Datasheet. DIN Rail Mount
|
|
- Allan Allen
- 5 years ago
- Views:
Transcription
1 DRH Series Ratings up to 18 & 20 Amps at 600VAC Fits standard 35mm DIN Rail Integrated over-temperature protection Alarm output in case of over-temperature Multicolor LED with input status and alarm indicator AC or DC control Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated Built-in Overvoltage Protection Fan controlled through thermistor and microprocessor to optimize fan operation PRODUCT SELECTION Control Voltage 18A VAC/VDC DRH3P60A VDC DRH3P60D18 20A DRH3P60A20 DRH3P60D20 AVAILABLE OPTIONS Series Required for valid part number For options only and not required for valid part number OUTPUT SPECIFICATIONS (1) Operating Voltage (47-63Hz) [VRMS] Transient Overvoltage [Vpk] (2) Maximum Off-State Leakage Rated Voltage [marms] Minimum Off-State Maximum Rated Voltage [V/μsec] Load Current, General Use 40 C [ARMS] (3) Function 3P: Contactor DRH 3P 60 A 18 U R Operating Voltage 60: VAC Control Voltage A: VAC/VDC D: 4-32 VDC Switching Type Blank: Zero Voltage Turn-On R: Instantaneous Turn-On Rated Load Current 18: 18 Amps (3 Controlled legs) 20: 20 Amps (2 Controlled legs) 18A 20A Load Current, Motor Starting UL C [ARMS] (3) Minimum Load Current [ARMS] Maximum Surge Current [Apk] 1Cycle 60Hz Maximum Surge Current [Apk] 1Cycle 50Hz Maximum I²t for Fusing (8.33 msec) [A²sec] Maximum I²t for Fusing (10 msec) [A²sec] Maximum On-State Voltage Rated Current [Vpk] 1.35 per channel 1.35 per channel Minimum Power Factor (with Maximum Load) Motor Rating UL 508/ IEC [HP/kW] :240 VAC 2/1.5 2/1.5 Motor Rating UL 508/ IEC [HP/kW] :380 VAC 3/2.2 3/2.2 Motor Rating UL 508/ IEC [HP/kW] :480 VAC 5/3.7 5/3.7 INPUT SPECIFICATIONS (1) DRH3P60Dx DRH3P60Ax Control Voltage Range 4-32 VDC VAC/VDC Minimum Turn-On Voltage 4 VDC 90 VAC/VDC Must Turn-Off Voltage 1 VDC 10 VAC Minimum Input Current (for on-state) 2 ma 1 ma Maximum Input Current 17 ma 3 ma Nominal Input Impedance [Ohms] 2k 100k Maximum Turn-On Time [msec] 1 Cycle (4) 30 Maximum Turn-Off Time [msec] 1 Cycle 40
2 POWER SUPPLY SPECIFICATIONS (1) DRH3P60Dx Voltage Range 8-32 VDC Minimum Turn-On Voltage 8 VDC Must Turn-Off Voltage 3 VDC Maximum Source Current [ma] 125 Maximun Start Up Time [msec] 20 Maximun Shut Off Time [msec] 40 DRH3P60Ax VAC/VDC 90 VAC/VDC 5 VAC/VDC ALARM OUTPUT (1) Maximum Contact Switching Voltage [Volts] Contact Rated Current [A] Minimum Recommended Contact Load [ma] Static Contact Resistance (max. init.)[ohms] Turn-On / Off Condition DRH3P60xxx 200 VDC, 120 VAC See Status Chart GENERAL SPECIFICATIONS (1) Parameters Dielectric Strength, Input/Output/Base (50/60Hz) (5) 3750 Vrms Minimum Insulation Resistance (@ 500 VDC) 10 9 Ohm Maximum Capacitance, Input/Output 20 pf Ambient Operating Temperature Range (6) -10 to 70 C Ambient Storage Temperature Range -40 to 70 C Weight (typical) 2 Controlled Legs (7.4 oz [210 g]) / 3 Controlled Legs (8.5 oz [242 g]) Housing Material UL94 V-0 Housing Color Black and Light Gray LED Status Indicator (color) See Status Chart Short Circuit Current Rating (7) 100kA Pollution Degree 2 Protection Degree (8) IP20 Humidity 85% non-condensing Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/nm) 12 / 1.36 Load Terminal Screw Torque Range (in-lb/nm) 15 / 1.7 Input Terminal Wire Capacity AWG (IEC 1-4 mm 2 ) (stranded /solid) Output Terminal Wire Capacity AWG (IEC 1-6 mm 2 ) (stranded /solid) THERMAL DERATE INFORMATION Single unit (9) DRH3P60x18 Multiple units Single unit (9) DRH3P60x20 Multiple units Load Current (Amps) Ambient Temperature (ºC) Load Current (Amps) Ambient Temperature (ºC)
3 WIRING AND BLOCK DIAGRAM L1 L2 L VAC, 50-60Hz L1 L2 L3 / > / > / > Power Supply VAC/VDC (for A Control Voltage) 8-32 VDC (for D Control Voltage) Alarm Output (0.5 A/200 VDC, 120 VAC) Normally Open L1 L2 L3 XXXX +A3 13 +A1 DRH3P60xxx IND. CONT. EQ. INPUT STATUS -A4 14 -A2 T1 T2 T3 CONTROL INPUT Motor Controller / AC-53a Application T1 T2 T3 General Use / AC-51 Application T1 T2 T3 T1 T2 T3 M 3 DRHP60x18 (3 controlled legs model) Main Circuit Alarm Output (DRHP60x18 & DRHP60x20) +A3 L1 L2 L3 +A1 13 -A4 T1 T2 T3 -A2 14 DRHP60x20 (2 controlled legs model) Main Circuit +A3 L1 L2 L3 +A1 -A4 T1 T2 T3 -A2
