Oil - kerosene burner

Similar documents
Light oil - kerosene burner

CODE MODEL TYPE G3BF 490T G5BF 492T G5BF 489T53

Kerosene - oil burner

CODE MODEL TYPE PRESS GW 605 T80

Installation, use and maintenance instructions. Gas oil burner. One stage operation CODE MODEL TYPE G20S 482T50

Kerosene and Gas oil burner

Installation, use and maintenance instructions. Gas oil burner. Two stage operation CODE MODEL TYPE G10I 466T1

Installation- and maintenance instruction B20KA/K

Installation- and maintenance instruction B20KAV/KV

Installation- and maintenance instruction BENTOFLEX ST120KAV

Installation- and maintenance instruction BENTOFLEX ST 108 PL

Installation- and maintenance instruction ST120 S75/21

Installation- and maintenance instruction B20K-2

Installation- and maintenance instruction B20KA/K

PRESS G SERIES. Two Stage Light Oil Burners FIRING RATES

Installation- and maintenance instruction BENTOFLEX ST133KA/K

OIL BURNERS MAIOR P 45 AB. techniques for energy saving MODEL. HYDRAULIC SYSTEM 220/380 V 60 Hz LB

RL/M BLU SERIES. Low NOx Modulating Light Oil Burners FIRING RATES. LOW NOx T. M 190/ kw M 223/ kw

RDB SERIES. One Stage Light Oil and Kerosene Burners FIRING RATES LIGHT OIL

Installation- and maintenance instruction B80-2/3

Installation- and maintenance instruction BENTOFLEX ST133K

X-Series Spare Parts List

ONE STAGE GAS BURNERS RDBS SERIES

RIELLO 40 F SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL. F kw F kw F kw

Kerosene burners. One stage operation. Installation, use and maintenance instructions CODE MODEL TYPE

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 CA

OIL FIRED FURNACE REPLACEMENT PARTS MANUAL FLF085D36C FLF110D48C. Models: Contents. General Notes. Important

product Information on oil, gas and dual fuel burners Industrial burners 1,000 11,700 kw flexible and reliable

TWO STAGE LIGHT OIL BURNERS PRESS G SERIES

Kerosene burners. One stage operation. Installation, use and maintenance instructions CODE MODEL TYPE

OIL BURNERS. MINOR 1 Snorkel 240 Volt 50 Hz

XL9 E-S Serial number N for XL9 E Edition 2005

SPARE PARTS LIST. for. Infrared oil heater. Model. Type. EPX5 for 120V 60Hz. May, 2017


VAILLANT SPARE PART CATALOGUE

Weishaupt Monarch oil burners Sizes 5 to 11 1/2002 GB

LIBERTY APPROVED OIL BURNERS AND SPECIFICATIONS. Supplemental Installation and Operating Instructions OIL-FIRED WATER AND STEAM BOILERS / NO.

RES G MRBLU SERIES. Low NOx One Stage Light Oil Burners FIRING RATES. LOW NOx LIGHT OIL

Mobile Diesel Heaters TOR / MIR Technical Training Course

822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE

Heating and Gas Installations - December 2014

SPARE PARTS MANUAL VAL HEATERS

XL9E-S Edition2005. Serial numbern forxl9e

Spareparts VAL 6-1 STEP KB - KL

Routine Burner Service

PRESS P/N - P/N ECO SERIES

Installation- and maintenance instruction B45A2.2

EC 200 EC 300 GE 360 GE 400 GE 600 L-S BM

Updated technical data can be found in this document, supplemented by the Riello BX Burner Manual regarding commissioning checks and adjustments.

Kerosene burners. One stage operation. Installation, use and maintenance instructions CODE MODEL TYPE

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw

Infrared oil heater. Model. Type. KBE5S for 120V 60Hz KBE5L for 120V 60Hz KBE5L 2-step for 120V 60Hz KBE1S for 230V 50Hz

Gas oil/ Kerosene burners

RIELLO 40 FS SERIES. One Stage Gas Burners FIRING RATES. FS kw FS kw FS kw FS kw FS kw FS kw GAS

RS/1 SERIES. One Stage Gas Burners RS 34/1 MZ RS 44/1 MZ kw kw GAS

X4 Installation and Operation Manual - POWER FLAME INCORPORATED

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES

RIELLO 40 GS SERIES. One Stage Gas Burners FIRING RATES. S kw S kw S kw S kw

RS/M SERIES. Modulating Gas Burners FIRING RATES

Weishaupt Monarch oil burners Sizes 1 and 3 1/2002 GB

Weishaupt oil burners Sizes 30 to 70 1/2003 CA

Specifications of MAXON VALUPAK burners for 50 Hz operation

MODEL B360 E ILLUSTRATED PARTS BREAKDOWN UNIT 1. From Serial Number: Untill Serial Number: Edizione 2010 Rev. A. Cod

