Product Description: Objective and Certification: Test Samples and Test Cable:

Similar documents
25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

Eaton s Cooper Power Systems

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

Loadbreak Apparatus Connectors

600 A 15 kv class Cleer loadbreak connector system

600 A 35 kv class BT-TAP deadbreak connector

600 A 28 kv class Cleer loadbreak connector system

600 A 25 kv class BT-TAP deadbreak connector

600 A 15 kv class T-OP II deadbreak connector

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

25 kv Apparatus Bushings

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Molded Current-Limiting Fuse

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

INSTALLATION PRODUCTION TESTS

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

PRODUCT BROCHURE. Elastimold ComboT integral separable connectors

Installation Instructions LINK---C

600 A 15 and 25 kv class Cleer grounding elbow

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

Edison modular fuse, vault application products

Elastimold & Hi-Tech Fuse Products

Low voltage bushings for pad-mounted distribution transformers Technical information guide

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability

25 kv class fused loadbreak elbow connector

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

15 kv and 25 kv Thru-Bushings

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

CATALOG. Hi-Tech Fuse Products


COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

ELB ES. Product Installation Instructions

100 / 110 DRYWELL FUSE SPECIFICATION

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

IEC Separable Connectors 17.5 kv/24 kv, 630A

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Cobra-S. Catalog Cobra-S

Technical Specification For Outdoor Substation Harmonic Filter Banks

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

ELB ELB

Typical Specification

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

600 A 35 kv class deadbreak accessories, tools, and replacement parts

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

TABLE OF CONTENTS Page

CERTIFIED TEST REPORT

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

600 A Deadbreak Connectors

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

Submersible Vacuum Fault Interrupters

Padmount Solid Dielectric Switchgear Catalog

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

GROUP C. Apparatus Bushing.

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Specifier's Guide COOPER POWER. Line installation and protective equipment master catalog 5 kv - 35 kv electrical distribution systems SERIES

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

your Green Power WIND POWER SOLUTIONS only Greener

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

GROUP D. Switch & Protective device.

600 A 35 kv class separable splices

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Contents. Design Test Results for Specimen Design Test Results for Specimen Voltage Impulse Oscillograms...9

Transcription:

Product Description: The CableMate 2LBE loadbreak elbow connector and 2LBI loadbreak bushing insert are fully-shielded, fully submersible, insulated plug-in terminations for connecting underground cables to distribution apparatus such as transformers and switchgear. The CableMate 2LBE elbow is a fully rated 25kV, 200 amp switching device, designed in accordance to the latest IEEE Std 386. It includes provisions for energized operation using standard hotstick tools allowing loadmake/break operation and a visible disconnect. An optional capacitive voltage test point is available for application of fault indicators and determining if the circuit is energized. The CableMate 2LBI loadbreak bushing insert is fully rated with a 25kV class, 200 Amp loadbreak insert bushing interface. The 2LBI loadbreak bushing insert connects to a universal bushing well and becomes the apparatus bushing interface for elbow connections. When mated with a comparably rated component, the 2LBI bushing insert provides a fully shielded and submersible connection for loadbreak operation. All CableMate 2LBE1 loadbreak elbows and 2LBI loadbreak bushing inserts are interchangeable with other manufacturers products that also comply with the IEEE 386 standard. Objective and Certification: The objective of these tests are to verify and confirm the CableMate 2LBE 25kV, 200 amp loadbreak elbow and 2LBI 25kV, 200 amp loadbreak bushing insert meet or exceed the requirements of the IEEE Standard 386-2006, Separable Insulated Connector Systems for Power Distribution Systems above 600 Volts. These products comply with the interface dimensions in Figures 7 and 15 of this standard. This report certifies that the tests shown below have been successfully performed on the CableMate 2LBE 25kV, 200 amp loadbreak elbow and 2LBI 25kV, 200 amp loadbreak bushing insert in accordance with IEEE 386-2006. 1. Partial discharge test section 7.4 2. AC withstand voltage test section 7.5.1 3. DC withstand voltage test section 7.5.2 4. Impulse withstand voltage test (BIL) section 7.5.3 5. Test point test section 7.17 6. Accelerated sealing life test section 7.12 7. Cable pull out test section 7.13 8. Operating force test section 7.14 9. Operating eye test section 7.15 10. Test point cap test section 7.16 Test Samples and Test Cable: Ten (10) pieces of the CableMate 25kV, 200 amp loadbreak elbow kit with test point, catalog number 2LBE1H03B07, were installed on 1/0 AWG AL 25kV class cable with 6.6 mm insulation thickness. The complete elbow kit contained: 1 piece 25kV, 200 amp loadbreak elbow housing with test point, CableMate catalog number 2LBE1H03 1 piece 25kV, 200 amp loadbreak elbow probe, CableMate catalog number 2LBEPR 1 piece Bi-metal compression lug connector, CableMate catalog number LACB07 Each loadbreak elbow kit was mated with a CableMate 25kV, 200 amp loadbreak bushing insert, catalog number 2LBI, and an Elastimold K1601PC-T1 25kV, 200 amp universal bushing well. TR151012-1 Page 2 of 6

