constant T dn cf, will increase the reactive power absorbed by HVDC from the receiving-side AC system. The simulation results are shown in Table CCA parameters CCA is one of the basic controllers in HVDC pole control system [21]. In the steady state, the rectifier current controller will take effect, but in the transient process after fault, the inverter will also take over to control the DC current in some period. In CCA, increasing the DC current filtering time constant T I dt and the gain constant Gain of constant current control will accelerate the DC current reduce speed after reaching the maximum value during commutation failure, and increase the reactive power sent by HVDC to the sending-side AC system. The simulation results are shown in Table 4. Table 3 Maximum input reactive power of the HVDC receiving side under different CFPREV parameters Fig. 8 VDCOL characteristic curves under different parameters a Basic characteristic bu dlow variation c U dhigh variation di omin variation G cf Q T dn cf Q
6 Table 4 Maximum output reactive power of the HVDC sending side under different CCA parameters T I dt Q Gain Q Conclusions (a) During commutation failure, HVDC will absorb nearly 0 reactive power from the receiving-side AC system under nearby fault and will absorb a large amount of reactive power from the receiving-side AC system under remote fault. (b) During commutation failure recovery, HVDC will firstly send a large amount of reactive power to the receiving-side AC system, then absorb some reactive power from the receiving-side AC system under the condition of the strong system, and will continually absorb some reactive power from the receiving-side AC system under the condition of the weak system. (c) During commutation failure, HVDC will absorb a large amount of reactive power from the sending-side AC system at the stage of DC current increase and will send large amount of reactive power to the sending-side AC system at the stage of DC current decrease. (d) Optimising important control parameters setting such as VDCOL, CFPREV, CCA and so on, can decrease the maximum reactive power exchanged between HVDC and the sending-side and receiving-side AC systems during the process of commutation failure. Studies such as the impact of reactive power impact on system stability and HVDC control parameters optimisation to improve system stability level will be conducted in the future. 7 References [1] Kimbark E.W.: Direct current transmission (Wiley-Inter science, New York, 1971) [2] Kundur P.: Power system stability and control (McGraw-Hill, New York, 1994) [3] Arrillaga J., Smith B.: AC-DC power system analysis (IET, London, 1998) [4] Zhou C., Xu Z.: Study on commutation failure of multi-infeed HVDC system. Proc. of 2002 Int. Conf. Power System Technology, 2002, pp [5] Wang Y., Li X., Wen C., ET AL.: Impact of AC system strength on commutation failure at HVDC inverter station. Proc. of 2012 Asia-Pacific Power and Energy Engineering Conf., 2012, pp. 1 4 [6] Rahimi E., Gole A.M., Davies J.B., ET AL.: Commutation failure analysis in multi-infeed HVDC systems, IEEE Trans. Power Deliv., 2011, 26, (1), pp [7] Aik D.L.H., Andersson G.: Voltage stability analysis of multi-infeed HVDC systems, IEEE Trans. Power Deliv., 1997, 12, (3), pp [8] Wang J., Zhao C., Hu J., ET AL.: The analysis and simulation of commutation failure and protection strategies. Proc. of the 4th Int. Conf. Electric Utility Deregulation and Restructuring and Power Technologies, 2011, pp [9] Xia C., Suo M., Xi L.: Analysis on commutation failure caused by AC faults in multi-infeed HVDC systems. Proc. of 2012 IEEE Power Engineering and Automation Conf., 2012, pp. 1 4 [10] He J., Li M., Yi J., ET AL.: Research on dynamic characteristics and countermeasures of AC-DC hybrid power system with large scale HVDC transmission. Proc. of 2014 Int. Conf. Power System Technology, 2014, pp [11] Zheng C., Tang Y., Ma S., ET AL.: Study on the dynamic reactive power characteristic of HVDC rectifier stations and optimization measure, Proc. CSEE, 2014, 34, (28), pp [12] Wang H., Zheng C., Ren J., ET AL.: Dynamic reactive power trajectory of HVDC inverter station and its optimization measures, Power Syst. Technol., 2015, 39, (5), pp [13] Xin H., Zhang F., Yu Y., ET AL.: Generalized short