4 SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES IEC standard make a distinction between two different types of protection, (called coordination ), which are designated types 1 and "2". Any short-circuit that occurs is cleared safely by either type of coordination. The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit. Type "1" coordination requires that in the event of a short-circuit, the does not endanger personnel or installations, but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination, the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used. Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations, and in addition the SSR will be able to operate after the fault condition is repaired. Type of coordination 1 For resistive loads: Nominal Current Protection by Thermal Magnetic Circuit Breaker or by Fuse Class gg fuses (example from Littlefuse) 2 controlled legs 3 controlled legs A CY14X51G25 DRH3P60x20 DRH3P60x18 (up to 18A) (10) For motor loads: Protection by Thermal Magnetic Circuit Breaker or by Fuse Nominal Motor Current Thermal Magnetic Circuit Breaker (Schneider Electric) Class gg fuses (example from Littlefuse) 2 controlled legs 3 controlled legs A GV2ME04 / GV2P04 CY14X51G16 DRH3P60x20 DRH3P60x A GV2ME05 / GV2P05 CY14X51G16 DRH3P60x20 DRH3P60x A GV2ME06 / GV2P06 CY14X51G25 DRH3P60x20 DRH3P60x A GV2ME07 / GV2P07 CY14X51G25 DRH3P60x20 DRH3P60x A GV2ME08 / GV2P08 CY14X51G25 DRH3P60x20 DRH3P60x A GV2ME10 / GV2P10 CY14X51G40 DRH3P60x20 DRH3P60x A GV2ME14 / GV2P14 CY14X51G40 DRH3P60x20 (up to 7.6A) DRH3P60x18 (up to 7.6A) (10) Type of coordination 2 For resistive loads: Nominal Current Protection by Fuse Semiconductor fuses with less than 2330 A 2 s Littlefuse SIBA1 (Cylindric) Ferraz (Cylindric) 2 controlled legs 3 controlled legs A LA50QS Z DRH3P60x20 DRH3P60x18 (up to 18A) (10) For motor loads: Nominal Motor Current Protection by Fuse Semiconductor fuses with less than 2330 A 2 s Littlefuse SIBA1 (Cylindric) Ferraz (Cylindric) 2 controlled legs 3 controlled legs A LA50QS A DRH3P60x20 DRH3P60x18 (10)
5 STATUS CHART Control Input A Power Supply A3 Output Over Temperature Alarm Pre-alarm Alarm Output LED Color 2s 3s 0% 50% 75% 100% 100% 75% 50% 3s 3s Fan Speed Step LED Color 1, 15 2, , 12 5, 11 6, Initial Condition Stand by condition. LED is blinking Blue. Fan is activated at full speed for 2 seconds after power is applied to A3 A1 is On, Output is activated, temperature rises. LED is Green Fan is activated at 50% speed. If A1 is disabled, LED changes to blinking Blue Fan is at 75% speed LED changes to blinking Red, fan is at full speed Output is Off, Alarm Output is On, LED changes to solid Red If A1 is disabled while alarm output is active, LED alternates between Blue and Red LED is solid Red, temperature starts to fall Fan is activated at 50% speed, temperature is steady Blue Green Red MECHANICAL SPECIFICATIONS 0.23 [5.8] 2.91 [73.9] 3.51 [89] Tolerances: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] +A3 13 +A [86.7] 1.23 [31.3] 2.29 [58.3] 2.58 [65.5] DRH3 IND. CONT. EQ [42.7] XXXX INPUT STATUS -A4 14 -A [95.6] 1.78 [45.3] TERMINAL SCREW TYPE Top/Bottom view (Fig. 1) Fig. 1
6 ACCESSORIES ID Marker ID Marker CNLB CNLN Package of 10 plastic strip comprising 10 individual markers which can be placed for easy identification during the use of multiple units. CNL2 AGENCY APPROVALS Certification in accordance with: United States Standard for Industrial Control Equipment - UL 508 and Canadian Standard Association for Industrial Control Equipment C22.2 No. 14. DRH series conforms to the harmonized EN standard EN/IEC Electromagnetic Compatibility: IEC : Electrostatic Discharge Level 3 IEC : Electrically Fast Transients Level 3 IEC : Electrical Surges Level 3 Vibration Resistance: IEC : Amplitude Range Hz, Displacement 0.75mm Shock Resistance: IEC : Peak Acceleration 15g, Duration 11msec. E GENERAL NOTES (1) All parameters at 25 C unless otherwise specified. (2) Relay will self trigger between V, Not suitable for capacitive loads. (3) Mounted in the Vertical position. (4) Turn-on time for Instantaneous turn-on version is 4 msec. (5) For input to alarm output the dielectric strength is 1.5kV. (6) UL approval up to 40 C surrounding temperature. (7) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20A or equivalent. (8) IP20 rating is not associated with the UL approval. (9) Minimum spacing to obtain max. current is 22mm between adjacent units. (10) Combination of these Protective Devices and have not been evaluated by UL. Rev
