BOILER FEED SYSTEM OPERATION AND MAINTENANCE MANUAL

Similar documents
NECO Pumping Systems

SERIES PC INSTRUCTION AND OPERATION MANUAL

SELF PRIMING CHEMICAL SERVICE PUMPS

Installation & Operating Manual

NECO Pumping Systems

Series Base mounted pump. Installation and operating instructions

END SUCTION CENTRIFUGAL PUMPS

HALLMARK INDUSTRIES INC

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS

ESE Series Cast Iron Sewage Pumps

P239-1 Supply Pumper Instructions

This manual presents installation, servicing, troubleshooting, and maintenance for M PUMPS CM MAG-M SERIES Information that may be required regarding

SLR / SLR-S/N. Instruction Manual. Walrus America Inc

StormPro BA Series Sump Pump

KP-C Series. Close Coupled End Suction Centrifugal Pumps. Installation, Operation and Maintenance

OWNER S MANUAL EVOLUTION 3500, 4500, 5500, & 8500 SERIES PUMPS

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting

READ THIS MANUAL CAREFULLY BEFORE USING THE PUMP

Installation, Operation, and Maintenance Manual Outdoor Glycol Feed System JWOP /055/100

END SUCTION CENTRIFUGAL PUMPS

SECTION H3 TRAYMASTER SERIES DEAERATORS

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

barmesapumps.com CD SERIES RPM Installation, Operation & Maintenance Manual End-Suction Centrifugal Stainless Steel Pumps

Operating Manual for Rotary Gear Pumps CMI, S.A. (Mendaro, Guipuzkoa, Spain)

End Suction Centrifugal

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

PRE-PLUMBED SEWAGE SYSTEM

Installation and operating instructions. Series 4312 and 4392 Vertical In-Line twin pumps

LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

Model 8309WC Barrier Free Shower & Eye/Face Wash

SECTION H4 BOILERMATE DEAERATORS

OWNER S MANUAL SUBMERSIBLE UTILITY PUMP

Model AM2 M40 Panel Installation, Operation, and Maintenance Manual

Warning and Safety Precautions

VSCP Vertical Suspended Column Pump Operation & Maintenance Manual

Owner s Manual GLASSLINED PUMP TANK

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

INSTRUCTION MANUAL AC2516 REVISION D INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Series 1580 In-Line Mounted Centrifugal Fire Pumps

OWNER S MANUAL SELF-PRIMING PORTABLE UTILITY PUMP

PROMAG SR SERIES SEAL-LESS CENTRIFUGAL PUMPS

CP series. Submersible utility pump 50HZ STAIRS INDUSTRIAL CO., LTD.

Aqua Ultraviolet Sunami Series Pumps 1/3HP, 3/4HP, 3HP, 4HP, 5HP

Val-Matic 1/2-3 Well Service Air Valve With Dual Port Throttling Device

Trouble Shooting Guide EWA, 3-phase (D2422)

TITAN FLOW CONTROL, INC.

TS400Q TS800Q. Auto Pressure Control Pump Instruction Manual. ISO 9001 Certified Walrus America Inc

Series Base mounted pump. Installation and operating instructions

Model 8309WC Barrier Free Shower & Eye/Face Wash

TP300 INDUSTRIAL TRASH PUMP OPERATOR S MANUAL

INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL MODEL 3310

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

barmesapumps.com IB SERIES & 3500 RPM Installation, Operation & Maintenance Manual End Suction Centrifugal Pumps

INSTALLATION AND OPERATING INSTRUCTIONS MANUAL Owner s manual FIXED SPEED BOOSTER SETS SERIES:

OPERATING SERVICE MAINTENANCE MANUAL

Matala. VersiFlow Series. Instruction and Maintenance Manual

PowerLevel s e r i e s

Model 6518FR. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

USER S MANUAL FOR F & Q. Submersible Sewage Pumps

PE 20 SERIES ELECTRIC POWER PUMPS

USER S MANUAL FOR F & Q. Submersible Sewage Pumps

Model 8317 Combination Shower Eye/Face Wash

GARDEN HOSE UTILITY PUMP

KJ4000LW Operating Instructions & Parts Manual NSN

Medi-Flow. Model M101 & M101D Medicator Instructions GETTING TECHNICAL ASSISTANCE

4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause

StormPro BCV400 Sewage Ejector Pump

SERVICE MANUAL 200 SERIES MOTORIZED 20352, 20452, 20551, 20552, AND MODELS

GRINDER PUMP MODEL # Zoeller is a registered trademark of Zoeller Co. All Rights Reserved. Español p. 13

