FUEL DISPENSING SYSTEMS Component Details SE-27 12V DC - 15 GPM Metered Tank-top Dispensing System 12V DC Electric Pump - 1 Inlet - 3/4 Outlet 3-Wheel Mechanical Meter 1 Automatic Nozzle, Swivel & Hose 40 GPM Particulate Filter - 30 Micron 2 - Emergency Vents - MNPT - 16 oz Pop-up Leak Gauge Swing-arm or Clock Level Gauge Overfill Prevention Valve Atmospheric Vent with Pipe Drop Tube - Pump Suction Pipe - 3 Lift Spill Bowl or Remote Fill Maximum tank diameter 64 Proudly made in America
12V DC Electric Pump - 1" Inlet - 3/4" Outlet This industry standard DC pump dispenses up to 15 GPM (57 LPM). The FR1204G is ideal for pumping gas, diesel fuel and kerosene. With an amp draw that's easy on your DC power source. Explosion proof UL/cUL listed 1/4 HP motor. The FR1204G is a pump only unit allowing you to customize your own system. Please see our full line up of meters and accessories to complement your system. Features & Benefits Up to 15 GPM 1/4 HP motor UL/cUL listed motor Compatible with Diesel, Gasoline, Kerosene, E15, and Biodiesel up to B20 2 year warranty Built in strainer 2 in. threaded base for tank mounting Heavy duty cast iron construction Cast bronze rotor with bronze rotary vanes http://www.fillrite.com/index.cfm/products/productdetail/?p=105&ps=80 1/4
3-Wheel Mechanical Meter The 807C Mechanical flow meter has a large easy to read display, flow ports can be positioned vertically or horizontally, UL/cUL listed, handles fluid of any viscosity, rated for Gasoline, Diesel, Kerosene, mineral spirits, Stoddard solvents and heptane. Fill Rite meters provide precision and durability in a cost effective design. The 807C is a 3 wheel mechanical meter designed for transfer pumps with a flow rate of 5 to 20 GPM. this meter has a 3/4 in. inlet and outlet. Features & Benefits +/ 1% accuracy UL/cUL, CE listed 5 20 GPM 50 PSI 3/4 in. inlet, 3/4 in. outlet Large easy to read display NPT threads tp://www.fillrite.com/index.cfm/products/productdetail/?p=165&ps=91 1/4
3/4" Automatic Nozzle, Swivel & Hose, Gas & Diesel The N Series nozzles are well suited for a broad range of high flow fueling applications from farm tractors and combines, heavy earth moving equipment, fleet re fueling, to above ground storage tanks and portable truck mounted fueling operations. This rugged series of automatic nozzles will provide years of service with minimal down time and quick fueling. Features & Benefits Compatible with diesel UL listed 3/4 in aluminum nozzle 3/4 in NPT F outlet Automatic shut off 50 PSI working pressure Green body cover to indicate diesel compatibility Heavy duty hanging hook compatible with all Fill Rite products Convenient one finger hold open clip to set flow rate ttp://www.fillrite.com/index.cfm/products/productdetail/?p=295&ps=120 1/4
3/4" Swivel & Hose Multi Plane, Full 360 spherical rotation for easy movement of the nozzle. Features & Benefits Double O ring Seals at each Swivel Provide Long Life at Low Temps ( 40 F/C) Compatible with unleaded Gasoline, Diesel & Ethanol Blends through E10 Dispense Diesel Fuel, Gasoline, Grease Kerosene and Petroleum Oils. The Fill Rite hose is a blend of Nitrile and PVC external materials provides rugged protection against cuts, abrasions, snags. Puncture Resistant. Features & Benefits 3/4 x 12' fuel transfer hose Dispense diesel fuel, gasoline, kerosene, and petroleum oils Neoprene exterior Designed for use with all electric pumps High quality Nitrile inner tube
18 GPM Particulate Filter - 10 Micron & Filter Head Particulate Fuel Dispenser Filter is designed with resin impregnated cellulose media for the removal of dirt, rust and microbes. Features & Benefits 10 Micron Filter 50 psi 18 gpm 1 12 UNF Compatible with gasoline, diesel, ethanol blends up to 15% and ultra low sulfur diesel
