EcoNet and Flash Codes

Similar documents
Application Engineering Europe

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

Modulating Furnace Information. Warning on Meter Setting - Read First!

Fault Codes. J control

TRIPS AND FAULT FINDING

Trouble Shooting. Symptom Possible Cause Solution Power switch ON but switch Light is Off. Main power to unit Off. Switch light defective.

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

620 Magnolia Avenue Suite B Ontario, CA (909) Diagnostic and Troubleshooting. Golf Cart. Revision: A Date:

ARM V FDBK ENSURE MOTOR IS NOT ROTATING DURING POWER UP STILL FAULTS? YES ENSURE ARMATURE WIRING IS ISOLATED FROM ANY OTHER POWER LEADS STILL FAULTS?

Electronic Products ELECTRONIC MAINTENANCE

MCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10

6. Troubleshooting. 6-1 Basic items for trouble shooting. Samsung Electronics 17

Application Engineering

Application Engineering

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC)

MAKING MODERN LIVING POSSIBLE. Service Manual VLTp Soft Starter - MCD500 *MG17L402*

RQ SERIES. Variable Speed Scroll Compressor Supplement

AC drive has detected too high a Check loading

Advanced EasyStart Troubleshooting

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

Service Manual. 9. Maintenance. 9.1 Precautions before Maintenance. discharge resistance or plug of soldering iron. Installation and Maintenance

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

Ion Technologies SUMPRO Battery Back-Up

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE

FSH1BF Series. Extra High Efficiency Heat Pump TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 16 SEER Residential System 2-5 Ton Capacity

P445 Series Electronic Lube Oil Control

Driftsinstruks. Utopia kontroller feilkoder PCP-2HTE og PC-ART. Vi håper de får stor glede av et Novema kulde produkt!

Subject Underhood G System Error Codes and Symptoms System or Parts affected

TECHNICAL SPECIFICATIONS

Variable speed application guidelines

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL

Copeland Screw TM Compressors

ADVANCED PID TROUBLESHOOTING

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Statim G4 Error Codes

A/C SYSTEM GENERAL DIAGNOSTIC PROCEDURES

Application Bulletin 140. H20J/H21J and H70J/H71J Series OVAL HOUSING ROUND HOUSING. BENCHMARK Compressor with Refrigerants R22 and R407C

9. Maintenance. 9.1 Error Code List. Service Manual. Installation and Maintenance

O5DMA-NRG O5DMA-NRG. Self-Contained Multi-Deck Merchandiser 4', 6', 8' & 12' (Dairy / Deli / Beverage / Produce) SHIPPING WEIGHT GENERAL NOTES

Product Specifications

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

Inverter scroll compressors VZH single and manifold

DESCRIPTION FEATURES

6. Document tasks performed during visit and report any observations to the appropriate

OMPRESSOR ELECTRONICS

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

TECHNICAL SPECIFICATIONS

BOILER PM & INSPECTION

Secondary Coolant 301

INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00

Service Facts. WARNING: HAZARdOuS VOLTAGe - disconnect POWeR and discharge 4TWX6024-SF-1K. ComfortLink II System Heat Pump 4TWX6024C1000A.

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS

GLM SERIES CONTROL Users Manual Rev:

1998 INDEX Sensors & Controls, Inc. All Rights Reserved

VTZ variable speed Reciprocating compressors

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis.

SCROLL - AIR COOLED PACKAGED & SPLIT SYSTEM ICE CHILLERS

Combined Ventilation Controller RVWS-T-224HA

Electronic Refrigerator Diagnostics

MODEL 422 Submersible Pump Controller

OD10 10A Outdoor Solar Charge Controller

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

Error code explanation Diagnostics...2 Error Code Chart...3 Tests Wiring diagram...6

CTi Automation - Phone: Fax: Web:

Ultra Sine Inverter (US) Generation 4 (G4) User Guide

SECONDARY PARAMETERS AND ENABLE CONDITIONS

R134a R134a R13. 4a R134a R134a R134

1998 INDEX Sensors & Controls, Inc. All Rights Reserved

Selection & Application guidelines. Condensing Units 50 Hz - 1, 2, 4 cylinders R22 - R134a - R404A / R507 REFRIGERATION AND AIR CONDITIONING

Idle Free Systems, Inc. Reference Guide System Component Information

TECHNICAL SPECIFICATIONS

LIB System for UPS Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

LUI / LUO. Condensing Units

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

Service Facts. WARNING: HAZARdOuS VOLTAGE - disconnect POWER and discharge 4TWZ0024-SF-1F. ComfortLink II System Heat Pump 4TWZ0024A1000A.

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Fault Code Check List

No Operation of air conditioner Explanation

OUTDOOR UNIT CONTROLLER (OUC)

AeroVironment Universal Solar Pump Controllers

CALTRAP INSTALLATION AND OPERATIONS MANUAL

Start Up Instructions for the Kiln, Page 1 of 2

SMART DRIVE ELECTRONIC WASHING MACHINE

ASU18RLB ASU24RLB AOU18RLB AOU24RLB SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTZ0036B-SF-1B. ComfortLink II System Cooling 4TTZ0036B1000A CAUTION

High Profile Evaporator

SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE

30GX AIR-COOLED LIQUID CHILLER

abc CPD7948/075 Rotors, rotor shafts and rotor casings are coated with an anti-corrosive and anti wear coating to prolong element life and efficiency.

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

30GX AIR-COOLED LIQUID CHILLER

TRITON ERROR CODES ERROR CODE MODEL SERIES DESCRIPTION RESOLUTION

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C

Transcription:

The error codes below will be displayed at the EcoNet Control Center under Service window / Current Faults or in the Fault History and will be time & date stamped. VSODC (Variable Speed Outdoor Unit Control EcoNet control board) fault code is what will be displayed on the VSODC EcoNet error code at Control Center A900_O Or A930_O Inverter Fault Identity Fault VSODU Fault Code Description Possible Resolution(s) EV2 Drive LED Code The inverter drive itself is not programmed and is not field serviceable. This fault should not occur in the field. Return Drive to Distributor T901_O Inverter Fault Compressor Overcurrent Compressor is pulling more current than allowed in order to start System Grossly Overcharged Compressor full of liquid/oil Compressor Shorted to Ground Check resistance of windings to ground. Tight Compressor Yellow 1 or 3 Flashes Or Red 4 Flashes T902 Inverter Fault Envelope Protection Compressor current outside of predetermined envelope for RPM s Will display 31 at VSODU at time of fault Will return to operation after time delay Must occur 15 times in a 24 hour period to be displayed in control center fault history. Verify refrigerant charge, often related to overcharge or high condensing pressures. Flooded Start Verify Airflow T903_O Inverter Fault PFC Overcurrent PFC (Power Factor Correction) module is detecting high current internally Check Choke Connections Replace Choke if it looks burnt. If Choke doesn t work, check drive

Inverter Product T905_O Inverter Fault DC Bus Undervoltage DC Bus voltage has dropped below acceptable voltage DC Bus Voltage <175 VDC Incoming Voltage should be greater than 187 VAC. Fault will reset when voltage is returned. Early VSODU firmware (Before VSODU Rev 57) may not properly reset this fault. Update VSODU firmware to current revision. Can occur with power flicker due to storms, will reset when voltage returns after 5 minute delay. Check Incoming Line Voltage to Drive. Drive will reset after fault first two times. If unit locks out on third fault, it will reset in 30 minutes. Countdown timer on EcoNet will display Locked Verify Incoming voltage to Drive by measuring voltage at L1 to L2 Contact Utility if voltage is greater than 253 VAC for a solution. Verify Incoming voltage to Drive by measuring voltage at L1 to L2 on drive. Voltage must be <187 VAC. Could be caused by dirty power. Yellow 8 Flashes A906_O Inverter Fault AC Input Overvoltage Incoming Voltage >253 VAC Yellow 10 Flashes A907_O Inverter Fault AC Input Undervoltage Incoming voltage <187 VAC Yellow 9 Flashes T908_O Inverter Fault PIM Over-temp Indicates the Power Inverter Module on the drive is overheated. May stop compressor, or fold back compressor RPM Check Outdoor fan operation Check Condenser coil for cleanliness Check Drive Heat Sink. Make sure unit clearances are correct. Yellow 4 or 18 Flashes