circuit ratio for multi-infeed DC systems: definition and theoretical analysis, Proc. CSEE, 2016, 36, (3), pp [14] Chen S., Rong J., Bi G., ET AL.: Study of the effect of rectifier side control modes on UHVDC commutation failure, Electr. Power, 2015, 48, (7), pp. 1 7 [15] Li Y., Lu Y., Liu X., ET AL.: Influence of inverter control strategy on commutation failure and recovery characteristic optimization, Electr. Power Constr., 2015, 36, (9), pp [16] Yang H., Zhu L., Cai Z., ET AL.: Influence of HVDC control on HVDC reactive power dynamic characteristic, Power Syst. Technol., 2014, 38, (10), pp [17] Wan L., Ding H., Liu W.: Simulation model of control system for HVDC power transmission based on actual project, Power Syst. Technol., 2013, 37, (3), pp [18] Arrillaga J.: High voltage direct current transmission (IET, London, 1998) [19] Zhou B., Du Z., Luo D., ET AL.: VDCOL parameters design of multiinfeed HVDC based on a simplified model of DC P-Q coupling recovery. Proc. of 2014 IEEE PES Asia-Pacific Power and Energy Engineering Conf., 2014, pp. 1 7 [20] Wei Z., Yuan Y., Lei X., ET AL.: Direct-current predictive control strategy for inhibiting commutation failure in HVDC converter, IEEE Trans. Power Syst., 2014, 29, (5), pp [21] Xie G., Wang M.: Parameter optimization for current controller in HVDC control system. Proc. of 2010 Int. Conf. Power System Technology, 2010, pp. 1 5
The Modeling and Simulation of DC Traction Power Supply Network for Urban Rail Transit Based on Simulink
Journal of Physics: Conference Series PAPER OPEN ACCESS The Modeling and Simulation of DC Traction Power Supply Network for Urban Rail Transit Based on Simulink To cite this article: Fang Mao et al 2018
More informationResearch on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC
Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,
More informationA novel synthetic test system for thyristor level in the converter valve of HVDC power transmission
A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission Longchen Liu 1, Ke Yue 2, Lei Pang 2, Xinghai Zhang 1, Yawei Li 1 and Qiaogen Zhang 2 1 State Grid Sichuan
More informationECEN 667 Power System Stability Lecture 19: Load Models
ECEN 667 Power System Stability Lecture 19: Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter 7 Homework 6 is
More informationCombination control for photovoltaic-battery-diesel hybrid micro grid system
, pp.93-99 http://dx.doi.org/10.14257/astl.2015.82.18 Combination control for photovoltaic-battery-diesel hybrid micro grid system Yuanzhuo Du 1, Jinsong Liu 2 1 Shenyang Institute of Engineering, Shenyang,
More informationFAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE
FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The
More informationParameters Matching and Simulation on a Hybrid Power System for Electric Bulldozer Hong Wang 1, Qiang Song 2,, Feng-Chun SUN 3 and Pu Zeng 4
2nd International Conference on Electronic & Mechanical Engineering and Information Technology (EMEIT-2012) Parameters Matching and Simulation on a Hybrid Power System for Electric Bulldozer Hong Wang
More informationMODELING AND SIMULATION OF INTERNAL CIRCULATION TWO-PLATEN INJECTION MOLDING MACHINE BASED ON AMESIM
MODELING AND SIMULATION OF INTERNAL CIRCULATION TWO-PLATEN INJECTION MOLDING MACHINE BASED ON AMESIM Lu Yang, Jiong Peng, Dongjie Chen and Jian Wang* Beijing Institute of Technology, Beijing 100081, China
More informationStudy on Flow Characteristic of Gear Pumps by Gear Tooth Shapes
Journal of Applied Science and Engineering, Vol. 20, No. 3, pp. 367 372 (2017) DOI: 10.6180/jase.2017.20.3.11 Study on Flow Characteristic of Gear Pumps by Gear Tooth Shapes Wen Wang 1, Yan-Mei Yin 1,
More informationInfluence of Ground Effect on Aerodynamic Performance of Maglev Train
2017 2nd International Conference on Industrial Aerodynamics (ICIA 2017) ISBN: 978-1-60595-481-3 Influence of Ground Effect on Aerodynamic Performance of Maglev Train Shi Meng and Dan Zhou ABSTRACT Three-dimensioned
More informationAdaptive Power Flow Method for Distribution Systems With Dispersed Generation
822 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 3, JULY 2002 Adaptive Power Flow Method for Distribution Systems With Dispersed Generation Y. Zhu and K. Tomsovic Abstract Recently, there has been
