Thermal-magnetic Miniature Circuit Breaker 40-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-, UL 1077 and UL 489 for DIN rail mounting, with toggle actuation, visual status indication and high rupture capacity. A positively trip-free snap action mechanism ensures reliable switching behaviour. A range of trip characteristics and add-on modules allow a great variety of applications. Typical applications Protection of cables, motors, generators and transformers, thyristors and silicon rectifiers. Protection of computers and their peripheral equipment, industrial process control systems, telecommunications equipment, power supplies. UL 489 version 40-T... IEC/EN60947- & UL1077 version Technical Data Voltage rating and current rating range to IEC/EN 60947-1-pole; AC 0 V; 1 A 6 A;,, 4-pole; AC 400 V, 1 A 6 A; to UL 1077 1-pole; AC 77 V; 1 A 6 A;,, 4-pole; AC 480 V, 1 A 6 A; 1-pole; DC 60 V; 1 A...6 A; -pole; DC 15 V; 1 A...6 A; to UL 489 1-pole; AC 10 V; 1A 6 A;, -pole; AC 40 V, 1 A 6 A; 1-pole; AC 77 V; 1 A A;, -pole; AC 480 V; 1 A A; 1-pole; DC 60 V; 1 A 6 A; -pole; DC 15 V; 1A 6 A; Endurance Mechanically Electrically 0,000 cycles 6,000 cycles Technical Data Rupture capacity to IEC/EN 60947- (Ics) to IEC/EN 60947- (Icu) 7,500 A 10,000 A to UL 489 10,000 A to UL1077 Number of Un In TC OL SC poles 1-pole AC 40 V 1...6 A 1 1 7.5 ka, U1 1-pole AC 77 V 1...6 A 1 0 5 ka, U1 -, -, AC 480 V 1...6 A 1 1 7.5 ka, U1 4-pole 1-pole DC 60 V 1...6 A 1 0 7.5 ka, U1 -pole in DC 15 V 1...6 A 1 0 7.5 ka, U1 series Insulation coordination Degree of protection Vibration (sinusoidal) test to IEC 60068--6, test Fc Shock, test to IEC 60068--7, test Ea Corrosion, test to IEC 60068--11, test Ka Humidity, test to IEC 60068--78, test Cab Terminals 6 kv/ (reinforced insulation at operating area) IP0 ± 0.8 mm (10 57 Hz), 5 g (57 500 Hz) 10 frequency cycles per axis 0 g (11 ms) 96 hrs in 5% salt mist 48 hours at 95% RH, temperature +40 C screw terminals Vertical connection possible by means of busbars Tightening torque Nm max. Cable cross section 5 mm² Ambient temperature: -5 C...+ 70 C Mounting rail mounting Mass approx. 116 g per pole (EN 60947-/ UL 1077) approx. 11 g per pole (UL 489) www.e-t-a.de - 1
Thermal-magnetic Miniature Circuit Breaker 40-T... Order numbering code Dimensions IEC/EN 60947- / UL1077 version Type No. 40 single and multipole thermal-magnetic high performance circuit breaker Mounting T1 rail mounting Number of poles 1 single pole protected double pole protected three pole protected 4 four pole protected* Accessories 0 without terminals K0 screw terminals Characteristic curve B: thermal 1.05-1.0 * In; magnetic. - 4.8*In C: thermal 1.05-1.0 * In; magnetic 6.4-9.6*In D: thermal 1.05-1.0 * In; magnetic 9.6-14.4*In E IEC/EN 60947- (TÜV) / UL 1077 U UL 489 (only 1-, - & -pole) / IEC/EN 60947- (TÜV) Current 1, 1., 1.5, 1.6,,, 4, 5, 6, 7, 8, 10, 1, 1, 15, 16, 0, 5, 0,, 5, 40, 50, 60, 6 A 40 - T1 1 0 - K0 C E - 10 A ordering example 4 P P P 1 P 70.5 ± 0.8 5.9 ± 0.6 5. ± 0.4 17.6 ± 0. 9 ± 0. 8 max. 49.8 ± 0. 60. ± 0. 45 ± 0. * not for UL 489 5.5 ± 0. Current ratings and voltage drop @ +5 C Dimensions UL 489 version Voltage drop in V at 1 I N I N (A) 1 4 6 10 16 V.0 1.5 0.75 0.50 0.0 0. I N (A) 0 5 40 50 6 V 0. 0.18 0.19 0.19 0.18 0.1 9 ± 0. Approval authority TÜV Standard Rated voltage Current ratings IEC/EN 60947-: AC 0/400 V 1 A, A, 4 A, 6 A, 10 A, 16 A, 0 A, 5 A, A, 40 A, 50 A, 6 A P P 1 P 5.9 ± 0.6 5. ± 0.4 17.6 ± 0. 60. ± 0. 60.1 ± 0. UL UL 1077 / CSA-C. No. 5 UL UL 489 / CSA-C. No. 5 AC 480Y/77 V DC 60 V, DC 15 V AC 40 V AC 480Y/77 V DC 60 V, DC 15 V 1...6 A 1...6 A 1...6 A 1... A 1...6 A 116 ± 0.4 45 ± 0. 5.5 ± 0. - www.e-t-a.de