Emergency Vents - MNPT - 16 oz UL Listed Emergency vent (pressure relief only) used on aboveground storage tanks, as a code requirement, to help prevent the tank from becoming over-pressurized and possibly rupturing if ever exposed to fire. Emergency vents must be used in conjunction with a normal vent. Correct application of this vent requires proper vent size and selection for the tank system in order to meet the specific venting capacity. Code Compliance: API 2000 International Fire Code National Fire Code of Canada NFPA 1, 30, 30A, 31, 37, 110 PEI RP200 & PEI RP800 Underwriters Laboratories Inc. - UL-142, UL-2085 & UL- 2244 Underwriters Laboratories of Canada - CAN/ULC S601-07, CAN/ULC S602-07 & CAN/ULC S652-08 California Air Resource Board (CARB) Phase 1 Enhanced Vapor Recovery (EVR) AST Certified Products (VR-402-B) Fig. 244OM WARNING: DO NOT FILL OR UNLOAD FUEL FROM A STORAGE TANK UNLESS IT IS CERTAIN THAT THE TANK VENTS WILL OPERATE PROPERLY. Emergency vents are designed only for use on shop fabricated atmospheric tanks which have been built and tested in accordance with UL 142, NFPA 30 & 30A, and API 650 and in accordance with all applicable local, state, and federal laws. In normal operation, dust and debris can accumulate in vent openings and block air passages. Certain atmospheric conditions such as a sudden drop in temperature, below freezing temperatures, and freezing rain can cause moisture to enter the vent and freeze which can restrict internal movement of vent mechanisms and block air passages. All storage tank vent air passages must be completely free of restriction and all vent mechanisms must have free movement in order to insure proper operation. Any restriction of airfl ow can cause excessive pressure or vacuum to build up in the storage tank, which can result in structural damage to the tank, fuel spillage, property damage, fire, injury, and death. Monthly inspection, and immediate inspection during freezing conditions, by someone familiar with the proper operation of storage tank vents, is required to insure venting devices are functioning properly before filling or unloading a tank.
Leak Gauge - Pop-Up Top mounted liquid leak gauge that can measure from 6" to 170" in depth. Gauges are custom made in house to fit your tank. This gauge is designed to monitor either the interstitial space of a double wall containment system, or it can mount into an external monitoring pipe. Calibration: Consists of 3 pieces. Outer plastic piece, inner plastic piece, and a piece of paper in between. Red Lock Nut: HDPE Plastic. This gauge is a simple visual tool. If the red indicator rises into the viewing window, it is indicating that there is a leak occurring in the double wall containment system. Bushing: Aluminum bushing, can be 2 or 1.5. Once installed, simply view the calibration to monitor the interstitial space. The indicator is not calibrated. It simply indicates leak or no leak. Internal Rods: Standard construction is aluminum rods. Additional Options Leak Union: Compression union Audible Alarm Accessory: This feature can turn the mechanical gauge into an audible Hi or Lo level alarm. Gauge Guard: A cover that protects the exposed plastic components on top of the gauge. Environmental Protection The Leak gauge is officially approved for use in double wall containment systems by several state environmental protection agencies. Float: HDPE Plastic
Level Gauge - Swing Arm Top mounted liquid level gauge that can measure from 6" to 144 in depth. This gauge is a simple volume reading tool. The top of the red indicator is an indication of approximate fuel level in the tank. Once installed, simply view the calibration to monitor tank level. Indicator is calibrated in eighths of a tank on one side, and quarters of a tank on the other. Calibration: Consists of 3 pieces. Outer plastic piece, inner plastic piece, and a piece of paper in between. Red Lock Nut: HDPE Plastic. Bushing: Aluminum bushing, can be 2 or 1.5. Gauges are custom made in house to fit your tank. Can also accommodate for double walls and pipe risers. HDPE Float: High Density Polyethylene Plastic. Additional Options Audible Alarm Accessory: This feature can turn the mechanical gauge into an audible Hi or Lo level alarm. LED At-A-Glance Accessory: This feature can give mechanical gauge remote reading capability. Gauge Guard: A cover that protects the exposed plastic components on top of the gauge. Internal Rods: Standard construction is galvanized steel rods with brass rivets. These replacement parts are available. Red HDPE Plastic Nut Duro Nitrile Gasket Plastic cellulose acetate inner and outer calibration Aluminum Lock Nut Glass inner calibration
