Flow controller (PN 16, 25, 40) AFQ / VFQ 2(1) - return and flow mounting

Similar documents
k VS DN (mm) Connections ( C) (m 3 /h)

Differential pressure controller (PN 16, 25, 40) AFP(-9) / VFG 2(1) return and flow mounting, adjustable setting

Differential pressure relief controller (PN 16, 25, 40) AFPA / VFG 2(1)

Pressure relief controller AFA / VFG 2(1) (PN 16, 25, 40)

Flow controller (PN 25) AVQ - return and flow mounting

Flow Control and Differential Pressure Controller AFPQ / VFQ 2(21) - Installation in return line AFPQ 4 / VFQ 2(21) - Installation in flow line

Flow controller (PN 25) AVQ - return and flow mounting

Differential pressure controller AFP / VFG 2 (VFG 21)

Differential pressure controller AFP / VFG 2 (VFG 21)

Pressure reduction controller AFD / VFG 2, VFG 21, VFGS 2

Pressure reduction controller AFD / VFG 2, VFG 21, VFGS 2

Differential pressure relief controller AFPA / VFG 2 (VFG 21)

Flow controller with integrated control valve (PN 16) AHQM return and flow mounting

Differential pressure controller AFP / VFG 2 (VFG 21)

Flow controller with integrated control valve (PN 16) AVQM - return and flow mounting

AVQMT. AVQT controller can be combined with AVT or STM thermostatic actuators.

Data sheet Pressure independent control valve with integrated flow limiter AVQM (PN 16) - return and flow mounting

Differential pressure controller with flow limitation and with integrated control valve (PN 16) AHPBM-F flow mounting, fixed setting

Pressure reduction controllers (PN 25) AVDS - for steam AVD - for water

Pressure relief controller for oil V22D28 (PN 16, 25)

Pressure relief controller AVA (PN 25)

Flow controller with integrated control valve (PN 16) AHQM - return and flow mounting

Pressure independent control valve with integrated flow limiter AVQM (PN 16) - return and flow mounting

Two- and three way valves VFG.. / VFGS 2 / VFU.. for self-acting thermostats and electrical actuators

Temperature controller for heating (PN 25) AVT / VG - external thread AVT / VGF - flange

2 - way valve (NO), pressure relieved (PN 25) VG - external thread VGF - flange

Temperature controller (PN 25) AVT / VG - external thread AVT / VGF - flange

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Seated valves (PN 16) VF 2-2-way valve, flange VF 3-3-way valve, flange

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25)

Seated valves (PN 16) VRB 2 2-way valve, internal and external thread VRB 3 3-way valve, internal and external thread

Temperature controller AVT with safety temperature monitor STM/VG(F) (PN25)

Seated valves (PN 16) VRB 2 2-way valve, internal and external thread VRB 3 3-way valve, internal and external thread

Seated valves (PN 16) VRG 2 2-way valve, external thread VRG 3 3-way valve, external thread

Thermostatic actuator RAVI - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16)

Flow-compensated temperature controller AVTQ DN 15

Seated valves VF 2, VL 2-2-way VF 3, VL 3-3-way

Your Personal Catalog Temperature Controllers All our know-how - is now yours

Pressure independent balancing and control valve

ZONE CONTROLE / 2-WAY

DA 50. Differential pressure controllers Adjustable set-point

Pressure independent balancing and control valve AB-QM DN

Combined automatic balancing valve AB-PM valve DN 15-25, PN 16

2, 3 and 4 - way valves VZL

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Butterfly valve with electrical actuator VFY-WA

Butterfly valve with electrical actuator VFY-WA

Pressure independent balancing and control valve AB-QM DN

Pressure independent balancing and control valve For ON/OFF control

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Static Balancing Valve

Automatic balancing valves ASV-PV DN (3rd gen.)