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps

Marlow Series Cast Iron Swimming Pool Pumps

Series 867 Reduced Pressure Zone Assemblies

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

SEWAGE PUMP MODEL # Zoeller is a registered trademark of Zoeller Co. All Rights Reserved. Español p. 14

Installation Operation & Maintenance Manual. Oil-Free (Dry) Rotary Vane Vacuum Pump Systems

SUNC1200 / ITEM #40882 SUBMERSIBLE UTILITY PUMP OPERATIONS MANUAL

DuraMAC LIGHT COMMERCIAL & IRRIGATION WATER PRESSURE BOOSTER SYSTEM INSTALLATION INSTRUCTIONS

INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL MODELS 3341 AND 3344 END SUCTION PUMPS

PT-516 Pumping Trap Installation and Maintenance

Model Series. PumpAgents.com - buy pumps and parts online ELECTRIC BILGE PUMPS. Model Series FEATURES SPECIFICATIONS STANDARD MODELS

INSTALLATION & MAINTENANCE MODEL mm

SAMPLE SPECIFICATIONS

METERING/DOSING PUMP CLOSE-COUPLED B4015D, B4050D, B4100D, B4190D, B2400D, AND B4400D MODELS

TITAN FLOW CONTROL, INC.

Val-Matic 1-4 Combination Air Valve (Single Housing Type)

MODELS 108 and 138 CRAWL SPACE PUMPING SYSTEM PREINSTALLATION CHECKLIST

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual

Operating Instructions - Electric Pow'r-Riser Models

PROJ. NO SECTION HYDRONIC PUMPS

Installation & Operating Manual

for Untempered - Make-Up Air Units

SUMMIT PUMP Horizontal End Suction Pump Close Coupled and Frame Mounted

STOP CITY PRESSURE BOOSTER PUMP INSTRUCTION MANUAL

Artesian2 Owners Manual

Hydraulic Maintenance & Troubleshooting. Content - Norman Kronowitz Presenter Jim Trinkle

Installation, Maintenance, & Repair Series 995 Reduced Pressure Zone Backflow Preventers

SHALLOW WELL JET PUMP

VADA - V60-J PRODUCT OVERVIEW CONSTRUCTION MOTOR USAGE LIMITATIONS WARRANTY

PEDESTAL SUMP PUMP. MODEL # Español p. 11. Zoeller is a registered trademark of Zoeller Co. All Rights Reserved.

Transcription:

BOILER FEED SYSTEM OPERATION AND MAINTENANCE MANUAL IMPORTANT These instructions are intended as a guide for the Installing Contractor and as a reference for the Operator, Owner and Serviceman. RETAIN THIS BOOKLET NEAR THE EQUIPMENT FOR READY REFERENCE 1

I. INSTALLATION A. Uncrating B. Placement C. Piping Connections D. Electrical Connections E. Flushing and Filling the System TABLE OF CONTENTS II. III. IV. PRE-START INSPECTION A. Mechanical System B. Electrical System C. Pump(s) STARTUP INSTRUCTIONS A. Startup B. Sparge System (Where installed) MAINTENANCE A. General B. Pump C. Float Level Control D. Sparge System (Where Installed) V. TROUBLESHOOTING A. Failure to Pump B. Inadequate Capacity or Pressure C. Pump Loses Prime After Starting D. Excessive Power Consumption E. Pump Vibrates or is Noisy F. Seal leakage G. Receiver Tank Overflows 2

I. INSTALLATION A. UNCRATING IMPORTANT: The Boiler Feed System was carefully packed for shipment and left the Precision Factory complete and in perfect condition. Refer all damages promptly to carrier. Precision is not responsible for shipping damage or shortages. 1. Care must be taken not to damage the unit during uncrating. 2. When using pry bars or forklifts, support the Feed System weight on its channel base only. 3. Storage: Electrical equipment can be damaged if exposed to adverse weather. The Feed System must be stored inside. The electrical panel and controls must be covered in plastic throughout all construction to avoid accumulation of dust and moisture. B. PLACEMENT 1. Installation must comply with all Federal, State and local codes. 2. Locate unit to provide easy access for inspection and maintenance. 3. Provide a firm, level foundation for the feed system, preferably a raised, concrete housekeeping pad. 4. Leave a permanent access space of 30 inches opposite the float level control, the sparge tube/temperature control valve (where applicable) and the pump(s) location. Leave a 36-inch access space opposite the control panel. 5. Once the feed system is in place, level it using shims as required and secure with foundation bolts. If desired, the unit may be grouted in place. 6. Under no circumstances should anyone climb on the feed system. Climbing may result in damage to the unit or may result in a fall, resulting in serious injury or even death. C. PIPING CONNECTIONS 1. Boiler piping connections and valves MUST comply with State and local codes and, where required, ANSI and ASME Boiler and Pressure Vessel Code piping requirements. 2. Pipe the vent connection full size to outdoors. Make provisions to prevent entry of rain and/or snow. 3