Thermal-magnetic Miniature Circuit Breaker 40-T... Time/current characteristics Schematic diagrams 10000 Ambient temperature +0 C No-trip current 1.05x In Trip current 1.0x In 1-pole 1 -pole 1 1000 Curve B magnetic trip current 4x In (±0%) Curve C magnetic trip current 8x In (±0%) Curve D magnetic trip current 1x In (±0%) 4 -pole 4-pole 100 1 5 1 5 7 Trip time in seconds 10 4 6 4 6 8 1 0,1 B C D 0,01 0,8 1 4 6 8 10 0 40...times rated current Magnetic tripping currents are increased by 0 % on DC supplies. All dimensions without tolerances are for reference only. E-T-A reserves the right change specifications at any time in the interest of improved design, performance and cost effectiveness, the right to make changes in these specifications without notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted. www.e-t-a.de -
Thermal-magnetic Miniature Circuit Breaker 40-T... Max. operating currents depending on ambient temperature Rated current I N (A) Max. operating currents depending on ambient temperature T (A) -5 C -0 C -5 C -0 C -15 C -10 C -5 C 0 C +5 C +10 C +15 C 1 1.7 1.5 1. 1.1 1.19 1.17 1.15 1.1 1.10 1.08 1.06.54.50.46.4.8.4.0.6.0.16.1 4 5.08 5.00 4.9 4.84 4.76 4.68 4.60 4.5 4.40 4. 4.4 6 7.70 7.58 7.46 7.4 7.1 7.09 6.96 6.8 6.70 6.56 6.4 10 1.89 1.6 1.5 1.07 1.81 1.5 1. 11.9 11.6 11. 11.01 16 0.78 0.4 0.08 19.75 19.40 19.05 18.70 18. 17.96 17.58 17.0 0 5.67 5.8 4.88 4.47 4.06.64..78.4 1.89 1.4 5.1 1.7 1. 0.70 0.18 9.65 9.10 8.55 7.98 7.41 6.8 41.04 40.46 9.8 9.17 8.51 7.84 7.15 6.47 5.75 5.0 4.0 40 51.6 50.86 50.04 49,1 48.7 47.51 46.6 45.74 44.8 4.90 4.95 50 64.9 6.97 6.9 61.86 60.77 59.67 58.54 57.40 56. 55.05 5.81 6 8.48 8.06 60.64 79.19 77.7 76. 74.70 7.14 71.54 69.91 68.4 Rated current I N (A) Max. operating currents depending on ambient temperature T (A) +0 C +5 C +0 C +5 C +40 C +45 C +50 C +55 C +60 C +65 C +70 C 1 1.05 1.0 1.00 0.97 0.94 0.91 0.89 0.86 0.8 0.80 0.77.10.04.00 1.94 1.88 1.8 1.78 1.7 1.66 1.60 1.54 4 4.0 4.08 4.00.88.76.64.56.44..0.08 6 6.7 6.14 6.00 5.84 5.68 5.5 5.6 5.19 5.01 4.8 4.64 10 10.67 10.4 10.00 9.6 9.4 8.85 8.45 8.01 7.55 7.06 6.55 16 16.80 16.40 16.00 15.55 15.11 14.66 14.0 1.71 1.1 1.70 1.75 0 0.96 0.47 0.00 19.47 18.95 18.4 17.87 17.0 16.71 16.10 15.47 5 6. 5.61 5.00 4..67.00.8 1.56 0.80 0.0 19.1.54.77.00 1.17 0.4 9.48 8.69 7.69 6.75 5.78 4.77 40 41.98 40.99 40.00 8.9 7.85 6.75 5.61 4.4.1 1.95 0.6 50 5.56 51.8 50.00 47.8 46.4 44.81 4. 41.81 40. 8.58 5.77 6 66.5 64.78 6.00 60.11 58.19 56.1 54.16 5.0 49.81 47.50 4.05-4 www.e-t-a.de
Auxiliary contact module X40-S for circuit breaker type 40-T... Description Add-on module for circuit breaker type 40-T. The auxiliary switch has a change-over contact as signal contact and is operated with actuation of the MCB. Typical applications Status monitoring of MCB and/or the connected loads. Mounting The add-on module is mounted on the left side of the MCB (seen from the front). For mounting, the MCB has to be in the OFF position. Order numbering code Type No. X40 Add-on module for type 40-T Module type S aux. contact switch Style 0 change-over contact terminals 1 screw terminals Key for nominal output A (to IEC/EN 60947-5-1) AC voltage DC