Combined Self-operated Regulators Regulators for Differential Pressure, Flow Rate and Temperature

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

ANSI version. The valve closes when the differential pressure rises

Maintenance-free metallic seat shut-off globe valves

Series 02: DN40 and DN50 Series 01: DN Three-port slipper valves PN6

Typetested versions With Type 3213 Globe Valve, unbalanced. With Type 3214 Globe Valve, balanced

Series 240 Electric Control Valve Type 3241/3274 Globe Valve Type 3241 Electric Control Valve Type 3244/3274 Three-way Valve Type 3244

Series 240 Pneumatic On-off Valve Type 3351

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Series 240 Type 3351 Pneumatic On/off Valve

Maintenance-free metallic seat shut-off globe valves

3-port seat valves PN16 with flanged connection

Ball Valves JIP (PN 16, 25, 40)

Combined automatic balancing valve AB-PM valve DN 10-32, PN 16

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Self-operated Temperature Regulators Type 1u Temperature Regulator

Technote. Frese YDF-2F & YDF-20F - differential pressure control valve. Application. Benefits. Features.

Self-operated Temperature Regulators Temperature Regulator Type 1u

Pressure relief controller V22 D28

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

Data Sheet T EN

Valve Series V2001 Three-way Valve Type 3323

2-Port Seat Valves with Flange, PN 25

Pressure Reducing Valve Type 2114/2415

Butterfly valves PN6, PN10, PN16

Butterfly valves PN 16

3-port valves vxf42..

Pneumatic Butterfly Valve Type 3335 / AT

SELF-ACTUATING DIFFERENTIAL PRESSURE AND FLOW REGULATORS TYPE ZSN91; 92

HERZ-Motorised flow controler

3-port seat valves PN6 with flanged connection

2-port seat valves PN16 with flanged connection

Butterfly valves PN6, PN10, PN16

2-way and 3-way globe valves

ARI-STEVI 423 / 463 (DN ) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

VBF21.. Three-port slipper valves PN6. Series 02: DN40 and DN50 Series 01: DN

Self-operated Temperature Regulators Type 1u Temperature Regulator

3-Port Seat Valves with Flange, PN 6

ARI-STEVI 423 / 463 Pneumatic actuator ARI-DP 34-34T. Electric actuator ARI-PREMIO 5-25 kn ARI-PREMIO-Plus 2G 5-25 kn

3-Port Seat Valves with Flange, PN 10

2-port ball valves with flanged connection, PN25

High capacity valve body, type RA-G

ON/OFF zone valves AMZ 112, AMZ 113

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Pressure reducing valve Pressure reducing valve in straightway form DN

STAF, STAF-SG. Balancing valves PN 16 and PN 25 DN

Transcription:

Data sheet Flow controller (PN 16, 5, 40) AFQ / VFQ ( - return and flow mounting Description The controller has a control valve with adjustable flow restrictor and an actuator with one control diaphragm. Further on two valve versions are available: - VFQ with metallic sealing cone - VFQ 1 with soft sealing cone (on special request) The controller is a self-acting flow controller primarily for use in district heating systems. The controller closes when set max. flow is exceeded. Main data: DN 15-50 k VS 4,0-400 m 3 /h Flow range: 0,1-50 m 3 /h PN 16, 5, 40 Flow restrictor p b : 0, bar or 0,5 bar Temperature: - Circulation water / glycolic water up to 30 %: 140 / 150 / 00 C Connections: - Flange Ordering Example 1: Flow controller; DN 15; k VS 4,0; PN 16; metallic sealing; flow restrictor p b 0, bar; T max 150 C; flange; - 1 VFQ DN 15 valve Code no: 065B654-1 AFQ actuator Code no: 003G104-1 AFQ DN 15 impulse tubes Code no: 003G1338 Products will be delivered separatly. VFQ Valves (metallic sealing cone) Picture DN k VS T max. Code No. Connections (mm) (m 3 /h) ( C) PN 16 PN 5 PN 40 15 4,0 065B654 065B667 065B677 0 6,3 065B655 065B668 065B678 5 8,0 065B656 065B669 065B679 3 16 065B657 065B670 065B680 40 0 065B658 065B671 065B681 150 00 50 3 065B659 065B67 065B68 65 50 Flanges acc. to EN 109-1 065B660 065B673 065B683 80 80 065B661 065B674 065B684 100 15 065B66 065B675 065B685 15 160 065B663 065B676 065B686 150 80 065B664-065B687 00 30 140-065B758-065B688 50 400 065B759-065B689 Impulse tubes AFQ Note: other valves available on special request. at temperatures above 150 C only with seal pots (see Accessories) AFQ Actuators Picture Flow restrictor p b Max. oper. pressure Code No. (bar) (PN) 0, 003G104 5 0,5 003G105 DEN-SMT/SI VD.CA.O3.0 Danfoss 01/015 1