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw

RS/E-EV MZ SERIES. Modulating Gas Burners FIRING RATES

ECONOMATIC REX/REXF REX/REXF DUAL STR

Doing more for clean environment and energy saving

Energysaver 559FT. Rinnai New Zealand Limited Page 1 of 6 Rinnai Energysaver 559FT Spare Parts: 01-11

XIII. Repair Parts 106

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw

available in battery up to 4 units for a total of 560 kw

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw

REX/REX F/REX K/REX K F REX DUAL/REX DUAL F

GULLIVER BSD SERIES. Low NOx Two Stage Gas Burners FIRING RATES. BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw.

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

GREENOx BT LOW RETURN TEMPERATURE DUAL BT WITH TILED BOILERS. GREENOx BT COND LOW RETURN TEMPERATURE WITH CONDENSER

3D drawings available at Kg GAS-NPT thread adapters available at page 1.117

Service Manual. Contents. Names of components. 3. Specifications Wiring Diagam Sequence Time Chart

DB Series. Technical Data Leaflet. Industrial Dual Block Oil, Gas and Dual Fuel Burners. Industrial TS0086UK00

Differential Pressure Sensors

Light oil burners. Low - High or modulating operation. Installation, use and maintenance instructions

GULLIVER BS SERIES. Low NOx One Stage Gas Burners FIRING RATES. BS kw BS kw BS kw BS kw.

Spare parts catalogue GB 07/2008. Wall-hung boilers ecotec VU 466/4-5 VU 656/4-5

Gas oil/ Kerosene burners

M K. MK is a pressurized steel boiler for heating system with hot water production up 90 C. High efficiency

SPARE PARTS LIST. for. Infrared oil heater. Model. discontinued model. KBE1JA for V 60Hz. ( Spare parts supply until 2018 ) May, 2017

VAL6 KBE5S. Service Manual

Spare parts list GREENSTAR CAMRAY. Burner 24/04/

ONE STAGE GAS BURNERS RS/1 SERIES RS 28/ kw RS 34/1 MZ kw RS 38/ kw RS 44/1 MZ kw

Gas oil/ Kerosene burners

Oil, gas and dual fuel burners. Burner series

RAYPAK ILLUSTRATED PARTS LIST

Valve monitoring system VDK 200 A S02

AHE S - 12 VDC AHE X - 12 VDC AHE X - 12 VDC

GENERAL WARNING. General instructions. Technical assistance. Doseuro S.r.l. Liability

PAGE 1. TES Operation & Testing Guidelines: Tes Trouble shooting

Finding and Fixing Vacuum Leaks on the LT5 Engine Marc Haibeck

product Oil burners, 1-11 monarch burners, sizes 1-11 ( kw) simply reliable Information on oil burners

HVF110, 210, 310, 410HD

Transcription:

Installation, use and maintenance instructions Oil - kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 9038 ()

TECHNICAL FEATURES Thermal power output 8 0 kw.3 5 kg/h Fuel Gas oil 35s, max. viscosity at 0 C: mm/s Kerosene 8s Electrical supply Single phase, 30V ± 0% ~ 50Hz Motor Capacitor Ignition transformer Pump Absorbed electrical power Run current 0.85A 850 rpm 98 rad/s 4 mf Secondary 8 kv ma Maximum pressure 4 bar (03 psi) 0. kw Burner with CE marking in conformity with EEC directives: EMC89/33/EEC, Low Voltage 73/3/EEC, Machines 89/39/EEC and Efficiency 9/4/EEC The burner meets protection level of IP 40, EN 059. Fig. 0 7 8 4 9 3 D5553 5 Return line Suction line 3 Gauge connection 4 Pump pressure regulator 5 Vacuum gauge connection Screws fixing air-damper 7 Hydraulic jack with air-damper 8 Lock-out lamp and reset button 9 Flange with insulating gasket 0 Combustion head adjustment screw EQUIPMENT Quantity Description Flexible pipe with nipple Flange with insulating gasket Screws and nuts for flange Hinge Screw of pump by-pass Grommet Screw with two nuts for flange 38