More informationCascading Fault in AC/DC Hybrid Power Grid Xinzhou Dong
Cascading Fault in AC/DC Hybrid Power Grid Xinzhou Dong Tsinghua University, Beijing, China 30 th March, San Francissico, USA 1 2 3 4 5 Background Cascading Fault in AC/DC Hybrid Grid Model and Simulation
More informationAbstract. Keywords. 1. Introduction. Zhi An, Ansi Wang, Huadong Sun, Yong Tang
Journal of Power and Energy Engineering, 214, 2, 624-631 Published Online April 214 in SciRes. http://www.scirp.org/journal/jpee http://dx.doi.org/1.4236/jpee.214.2484 Influencing Factors of the Power
More informationChina. Fig. 1 Chain SVG Electrical Diagram
Applied Mechanics and Materials Submitted: 2014-07-20 ISSN: 1662-7482, Vols. 644-650, pp 3861-3865 Accepted: 2014-07-22 doi:10.4028/www.scientific.net/amm.644-650.3861 Online: 2014-09-22 2014 Trans Tech
More informationCorrelation of Occupant Evaluation Index on Vehicle-occupant-guardrail Impact System Guo-sheng ZHANG, Hong-li LIU and Zhi-sheng DONG
07 nd International Conference on Computer, Mechatronics and Electronic Engineering (CMEE 07) ISBN: 978--60595-53- Correlation of Occupant Evaluation Index on Vehicle-occupant-guardrail Impact System Guo-sheng
More informationEngine Control Strategy for AMT Upshifting of Commercial Vehicle
06 International Conference on Applied Mechanics, Electronics and Mechatronics Engineering (AMEME 06) ISBN: 978--609-7- Engine Control Strategy for AMT Upshifting of Commercial Vehicle Zhen-jie LIU,*,
More informationTransient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode
International Journal for Research in Engineering Application & Management (IJREAM) Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode 1 Soumitra S. Kunte,
More informationFaults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC
SPEEDAM 2010 International Symposium on Power Electronics, Electrical Drives, Automation and Motion Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations
More informationWind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment
2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in
More informationKey Parameters Investigation on Small Cycle Fuel Injection Quantity for a Diesel Engine Electronic Unit Pump System
Page63 EVS25 Shenzhen, China, Nov 5-9, 21 Key Parameters Investigation on Small Cycle Fuel Injection Quantity for a Diesel Engine Electronic Unit Pump System Abstract Liyun Fan 1, Bingqi Tian 1, and Xiuzhen
More informationAvailable online at ScienceDirect. Physics Procedia 67 (2015 )
Available online at www.sciencedirect.com ScienceDirect Physics Procedia 67 (2015 ) 518 523 25th International Cryogenic Engineering Conference and the International Cryogenic Materials Conference in 2014,
More informationResearch on the charging system of electric vehicle photovoltaic cells HUANG Jun ( Hunan Railway Professional Technology College, Zhuzhou, )
6th International Conference on Information Engineering for Mechanics and Materials (ICIMM 2016) Research on the charging system of electric vehicle photovoltaic cells HUAG Jun ( Hunan Railway Professional
More informationA Method of Spot Price Bidding in Day-Ahead Power Market With the consideration of power shortage factor
A Method of Spot Price Bidding in Day-Ahead Power Market With the consideration of power shortage factor CHEN YUCHEN 1,2, CAO MINNIAN 2, HOU ZHIJIAN 1 1. The Electrical Engineering Dept. 2. The Electrical
More informationResearch on PV and battery control system with energy management technology in stand-alone DC micro grid
International Industrial Informatics and Computer Engineering Conference (IIICEC 25) Research on PV and battery control system with energy management technology in stand-alone DC micro grid Chunxue Wen,a,
More informationA Measuring Method About the Bullet Velocity in Electromagnetic Rail Gun
Sensors & Transducers 214 by ISA Publishing, S. L. http://www.sensorsportal.com A Measuring Method About the Bullet Velocity in Electromagnetic Rail Gun Jianming LIU, Zhiyong BAO, Yang LIU, Zhenchun WANG,
More informationIEEE Transactions on Applied Superconductivity, 2012, v. 22 n. 3, p :1-5
Title Transient stability analysis of SMES for smart grid with vehicleto-grid operation Author(s) Wu, D; Chau, KT; Liu, C; Gao, S; Li, F Citation IEEE Transactions on Applied Superconductivity, 2012, v.
More informationVoltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC
IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 01 July 2015 ISSN (online): 2349-784X Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC Ravindra Mohana
More informationThe Design of Vehicle Tire Pressure Monitoring System Based on Bluetooth
5th International Conference on Advanced Engineering Materials and Technology (AEMT 2015) The Design of Vehicle Tire Pressure Monitoring System Based on Bluetooth Liqing Geng 1, a *, Li Zhao 2,b, Zeyu
More informationEnhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System
Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Raju Pandey, A. K. Kori Abstract FACTS devices can be added to power transmission and distribution systems at appropriate
More informationAnalysis on natural characteristics of four-stage main transmission system in three-engine helicopter
Article ID: 18558; Draft date: 2017-06-12 23:31 Analysis on natural characteristics of four-stage main transmission system in three-engine helicopter Yuan Chen 1, Ru-peng Zhu 2, Ye-ping Xiong 3, Guang-hu
More informationCHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM
61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this
More informationElectromagnetic Field Analysis for Permanent Magnet Retarder by Finite Element Method
017 Asia-Pacific Engineering and Technology Conference (APETC 017) ISBN: 978-1-60595-443-1 Electromagnetic Field Analysis for Permanent Magnet Retarder by Finite Element Method Chengye Liu, Xinhua Zhang
More informationResearch on Collision Characteristics for Rear Protective Device of Tank Vehicle Guo-sheng ZHANG, Lin-sen DU and Shuai LI
2017 2nd International Conference on Computer, Mechatronics and Electronic Engineering (CMEE 2017) ISBN: 978-1-60595-532-2 Research on Collision Characteristics for Rear Protective Device of Tank Vehicle
More informationRotor Position Detection of CPPM Belt Starter Generator with Trapezoidal Back EMF using Six Hall Sensors
Journal of Magnetics 21(2), 173-178 (2016) ISSN (Print) 1226-1750 ISSN (Online) 2233-6656 http://dx.doi.org/10.4283/jmag.2016.21.2.173 Rotor Position Detection of CPPM Belt Starter Generator with Trapezoidal
More informationOverview of Flexible AC Transmission Systems
Overview of Flexible AC Transmission Systems What is FACTS? Flexible AC Transmission System (FACTS): Alternating current transmission systems incorporating power electronic-based and other static controllers
More informationReactive power support of smart distribution grids using optimal management of charging parking of PHEV
Journal of Scientific Research and Development 2 (3): 210-215, 2015 Available online at www.jsrad.org ISSN 1115-7569 2015 JSRAD Reactive power support of smart distribution grids using optimal management
More informationEnhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor
> 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper
More informationThe design and implementation of a simulation platform for the running of high-speed trains based on High Level Architecture
Computers in Railways XIV Special Contributions 79 The design and implementation of a simulation platform for the running of high-speed trains based on High Level Architecture X. Lin, Q. Y. Wang, Z. C.
More informationAn Energy Efficiency Measurement Scheme for Electric Car Charging Pile Chun-bing JIANG
2017 2 nd International Conference on Test, Measurement and Computational Method (TMCM 2017) ISBN: 978-1-60595-465-3 An Energy Efficiency Measurement Scheme for Electric Car Charging Pile Chun-bing JIANG
More informationThe Simulation of Metro Wheel Tread Temperature in Emergency Braking Condition Hong-Guang CUI 1 and Guo HU 2*
2017 3rd International Conference on Computer Science and Mechanical Automation (CSMA 2017) ISBN: 978-1-60595-506-3 The Simulation of Metro Wheel Tread Temperature in Emergency Braking Condition Hong-Guang
More informationSimulation of Voltage Stability Analysis in Induction Machine
International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 6, Number 1 (2013), pp. 1-12 International Research Publication House http://www.irphouse.com Simulation of Voltage
More informationKeywords: DFIG wind turbine, MPPT, Voltage stability control, Power factor control, PSCAD simulation, Voltage oriented vector control.