7 DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH. Disconnect all power before installing or working with this equipment. Verify all connections and replace all covers before turning on power. Failure to follow these instructions will result in death or serious injury. RIESGO DE DESCARGA ELECTRICA O EXPLOSION. Desconectar todos los suministros de energia a este equipo antes de trabajar con este equipo. Verificar todas las conexiones y colocar todas las tapas antes de energizer el equipo. El incumplimiento de estas instrucciones puede provocar la muerte o lesiones serias. RISQUE DE DESCHARGE ELECTRIQUE OU EXPLOSION Eteindre toutes les sources d'énergie de cet appareil avant de travailler dessus de cet appareil Vérifier tous connections, et remettre tous couverts en olace avant de mettre sous De non-suivi de ces instructions provoquera la mort ou des lésions sérieuses sérieuses. GEFAHR EINES ELEKTRISCHE N SCHLAGES ODER EINER EXPLOSION. Stellen Sie jeglichen Strom ab, der dieses Gerät versorgt, bevor Sie an dem Gerät Arbeiten durchführen Vor dem Drehen auf Energie alle Anschlüsse überprüfen und alle Abdeckungen ersetzen. Unterlassung dieser Anweisungen können zum Tode oder zu schweren Verletzungen führen. RISCHIO DI SCOSSA ELETTRICA O DELL ESPLOSIONE. Spenga tutta l'alimentazione che fornisce questa apparecchiatura prima di lavorare a questa apparecchiatura Verificare tutti i collegamenti e sostituire tutte le coperture prima dell accensione L'omissione di queste istruzioni provocherà la morte o lesioni serie 存在电击 爆炸或电弧闪烁危险 在操作此设备之前请先关闭电源 若不遵守这些说明, 可能会导致严重的人身伤害甚至死亡 WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE The product's side panels may be hot, allow the product to cool before touching. Follow proper mounting instructions including torque values. Do not allow liquids or foreign objects to enter this product. Failure to follow these instructions can result in serious injury, or equipment damage. RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfríe antes de tocarlo. Respetar las instrucciones de montaje, y en particular los pares de apretado. No dejar que penetren líquidos o cuerpos extraños en el producto. Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales. RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER Les panneaux latéraux du produit peuvent être chauds. Laisser le produit refroidir avant de le toucher. Respecter les consignes de montage, et notamment les couples de serrage. Ne pas laisser pénétrer de liquide ni de corps étrangers à l'intérieur du produit. Le non-respect de cette directive peut entraîner, des lésions corporelles graves ou des dommages matériels. RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo. Seguire le istruzioni di montaggio corrette. Non far entrare liquidi o oggetti estranei in questo apparecchio. La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature. GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG Die Seitenwände können heiß sein. Lassen Sie das Produkt abkühlen, bevor Sie es berühren. Beachten Sie die Montageanweisungen, Führen Sie keine Flüssigkeiten oder Fremdkörper in das Produkt ein. Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben. 材料损坏和高温外壳的危险性 产品的一侧面板可能很热, 在其冷却前请不要触碰 遵照正确的安装说明, 包括扭矩值 请勿让液体及其他异物进入本产品 如不能正确执行这些操作说明, 极有可能造成严重人体伤害或者设备的损坏
8 ANNEX - ENVIROMENTAL INFORMATION The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People s Republic of China Electronic Industry Standard SJ/T , Marking for Control of Pollution Caused by Electronic Information Products. Part Name Toxic or hazardous Substance and Elements Lead Mercury Cadmium Hexavalent Polybrominated Polybrominated (Pb) (Hg) (Cd) Chromium biphenyls diphenyl ethers (Cr (VI)) (PBB) (PBDE) Semiconductor die Solder 部件有毒有害物质或元素名称铅汞镉六价铬多溴联苯多溴二苯醚 半导体芯片焊接点 (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE) 50
SeriesOne DR Series. Control Voltage 280V, 3A 600V, 3A 60V, 3A 100V, 3A 4-32 VDC DR24D03. Rated Load Current 03: 3 Amps
SeriesOne DR Series DataSheet Ratings 3 Amps Load voltage ratings of 1-60VDC, 1-100VDC, 24-280VAC and 48-600VAC Fits standard 35mm DIN-RAIL LED input status indicator AC or DC control Zero-crossing (resistive
More informationSeriesOne DR Series DR48E12. Rated Load Current 03: 3 Amps 06: 6 Amps 12: 12 Amps. Agency Approvals X: ATEX II 3G Ex na IIC T4 Gc approved
SeriesOne DR Series DataSheet Ratings of 6 & 12 Amps Load voltage ratings of 1-60VDC, 1-100VDC, 24-280VAC and 48-600VAC Fits standard 35mm DIN-RAIL LED input status indicator AC or DC control Zero-crossing
