Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Similar documents
3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Mechanical Shearbolt Connectors, QCI Series

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

QT-III Cold Shrink Silicone Rubber

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

Branch Splice QS-2001B

ELB ES. Product Installation Instructions

Cable Ties. Data Sheet

3M Cold Shrink Splice Kits, QS T Series

3M Locator Plate

3M Cross-Connect Cabinets 4220SVC and 4220SVE Tall Skirt Installation Guide

High Voltage Joints and Terminations up to 72,5 kv 145 kv

3M Locator Plate

ELB ELB

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

3M Closure System 2-Type Cover (505)

3 Reenterable Encapsulated PST Dome Closure

3M Ladder Kit 3M710/MS 2 -TMK-LK

SLiC Aerial Terminal and Spiral End Seal for use with AMP* Quiet Front Terminal Blocks

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900 µm Instructions

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

3M No Polish Connector 8800-APC/AS SM SC/APC, Angle Splice, 250/900-µm. Instructions. October C

3M Electrical Tapes Product Selection Guide. Insulate & Protect. with Quality Tapes. Preliminary

Data Sheet July For RoHS information, please visit

710 Splicing Rig. Instructions. January E

3M No Polish LC/APC Connector SM, Angle Splice, 250/900 µm 8830-APC/AS

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

3M Mini D Ribbon (MDR) Cable Assembly.050 High Speed Video Data Transmission System, 50 Position 14X50-SZWB-XXX-0NC

3M Pleated Foil I/O Cable Assemblies MDR Series

3M Electrical Markets Division. Rubber, Mastic and Specialty Tapes Application Guide. Choose the. Right Tape. for your. Electrical Project

3M No Polish LC Connector SM and MM, Flat Splice, 250/900 µm

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

Volition. VF-45 Quick Install kit. and Maintenance Cleaning Kit. 3Innovation

3M Cushion-Mount Plus Plate Mounting Tapes with Easy Mount Adhesive

Installation Instructions

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

3M Cable Ties Product Guide. Made in USA. & Plenum Rated

3M Fiber Dome Closure FDC 10

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

3M Textool Test and Burn-In Sockets for 1.0 mm Area Array Packages Including Ball Grid Array and Land Grid Array

Door Edge Protection Film 36 inch

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

HVS S 15kV Class

C Power Connection Kit

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

SLiC Aerial Closures

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

Installation Instructions

3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7640-S, 7650-S and 7660-S Series 5, 8, 15, 25/28 and 35 kv

Model 1100B CHG Terminator. Installation Instructions

protect mask conduct reflect enhance 3M Specialty Tape Solutions

Repair Method for 3M Resilient Floor Protection System

GM Specification Annual Test Data

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

GM Specification Annual Test Data

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

Volition. Fiber Optic Cable. 3Innovation

8400 Series Fiber Distribution System

K SERIES PUSH ON & BULLET TERMINALS

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

Installation Instruction EPP /92

DOCUMENT OBSOLETE. Volition. VF-45 Socket Termination and Maintenance Cleaning Kits COOL HAND TOOLS. CLEAN UP YOUR ACT. VF-45 Socket Termination Kit

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

3 740 Wrist strap + shoe tester

Transcription:

3 Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class 350 kv BIL IEC 60840 72,5 kv Kit Contents: 1 Silicone Rubber Lug Seal Insulator Assembly 1 Hi-K Stress Control Assembly 1 Silicone Rubber Insulator Assembly 1 Silicone Rubber Skirted Insulator Assembly 1 Pre-formed Ground Braid Assembly 3 Constant Force Springs 1 Roll Scotch Electrical Shielding Tape 24 6 Tubes P55/R Red Compound (Non-Silicone Grease) 1 Roll Scotch Sealing Mastic 2229, 1" (25 mm) wide 8 Strips Hi-K Mastic (1-6" 22", 7-2" 11") 1 Roll Scotch Silicone Rubber Tape 70 1 Roll Scotch Vinyl Electrical Tape Super 88, 1½" 44' 1 6" (150 mm) Hi-K Mastic Pad 1 3M Cable Cleaning Pads CC-3 1 Copper Foil Tape Strip 1181, 15" long 4 Instruction Sheets Note: Do not use knives to open plastic bags. Kit Number 7672-S-8 Primary Insulation O.D. Range 1.94" 3.08" (49.3 75.4 mm) Table 1 Jacket O.D. Range 2.45" 3.61" (62.2 91.7 mm) Conductor Size Range AWG (mm 2 ) 250 1750 (120 850) 3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III for Jacketed Concentric Neutral (JCN) Cable 7672-S-8-JCN 78-8126-9535-7-B m CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product.