Overfill Prevention Valve The overfill prevention valve is installed at the fill port of a storage tank. Used in a pressurized tight fill application, the valve helps prevent tank overfills by closing when the liquid level reaches a pre-set warning level (90-95% full). The valve is installed through a 4" or 6" threaded opening and has a built-in bleed hole that allows the fill hose pressure to be relieved after the valve closes. This bleed hole also provides anti-siphon protection for the valve. When installed to manufacturer requirements, the overfill prevention valve can eliminate hazardous liquid spills. The valve can be used in conjunction with AST spill containers or remote fill boxes for added spill protection. All models are supplied with an adaptor to mount an aluminum drop tube. A test mechanism is also sold separately if needed. The test mechanism allows a technician to pull on the test line at any time during the filling process to actuate the float and stop the filling process. This allows a technician to verify the valve is working properly. Features The 3" valve can be used with 6" Sch. 40 or 80 pipe. The 2" valves can only be used with 4" Sch. 40 pipe. Construction Details Anodized aluminum body Brass/stainless steel internal components Stainless steel linkage Failure to follow any or all of the warnings listed below may render the valve non-functional and could result in an accidental product spill, property damage, fire, explosion, injury or death. Warnings and Cautions 5 PSI & 5 GPM is the minimum flow requirement for valve operation. Valve will NOT function in gravity fill applications. Maximum viscosities (in centistokes): 2" Valve-150, 3" Valve-60. Flow rate of the 2" valve is 350 GPM maximum flow (183 GPM @ 10 PSI pressure drop). The 3" valve is 800 GPM maximum flow rate (566 GPM @ 10 PSI pressure drop). Once closed the valve will allow fl ow of less than 2% of max fl ow rate to relieve fill line pressure. A tight fill is required for the valve to operate. Do not substitute any other fill adaptors for the special adaptor supplied. The valve must be used with clean product. Debris from products such as contaminated used oil may cause the valve to function improperly. These valves are rated for a maximum pressure of 100 PSI. Not suitable for motor oil or other heavy oils. Consult Morrison Bros. Co. for product compatibility with the valve. Code Compliance ULC, NFPA 30, 30A, UFC, IFC and PEI /RP200, PEI /RP600, Florida DEP EQ356, CARB VR 402A
Drop Tube & Normal (Mushroom) Vent with Pipe The drop tube directs product flow to liquid level when filling a storage tank. The drop tube prevents free fill and reduces agitation of liquid when filling. The flanges fits between tight fill adaptor riser pipe. The tube extends to near bottom for submerged fill. All drop tubes are extruded aluminum. The 2 and 3 drop tubes can also be attached to the AST Overfill Prevention Valve. Drop tube length determined by tank diameter. Mushroom style free flow vent Stainless-steel mesh screen. Domed vent top prevents tank contamination from entering vent lines. NPT threads Cast iron, zinc plated 2" diameter galvanized steel vent pipe Length determined by tank volume/size
Spill Bowl Tank top spill containers are designed tocontain small spills that occur at the fill point on aboveground storage tanks. Features 3½ gallon (13.25 liters) capacity Hinged cover is lockable with a padlock Centered connection Female threaded inlet and outlet Includes removable screen for use as used oil collection point, male threads Construction Details 16 gauge spun steel, powder-coated white body and cover Capacity: 3.5 Gallons Mounting Connection: Female Mounting Location: Center Size: 2 NPT threads Drain: No Screen: No Height: 8 Width: 17.25 Body diameter: 13.14 517 Certifications & Listings Florida DEP EQ 345 Meets the new and revised requirements for CAN-ULC-S663-11 (effective September 25, 2015)