More informationValveMate 8040 Controller Operating Manual
A NORDSON COMPANY ValveMate 8040 Controller Operating Manual 8040 SPRAY VALVE CONTROLLER To order ValveMate 8040 controller, refer to part #7022120. Electronic pdf files of EFD manuals are also available
More informationValveMate 8040 Controller
ValveMate 8040 Controller Operating Manual 8040 SPRAY VALVE CONTROLLER To order ValveMate 8040 controller, refer to part #7022120. IMPORTANT! Save this Sheet. Forward to Maintenance or Tool Crib Supervisors
More informationLV REMOTE CONTROLLER INSTRUCTION MANUAL
LV 7800-01 REMOTE CONTROLLER INSTRUCTION MANUAL TABLE OF CONTENTS 1. INTRODUCTION... 1 1.1 Scope of Warranty... 1 1.2 Power Supply Voltage... 1 1.3 Trademarks... 1 2. SPECIFICATIONS... 2 2.1 General...
More informationValveMate 7094DC Auger Valve Controller Operating Manual
A NORDSON COPANY Valveate 7094DC Auger Valve Controller Operating anual VALVEAT E 7094DC AUGER VALVE CONTROLLER Electronic pdf files of EFD manuals are also available at www.efd-inc.com Introduction The
More informationValveMate 8040 Controller
ValveMate Controller Operating Manual Electronic pdf files of Nordson EFD manuals are also available at www.nordsonefd.com ValveMate Controller You have selected a reliable, high-quality dispensing system
More informationLT 9213A LCD FLICKER CHECKER INSTRUCTION MANUAL
LT 9213A LCD FLICKER CHECKER INSTRUCTION MANUAL TABLE OF CONTENTS GENERAL SAFETY SUMMARY... I 1. PRECAUTIONS...1-1 1.1 Supply Voltage and Fuses...1-1 1.2 Maximum Allowable voltage on input Terminal...1-1
More informationValveMate 7060RA Controller
Valveate 7060RA Controller Operating anual A NORDSON COPANY VALVEATE 7060RA For order purpose, please refer to this # 7014235 IPORTANT! Save this Sheet. Forward to aintenance or Tool Crib Supervisors Electronic
More informationImpact Torque Meters HIT-Series
Impact Torque Meters HIT-Series HIT-200 HIT-500 HIT-2000 Owner s Manual (December, 2016) 16A 1-16-5 Akiyama, Matsudo City, Chiba Pref., Japan TEL: 81-47-392-2001 FAX: 81-47-392-7773 Operation Manual No.:
More information781RC MicroMark Recirculating Spray Marking System
781RC MicroMark Recirculating Spray Marking System Operating Manual Electronic pdf files of Nordson EFD manuals are also available at nordsonefd.com Contents Contents...2 Safety Warnings...3 Equipment
More information794 Series Auger Valve
794 Series Auger Valve Operating Manual Electronic pdf files of Nordson EFD manuals are also available at www.nordsonefd.com You have selected a reliable, high-quality dispensing system from Nordson EFD,
More informationEAB stand-alone battery tool from F
Part no 6159930390 Issue no 05 Date 04/2014 Page 1 / 108 EAB stand-alone battery tool from F4.02.04 Model Part number Series 6151657310 D 6151657320 D 6151657330 D 6151657340 D 6151657350 D-E 6151657360
More informationOperation Manual. Checking the Package Contents. Electronic Load Booster PLZ2004WB PLZ2004WHB. Accessories (PLZ2004WB) About the Operation Manual
Operation Manual Electronic Load Booster PART NO. Z-005-60, IB076 Nov. 06 Checking the Package Contents When you receive the product, check that all accessories are included and that the product and accessories
More informationCartridge Filling System
Cartridge Filling System Operating Manual www.nordsonefd.com info@nordsonefd.com USA & Canada: 800.556.3484 Europe: +44 (0) 1582 666334 Asia & China: +86 (21) 3866 9006 Sales and service of Nordson EFD
More informationPremium Complete Rework Station with Electric Pump
www.jbctools.com INSTRUCTION MANUAL Premium Complete Rework Station with Electric Pump Ref. RMSE-E Packing List The following items should be included: JTSE Control Unit... 1 u Ref. JTSE-1A (100V - 120V)
More informationDeclaration of Compliance for Elo AccuTouch Screens
Declaration of Compliance for Elo AccuTouch Screens Date: June 14, 2016 Product: AccuTouch Screens (model numbers starting with SCN-AT or SCN-A5) See attached list of applicable part numbers Elo Touch
More informationAGQ300-48S1V2 DC/DC Converter. Technical Reference Notes
AGQ300-48SV2 DC/DC Converter Technical Reference Notes Industry standard quarter brick: 36V~75V input,.2v single output Features Industry standard quarter brick (open-frame) 2.28.45 0.4 (open-frame) 2.28.45
More informationBar Code Scanner. Quick Start Guide QS Rev A 3/12