2017 2nd International Conference on Mechatronics, Control and Automation Engineering (MCAE 2017) ISBN: 978-1-60595-490-5 Establishment and Parameter Allocation of DFIG Wind urbine Control Model of PSCAD
More informationStatcom Operation for Wind Power Generator with Improved Transient Stability
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 3 (2014), pp. 259-264 Research India Publications http://www.ripublication.com/aeee.htm Statcom Operation for Wind Power
More informationChina Electric Power Research Institute, Beijing, , China
5th International Conference on Environment, Materials, Chemistry and Power Electronics (EMCPE 2016) Research on Detection Method of AC/DC Charging Interface Consistency of Electric Vehicles Kang Li1,
More informationOpen Access Study on the Relationship Between Energy Storage Efficiency and Charging Mode of Super Capacitor
Send Orders for Reprints to reprints@benthamscience.ae 328 The Open Electrical & Electronic Engineering Journal, 2015, 9, 328-334 Open Access Study on the Relationship Between Energy Storage Efficiency
More informationApplication of Airborne Electro-Optical Platform with Shock Absorbers. Hui YAN, Dong-sheng YANG, Tao YUAN, Xiang BI, and Hong-yuan JIANG*
2016 International Conference on Applied Mechanics, Mechanical and Materials Engineering (AMMME 2016) ISBN: 978-1-60595-409-7 Application of Airborne Electro-Optical Platform with Shock Absorbers Hui YAN,
More informationTemperature Field in Torque Converter Clutch
3rd International Conference on Mechanical Engineering and Intelligent Systems (ICMEIS 2015) Temperature Field in Torque Converter Clutch Zhenjie Liu 1, a, Chao Yi 1,b and Ye Wang 1,c 1 The State Key Laboratory
More informationCharacteristics of wheel-rail vibration of the vertical section in high-speed railways
Journal of Modern Transportation Volume, Number 1, March 12, Page -15 Journal homepage: jmt.swjtu.edu.cn DOI:.07/BF03325771 Characteristics of wheel-rail vibration of the vertical section in high-speed
More informationPower Quality Improvement Using Statcom in Ieee 30 Bus System
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 727-732 Research India Publications http://www.ripublication.com/aeee.htm Power Quality Improvement Using
More informationThe Research of Full Automatic Intelligent Oil Filtering System Based on Flow Totalizer Control
2017 2nd International Conference on Mechanical Control and Automation (ICMCA 2017) ISBN: 978-1-60595-460-8 The Research of Full Automatic Intelligent Oil Filtering System Based on Flow Totalizer Control
More informationA starting method of ship electric propulsion permanent magnet synchronous motor
Available online at www.sciencedirect.com Procedia Engineering 15 (2011) 655 659 Advanced in Control Engineeringand Information Science A starting method of ship electric propulsion permanent magnet synchronous
More informationSoft Start for 3-Phase-Induction Motor
Soft Start for 3-Phase-Induction Motor Prof. Vinit V Patel 1, Saurabh S. Kulkarni 2, Rahul V. Shirsath 3, Kiran S. Patil 4 1 Assistant Professor, Department of Electrical Engineering, R.C.Patel Institute
More informationStatic Voltage Stability Investigations on a Part of a Transmission Grid
Trivent Publishing The Authors, 215 Available online at http://trivent-publishing.eu/ Engineering and Industry Series Volume Deregulated Electricity Market Issues in South Eastern Europe Static Voltage
More information837. Dynamics of hybrid PM/EM electromagnetic valve in SI engines
837. Dynamics of hybrid PM/EM electromagnetic valve in SI engines Yaojung Shiao 1, Ly Vinh Dat 2 Department of Vehicle Engineering, National Taipei University of Technology, Taipei, Taiwan, R. O. C. E-mail:
More informationInternational Journal of Advance Research in Engineering, Science & Technology
Impact Factor (SJIF): 4.542 International Journal of Advance Research in Engineering, Science & Technology e-issn: 2393-9877, p-issn: 2394-2444 Volume 4, Issue 4, April-2017 Simulation and Analysis for
More informationNumerical Investigation of Diesel Engine Characteristics During Control System Development
Numerical Investigation of Diesel Engine Characteristics During Control System Development Aleksandr Aleksandrovich Kudryavtsev, Aleksandr Gavriilovich Kuznetsov Sergey Viktorovich Kharitonov and Dmitriy
More informationCOMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES
Maszyny Elektryczne Zeszyty Problemowe Nr 3/2015 (107) 89 Stefan Schmuelling, Christian Kreischer TU Dortmund University, Chair of Energy Conversion Marek Gołȩbiowski Rzeszow University of Technology,
More informationWind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in Isolated Network
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in Isolated Network Saleem Malik 1 Dr.Akbar Khan 2 1PG Scholar, Department of EEE, Nimra Institute of Science and Technology, Vijayawada,
More informationSimulation research on rail transit traction grid voltage stabilization and its energy saving effects based on BESS
International Journal of Smart Grid and Clean Energy Simulation research on rail transit traction grid voltage stabilization and its energy saving effects based on BESS Shili Lin *, Wenji Song, Ziping
More informationENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG
ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG C.Nikhitha 1, C.Prasanth Sai 2, Dr.M.Vijaya Kumar 3 1 PG Student, Department of EEE, JNTUCE Anantapur, Andhra Pradesh, India.