Correct Installation of Termination 2 78-8126-9535-7-B

Note: Check to insure all of the 3M Termination Assemblies QT-III will fit over the lug. If the lug will not fit through the assembly cores, this termination can not be installed using this lug. Do not remove any of the cores at this time. 1.0 Prepare Cable 1.1 Check to be sure the cable fits within the kit ranges as shown in Table 1. 1.2 Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug plus 0.5" (13 mm) plus crimp growth. Note: Provide additional exposed conductor to allow for growth of aluminum lugs or connectors during crimping. Conductor Size 250 350 400 650 750 1000 1100 2000 Growth Allowance 0.25" (6 mm) 0.5" (13 mm) 0.75" (19 mm) Field Determined Table 2 Figure 1 1.3 Select the roll of 1" (25 mm) wide Scotch Sealing Mastic 2229 from the kit. Cut a length of the mastic long enough to wrap around the cable jacket. Remove the release liner from the mastic and, using a light tension, apply a single wrap of mastic around the cable jacket 1" (25 mm) from the cut edge. (Figure 2) Figure 2 78-8126-9535-7-B 3

1.4 Bend neutral wires back over applied sealing mastic and secure to cable jacket with vinyl tape 12" (305 mm) below jacket cutback. (Figure 3) 1.5 Select the roll of 1" (25 mm) wide Scotch Sealing Mastic 2229 from the kit and cut a length of the mastic. Remove the release liner and, using a light tension, apply a single wrap of mastic around the cable jacket over the neutral wires and previously applied mastic. (Figure 3) Figure 3 1.6 Compress neutral wires into mastic by over-wrapping seal strips with two half-lapped layers of highly-tensioned Scotch Vinyl Electrical Tape Super 88. Cover all exposed mastic and neutral wires, overlapping 0.25" (6 mm) onto the exposed cable semi-con. (Figure 4) Note: Take care not to cover the exposed semi-con. A minimum of 2.5" (75 mm) of semi-con must be exposed. Figure 4 2.0 Install Lug or Connector 2.1 Check to be sure the cable fits within the kit ranges as shown in Table 1. 2.2 Position lug/connector and crimp according to manufacturer s directions. Remove excess oxide inhibitor and sharp crimp flashing following crimping. Refer to pages 11 12 for 3M lug/connector crimping information up to 1000 kcmil. 4 78-8126-9535-7-B

3.0 Clean Cable Insulation and Lug Barrel Using Standard Practice 3.1 Use only aluminum oxide abrasive to finish and polish insulation surface. 3.2 Use abrasive only on cable insulation. Do not use on semi-con. 3.3 When using abrasive, do not reduce the cable insulation diameter below that allowed by the kit. 3.4 Wipe the cable insulation clean with an approved solvent. Do not allow the solvent to touch semi-con insulation shield. Note: Remove any remaining solvent with 3M CC-DRY Cable Cleaning Pads (not supplied with kit) or lint-free cloth. 4.0 Install Termination 4.1 Select the large hi-k mastic pad from the kit. Remove the liners and align the pad with 1" (25 mm) covering the semi-con, and 5" (127 mm) covering the cable insulation. Using light tension, wrap the pad around the cable insulation two times. Trim the pad to overlap the start by approximately 0.25" (6 mm). Taper the pad edge by gently pressing along the edge with your finger. (Figure 5) Figure 5 78-8126-9535-7-B 5

4.2 Wrap two half-lapped layers of highly-tensioned Scotch Vinyl Electrical Tape Super 88 over the hi-k mastic pad, leaving approximately 0.125" (3 mm) of mastic exposed at each end. Taper the exposed edges of the hi-k mastic onto the cable by gently pressing along the edge with your finger. (Figure 6) Figure 6 4.3 Starting 5" (127 mm) from the cut end of the insulation, apply 2 tubes of P55/R Red Compund (non-silicone grease) over exposed insulation and vinyl tape-wrapped mastic pad. (Figure 7) Figure 7 4.4 Select the Stress Control Assembly (medium length tubular assembly on white core) from the kit. Slide the Stress Control Assembly over the lug and cable with the loose core end toward the lug. Butt the Stress Control Assembly Tube (not the core) up to the folded back neutral wires, and remove the core by pulling the loose end while unwinding counter-clockwise. Clean exposed cable insulation after installation. (Figure 8) Figure 8 6 78-8126-9535-7-B