voltage Rated Rated Rated Rated voltage current voltage current 40 V 6 A 4 V 6 A 415 V A 48 V A 10 V 1 A B (to UL 489) 1...40 V 6 A 1...4 V 6 A 77 V A 48 V A 110...0 V 1,5 A Delivery condition: L supplied separately, has to be mounted by the user Approval Standard Types authority TÜV IEC/EN 60947-5-1 with key index "A" UL UL 489 with key index "B" Mounting instructions Mounting to MCB to UL 489 The following steps have to be carried out for mounting the auxiliary contact module: - Remove the left-side covers for the latching notches of the auxiliary contact module on both isolation pieces of the MCB, e.g. by means of a screw driver - Pull off the isolation pieces from the MCB to the front - Remove blanking plug on MCB to open left-side holes for latching notches of auxiliary switch - Re-insert isolation pieces onto MCB - Pull off left-side adhesive cover and carefully remove the perforated cover below Caution: the MCB to UL489 must only be operated with the insulation pieces fitted. Schematic diagrams 11 1 14 Mounting principle Note: As soon as the auxiliary contact module is mounted on the MCB, the terminals 11 and 14 are connected when the MCB is in ON condition. Terminals 11 and 1 are connected when the MCB is in OFF condition. X40- S 0 1 A L ordering example 81 ± 0.5 45 ± 0.5 9 Technical Data Rated currents to IEC/EN 60947-5-1: Voltage Current Rated currents to UL 489: Voltage Current AC 40 V AC 415 V DC 4 V DC 48 V DC 10 V 6 A A 6 A A 1 A AC 1 40 V AC 77 V DC 1... 4 V DC 48 V DC 110... 0 V 6 A A 6 A A 1.5 A 66 ± 0.5 60.4 ± 0.5 85.8 ± 0.5 5.5 ± 0.5 Endurance 0,000 cycles 40-T... X40-S Tightening torque 1 Nm max. Ambient temperature -5 C...+ 70 C Width Mass 9 mm approx. 9 g www.e-t-a.de - 5
Fault indicator module X40-A for circuit breaker type 40-T... Description Add-on module for MCB type 40-T. The fault indicator has a change-over contact as signal contact. There will only be a signal when the MCB tripped on grounds of a failure (overload, short circuit), but and not when the MCB was switched on or off manually. By actuating the reset lever on the front the tripping signal is acknowledged. Typical applications Status monitoring of MCB and/or the connected loads. Mounting The add-on module is mounted on the left side of the MCB (seen from the front). For mounting, the MCB has to be in the OFF position. Order numbering code Type No. X40 Add-on module for type 40-T Module type A Fault indicator module Style 0 change-over contact terminals 1 screw terminals Key for nominal output A (to IEC/EN 60947-5-1) AC voltage DC voltage Rated Rated Rated Rated voltage current voltage current 40 V 6 A 4 V 6 A 77 V A 48 V A 10 V 1 A B (to UL 489) 1...40 V 6 A 1...4 V 6 A 415 V A 48 V A 10 V 1.5 A Delivery condition: L supplied separately, has to be mounted by the user X40-A 0 1 A L ordering example Approval Standard Types authority UL UL 489 with key index "B" Mounting instructions Mounting to MCB to UL 489 The following steps have to be carried out for mounting the fault indicator module: - Remove the left-side covers for the latching notches of the fault indicator module on both isolation pieces of the MCB, e.g. by means of a screw driver - Pull off the isolation pieces from the MCB to the front - Remove blanking plug on MCB to open left-side holes for latching notches of indicator switch - Re-insert isolation pieces onto MCB - Pull off left-side adhesive cover and carefully remove