More informationPerformance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC
Int. J. of P. & Life Sci. (Special Issue Engg. Tech.) Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC Durgesh Kumar and Sonora ME Scholar Department of Electrical
More information2nd International Conference on Electronic & Mechanical Engineering and Information Technology (EMEIT-2012)
Analysis and Control of Shift Process for AMT without Synchronizer in Battery Electric Bus Sun Shaohua 1,a, LEI Yulong 1,b, Yang Cheng 1,c, Wen Jietao 1,d 1 State Key Laboratory of automotive simulation
More informationExperimental investigation on vibration characteristics and frequency domain of heavy haul locomotives
Journal of Advances in Vehicle Engineering 3(2) (2017) 81-87 www.jadve.com Experimental investigation on vibration characteristics and frequency domain of heavy haul locomotives Lirong Guo, Kaiyun Wang*,
More informationResearch on V2G Control Strategy for EV Charge and Discharge Equipment
Energy and Power Engineering, 2013, 5, 1352-1356 doi:10.4236/epe.2013.54b256 Published Online July 2013 (http://www.scirp.org/journal/epe) Research on V2G Control Strategy for EV Charge and ischarge Equipment
More informationGrouped and Segmented Equalization Strategy of Serially Connected Battery Cells
5th International Conference on Environment, Materials, Chemistry and Power Electronics (EMCPE 2016) Grouped and Segmented Equalization Strategy of Serially Connected Battery Cells Haolin Li1, a, Guojing
More informationRegenerative Braking System for Series Hybrid Electric City Bus
Page 0363 Regenerative Braking System for Series Hybrid Electric City Bus Junzhi Zhang*, Xin Lu*, Junliang Xue*, and Bos Li* Regenerative Braking Systems (RBS) provide an efficient method to assist hybrid
More informationStudies on the Effects of Thyristor Dynamic Extinction angle on HVDC Commutation Failure
IEEE PEDS 2017, Honolulu, USA 12 15 December 2017 Studies on the Effects of Thyristor Dynamic Extinction angle on HVDC Commutation Failure Weihua Xu, Xiaoguang Wei, Kunpeng Zha, Zhiyuan He, Jie Yang Abstract
More informationImplementation of FC-TCR for Reactive Power Control
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 5, Issue 5 (May. - Jun. 2013), PP 01-05 Implementation of FC-TCR for Reactive Power Control
More informationResearch of Driving Performance for Heavy Duty Vehicle Running on Long Downhill Road Based on Engine Brake
Send Orders for Reprints to reprints@benthamscience.ae The Open Mechanical Engineering Journal, 2014, 8, 475-479 475 Open Access Research of Driving Performance for Heavy Duty Vehicle Running on Long Downhill
More informationThe Characteristic Analysis of the Electromagnetic Valve in Opening and Closing Process for the Gas Injection System
Journal of Electromagnetic Analysis and Applications, 2016, 8, 152-159 Published Online August 2016 in SciRes. http://www.scirp.org/journal/jemaa http://dx.doi.org/10.4236/jemaa.2016.88015 The Characteristic
More informationHybrid Three-Port DC DC Converter for PV-FC Systems
Hybrid Three-Port DC DC Converter for PV-FC Systems P Srihari Babu M.Tech (Power Systems) B Ashok Kumar Assistant Professor Dr. A.Purna Chandra Rao Professor & HoD Abstract The proposed a hybrid power
More informationSimulation Modeling and Control of Hybrid Ac/Dc Microgrid
Research Inventy: International Journal of Engineering And Science Vol.6, Issue 1 (January 2016), PP -17-24 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Simulation Modeling and Control
More informationChina. Keywords: Electronically controled Braking System, Proportional Relay Valve, Simulation, HIL Test
Applied Mechanics and Materials Online: 2013-10-11 ISSN: 1662-7482, Vol. 437, pp 418-422 doi:10.4028/www.scientific.net/amm.437.418 2013 Trans Tech Publications, Switzerland Simulation and HIL Test for
More informationStudy on Braking Energy Recovery of Four Wheel Drive Electric Vehicle Based on Driving Intention Recognition
