Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

Similar documents
3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

Branch Splice QS-2001B

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

High Voltage Joints and Terminations up to 72,5 kv 145 kv

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A


Contents. Design Test Results for Specimen Design Test Results for Specimen Voltage Impulse Oscillograms...9

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

INSTALLATION PRODUCTION TESTS

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

Product Description: Objective and Certification: Test Samples and Test Cable:

600 A 15 kv class T-OP II deadbreak connector

MEDIUM VOLTAGE TERMINATIONS

High Voltage Technology & Testing

Eaton s Cooper Power Systems

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

25 kv Apparatus Bushings

3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7640-S, 7650-S and 7660-S Series 5, 8, 15, 25/28 and 35 kv

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

4 AWG to 2000 kcmil at 15 kv, 2 AWG to 1750 kcmil at 25 kv and 1 AWG to 1500 kcmil at 34.5 kv. Stress Control

600 A 35 kv class BT-TAP deadbreak connector

power cable accessories

600 A 25 kv class BT-TAP deadbreak connector

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

15 kv and 25 kv Thru-Bushings

REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

Medium Voltage. Joints & Terminations

Power Cable Splicing and Terminating Guide. Quality Workmanship that Lasts

3M Cold Shrink Splice Kits, QS T Series

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

IEC Separable Connectors 17.5 kv/24 kv, 630A

GAS INSULATED VOLTAGE TRANSFORMERS.

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Independent Testing Laboratory for High Voltage Equipment

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Joined Forces Extensive product portfolio and technologies. Cable Accessories from 1 kv to 550 kv. nkt.com

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Loadbreak Apparatus Connectors

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

CABLE SYSTEMS. Accessories and Systems for Medium and High-Voltage Cables up to 300 kv.

IEEE Insulated Conductors Committee. Subcommittee B, Cable Accessories

3M Cold Shrink QT-III Silicone Rubber Termination

The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI

Medium Voltage Catalog

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations

QTII (X) Series Silicone Rubber Cold Shrink Termination Kits

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

3 TM Cold Applied Barrier Boot System

3M Products for Electrical Networks Wind Farm Capabilities. Leading Edge. Electrical Solutions for. Wind Farms

Transformer bushings, type GOH. Technical guide

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

22kV 425 AMP KA STYLE COUPLER 224BKA - Range

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

Separable Connectors and Kits

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

CTT & WPU CABLE TEST TERMINATIONS & WATER PROCESSING UNIT. H I G H V O LTA G E TEST SOLUTIONS

Completing the picture

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

Bushings for High Voltage AC Applications

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

This small footprint makes a BIG impact

Installation device. HelaTape. Electrical tapes for sealing, insulation and bundling of cable and conduits.

High Voltage Surge Arresters Station Class

HIGH VOLTAGE POWER SUPPLY DESIGN AND MANUFACTURING PRACTICES

Natural Ester Fluid Diagnostics

DURESCA Busbar system. For indoor and outdoor applications, type DE / type DG DURESCA

Cold Shrink QS T Trifurcating Transition Splice Kit

TEMPERATURE RISE TESTS

VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Transcription:

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. George Fofeldea Power Engineer, 3M Canada August 2018

Abstract 3M invented cold shrink technology in 1968. 3M engineers used Ethylene propylene diene monomer (EPDM) rubber, which was a new rubber at the time, and developed a unique formulation that paved the way for 3M Cold Shrink Technology a live seal to help manage electrical stress. These specially formulated rubber tubes also offered installation benefits; with no source of heat or extra tools required, 3M Cold Shrink Technology became a vastly simplified solution to cable termination. Realizing the benefits of this cable termination method (i.e., ease of installation, living seal, etc.), other manufacturers have introduced similar-looking designs. But if they look the same, does it mean that they perform the same? 2

Table of contents Introduction... page 4 Materials and methods... page 4 5 Stress control methods... page 5 Study methodology... page 5 Results... page 6 Table 1: testing results... page 6 Observations... page 7 Research samples... page 8 Discussion... page 9 10 Table 2: approximate lengths of an installed 15 kv tape stress cone termination... page 10 Conclusion... page 11 References... page 12 3

Introduction The goal of this study is to answer: are all cold shrink medium voltage terminations equal? One would think the answer is yes since the industry follows the same IEEE 48 type test standard. However, test results indicate this may not always be the case. Materials and methods It s important to understand what happens to the electric field when a cable termination is installed. In a typical shielded, medium voltage cable (5-46 kv) with a continuous insulation shield, the electric field is uniform along the cable axis, but the field itself varies in a radial direction. When a termination is installed on a cable, removing the insulation shield causes a discontinuity in the axial direction of the cable, resulting in a field that is no longer uniform along the axis. This process produces a high concentration of electrical stress closer to the insulation shield end. Figure 1 shows a field plot without stress control. These electrical stresses at the end of the insulation shield must be reduced to avoid cable insulation failure. This reduction is referred to as electrical stress control. The removal of the insulation shield results in a discontinuity in the axial direction of the cable The field is no longer axially uniform along the cable Shield removal produces a high concentration of stresses Steps must be taken to avoid cable insulation failure Field plot without stress control 40% 50% 60% Equipotential lines Electric flux lines 20% 80% Cable Insulation shield Figure 1 4