5800 Bar Code Scanner Quick Start Guide 5800-QS Rev A 3/12 Getting Started Turn off the computer s power before connecting the scanner, then power up the computer once the scanner is fully connected. Connecting
More informationSACE FORMULA Link. Incoming for CB A2 X3 X3 X3 X4 X4 X4. Outgoing for A1. Incoming kit for lugs. Doc. N. 1SDH000717R L5808
Phase indent Circuit No Cable Size FORMULA Link FORMULA Link is approved for use with the following ABB SACE Circuit Breakers: - SACE Tmax T6 - SACE FORMULA A - SACE FORMULA A - SACE FORMULA A In selecting
More informationup to 63 A (1 module per pole)
87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 Direct current MCB DX 3 16kA, up to 63 A (1 module per pole) CONTENTS PAGE 1. Description - Use... 1 2. Range... 1 3. Overall dimensions...
More informationAGQ200-48S1V5 DC/DC Converter. Technical Reference Notes
AGQ200-48S1V5 DC/DC Converter Technical Reference Notes Industry standard quarter brick: 36V~75V input, 1.5V single output Features Industry standard quarter brick (open-frame) 2.28 1.45 0.39 (open-frame)
More informationATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)
Product datasheet Characteristics ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/400...440V(45kW) Complementary Assembly style Function available Supply voltage limits Main Range of product
More informationSolid State Relays contactor with Integrated Fuse Type RGC1F
Solid State Relays contactor with Integrated Fuse Type RGC1F Solid State Contactor with integrated fuse Zero Cross Switching Operational voltage: 230 VAC and 600 VAC 35mm width Control voltage: 4-32 VDC
More informationSACE FORMULA Link. Incoming kit for lugs. Outgoing for A1. Incoming for CB T6. Outgoing for A2. Doc. N. 1SDH000717R L5808
Phase indent Circuit No Cable Size FORMULA Link FORMULA Link is approved for use with the following ABB SACE Circuit Breakers: - SACE Tmax T6 - SACE FORMULA A - SACE FORMULA A - SACE FORMULA A In selecting
More information(1,5 modules per pole)
87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 36kA, 80A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More information1.1 Caution Statements
USER MANUAL 1.1 Caution Statements Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read and
More informationRX 3 M.C.B A up to 63 A
87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 RX 3 M.C.B. 6000 A up to 63 A CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationSoft Starter. Types RSBD. Product Description. Type Selection. Ordering Code RSB D E V 61 HP
Soft Starter Three-Phase Scroll Compressor Soft Starter Types RSBD Soft starting of 3-phase scroll compressors up to 95Amp Patented auto-adaptive algorithm for optimum inrush current reduction (No user
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation
More informationRX 3 M.C.B A up to 63 A
87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 RX 3 M.C.B. 6000 A up to 63 A Cat. N (s): 4 197 49 to 4 199 23 CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Overall dimensions...
More informationMAx1-720x Two-Position, MFx Floating, MSx Proportional Series SmartX Actuators Linear Spring Return
Selection Guide MAx-70x Two-Position, MFx-703 Floating, MSx-703 Proportional Series SmartX Actuators Linear Spring Return schneider-electric.com Application Linear SmartX Actuators are designed to mount
More informationDX³ RCCBs - ID 4P up to 100 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationSOLITRON MIDI - With Integrated Heatsink Types RJ1A, RJ1B
Solid State Relays SOLITRON MIDI - With Integrated Heatsink Types RJ1A, RJ1B AC semiconductor contactor Zero switching (RJ1A) or instant-on switching (RJ1B) Direct copper bonding (DCB) technology LED-indication
More informationEZ Fingerprint Recognition Unit Installation Guide
EZ Fingerprint Recognition Unit Installation Guide www.pro-face.com DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Disconnect all power before servicing equipment. Failure to follow these instructions
More informationPhase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More informationAGQ300-48S1V2 DC/DC Converter. Technical Reference Notes
AGQ300-48SV2 DC/DC Converter Technical Reference Notes Industry standard quarter brick: 36V~75V input,.2v single output Features Industry standard quarter brick (open-frame) 2.28.45 0.4 (open-frame) 2.28.45
More informationE30 Series. Installation Guide Power Monitoring. Branch Circuit Power Meter. Product Overview. Product Identification.