Open Access Library Journal 2018, Volume 5, e4295 ISSN Online: 2333-9721 ISSN Print: 2333-9705 Study on Braking Energy Recovery of Four Wheel Drive Electric Vehicle Based on Driving Intention Recognition
More informationStructure Parameters Optimization Analysis of Hydraulic Hammer System *
Modern Mechanical Engineering, 2012, 2, 137-142 http://dx.doi.org/10.4236/mme.2012.24018 Published Online November 2012 (http://www.scirp.org/journal/mme) Structure Parameters Optimization Analysis of
More informationProtective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON
21, rue d Artois, F-75008 PARIS B4-70 CIGRE 2016 http : //www.cigre.org Protective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON VILES Consulting
More informationThe hierarchical three layer protection of photovoltaic generators in microgrid with co-ordinated droop control for hybrid energy storage system
The hierarchical three layer protection of photovoltaic generators in microgrid with co-ordinated droop control for hybrid energy storage system Vignesh, Student Member, IEEE, Sundaramoorthy, Student Member,
More informationDynamic Simulation of the Impact Mechanism of Hydraulic Rock Drill Based on AMESim Yin Zhong-jun 1,a, Hu Yi-xin 1,b
Advanced Materials Research Online: 2012-01-24 ISSN: 1662-8985, Vols. 452-453, pp 1296-1300 doi:10.4028/www.scientific.net/amr.452-453.1296 2012 Trans Tech Publications, Switzerland Dynamic Simulation
More informationTRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) Nazneen Choudhari Department of Electrical Engineering, Solapur University, Solapur Nida N Shaikh Department of Electrical
More informationModeling and Simulation of the drive system of elevator based on AMESIM
3rd International Conference on Material, Mechanical and Manufacturing Engineering (IC3ME 2015) Modeling and Simulation of the drive system of elevator based on AMESIM Yingjie Liu 1, 2, a *, Hejun Yu 1,
More informationUnited Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations
rd International Conference on Mechatronics and Industrial Informatics (ICMII 20) United Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations Yirong Su, a, Xingyue
More informationResearch and Design on Electric Control System of Elevator Tower for Safety Devices Yuan Xiao 1, a, Jianping Ye 2,b, Lijun E 1, Ruomeng Chen 1
Applied Mechanics and Materials Online: 2013-09-11 ISSN: 1662-7482, Vol. 421, pp 601-604 doi:10.4028/www.scientific.net/amm.421.601 2013 Trans Tech Publications, Switzerland Research and Design on Electric
More informationPipeline to Hydraulic Pressure Position-Control System. Performance Research
International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 3 Issue 6 ǁ June 2015 ǁ PP.30-35 Pipeline to Hydraulic Pressure Position-Control
More informationPerformance of DC Motor Supplied From Single Phase AC-DC Rectifier
Performance of DC Motor Supplied From Single Phase AC-DC Rectifier Dr Othman A. Alnatheer Energy Research Institute-ENRI King Abdulaziz City for Science and Technology- KACST P O Box 6086, Riyadh 11442,
More informationComputation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation
Computation of Sensitive Node for IEEE- 4 Bus system Subjected to Load Variation P.R. Sharma, Rajesh Kr.Ahuja 2, Shakti Vashisth 3, Vaibhav Hudda 4, 2, 3 Department of Electrical Engineering, YMCAUST,
More informationInternational Conference on Advances in Energy and Environmental Science (ICAEES 2015)
International Conference on Advances in Energy and Environmental Science (ICAEES 2015) Design and Simulation of EV Charging Device Based on Constant Voltage-Constant Current PFC Double Closed-Loop Controller
More informationSimulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line
Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line Nitin goel 1, Shilpa 2, Shashi yadav 3 Assistant Professor, Dept. of E.E, YMCA University