1. IEEE 386-2006 Sec. 7.4: Partial Discharge Test: The purpose of this test is to verify that the partial discharge level of the CableMate 2LBE 25kV, 200 amp loadbreak elbow and CableMate 2LBI loadbreak bushing insert meet the IEEE 386 requirement of 3pC at 19kV. After installation on the test stand, the test voltage was raised to 24kV and higher until the partial discharge peak value exceeded 3 pc. The test voltage was then lowered to 19kV and was maintained at this level for at least three (3) seconds but not more than one (1) minute. Partial discharge readings taken during this interval did not exceed 3 pc peak. Test result: All ten (10) samples tested had partial discharge levels less than or equal to 3pC at 19kV or greater. All ten (10) samples tested meet the requirements of Section 7.4 of IEEE Standard 386-2006. 2. IEEE 386-2006 Sec. 7.5.1: AC Withstand Voltage Test: The purpose of this test is to verify the CableMate 2LBE 25kV, 200 amp loadbreak elbow and CableMate 2LBI loadbreak bushing insert meet the IEEE 386 AC Withstand Voltage requirement of 40kV for one minute. Using the same ten (10) test samples that just completed the partial discharge test above, (Sec. 7.4), the test voltage was raised on all test samples to 40kV AC rms in less than thirty (30) seconds. Each of the ten (10) test samples withstood the 40kV AC test voltage for one (1) minute without flashover or puncture. Test result: All ten (10) samples passed the test at 40kV AC, 60 Hz, 1 minute. All ten (10) samples tested meet the requirements of Section 7.5.1 of IEEE Standard 386-2006. 3. IEEE 386-2006 Sec. 7.5.2: DC Withstand Voltage Test: The purpose of this test is to verify the CableMate 2LBE 25kV, 200 amp loadbreak elbow and CableMate 2LBI loadbreak bushing insert meet the IEEE 386 DC Withstand Voltage requirement of 78kV DC for fifteen (15) minutes. Using the same ten (10) test samples used in the partial discharge test (sec 7.4) and AC Withstand Voltage Test (Sec 7.5.1) above, the test voltage was raised to 78kVdc for fifteen (15) minutes. Each of the ten (10 test samples withstood the 78kV DC test voltage for fifteen (15) minutes without flashover or puncture. Test result: All 10 samples passed the test at 78kV DC for 15 minutes. All ten (10) samples tested meet the requirements of Section 7.5.2 of IEEE Standard 386-2006. 4. IEEE 386 Sec. 7.5.3: Impulse Withstand Voltage (BIL) Test: The purpose of this test is to verify the CableMate 2LBE 25kV, 200 amp loadbreak elbow and CableMate 2LBI loadbreak bushing insert meet the IEEE 386 requirement of 125kV crest, 3 positive and 3 negative full-wave impulses. Using the same ten (10) test samples used in the partial discharge test (sec 7.4), AC Withstand Voltage Test (Sec 7.5.1), and DC Withstand Voltage Test (Sec. 7.5.2) a test voltage having 1.2 x 50 µs wave with crest value at 125kV was applied to all ten (10) samples for three positive and three negative full-wave impulses. Test result: All ten (10) samples passed 3 positive and 3 negative full wave impulse at 125kV crest. All ten (10) samples tested meet the requirements of Section 7.5.3 of IEEE Standard 386-2006. TR151012-1 Page 3 of 6