Z4998-0P Page 1 of 49 15 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0815 Installation Guide Power Monitoring Product Overview E30 Series Branch Circuit Power Meter Other current
More informationTX³ RCCBs 2P up to 100 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More information, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More informationModel HT640B02. High Temperature 4-20 ma Output Velocity Sensor. Installation and Operating Manual
Model HT640B02 High Temperature 4-20 ma Output Velocity Sensor Installation and Operating Manual For assistance with the operation of this product, contact PCB Piezotronics, Inc. Toll-free: 800-959-4464
More informationInternational 9/8/11 WORKING PAPER Edition battery or the exposed to prevent 1.3 (5 页 ) C
International Civil Aviation Organization DGP/23-WP/16 9/8/11 WORKING PAPER DANGEROUS GOODS PANEL (DGP) TWENTY-THIRD MEETING Montréal, 111 to 21 October 2011 Agenda Item 2: Development of recommendations
More informationPhase + Neutral, neutral on right side
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34
More informationControl Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD
Bulletin Product Selection Open Type and Non-Combination Enclosed (IP, NEMA /) Controllers For use with Line-Connected Motors Rated Voltage [V AC] / Motor Current [A]...... Max. kw, Hz Max. Hp, Hz Control
More informationEEMB CO., LTD. Specification
ZJQM-RD-SPC-H0138 0.0 2018-10-30 1/8 EEMB CO., LTD Lithium Thionyl Chloride Battery High Power Type 锂亚硫酰氯电池产品规格书 Model 型号 : Capacity 容量 : 14Ah Prepared 编制 Checked 审核 Approved 批准 Customer 客户名称 : Customer
More informationRobot System. Safety and Installation. Robot Controller Control Unit RC700 RC700-A Drive Unit RC700DU RC700DU-A. Programming Software EPSON RC+7.
Robot System Safety and Installation Read this manual first Rev.14 EM174B3448F Robot Controller Control Unit RC700 RC700-A Drive Unit RC700DU RC700DU-A Programming Software EPSON RC+7.0 Manipulator G1
More informationModels. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery
AC/DC Battery Controller Power Supply TSPC-240UPS Series Compact universal 24 VDC power supply with integrated battery controller module Battery protection for over voltage, deep discharge, short circuit
More informationThe Torque Value Checking Meters For Automatic Controlled System HM-10 HM-100
The Torque Value Checking Meters For Automatic Controlled System HM-10 HM-100 Operation Manual (As of December 2016) 16A 1-16-5 Akiyama, Matsudo City, Chiba Pref., Japan TEL: 81 (Japan) 47-392-2001 FAX:
More informationEEMB CO., LTD. Specification
ZJQM-RD-SPC-H0138 0.0 2018-11-9 1/9 EEMB CO., LTD Lithium Thionyl Chloride Battery 锂亚硫酰氯电池 Energy Type 产品规格书 Model 型号 : Capacity 容量 : 1200mAh Prepared 编制 Checked 审核 Approved 批准 Customer 客户名称 : Customer
More informationAVO100-48S1V5 DC/DC Converter. Technical Reference Note
AVO00-48SV5 DC/DC Converter Technical Reference Note Industry standard eighth brick: 36~75v input,.5v single output Features Industry standard eighth brick : 2.28 0.9 0.36 Options Choice of positive logic
More informationINSTALLATION INSTRUCTION Magnetic Transformer
IMPORTANT: Read all instructions before installing. Read all instructions before proceeding with the installation. This power supply complies with the requirements of UL1838. This power supply should be
More informationASTAT XB USER MANUAL. 1 Caution Statements
ASTAT XB USER MANUAL 1 Caution Statements Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read
More informationPresentation Soft starters 0 Altistart 48 soft start - soft stop units
Presentation Soft starters 5 6 7 65_Ver.-EN.fm/ Presentation (continued) Soft starters Applications The Altistart 8 soft start - soft stop unit is a controller with 6 thyristors which is used for the torque-controlled
More informationThe Global Expert in Solid State Switching Technology. solicon. DRC Series
The Global Expert in Solid State Switching Technology solicon DRC Series Crydom's innovative Motion Control solutions leverage the advantage of having an all solid state design making them ideal for motor
More informationRX 3 MCB 4500 A Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 RX 3 MCB 4500 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationValveMate 7194 Auger Valve Controller
ValveMate 7194 Auger Valve Controller Operating Manual Electronic pdf files of Nordson EFD manuals are also available at www.nordsonefd.com You have selected a reliable, high-quality dispensing system
More informationFAMILY. 1-Phase 1 Up to 25A Up to 40A Up to 80A Up to 600VAC 3-Phase, 2 leg 1 No Up to 33A Up to 80A Gang 2 units
THE DIN-A-MITE FAMILY 1 Refer to curves on reverse side for specific ratings. ➁ angle fire is not CE approved for conducted or radiated emissions. ➂ Will fit within the width dimension of most comparable
More informationLAL SERIES LED LUMINAIRE
INSTALLATION, OPERATION & MAINTENANCE DATA SHEET LAL SERIES LED LUMINAIRE CAUTION: LAL SERIES LED LUMINAIRE Before installing, make sure you are compliant with area classifications, failure to do so may
More informationRE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC
Characteristics time delay relay 2 functions - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical
More informationModel Number Structure