Ordering (continuous) Example : Flow controller; DN 15; k VS 4,0; PN 16; metallic sealing; flow restrictor p b 0, bar; T max 00 C; flange; - 1 VFQ DN 15 valve Code no: 065B654-1 AFQ actuator Code no: 003G104 - AFQ DN 15 impulse tubes Code no: 003G1391 - Seal pot V1 Code no: 003G139 Products will be delivered separatly. Accessories Picture Type designation For controller Impulse tubes (Stainless steel) AFQ DN (mm) PN Code No. 15 003G1338 0 5 003G1340 3 40 003G134 50 16, 5, 40 003G1343 65 003G1344 80 100 003G1346 15 003G1347 150 003G1348 00 16 003G1414 40 003G1349 50 16 003G1350 40 003G1404 With combination piece KF or KF3 use 003G1391 at PN 16 and T<150 C. Otherwise impulse tubes on special request. Seal pot V1 Impulse tubes AFQ Accessories Picture Type designation Description Ordering number Code No. Impulse tube set AF - 1 Copper tube Ø10 1 1500 mm - 1 compression fitting for imp. tube connection to pipe (G 1/4) - socket DN 15-50 DN 00, 50 3 003G1391 Seal pot V1 Compression fitting ) Capacity 1 liter; with compression fittings for imp. tube Ø10 For impulse tube Ø10 connections to controller AFQ 003G139 G 1/4 003G1468 Combination piece KF3 For combination with pressure and electrical actuators G 11/4 / G 11/4 003G1397 Combination piece KF For combination with thermostat 003G1398 Shut off valve Throttle valve For impulse tube Ø10-003G1401 065B909 Seal pot has to be used on impulse tubes always when T max 150 C ) Consist of a nipple, compression ring and nut Service kits Picture Type designation For valve Valve insert VFQ Stuffing cone (with EPDM O-rings) DN k VS (mm) (m 3 /h) Code No. 15 4.0 065B796 0 6.3 065B797 5 8 3 16 065B798 40 0 50 3 065B799 65 50 80 80 065B800 100 15 15 160 065B801 150 80 065B964 50 400 065B965 003G1464 VD.CA.O3.0 Danfoss 01/015 DEN-SMT/SI

Technical data Valve Nominal diameter DN 15 0 5 3 40 50 65 80 100 15 150 00 50 k VS value Range of max. flow setting 4,0 6,3 8,0 16 0 3 50 80 15 160 80 30 400 from 0,1 0, 0, 0,4 0,6 0,8 3 4 6 8 1 15 18 p b = 0, bar to m 3 /h 3 4 7 11 16 8 40 63 80 15 150 180 p b = 0,5 bar from 0, 0,3 0,3 0,5 0,8 1, 4 6 9 1 18 5 to 3 4.5 6 10 16 4 40 58 90 10 180 0 50 Cavitation factor z 0,6 0,6 0,6 0,55 0,55 0,5 0,5 0,45 0,4 0,35 0,3 0, 0, Leakage acc. to standard IEC 534 (% of k VS ) VFQ 0,03 0,05 VFQ 1 0,01 Nominal pressure PN 16, 5, 40 Min. differential pressure Max. differential pressure PN 16 bar 16 PN 5, 40 0 see remark ) Medium Circulation water / glycolic water up to 30 % Medium ph Min. 7, max. 10 Medium temperature Connections Materials Valve body 15 1 10 VFQ 150 / 00 3) C 140 VFQ 1 150 PN 16 PN 5 Flange Grey cast iron EN-GJL-50 (GG-5) Ductile iron EN-GJS-400(GGG-40.3) PN 40 Cast steel GP40GH (GS-C 5) Valve seat Stainless steel, mat. No. 1.401 Valve cone Stainless steel, mat. No. 1.4404 Sealing VFQ VFQ 1 Metal EPDM Stainless steel, mat. No. 1.4313 Stainless steel, mat. No. 1.401 Pressure relieve system Bellows (Stainless steel, mat. No. 1.457 Diaphragm (EPDM) p b - differential pressure over flow restrictor ) Depends on the flow rate and valve k VS ; For Q set = Q max -> p min 0,5 bar; For Q set < Q max -> p 3) at temperatures above 150 C only with seal pots (see Accessories) min Q k VS pb Actuator Type Actuator size cm 50 Max. operational pressure PN 5 AFQ Flow restrictor diff. press. p b bar 0, / 0,5 Materials Actuator housing Control diaphragm Impulse tube Stainless steel, mat. No.1.0338, zinc plated and yellow chromate EPDM (Rolling; fibre enforced) Stainless steel tube Ø10 0,8 mm / copper tube Ø10 1 mm, threaded fitting G 1/4, ISO 8 DEN-SMT/SI VD.CA.O3.0 Danfoss 01/015 3