3. Pipe the feedwater supply line to the boiler. Be sure to include a manual isolation valve and check valve in this line. The check valve should be closest to the feedpump. 4. Pipe the make-up water supply line to the the float-feeder connection. Be sure to include a manual isolation valve in this line and verify that the line pressure does not exceed the allowable shutoff pressure of the make-up valve. 5. (On units with steam sparge preheater) Plumb the steam line to the steam temperature control valve. Be sure to include a manual isolation valve in this line. 6. Pipe the overflow line to a safe drain. 7. Pipe the system condensate return line to the marked connection on the tank. 8. Pipe the drain line from the drain valve mounted on the unit to a safe drain. D. ELECTRICAL CONNECTIONS 1. Power Feed Wiring Recommended wire sizes are listed on the Feed System Parts List. The full load amperage is listed on both the Parts List and the Nameplate. Feed wires must be rated for voltage and full load amperage as specified in the current edition of the National Electrical Code. 2. Equipment Grounding Conductors The Feed System is equipped with ground lug(s) inside the control panel. Grounding conductor(s), properly sized in accordance with the current edition of the National Electrical Code, must be installed. E. FLUSHING AND FILLING THE SYSTEM 1. The Feed System and associated piping must be thoroughly flushed before the final fill. 2. Consult a local water treatment company for recommendations on proper flushing procedures and ongoing water treatment. The extent to which the Feed System needs cleaning before operation depends upon the nature of the process using the steam. 3. Before filling the unit, remove and examine each pump inlet strainer and any other strainers installed on the feed system. Clean strainers and replace. 4. Fill the unit with water using the automatic water level control. Once the level control reaches its close-off point, verify the level in the water level gauge glass. Adjust float height if necessary (see Item IV.C below). 4

II. PRE-STARTUP INSPECTION A. MECHANICAL SYSTEM 1. Are all plumbing connections complete and correct? 2. Have piping leak tests been completed and necessary repairs finished? B. ELECTRICAL SYSTEM 1. With all power turned off; inspect all internal and external electrical components to assure that there has been no damage during shipment or installation. Check tightness of all wire connections. 2. Are correctly sized fuses, circuit breakers and/or thermal overloads properly installed? C. PUMP(S) 1. With power turned off, rotate each pump by hand to insure that pump and motor are not bound up. 2. On each coupled pump, check alignment of coupling between pump and motor in accordance with pump manufacturer s instructions. 3. Run each motor momentarily to be sure pump rotation matches arrow on pump casing. Caution: Do not run pump dry, as damage will occur to seal and internals. III. START-UP INSTRUCTIONS A. STARTUP 1. Open all valves on suction, discharge and makeup water lines. 2. Verify that the receiver contains water and that the float level control is operating properly. 3. For vertical pumps with seal bleed connection, verify that bleed line manual valve is open. 4. If bypass/recirculation lines are provided, make sure any stop valves in those lines are open. 5. Switch HAND-OFF-AUTO switch to the HAND position. Pump should run, feeding water the boiler. 6. Switch HAND-OFF-AUTO switch to AUTO position. System will now feed water on demand from the boiler pump control. 5

B. SPARGE SYSTEM (WHERE INSTALLED) 1. Verify that steam is available for the sparge assembly. 2. Adjust the temperature control setting to 200 deg F mimimum. Oxygen content in water is zero at 210F and sea-level atmospheric pressure. 3. Open the manual shut off valve to allow steam to reach the sparge assembly. Steam will be injected into the water in the receiver and the water temperature will rise. As the water temperature reaches the set point, the automatic steam valve will close. IV. MAINTENANCE A. GENERAL 1. Most wear and tear damage occurring to feed systems and their components is caused by corrosion resulting from leaking external pipe joints. Look over the system frequently and repair any piping leaks and resultant corrosion damage immediately. B. PUMP 1. Refer to the pump manufacturer s instruction manual for detailed maintenance procedures. Generally, the only maintenance work required is occasional bearing lubrication or seal replacement. For more extensive repairs, pump replacement may be required. In some cases, service exchange pumps are available from the pump manufacturer. C. FLOAT LEVEL CONTROL 1. Periodically (use caution the water in the receiver tank is generally scalding hot!) check float level control operation to ensure that float moves freely and shuts off make-up water at the correct level. Should it be necessary to reset the shutoff level, this can be achieved as follows. Access to this adjustment is through the handhole in the side of the tank. a. Loosen the knurled knob on the serrated elbow join on the float valve. b. Adjust float height. c. Tighten the knurled knob, clamping the float arm in its new position. D. SPARGE SYSTEM (WHERE INSTALLED) 1. Sparge system components do not require maintenance unless there is a loss of performance. Refer to Troubleshooting section below. 6