Solid State Relays (Single-phase) G3PB New Single-phase Solid State Relays with Compact Size for Heater Control Slim models with a thickness of only 22.5 mm are also available. Compact design achieved
More informationValveMate 7160RA Radial Valve Controller
Operating Manual Electronic pdf files of Nordson EFD manuals are also available at www.nordsonefd.com You have selected a reliable, high-quality dispensing system from Nordson EFD, the world leader in
More informationRobot System. Safety and Installation. Robot Controller RC90 Programming Software EPSON RC Manipulator LS series (LS3 / LS6 / LS20)
Robot System Safety and Installation Read this manual first Rev.10 EM174B3450F Robot Controller RC90 Programming Software EPSON RC+ 7.0 Manipulator LS series (LS3 / LS6 / LS20) Robot System Safety and
More information1 Phase electronic contactor (SC 1)
1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or
More informationDX³ 4-pole RCBO 6000 A/10 ka
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationDEVICE STATE/BYPASSED FAILURE OVERLOAD
Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated
More informationComfortPoint Open CPO-Rxx ROOM CONTROLLERS
ComfortPoint Open CPO-Rxx ROOM COTROLLERS MOUTIG ISTRUCTIOS / MOTAGEAWEISUG / ISTRUCTIOS D'ISTALLATIO / ISTRUCCIOES DE MOTAJE / ISTRUZIOI DI MOTAGGIO E Keep these instructions together with the device
More informationSoftstarter Intelligent Controllers
Softstarter Intelligent Controllers Series Modes of Operation (Standard) Soft Start 100% Percent Voltage Initial Torque Start Run This method has the most general application. The motor is raised from
More informationUltimus IV Series Dispensing System
Ultimus IV Series Dispensing System User s Guide Ultimus IV-3cc #7017178 Ultimus IV-5cc #7017181 Ultimus IV-10cc #7017177 Ultimus IV-30cc #7017179 Electronic pdf files of EFD manuals are also available
More informationCSD Series Current Devices Split Core
CSD Series Current Devices Split Core Installation Instructions CSD-CF0A0-1 CSD-CF0J0-1 CSD-CA1G0-1 Part. 24-10345-34, Rev. D Issued March 31, 2014 Supersedes April 5, 2013 Applications The Current Switch
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationValveMate 7000 Controller Operating Manual
A NORDSON COMPANY ValveMate 7000 Controller Operating Manual Steady Test Clear Time Set Fast Slow POWER RUN SETUP CYCLE A NORDSON COMPANY VALVEMATE 7000 Run Setup Purge Program Fast Slow Time Set Pressure
More informationMULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers
IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when
More informationSET Thermally protected MOV (Abbreviated TMOV) is a new patent technology in the field of surge protection.
Introduction of Thermally Protected MOV SET Thermally protected MOV (Abbreviated TMOV) is a new patent technology in the field of surge protection. The TMOV is a fail-safe device, which integrated a disk
More informationFeatures. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter
Features TRIAC Dimmable LED Driver Triac dimmable with leading or trailing edge dimmers Class II with SELV output (no earth required) Extra-large screw terminals and integrated cable clamps for easy installation
More informationDX³ RCBO 6000 A Phase + Neutral, neutral right side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1
More informationInstallation Manual Type DDR DIN rail power supply Series DDR-120, DDR-240
Type:DDR DIN rail power supply(series:ddr-120, DDR-240) DDR-120A-12 INPUT: 9~18VDC 13.5A OUTPUT: 12V 7.1A (9~10.8Vin) 12V 8.3A (10.8~18Vin) DDR-120A-24 INPUT: 9~18VDC 13.5A OUTPUT: 24V 3.6A (9~10.8Vin)
More informationD4DL. Guard Lock Safety-door Switch. Model Number Structure
Guard Lock Safety-door Switch Two new types added to series: Mechanical-lock models that lock automatically when the Operation Key is inserted, and solenoid-lock models that lock when voltage is applied
More information2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4
CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power
More informationCat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090
More informationGV-10 Manual 10.5A / 140W IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Solar Charge Controllers with Maximum Power Point Tracking
GV-10 Manual Solar Charge Controllers with Maximum Power Point Tracking For models: GV-10-Pb-12V: GV-10-Pb-CV: 12V Lead-Acid/AGM/Gel/Sealed/Flooded 12V Custom Multi-Stage Lead-Acid/AGM/Gel/ Sealed/Flooded
More informationDX³ RCBO 6000A Phase + Neutral, neutral on left
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationHIOS Digital Torque Meters HP-100 HP-10 HP-1 ( ) Option. Operation manual. (May 2018) 18A. No. ET-C006
HIOS Digital Torque Meters HP-100 HP-10 HP-1 ( ) Option Operation manual (May 2018) 18A No. ET-C006 Contents Applications and features of HIOS Digital Torque Meters...1 Safety Precautions... 2 HIOS Digital
More information1. Caution Statements System Design Electrical Installation Adjustments Troubleshooting... 16
CSXi RIGHT FROM THE START Contents 1. Caution Statements... 2 2. System Design... 4 3. Electrical Installation... 11 4. Adjustments... 14 5. Troubleshooting... 16 The examples and diagrams in this manual
More informationDescription 1/8-7.5HP
Description 1/8-7.5HP J1000 In our pursuit to create drives optimized for variable speed needs in compact applications, the J1000 is the solution. This micro-drive is simple and reliable with Yaskawa quality.