T909_O Inverter Fault PFC Over-temp Indicates the Power Factor Correction circuit is overheated. May stop or fold back compressor RPM Check Outdoor fan operation Check Condenser coil for cleanliness Check Drive Heat Sink. Make sure unit clearances are correct. Yellow 5 or 19 Flashes A910_O Inverter Fault Lost Rotor Position Compressor speed not matching speed command from control Verify Compressor Connections at U, V, W and Molded plug Verify order/wiring at U, V, W. Check for Equal Resistance on compressor windings System Grossly Overcharged Compressor Tight or Locked Yellow 2 Flashes T911_O Inverter Fault Current Imbalance Compressor Current Imbalance Verify Compressor Connections at U, V, W and Molded plug Check Compressor Windings for significant differences in resistance as they should be equal. Red 14 Flashes A912_O Inverter Fault Micro Fault Micro on Drive faulted Hard Reset on Drive If Hard Reset fails, replace Drive Red 13 Flashes A913_O Inverter Fault - PIM Sensor Open Power Inverter Module temperature sensor is open Hard Reset on Drive If fault persists, Replace Drive Red 2 Flashes T914_O Inverter Fault DC Voltage Low DC Bus Voltage is running low Check Incoming Line Voltage to drive at L1 to L2. Voltage on DC Bus is generally 300 to 380 VDC. Check choke connections. PIM on Drive Defective Yellow 17 Flashes

Verify Operating Superheat and T916_O Inverter Fault Discharge Temp Compressor Discharge Temperature has exceed 235 F degrees for 30 seconds, and compressor may fold back until temperature is below 200 F Charge Check Reversing Valve for leakage from Discharge to Suction Check DLT Sensor Connection to Drive Verify DLT sensor resistance Should trip on T961_O first. Yellow 6 Flashes A919_O Inverter Fault PFC/DSP Comm Fault Drive lost internal communication between PFC and DSP Hard Reset of Drive If fault persists - replace drive Red 9 Flashes A920_O Inverter Fault COM/DSP Comm Fault Drive lost internal communication between PFC and DSP Hard Reset of Drive If fault persists - replace drive Red 8 Flashes Verify proper airflow over the A921_O Inverter Fault PFC Temp Sensor Open Sensor to PFC Is either low or open heatsink of the drive. Remove any obstructions. If the problem still persists after a hard reset of the drive, replace the drive. Red 1 Flash

T922_O Inverter Fault PIM Temp Foldback Drive has folded back as a result of PFC temperature Verify proper airflow over the heatsink of the drive. Remove any obstructions. Ensure OD fan is operating and coil is clean Check OD unit clearances. Yellow 21 Flashes T923_O High Refrigerant Pressure System High pressure switch has opened. Check Refrigerant Charge Check connection of HPS to Drive Check fan at condenser Verify unit clearances Yellow 20 Flashes A923_O High Refrigerant Pressure System High pressure switch has opened 3 times and is locked out for one hour Check Refrigerant Charge Check connection of HPS to Drive Check fan at condenser Verify unit clearances Yellow 20 Flashes A925_O Inverter Fault Compressor Model Unkown Drive size and model data card do not match Incorrect Memory Card has been installed Incorrect Inverter Drive has been installed Yellow 22 Flashes A927_O Inverter Fault DLT sensor Open Discharge Line Temperature Sensor is open Check DLT sensor connection to drive Check DLT sensor resistance to temp Red 3 Flashes A928_O Locked This is an indication that the system is locked out and needs to be reset Check fault history for cause of lockout condition at control center Address fault as indicated in history