WORKING RANGE (as EN 7) Pressure in the combustion chamber mbar 0,8 0, 0,4 0, 0,3 3 4 5 Fuel output - kg/h D5 5 30 35 40 45 50 55 0 Thermal power - kw DIMENSIONS Flange 80 = Burner 7 7 3 = 45 45 75 7 33 80 ø 89 30 50 37 D5554 MOUNTING THE BURNER It is necessary that the insulating gasket (9, fig. ) is placed between the boiler door and the burner flange. This insulating gasket has six holes, which, if necessary, can be modified as shown on the drawing on the right. Verify that the installed burner is lightly leaned towards the button. (See figure ). The burner is designed to allow entry of the flexible oil-lines on either side of the burner. D54 Fig. BURNER FIXING AND HINGE ASSEMBLY D557 S7384 38

OIL LINES D59 min. 0. m H max. 4 m PRIMING THE PUMP Loosen the plug of the vacuum gauge (5, fig. ) and wait until the fuel flows out. H meters 0.5.5 L meters I. D. 8 mm 0 0 40 0 I.D. 0 mm 0 40 80 00 H = Difference of level. L = Max. length of the suction line. I.D. = Internal diameter of the oil pipes H D50 H max. 4 m H meters 0 0.5.5 3 3.5 L meters I. D. 8 mm 35 30 5 0 5 8 I.D. 0 mm 00 00 00 90 70 30 0 A WARNING The pump is supplied for use with a one pipe system. For use on a two pipe system, it is necessary to screw the by-pass screw (A) supplied as burner s accessory. (See figure). The pump vacuum should not exceed a maximum of 0.4 bar (30 cm Hg). Beyond this limit gas is released from the oil. Oil lines must be completely airtight. The return line should terminate in the oil tank at the same level as the suction line; in this case a non-return valve is not required. Should however the return line arrives over the fuel level, the nonreturn valve is indispensable. This solution however is less safe than previous one, due to the possibility of leakage of the valve. D599 PRIMING THE PUMP: Start the burner and wait for the priming. Should lock-out occur prior to the arrival of the fuel, await at least 0 seconds before repeating the operation. Warning: before starting the burner make sure that the return pipe-line is not clogged: any obstruction would cause the pump seals to break. WARNING: Check periodically the flexible pipes conditions. Using kerosene, they have to be replaced at least every years. A metal bowl filter with replaceable micronic filter must be fitted in the oil supply pipe. 38 3

BURNER ELECTRICAL WIRING 30V ~ 50Hz N L WARNING Do not exchange the neutral with the phase. Switch with fuse A max. Neutral T Regulating thermostat T Limit thermostat with manual resetting N L Remote lock-out lamp (30V - 0.5A max.), if required CARRIED-OUT IN THE FACTORY Valve 3 4 5 7 8 9 Blue Blue White (50V) Brown Brown Black Black Capacitor M ~ Motor Terminal block of control-box 530SE * D58 NOTES Wires of mm section. The electrical wiring carried out by the installer must be in compliance with the rules in force in the Country. To remove the control-box from the burner, loosen screw (A) (see figure) and pull towards the arrow. The photoresistance is fitted directly into the control-box (underneath the ignition-transformer) on a plug-in support. A 3 S70 TESTING Check the shut-down of the burner by opening the thermostats. RUN OF THE ELECTRICAL CABLE - Cable gland N - Neutral - Cable-clamp L - Phase 3 - Terminal block - Burner-earth 38 4

COMBUSTION ADJUSTMENT In conformity with Efficiency Directive 9/4/EEC the application of the burner on the boiler, adjustment and testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO concentration in the flue gases, their temperatures and the average temperature of the water in the boiler. To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of the combustion head and the air damper opening in accordance with the following schedule. FUEL GAS OIL 3 4 Nozzle Pump pressure Burner output FUEL KEROSENE Comb. head adjustment NOZZLES RECOMMENDED: Monarch type R - NS ; Delavan type W -A - E Steinen type Q - H ; Danfoss type B - H Angle: 0 - in most cases. 80 - in case of flame detachment, during ignitions at low temperatures. Air damper adjustment GPH Angle bar kg/h ± 4% Set-point Set-point 0.0 0 /80..5 0.5 0 /80.8. 0.75 0 3..5.5 0.85 0 3.7 3 3.00 0 4.3 4 4.5.0 0 4.8 5.0 0 3 5.0 7 3 4 Nozzle Pump pressure Burner output Comb. head adjustment Air damper adjustment GPH Angle bar kg/h ± 4% Set-point Set-point 0.75 0 8. 0.85 0 8.5.5.00 0 8.9.3.0 0 8 3..5.5.5 0 8 3.7 3 3.35 0 8 4.0 4 4.50 0 8 4.4 5 5.50 0 0 5.0 7 PRESSURE: 8 bar: the pump leaves the factory set at this value, which is suitable only for kerosene. 0 bar: maximum pressure for kerosene. FOR GAS OIL INCREASE PRESSURE bar: in most cases. 4 bar: improves flame retention; it is therefore suitable for ignitions at low temperatures. 38 5