More informationSolid State Relays, 3-phase
PMA Prozeß- und Maschinen-Automation GmbH Solid State Relays, 3-phase Zero-Point switching, heatsink integrated Main Characteristics: Three-phase controlled Zero switching LED display Various connection
More informationSafety Standards. Model Number:
Highlights & Features RoHS Compliant Relay alarm indirection Built-in 2 channel DC OK signal Caused by rugged handing Conformal coating on PCBA to protect against chemical and dust pollutants Class I,
More informationProduct Overview. Product Identification. Amps One CT Two CTs Three CTs
AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More information(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2
Solid-state Contactor (New Heat Sink Construction) G3PB Space and working time saved with new heat sink construction. Series now includes 480-VAC models to allow use in a greater range of applications.
More informationDX³ RCBO 4500/6 ka Phase + Neutral, neutral on left
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationGVB-8 (Boost) Manual
www.genasun.com GVB-8 (Boost) Manual Solar Charge Controllers with Maximum Power Point Tracking For models: GVB-8-Pb-12V: 12V Lead-Acid/AGM/Gel/Sealed/Flooded GVB-8-Pb-24V: 24V Lead-Acid/AGM/Gel/Sealed/Flooded
More informationDIN-A-MITE C. SCR Power Controller Delivers Up To 80 Amperes in a Compact Package. TOTAL CUSTOMER SATISFACTION 3 Year Warranty. Features and Benefits
DIN-A-MITE C TOTAL CUSTOMER SATISFACTION 3 Year Warranty SCR Power Controller Delivers Up To 80 Amperes in a Compact Package The DIN-A-MITE C silicon controlled rectifier (SCR) power controller provides
More informationAF09... AF30 3-pole Contactors up to 20 HP / 480 VAC
AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory
More informationMotor Controllers AC Semiconductor Motor Controller Type RSHP Flexy
otor Controllers AC Semiconductor otor Controller Type RSHP Flexy Soft starting and stopping of 3-phase squirrel cage motors Low surge and vibration-free starting User-selected ramping profiles Integral
More informationCD3000S-1PH Thyristor Unit Heater Break version
USER S MANUAL Rev. 01/2007 CD3000S-1PH Thyristor Unit Heater Break version from 15A to 110A CD Automation S.r.l. Via Picasso 34/36-20025 Legnano (MI) ITALY Tel +39 0331 577479 Fax +39 0331 579479 E-Mail:
More informationIF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY X-RITE PANTONE, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED
EN Operation Manual Register your product and get access to important product updates, exclusive content, service support, and other tools to help you get the most of your product. www.xrite.com/registration
More informationVD Range Gamme VD. 100% electronic voltage detector. Détecteur de tension 100% électronique. Technical argumentation. Argumentation technique
Technical argumentation Argumentation technique VD Range Gamme VD 1SBC147007C1701 Technical Presentation VD range 1.0 - Version 1.0 100% electronic voltage detector Détecteur de tension 100% électronique
More informationAF09... AF30 3-pole Contactors up to 25 HP / 600 VAC
AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24
More informationMotor Controllers AC Semiconductor Motor Controller Type RSHP Flexy
Controllers AC Semiconductor Controller Type Soft starting and stopping of -phase induction squirrel cage motors Low inrush and reduced vibration during starting User-selected ramping profiles Integral
More informationUltimus IV Series. User s Guide. Dispensing System. Ultimus IV-3cc # Ultimus IV-5cc # Ultimus IV-10cc #
Ultimus IV Series Dispensing System User s Guide Ultimus IV-3cc #7017178 Ultimus IV-5cc #7017181 Ultimus IV-10cc #7017177 Ultimus IV-30cc #7017179 IMPORTANT! Save this Sheet. Forward to Maintenance or
More informationFor Motor Starting Use Schneider Electric Overload Relay Series LR. WARNING
LC / LC D5 D50 www.schneider-electric.com Contacteurs / Contacteurs-inverseurs Contactors / Reversing contactors Schütze / Wendeschütze Contattori / Teleinvertitori Contactores / Contactores-inversores
More information