4.5 Select one 2' x 11" (50 mm x 280 mm) hi-k mastic strip from the kit. Remove the liners and wrap around the end of the stress control assembly tube and cable insulation. Position the hi-k mastic so that half covers the stress control assembly tube, and half covers the cable insulation. (Figure 9) Figure 9 4.6 Wrap two half-lapped layers of highly-tensioned Scotch Vinyl Electrical Tape Super 88 over the hi-k mastic, leaving approximately 0.125" (3 mm) of mastic exposed at each end. Taper the exposed edges of the hi-k mastic onto the cable by gently pressing along the edge with your finger. (Figure 10) Figure 10 4.7 Select one or more of the 2" x 11" (50 mm x 280 mm) hi-k mastic strips from the kit. Remove the liner and fold the mastic strip twice lengthwise to form a 0.5" (12 mm) wide strip. (Figure 11) Figure 11 78-8126-9535-7-B 7

4.8 Wrap the mastic strip around the exposed conductor between the cable insulation and lug. Build the mastic up to the insulation O.D. (Figure 12) Figure 12 4.9 Apply additional wrap(s) of hi-k mastic (not folded) onto the cable insulation for 1" (25 mm) and taper the hi- K mastic 2" (50 mm) onto the lug barrel. (Figure 13) When using a tapered barrel lug, extend the hi-k mastic onto the barrel 2" (50 mm) past the tapered part of the barrel. (Figure 13) Figure 13 4.10 Select the roll of Scotch Silicone Rubber Tape 70 from the kit. Using moderate tension, wrap 2 half-lapped layers of tape over the hi-k mastic, leaving approximately 0.125" (3 mm) of mastic exposed at each end. Taper the exposed edges of the hi-k mastic onto the cable by gently pressing along the edge with your finger. (Figure 14) Figure 14 8 78-8126-9535-7-B

4.11 Apply 1 tube of P/55R Red Compound (non-silicone grease) 2" (50 mm) over the lug seal area and onto the cable insulation for approximately 4 inches (100 mm). (Figure 15) Figure 15 4.12 Select the Silicone Rubber Lug Seal Insulator from the kit. Slide the lug seal insulator onto the cable insulation with the loose core end toward the cable insulation. Position the lug seal insulator tube (not the core) 2" (50 mm) onto the lug barrel. Remove the core by pulling the loose core end while unwinding counter-clockwise. (Figure 16) Figure 16 78-8126-9535-7-B 9

4.13 Apply 3 tubes of P55/R Red Compound to the exposed cable insulation and hi-k stress control assembly tube. Fill the bottom edge of the silicone rubber lug seal the the P55/R Red Compound. Do not apply P55/R Red Compound to the surface of the lug seal insulator tube. (Figure 17) Figure 17 4.14 Select the Silicone Insulator Assembly (long tubular assembly) from the kit. Slide the Silicone Insulator Assembly over the lug and cable with the loose core end toward the cable jacket. Overlap the lug seal insulator tube, and align the Silicone Insulator Assembly (not the core) with the end of the lug seal. Remove the core by pulling the loose end while unwinding counter-clockwise. (Figure 18) Figure 18 4.15 Clean the Silicone Insulator Assembly Tube with an approved cable cleaner and wipe dry. 10 78-8126-9535-7-B

4.16 Select the Skirted Insulator Assembly from the kit. Carefully remove the red shipping core by pulling the loose end while unwinding counter-clockwise and discard. Slide the Skirted Insulator Assembly over the lug and cable with the loose core end toward the cable jacket. Align the Skirted Insulator Assembly Tube (not the core) with the leading edge of the previously installed Silicone Insulator Assembly Tube. Remove the core by pulling the loose end while unwinding counter-clockwise. (Figure 19) Figure 19 4.17 Connect the completed termination to equipment/system following standard practice. 4.18 Connect the neutral wires to the ground system following standard practice. Tooling Index Y 3 5, *Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. **Anderson VC6 3, VC6 FT, VC8C and Burndy Y1000 require no die set. 78-8126-9535-7-B 11

3M is a trademark of 3M Company. Scotch is a registered trademark of 3M Company. Important Notice All statements, technical information, and recommendations related to 3M s products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M s current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture for a period of one (1) year from the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800-245-3573 Fax 800-245-0329 www.3m.com/electrical Recycled paper 40% Pre-consumer waste paper 10% Post-consumer waste paper Litho in USA 3M 2006 78-8126-9535-7-B