Application principles - Return mounting Direct-connected heating system Indirectly connected heating system - Flow mounting Direct-connected heating system Indirectly connected heating system Combinations Example: Flow temperature controller, return mounting; DN 15; k VS 4,0; PN 16; metallic sealing; flow restrictor p b 0, bar; T max 150 C; flange; - 1 VFQ DN 15 valve Code no: 065B654-1 AFQ actuator Code no: 003G1038 - Impulse tube set AF Code no: 003G1391-1 AFT06 thermostat Code no: 065-4390 - 1 Combination piece KF Code no: 003G1398 Products will be delievered separatelly. Note: For AFT06 and STFW thermostats data see relevant data sheets AFT06 / KF / AFQ / VFQ - Flow and temperature controller STFW / KF / AFQ / VFQ - Flow and safety temperature controller 4 VD.CA.O3.0 Danfoss 01/015 DEN-SMT/SI

Installation positions DN 15-80 T max 10 C The controllers can be installed in any position. DN 15-80 T max > 10 C; DN 100-50 The controllers can be installed in horizontal pipes only, with a pressure actuator oriented downwards. DN 15-80 T max 10 C DN 15-80 T max > 10 C; DN 100-50 Pressure temperature diagram Working area is below P-T line and it ends at Tmax for each valve PN 16 working area 1 EN-GJL-50 (GG-5) 140 (for DN 150-50) Maximum allowed operating pressure as a function of medium temperature (according to EN 109-) PN 5 working area 1 EN-GJS-400 (GGG-40.3) Maximum allowed operating pressure as a function of medium temperature (according to EN 109-) PN 40 EN-GP-40-GH (GS-C 5) working area 1 140 (for DN 150-50) Maximum allowed operating pressure as a function of medium temperature (according to EN 109- Note: 1 at temperatures above 150 C only with seal pots (see Accessories) DEN-SMT/SI VD.CA.O3.0 Danfoss 01/015 5

Sizing - Directly connected heating system Example 1 Motorised control valve (MCV) for mixing circuit in direct-connected heating system requires differential pressure of 0,3 bar (30 kpa) and flow less than 600 l/h. Given data: Q max = 0,6 m 3 /h (600 l/h) p min = 0,9 bar (90 kpa) p circuit = 0,1 bar (10 kpa) p MCV = 0,3 bar (30 kpa) selected p ) b = 0, bar (0 kpa) Remark: p circuit corresponds to the required pump pressure in the heating circuit and is not to be considered when sizing the AFQ. ) p b is differential pressure over flow restrictor. The total (available) pressure loss across the controller is: p AFQ,A = p min p MCV = 0,9 0,3 p AFQ,A = 0,6 bar (60 kpa) Possible pipe pressure losses in tubes, shut-off fittings, heatmeters, etc. are not included. Select controller from table, page 3, with the smallest possible k VS value considering available flow ranges. k VS = 4,0 m 3 /h The min. required differential pressure across the selected controller is calculated from the formula: Δp AFQ, MIN Q k max VS p AFQ,MIN = 0, bar ( kpa) p AFQ,A > p AFQ,MIN 0,6 bar > 0, bar 0,6 Δpb 0, 4 Solution: The example selects AFQ DN 15; k VS value 4,0; flow setting range 0,1-,0 m 3 /h. Q max Δp min AFQ Δp circuit Δp b Δp AFQ Δp MCV AFQ Q max Δp min Δp circuit Δp b Δp AFQ Δp MCV 6 VD.CA.O3.0 Danfoss 01/015 DEN-SMT/SI