the perforated cover below Caution: the MCB to UL489 must only be operated with the insulation pieces fitted. Schematic diagrams 91 94 9 Mounting principle 81 ± 0.5 45 ± 0.5 Note: As soon as the fault indicator module is mounted on the MCB, the terminals 91 and 9 are connected when the MCB is in ON condition; ther terminals 91 and 94 are connected when the MCB tripped electrically; the terminals 91 and 9 are connected when the MCB was tripped manually; at the same time the terminals 91 and 94 do not have contact. 9 Technical Data Rated currents to IEC/EN 60947-5-1: Voltage AC 40 V AC 415 V DC 4 V DC 48 V DC 10 V Current 6 A A 6 A A 1 A Rated currents to UL 489: 66 ± 0.5 60.4 ± 0.5 5.5 ± 0.5 Voltage Current AC 1 40 V AC 77 V DC 1... 4 V DC 48 V DC 110... 0 V 6 A A 6 A A 1.5 A 85.8 ± 0.5 40-T... X40-A Endurance 0,000 cycles Tightening torque 1 Nm max. Ambient temperature -5 C...+ 70 C Width 9 mm Mass approx. 9 g - 6 www.e-t-a.de
Working current module X40-FA for circuit breaker type 40-T... Description Add-on module for MCB type 40-T. The working current module serves for remote trip of the MCB and for signalling whether the MCB was tripped electrically or manually. Typical applications Electrical remote trip of safety equipment with simultaneous monitoring of MCB status or its connected load. Mounting The add-on module is mounted on the left side of the MCB (seen from the front). For mounting, the MCB has to be in the OFF position. When auxiliary contact module/fault indicator module and a working current module are mounted at the same time, the working current module always has to be mounted first. Order numbering code Type No. X40 Add-on module for type 40-T Module type F Working current module Style A Magnetic coil and auxiliary switch (changeover) physically isolated from the MCB terminals 1 screw terminals A without B UL 489 Delivery condition: L supplied separately, has to be mounted by the user Rated voltage Approval A B AC 10 V --- UL 489 AC 40 V without UL 489 AC 77 V --- UL 489 AC 415 V without --- DC 1 V --- UL 489 DC 4 V without UL 489 DC 48 V without UL 489 DC 15 V --- UL 489 X40- F A 1 A L - AC 40 V ordering example Technical Data Voltage ratings AC AC 415 V AC 77 V AC 40 V AC 10 V Min. trip voltage AC 00 V AC 160 V AC 160 V AC 80 V Power consumption 40 W 40 W 00 W 00 W min. response power 5 W 5 W 5 W 5 W Rated current of A A 6 A 6 A auxiliary contact Voltage ratings DC DC 15 V DC 48 V DC 4 V DC 1 V Min. trip voltage DC 80 V DC 4 V DC 16 V DC 8 V Power consumption 00 W 00 W 00 W 00 W min. response power 0 VA 0 VA 0 VA 0 VA Rated current of 1.5 A A 6 A 6 A auxiliary contact Trip time < 10 ms Endurance 0,000 cycles Tightening torque 1 Nm max. Ambient temperature -5 C...+ 70 C Width 18 mm Mass approx. 60 g Mounting instructions Mounting to MCB to UL 489 The following steps have to be carried out for mounting the working current module: - Remove the left-side covers for the latching notches of the working current module on both isolation pieces of the MCB, e.g. by means of a screw driver - Pull off the isolation pieces from the MCB to the front - Remove blanking plug on MCB to open left-side holes for latching notches of working current module - Re-insert isolation pieces onto MCB - Pull off left-side adhesive cover and carefully remove the perforated cover below Caution: the MCB to UL489 must only be operated with the insulation pieces fitted. Mounting principle 81 ± 0.5 45 ± 0.5 18 max. Approval Standard Types authority UL UL 489 Approval type "B" according to ordering number code Schematic diagrams 66 ± 0.5 60.1 ± 0.5 N / - C1 L / + C 11 5.5 ± 0.5 14 FA 1 8 ± 0.5 40-T... X40-FA www.e-t-a.de - 7