Verify Line voltage to unit is on and is measured by reading line voltage into A929_O 240VAC Missing or Comm Failure (Formerly Comm Failure) Drive is either not powered or there is a problem with the mod bus cable between VSODU and Drive drive at L1-L2 (Black to Yellow in bottom left corner of drive) Check Modbus cable between VSODU and Drive. Closely Examine pins in connectors. Is choke connected or open? Hard Reset of Drive Red 11 Flashes A950_O Configuration Data Restore Failure Firmware in VSODU is corrupt Replace VSODU Possible Damage to solder joints on A951_O Memory Card Data Write Failure VSODU is unable to write data to memory card back of memory card socket on VSODU Replace VSODU Replace Memory Card also if VSODU does not resolve. T952_O Outside Temperature Thermistor Failure Outdoor Temperature Thermistor is either Open, Shorted or Low Check connection at VSODU Verify leads to sensor are not pinched, or damaged Check sensor resistance/temp A953_O Coil Temperature Thermistor Failure (Formerly called Evap Temperature Thermistor) Coil Temperature Thermistor is either Open, Shorted or Low Unit will run in cooling mode, but will resort to time/temperature defrost in heating mode Check connection at VSODU Verify leads to sensor are not pinched, or damaged Check sensor resistance/temp

A954_O Suction Temperature Thermistor Failure Suction Thermistor is either Open, Shorted, or Low Unit will run in cooling mode but will not run in heating mode Check connection at VSODU Verify leads to sensor are not pinched, or damaged Check sensor resistance/temp T955_O Compressor Temperature Thermistor Failure A956_O Suction Pressure Sensor Failure T957_O Low Refrigerant Pressure A957_O Low Refrigerant Pressure Sump Thermistor is either Open, Shorted, or Low Stator heat will not operate Suction Transducer is either, shorted, grounded or open or outside of acceptable range Pressure at Transducer has fallen below settings. 50 PSIG for Cooling and 15 PSIG for Heating modes System has tripped the low pressure threshold 3 times in one call. Unit will be locked out for one hour Check connection at VSODU Verify leads to sensor are not pinched, or damaged Check sensor resistance/temp Check Transducer using formula PSIA= 375*(DCVout/DCVin)-22.8 PSIG=PSIA-14.7 Verify Connections at VSODU and Transducer Check Refrigerant Charge Check for Restrictions in liquid or suction lines, drier, strainers etc. Check airflow and load at evaporator Check Refrigerant Charge Check for Restrictions in liquid or suction lines, drier, strainers etc. Check airflow and load at evaporator

Often times this is a result of short cycling due to envelope protection or pressure switch trips. T959_O Compressor Heater On (Normal Operation) Flashing Indicated only at control center Usually related to overcharge conditions Compressor Sensor not in correct location or not making good surface contact with compressor. Only Occurs on Firmware version 42 and Earlier. Install new VSODU Check refrigerant charge Can happen in extreme cold temperatures when compressor slows T960_O Compressor Lube Protection Compressor Temperature fell below saturated refrigerant temperature indicating liquid is returning to compressor. down from overdrive Verify sump sensor is firmly mounted on compressor Compressor speed will fold back or be limited unit sump temperature is 10 degrees above saturated suction temperature. When Discharge temperature exceeds 225 F, Compressor will slow down to T961_O Compressor Discharge Temperature High Folding back due to high discharge temperature bring discharge temperature down below 200 F. Check system superheat and charge Verify reversing valve is not leaking from discharge to suction. Yellow 6 Flashes

A962_O or A970_O Inverter/Compressor Mismatch Memory card does not match the compressor and drive installed in the equipment Likely an incorrect component such as a drive was installed in unit. Check current parts list to make sure correct drive is used. Troubleshooting Notes: If reversing valve will not shift to heating mode, check fuse on VSODU in addition to solenoid and wiring to reversing valve. If compressor RPM s are not as expected, check LED on drive to see if it is folding back as a result of an issue. Many faults can be attributed to system overcharge. Charge in system is critical.