3 COMBUSTION HEAD SETTING This is done when fitting the nozzle, with the blast tube removed. It depends on the output of the burner and is carried out by rotating the regulating rod, till the terminal plane of the blast tube is level with the set-point, as indicated in the schedule. In the sketch below, the combustion head is set for an output of 0.85 GPH at bar (for gas-oil) or.5 GPH at 8 bar (for kerosene). The shutter is level with set-point 3, as required by the schedule at page 5. Terminal plane of the blast tube 3 5 3 Regulating rod D53 Blast tube Shutter D555 Combustion head settings indicated in the schedule are valid for most cases. The setting of the fan output according to the installation should normally be done only through the air damper. Should one subsequently want to retouch also the setting of the combustion head, with the burner running, operate on the rod () with a mm spanner () as follows: TURN TO THE RIGHT: (SIGN +) In order to increase the volume of air entering the combustion chamber and thus diminishing its pressure. There is a reduction of CO and the adhesion of the flame to the air diffuser disc improves. (Setting advisable for ignitions at low temperatures). TURN TO THE LEFT: (SIGN ) In order to reduce the volume of air entering the combustion chamber and thus increasing its pressure. The CO improves and the adhesion of the flame to the diffuser tends to reduce. (This setting is not advisable for ignitions at low temperatures). In any case do not bring the combustion head setting more than one point away from that indicated in the schedule. One set-point corresponds to 3 turns of the rod; a hole (3) at its end facilitates counting the number of turns. 38

4 AIR DAMPER ADJUSTMENT: The mobile air damper () operated by the jack () assures the complete opening of the air intake. The regulation of the air-rate is made by adjusting the fixed air damper (3), after loosing the screws (4). When the optimal regulation is reached, screw tight the screws (4) to assure a free movement of the mobile air damper (). 4 D5550 3 4 The settings indicated in the schedule refer to the burner with its metal cover fitted and the combustion chamber with zero depression. These regulations are purely indicative. Each installation however, has its own unpredictable working conditions: actual nozzle output; positive or negative pressure in the combustion-chamber, the need of excess air, etc. All these conditions may require a different air-damper setting. It is important to take account of the fact that the air output of the fan differs according to whether the burner has its metal cover fitted or not. Therefore we recommended to proceed as follows: adjust the air damper as indicated in the schedule (4); mount the cover, simply by means of the upper screw; check smoke number; should it become necessary to modify the air output, remove the cover by loosening the screw, adjust the air damper, remount the cover and finally recheck the smoke number. ELECTRODE SETTING Attention: Before removing or assembling the nozzle, loosen the screw (A) and move the electrodes ahead. 4 ± 0.3 mm IMPORTANT: THESE DIMENSIONS MUST BE OBSERVED D530 A.5 mm 38 7

BURNER START-UP CYCLE Thermostat Motor Ignition transformer Valve Flame Lock-out lamp Normal ~ s Lock-out, due to light-failure ~ s ~ 5s D59 ONLY FOR GAS OIL ADJUSTMENTS, TO AVOID FLAME - DETACHMENT, AT BURNER - IGNITION This inconvenience can occur, when the temperature of the gas-oil decreases below +8 C. ) CORRECT POSITIONING OF THE ELECTRODES 4 ± 0.3 mm IMPORTANT: THESE DIMENSIONS MUST BE OBSERVED D530 A.5 mm ) PUMP - SETTING When the temperature of the gas-oil decreases below +8 C, increase the pressure to 4 bar. 3) COMBUSTION-HEAD SETTING Regulate the combustion-head one set-point further ahead than indicated in the instructions. Example: the instructions require to set the combustion-head on set-point 3. Instead, the setting is made on set-point 4. 4) FAN - AIR DAMPER ADJUSTMENT Adjust the air damper of the fan, such as to obtain a smoke number not inferior to. (i.e. a combustion with the lowest possible excess-air). 38 8