Accessories - Busbars for 40-T... Busbars UL 489 to be cut to length Busbars for the connection of circuit breakers type 40-..U.. to UL 489. The busbars of 1m length can individually be cut to a suitable length for the application and isolated with end caps. Depending on the control cabinet design, the supply is by means of supply terminals without increasing the installation width or by means of a terminal block directly on the rail without increasing the installation height. The models marked with "HS" are suitable for use with auxiliary contact modules with a width of 9 mm. Busbar cross section: Max. busbar current I s (at 5 C): with supply at the end: with supply in the middle: Short circuit strength I cc : Max. operating voltage: Degree of protection: Step size: 18 mm² 80 A 160 A 10 ka 480 V AC/DC IP0 17.8 mm 14.5 5 17.8 6.4 15x6.4 = 96 19. Accessories for busbars UL489 that can be cut to length: supply terminal part no. X40-FTUC5 1.8 8.5 0.7.5-5 mm² ( 14 AWG), 5.5 Nm (50 lbf.in) max. 115 A 1.1 16.4 59. supply with supply terminal 6 85 16. Terminal block part no. X40-FBU50 1.5 50 mm² (1 14 AWG), solid/stranded 1.5-5 mm² ( 14 AWG), finely stranded with wire end ferrule supply:.5 Nm (5 lbf.in) output (track side):.5 Nm ( lbf.in) max. 115 A supply with terminal block Number of poles Number of modules part no. 1-pole 57 X40-BU157P18S -pole 56 X40-BU56P18S -pole 57 X40-BU57P18S 1-pole + HS 7 X40-BU17P18HS -pole + HS 46 X40-BU46P18H1S -pole + HS 48 X40-BU48P18H1S end caps part no. X40-EC1 Accessories for all busbars UL489 that can be cut to length: Protection against brush contact part no. X40-TC for covering unused modules HS = application with auxiliary switch 9 mm - 8 www.e-t-a.de
Accessories - Busbars for 40-T... Busbars UL 489, cannot be cut to length Busbars for the connection of circuit breakers type 40-..U.. to UL489. Depending on busbar type suitable for up to 18 poles. Busbar cross section: Max. busbar current I s : Short circuit strength I cc : Max. operating voltage: Degree of protection: Step size: Number of poles Number of modules 16 mm² 115 A 10 ka 480 V AC/DC IP0 17.6 mm part no. 1-pole 6 X40-BU106P16A 1-pole 1 X40-BU11P16A 1-pole 18 X40-BU118P16A -pole 6 X40-BU06P16A -pole 1 X40-BU1P16A -pole 18 X40-BU18P16A -pole 6 X40-BU06P16A -pole 1 X40-BU1P16A -pole 18 X40-BU18P16A Accessories for busbars UL489 that cannot be cut to length: Terminal block part no. X40-FBU50 1.5 50 mm² (1 14 AWG), solid/stranded 1.5-5 mm² ( 14 AWG), finely stranded with wire end ferrule: supply:.5 Nm (5 lbf.in) output (track side):.5 Nm ( lbf.in) max. 115 A 99 15.5 Protection against brush contact part no. X40-TC1 5 7.6 5 17.6 1.5 1.5 max. 1.5 4 5x17.6 = 88 1 16 Accessories for busbars UL489 that cannot be cut to length: 48. supply terminal part no. X40-FTU5.5-5 mm² ( 14 AWG), 5.5 Nm (50 lbf.in) max. 115 A Approval authority Standard Types UL UL 489 X40-BU... UL UL 508 X40-BR 6 16.1 48.5 74. 16. 1.1 www.e-t-a.de - 9