5. IEEE 386 Sec. 7.17: Test Point Test: The purpose of this test is to verify that the capacitance values of the CableMate 2LBE 25kV, 200 amp loadbreak elbow test point meet the requirements of section 7.17.1 test point capacitance test and section 7.17.2 test point voltage test. Following the above tests, all ten (10) samples were subject to the test point test 7.17.1. The capacitance from the test-point of the elbow to the cable conductor and the test point to the shield was measured with appropriate instrumentation. The measured capacitance value was no less than 1.0pF. The capacitance ratio between the test point and the shield and the shield to the conductor was less than 12.0. Subsequent to the above, all (ten) 10 test samples were subject to section 7.17.2 test point voltage test. A test voltage was applied to the conductor system of the connectors. A voltage indicator (Elastimold V2) mounted on a hotstick was placed on the test point and all samples responded with positive voltage indication. Test result: All ten (10) samples passed. All ten (10) samples tested meet the requirements of Sections 7.17.1 and 7.17.2 of IEEE Standard 386-2006. 6. IEEE 386 Section 7.12: Accelerated Sealing Life Test. The purpose of this test is to verify the CableMate 2LBE 25kV, 200 amp loadbreak elbow and CableMate 2LBI loadbreak bushing insert can maintain a long-term seal at all interfaces to prevent the entrance of moisture. Four (4) new sets of test sample assemblies were prepared for this test (using the same components identified in the Test Samples and Test Cable section above) and subject to the test procedure defined in section 7.12. All four (4) test samples were placed in an oven having 121 C temperature for three weeks. Once removed from the oven, all four (4) test samples were operated once using the operating eye, then connected in series, and subjected to 50 cycles of the following sequence: a) The assemblies were heated in air using sufficient current to raise the temperature of the conductor of the control cable to 90 C ± 5 C for 1 hour; b) The assemblies were de-energized and within 3 minutes were submerged in 25 C ± 10 C conductive water (5000 Ω-cm maximum) to a depth of 30 cm (1 ft) for 1 hour. Following the above sequence, each test sample assembly passed the Impulse Withstand Test at 125kV crest, 3 positive and 3 negative full-wave impulses according to Section 7.5.3 and the Test Point Test according to Sections 7.17.1 and 7.17.2 of the IEEE 386-2006 standard. Test result: All four (4) test sample assemblies passed. All four (4) samples tested meet the requirements of Section 7.12 of IEEE Standard 386-2006. TR151012-1 Page 4 of 6

7. IEEE 386 Sec. 7.13: Cable Pull Out Test: The purpose of this test is to determine if the connection between the cable conductor and the compression lug of the connector is capable of withstanding a tensile force of 890 N (200 lbf) for 1 minute without impairing the connector's ability to meet the other requirements of the IEEE 386-2006 standard. Four (4) CableMate bi-metal compression lugs catalog number LACB07 were appropriately crimped onto 1/0 AWG aluminum conductor for this test. Section 7.13 of IEEE Standard 386-2006. 8. IEEE 386 Sec. 7.14: Operating Force Test: The purpose of this test is to verify that the that the force necessary to operate the CableMate 2LBE 25kV, 200 amp loadbreak elbow connector meets the requirements of IEEE 386-2006 standard section 6.2. and 7.14. The force required to open or close the loadbreak connector shall be within the range of 222 N to 890 N (50 lbf to 200 lbf). Four (4) new sets of test samples were prepared for this test. Each test sample was assembled and lubricated in accordance with CableMate s instructions and consisted of: - One (1) CableMate 25kV, 200 amp loadbreak elbow, catalog number 2LBE1H. - One (1) CableMate 25kV, 200 amp loadbreak elbow probe, catalog number 2LBEPR. - One (1) CableMate Bi-metal compression lug connector, catalog number LACB07. - One (1) CableMate 2LBI loadbreak bushing insert. The temperature of the loadbreak elbow was at 20 C, +25 C, and +65 C respectively for three independent tests. A force was applied parallel to the probe axis at a rate of 13 cm/min (5 in/min). Each test consisted of closing (loadmake) and then reopening (loadbreak) each connector within 10 minutes. Section 7.14 of IEEE Standard 386 2006. 9. IEEE 386 Sec. 7.15: Operating Eye Test: The purpose of this test is to verify the CableMate 2LBE 25kV, 200 amp loadbreak elbow operating eye meets the requirements of IEEE standard 386-2006 section 6.2 and 7.15 at 25 C ± 5 C. Four (4) new sets of samples were prepared for this test. A static tensile force of 500 lbf was gradually applied to the operating-eye of each elbow parallel to the probe access for a minimum of one minute. A rotational force of 120 lbf-in was then applied to the operating-eye in a clockwise direction, then in a counter-clockwise direction with a suitable live-line tool. After the tensile and rotational forces were applied, each elbow was subjected to the Partial Discharge Test from Section 7.4. Section 7.15 of IEEE Standard 386 2006. TR151012-1 Page 5 of 6

10. IEEE 386 Sec. 7.16: Test Point Cap Test: The purpose of this test is to demonstrate that force required to remove the test point cap is within the range of 36 N 218 N (8 lbf 49lbf) and the cap operating eye is capable of withstanding a maximum static operating force of 445 N (100 lbf) over the environmental temperature range of 20 C to +65 C. Four (4) new sets of samples were prepared for this test. A tensile force was gradually applied to the test point cap in the direction parallel with the operating interface axis at 20 C, +25 C, and +65 C. The force required to remove the test-point cap was within the range of 8 to 49 lbf for all four (4) samples tested. A tensile force of 100 lbf was then applied to all four (4) samples for 1 minute at 20 C, +25 C, and +65 C. Section 7.16. of IEEE Standard 386 2006. TR151012-1 Page 6 of 6