V. TROUBLESHOOTING A. FAILURE TO PUMP 1. Pump not running at rated speed assure proper voltage and wiring connections. Use tachometer to check pump speed. 2. Pump not primed check that suction pipe is flooded and that receiver contains water. 3. Discharge head too high check discharge pressure against design value. 4. Wrong direction of rotation compare pump rotation with arrow on pump. 5. Clogged suction line or inlet strainer Inspect, clean if necessary. B. INADEQUATE CAPACITY OR PRESSURE 1. Mechanical wear or damage rotate the pump by hand to check for tight spots. If wear or damage is suspected, remove pump for inspection/repair/replacement. 2. Insufficient net positive suction head (NPSH) - throttle pump discharge - increase size of suction piping. - elevate receiver tank. 3. Pump not running at rated speed Check voltage and wiring connections. Use tachometer to check pump speed. 4. Clogged suction line or inlet strainer Inspect, clean if necessary. 5. Air leak in suction line test suction line for leaks and repair as necessary. 6. Discharge head too high - Check discharge pressure against design value. - Check for obstruction in feedwater line. - Check for proper operation of check valve(s). C. PUMP LOSES PRIME AFTER STARTING 1. Insufficient net positive suction head (NPSH) - Throttle pump discharge. - Increase size of suction piping. - Elevate receiver tank. 2. Air leak in suction line test suction line for leaks and repair as necessary. 3. Air entering pump through inlet seal or O rings hydrostatically test pump and repair leaks. 7

D. EXCESSIVE POWER CONSUMPTION 1. Pump not completely broken in it is normal for new pumps to consumer higher than normal power levels during the break in period. If high power consumption persists beyond a few weeks, look for alternate causes. 2. Verify that water flow rate is not too high. This is the most common cause of excessive power consumption. 3. Mechanical wear or damage rotate the pump by hand to check for tight spots. If wear or damage is suspected, remove pump for inspection/repair/replacement. 4. Pump and motor misaligned follow pump manufacturers instructions to realign pump. E. PUMP VIBRATES OR IS NOISY 1. Pump and motor misaligned follow pump manufacturers instructions to realign pump. 2. Pump not properly bolted to mounting base/foundation. 3. Piping load on pump check piping to ensure there is no strain on pump housing. Install piping supports and/or flexible couplings as required. 4. Mechanical wear or damage rotate the pump by hand to check for tight spots. If wear or damage is suspected, remove pump for inspection/repair/replacement. Check alignment. 5. Pump cavitating Insufficient net positive suction head (NPSH): - Throttle pump discharge. - Increase size of suction piping. - Elevate receiver tank. Air leak in suction line: - Test suction line for leaks and repair as necessary. F. SEAL LEAKAGE 1. Seal leaks - Worn seal or rotating member replace seal. - Improperly installed seal or rotating member replace seal. - Broken parts replace seal. - Shaft pitted under seal replace shaft and seal. 8

G. RECEIVER TANK OVERFLOWS 1. Water level set too high, insufficient capacity for surge loads reset level control lower to allow more reserve capacity. 2. Float leaking repair or replace float. 3. Float mechanism sticking repair or replace. VI. WARRANTY PRECISION BOILERS LIMITED WARRANTY PRECISION warrants all electrical components (except pilot lights and fuses), tank and mechanical controls, if found defective in workmanship or material while under normal use and service, within the first year of operation or until 18 months after shipment from PRECISION S factory, whichever occurs first, after authorized return by purchaser to PRECISION (at purchaser s expense) and after examination discloses to PRECISION S reasonable satisfaction to be defective. The repair or replacement of defective parts will be made by PRECISION without charge. PRECISION will not be held responsible for any field charges in connection with the removal or replacement of allegedly defective parts nor for incidental or consequential damages. This guarantee does not include damage resulting from unsuitable water. 9