Accessories - Busbars for 40-T... Busbars UL 508 to be cut to length Busbars for the connection of circuit breakers type 40-..E.. to UL1077 The busbars of 1m length can individually be cut to a suitable length for the application and isolated with end caps. Depending on the control cabinet design, the supply is by means of supply terminals without increasing the installation width or by means of a terminal block directly on the rail without increasing the installation height. The models marked with "HS" are suitable for use with auxiliary contact modules with a width of 9mm. Busbar cross section: Max. busbar current I s (at 5 C): with supply at the end: with supply in the middle: Short circuit strength I cc : Max. operating voltage: Degree of protection: Step size: 18 mm² 80 A 160 A 10 ka 480 V AC/DC IP0 17.8 mm Number of poles Number of part no. modules 1-pole 57 X40-BR157P18SB -pole 56 X40-BR56P18SL -pole 57 X40-BR57P18SL 1-pole + HS 7 X40-BR17P18H1SB -pole + HS 46 X40-BR46P18H1SL -pole + HS 48 X40-BR48P18H1SL HS = application with auxiliary switch 9 mm Accessories for busbars UL508 that can be cut to length: supply terminals for single pole busbars: for multipole busbars: 7.6 16.1 8.5 16. 8.5 1.9 6 59 part no. X40-FTR15 part no. X40-FTR5 6-50 mm² (1-10 AWG), solid/stranded 6-5 mm² (-10 AWG), finely stranded with wire end ferrule 5.5 Nm (50 lbf.in) max. 115 A Accessories for busbars UL508 that can be cut to length: Terminal block part no. X40-FBR50 18.5 6. 5.5 1.5 17.8 56x17.8 = 996.8 5 6.5 14.8 15 1. ferrule: 6-50 mm² (1-10 AWG), solid/stranded 6-5 mm² (-10 AWG), finely stranded with wire end supply:.5 Nm (5 lbf.in) output (track side):.5 Nm ( lbf.in) max. 115 A 6 17.8 56x17.8 = 996.8 1.5 1. 8.8 9.8 4 end caps for single pole busbars: for multipole busbars: part no. X40-EC part no. X40-EC 17.75 40 10.5 5.1 Protection against brush contact part no. X40-TC for covering unused modules. 85. 14.8-10 www.e-t-a.de
Accessories - Busbars for 40-T... Busbars for IEC applications, to be cut to length Busbars for the connection of circuit breakers type 40-..E.. to IEC 60947-. The busbars of 1m length can individually be cut to a suitable length for the application and isolated with end caps. The models marked with "HS" are suitable for use with auxiliary contact modules with a width of 9 mm. Busbar cross section: Max. busbar current Is (at 5 C): with supply at the end: with supply in the middle: Short circuit strength Icc: Max. operating voltage: Degree of protection: Step size: 16 mm² 80 A 10 A 10 ka 690 V AC/DC IP0 17.8 mm Accessories for busbars to IEC 60947 that can be cut to length: supply terminal for multipole busbars: part number Y 11 60 01 6 6 5 mm², solid/stranded 4 16 mm², finely stranded with wire end ferrule: max. 80 A Number of poles Number of modules part no. 1-pole 57 Y 11 6 01 -pole 56 Y 11 6 01 -pole 57 Y 11 64 01 4-pole 56 Y 11 65 01 1-pole + HS 7 Y 11 66 01 -pole + HS 46 Y 11 67 01 -pole + HS 48 Y 11 68 01 4-pole + HS 5 Y 11 69 01 HS = application with auxiliary switch 9 mm 1 Accessories for busbars to IEC 60947 that can be cut to length: supply terminal for multipole busbars: part no. Y 11 61 01 49.5 17.7 56x17.8 = 996.8 17.8.6 1.5 4.6 15.8 14.7 56x17.8 = 996.8 17.8 4 1 11.7 17,5 9. 14.5 Degree of protection: 11 6 6 50 mm², solid/stranded 4 5 mm², finely stranded with wire end ferrule: 1 Nm (at 6 mm²).5 Nm (at 50 mm²) max. 15 A IP0, isolated bottom end caps for single pole busbars: part no. Y 07 851 01 for -/-pole busbars part no. Y 08 506 01 for four-pole busbars: part no. Y 11 6 01.5 15 5.5 Protection against brush contact part no. Y 11 6 01 17.8 4x17.8 = 71. 16.5 7.1 1 84. www.e-t-a.de - 11