More informationTorque Management Strategy of Pure Electric Vehicle Based On Fuzzy Control
International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 6 Issue 4 Ver. II ǁ 2018 ǁ PP. 01-09 Torque Management Strategy of Pure Electric
More informationPOWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION
International Journal of Latest Research in Science and Technology Volume 3, Issue 1: Page No.68-74,January-February 2014 http://www.mnkjournals.com/ijlrst.htm ISSN (Online):2278-5299 POWER QUALITY IMPROVEMENT
More information3rd International Conference on Material, Mechanical and Manufacturing Engineering (IC3ME 2015)
3rd International Conference on Material, Mechanical and Manufacturing Engineering (IC3ME 2015) A High Dynamic Performance PMSM Sensorless Algorithm Based on Rotor Position Tracking Observer Tianmiao Wang
More informationOpen Access Calculation for the Heating and Safe Operation Time of YKK Series Highvoltage Motors in Starting Process
Send Orders of Reprints at reprints@benthamscience.net The Open Electrical Electronic Engineering Journal, 213, 7, (Supple 1: M3) 39-45 39 Open Access Calculation for the Heating and Safe Operation Time
More informationResearch on vibration reduction of multiple parallel gear shafts with ISFD
Research on vibration reduction of multiple parallel gear shafts with ISFD Kaihua Lu 1, Lidong He 2, Wei Yan 3 Beijing Key Laboratory of Health Monitoring and Self-Recovery for High-End Mechanical Equipment,
More informationZero-turn-off thyristor zero voltage block media recovery analysis of influencing factors FANG Wei1, a*, XU Guo-shun1, b, ZHUANG Jin-wu1, c
International Symposium on Mechanical Engineering and Material Science (ISMEMS 2016) Zero-turn-off thyristor zero voltage block media recovery analysis of influencing factors FANG Wei1, a*, XU Guo-shun1,
More informationAPPLICATION OF BOOST INVERTER FOR GRID CONNECTED FUEL CELL BASED POWER GENERATION
APPLICATION OF BOOST INVERTER FOR GRID CONNECTED FUEL CELL BASED POWER GENERATION P.Bhagyasri 1, N. Prasanth Babu 2 1 M.Tech Scholar (PS), Nalanda Institute of Engineering and Tech. (NIET), Kantepudi,
More informationIMPACT OF THYRISTOR CONTROLLED PHASE ANGLE REGULATOR ON POWER FLOW
International Journal of Electrical Engineering & Technology (IJEET) Volume 8, Issue 2, March- April 2017, pp. 01 07, Article ID: IJEET_08_02_001 Available online at http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=8&itype=2
More informationPreliminary Study on Quantitative Analysis of Steering System Using Hardware-in-the-Loop (HIL) Simulator
TECHNICAL PAPER Preliminary Study on Quantitative Analysis of Steering System Using Hardware-in-the-Loop (HIL) Simulator M. SEGAWA M. HIGASHI One of the objectives in developing simulation methods is to
More informationDesign of closing electromagnet of high power spring operating mechanism
Abstract Design of closing electromagnet of high power spring operating mechanism Pengpeng Li a, Xiangqiang Meng, Cheng Guo Mechanical and Electronic Engineering Institute, Shandong University of Science
More informationThe Testing and Data Analyzing of Automobile Braking Performance. Peijiang Chen
International Conference on Computational Science and Engineering (ICCSE 2015) The Testing and Data Analyzing of Automobile Braking Performance Peijiang Chen School of Automobile, Linyi University, Shandong,
More informationDC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach
DC Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach F. Akhter 1, D.E. Macpherson 1, G.P. Harrison 1, W.A. Bukhsh 2 1 Institute for Energy System, School of Engineering
More informationAnalysis and Design of Independent Pitch Control System
5th International Conference on Civil Engineering and Transportation (ICCET 2015) Analysis and Design of Independent Pitch Control System CHU Yun Kai1, a *, MIAO Qiang2,b, DU Jin Song1,c, LIU Yi Yang 1,d
More information