Sizing (continuous) - Indirectly connected heating system Example Motorised control valve (MCV) for indirectly connected heating system requires differential pressure of 0,3 (30 kpa) bar and flow less than 1900 l/h. Given data: Q max = 1,9 m 3 /h (1900 l/h) p min = 1,1 bar (110 kpa) p exchanger = 0,1 bar (10 kpa) p MCV = 0,3 bar (30 kpa) selected p b = 0, bar (0 kpa) Remark: p b is differential pressure over flow restrictor The total (available) pressure loss across the controller is: p AFQ,A = p min p exchanger p MCV = 1,1 0,1 0,3 p AFQ,A = 0,7 bar (70 kpa) Possible pipe pressure losses in tubes, shut-off fittings, heatmeters, etc. are not included. Select controller from table, page 3, with the smallest possible k VS value considering available flow ranges. k VS = 4.0 m 3 /h The min. required differential pressure across the selected controller is calculated from the formula: Δp AFQ, MIN Q k max VS p AFQ,MIN = 0,43 bar (43 kpa) Δp AFQ,A > Δp AFQ,MIN 0,7 bar > 0,43 bar 1,9 Δpb 0, 4,0 Solution: The example selects AFQ; DN 15; k VS value 4,0; flow setting range 0,1-,0 m 3 /h. Q max Δpmin AFQ Δp exchanger Δp b Δp AFQ Δp MCV AFQ Q max Δp min Δp exchanger Δp b ΔpAFQ Δp MCV DEN-SMT/SI VD.CA.O3.0 Danfoss 01/015 7

Design 1. Valve body. Cover 3. Adjustable flow restrictor 4. Valve seat 5. Valve insert 6. Pressure relieved valve cone 7. Valve stem 8. Bellows for pressure relief of valve cone 9. Diaphragm for pressure relief of valve cone 10. Actuator 11. Control diaphragm for flow control 1. Built-in spring for flow control 13. Stuffing cone 14. Union nut 15. Impulse tube 16. Compression fitting for impulse tube 17. Upper casing of diaphragm 18. Lower casing of diaphragm 19. Valve body extension 0. Shut off valve for water filling 1. Closing plug 15 14 10 1 16 AFQ / VFQ DN 15-15 1 3 4 6 5 7 8 15 13 17 16 11 18 VFQ ( DN 150-50, T max 140 C 9 1 19 9 0 VFQ DN 150-50, T max 00 C Function Flow volume causes pressure drop across the adjustable flow restrictor. Resulting pressures are being transferred through the impulse tubes to the actuator chambers and act on control diaphragm for flow control. The flow restrictor diff. pressure is controlled and limited by means of built-in spring for flow rate control. Control valve closes on rising differential pressure and opens on falling differential pressure to control max flow. Settings Flow setting Flow setting is being done by the adjustment of the flow restrictor position. The adjustment can be performed on the basis of flow adjustment diagram (see relevant instructions) and/or by the means of heat meter. 8 VD.CA.O3.0 Danfoss 01/015 DEN-SMT/SI

L L VFQ DN 15-15 ø60 78 ø89 10 B H L H 1 B H B 1 VFQ DN 150-50 VFQ DN 150-50 with valve body extension up to 00 C A SW 110 Shut off valve Ø10 40 H Data sheet Flow controller AFQ / VFQ ( (PN 16, 5, 40) Dimensions VFQ, VFQ 1 Valves DN 15 0 5 3 40 50 65 80 100 15 150 00 50 L 130 150 160 180 00 30 90 310 350 400 480 600 730 B mm 13 13 39 39 41 41 76 76 381 381 36 354 401 H 337 337 374 374 393 393 440 440 575 575 595 686 756 Weight PN 16 / 5 8,5 31 61 71 10 193 337 kg 8 9 10,5 1,5 15,5 18,5 PN 40 31 34 63 7 147 64 347 B 1 60 85 1199 mm H 1 889 1184 1555 Weight (valve with body extension) PN 16 / 5 160 314 489 kg PN 40 187 350 56 AFQ Actuator Size cm 50 Ø A 63 mm H 160 Weight kg 9 40 Seal pot V1 70 Comb. piece KF, KF3 G1/4 SW19 Compression fitting DEN-SMT/SI VD.CA.O3.0 Danfoss 01/015 9

10 VD.CA.O3.0 Danfoss 01/015 DEN-SMT/SI

DEN-SMT/SI VD.CA.O3.0 Danfoss 01/015 11

1 VD.CA.O3.0 Produced by Danfoss A/S 01/015