Stress control methods 1 Traditional geometric stress cone This method reduces the stress at the shield discontinuity by extending the shield and gradually increasing the thickness of insulation under the shield. The areas where there is higher electrical stress receive additional insulation, as shown in Figure 2, below. 2 High dielectric constant (Hi K) stress control This method lowers the electrical stress at the point of shield discontinuity by refracting the electrical stress. This allows the equipotential lines to spread out along the cable insulation interface. By doing this, the surface stress of the termination is greatly reduced, which improves cable termination performance and life expectancy shown in Figure 3, below. 1,3 Geometric Stress Control Capacitive Stress Control Equipotential lines 20% 40% 50% 60% 40% Equipotential lines 20% Hi K material 50% 60% 80% 80% Figure 2 Figure 3 Study methodology A test was conducted in a controlled laboratory environment to determine which method is most effective at controlling electrical stress. The comparison: 3M Cold Shrink Products that use Hi-K capacitive stress control versus competitive cold shrink products that use geometric stress control. 1 Competitive cold shrink geometric stress cone termination testing Competitive 15 kv and 25/28 kv cold shrink geometric stress cone terminations were tested in compliance with the IEEE 48-2009 short-term testing sequence 15 kv terminations were installed on 350 Kcmil/15 kv cables 25/28 kv terminations were installed on 4/0/25 kv cables Partial discharge (PD) testing was conducted using a 3pC threshold 2 3M Cold Shrink Hi-K capacitive termination testing 3M Cold Shrink Termination 7695-S-4 (test report: CRQTIII-7695-S-4) rated for 25/28 kv applications, tested to 28 kv levels, according to IEEE 48-2009, on a 750 Kcmil/25 kv cable 3M Cold Shrink Termination 7655-T-150 (test report: CRQTIII-7655-T-150) rated for 25/28 kv applications tested to 35 kv levels for indoor applications ( BIL), according to IEEE 48-2009, installed on a 500 Kcmil/35 kv cable 5

Results The presented test results are a reflection of the performance of the stress control method. Table 1: testing results Pass: Fail: Not tested: Competitive Cold shrink stress cone termination Voltage Class PD (CSV/CEV) 1 Minute AC Withstand 15 Minute DC Withstand BIL (10+/- Surges) HOT BIL (10+/- Surges) PD (CSV/CEV) 5 Hour AC Withstand 5 Minute AC Withstand BIL (10+/- Surges) PD (CSV/CEV) Sample 1 15 kv DF at 31 kv 50 kv -75 kv 110 kv 110 kv DF at 31 kv 31 kv 39 kv 110 kv DF at 31 kv Sample 2 28 kv (tested at 28 kv levels) 17.3/ 14.2 kv (Fail) (Fail) Sample 3 28 kv (tested at 28 kv levels) 21.0/ 18.5 kv (Fail) (Fail) Sample 4 28 kv (tested at 25 kv levels) 15.4/ 13.9 kv (Fail) 65 kv (Fail) Sample 5 28 kv (tested at 25 kv levels) DF at 50 kv 65 kv -105 kv 34.7/33.3 KV 50 kv (Fail) Sample 6 28 kv (tested at 25 kv levels) 15.9/ 14.6 kv (Fail) -116 kv 16.6/15.6 kv (Fail) 56 kv (Fail) 3M Cold Shrink Hi-K Termination 7695-S-4, Specimen 1 * 25/28 kv (tested at 28 kv levels) 44.6 kv/44 kv -116 kv DF at 56 kv 56 kv DF at 56 kv 3M Cold Shrink Hi-K Termination 7695-S-4, Specimen 2 * 25/28 kv (tested at 28 kv levels) 46.3 kv/45.5 kv -116 kv DF at 56 kv 56 kv DF at 56 kv 3M Cold Shrink Hi-K Termination 7655-T-150, Specimen 1 * 25/28 kv (tested at 35 kv levels) 62.4 kv/ 59.5 kv 90 kv -140 kv DF at 71 kv 71 kv 91 kv DF at 71 kv 3M Cold Shrink Hi-K Termination 7655-T-150, Specimen 2 * 25/28 kv (tested at 35 kv levels) DF free at 71 kv 90 kv -140 kv DF at 71 kv 71 kv 91 kv DF at 71 kv Legend: AC: Alternating current BIL: Basic lightning impulse insulation level CSV/CEV: Corona starting voltage/corona extinction voltage DC: Direct current DF: Discharge free HOT BIL: Basic insulation level at cable emergency temperature PD: Partial discharge *Each specimen consists of a piece of cable with terminations at each end. A total of 4 terminations were tested. 6

Observations 3M Cold Shrink Products with high dielectric constant (Hi-K) capacitive stress control proved to be more effective in controlling electrical stress than the competitive products with geometric stress control. Both 3M Cold Shrink Termination 7695-S-4 specimens and 3M Cold Shrink Termination 7655-T-150 specimens passed each test for their voltage class. The results of the competitive cold shrink geometric stress cone termination testing did not have the same success: Sample 1 of the cold shrink stress cone design 15 kv termination passed the short-term test sequence based on the IEEE 48-2009 design test requirements. Samples 2, 3, 4, 5 and 6 of the cold shrink stress cone design 25/28 kv terminations did not pass the IEEE 48-2009 design test requirements. Samples 2 and 3 failed the initial PD test (17.3 kv inception voltage, 14.2 kv extinction voltage, 21 kv inception, and 18.5 kv extinction voltage respectively). Additionally, internal failure of the terminations occurred at the end of the void-filling mastic during the 1-minute AC withstand test at, which resulted in the breakdown of the cable insulation at that location. Sample 4 failed the initial PD test (inception voltage at 15.4 kv and extinction voltage of 13.9 kv). Internal failure of the termination also occurred at the end of the geometric stress cone during the 1-minute AC withstand test at 65 kv, which also resulted in cable failure. Sample 5 passed PD testing both initially and after the HOT BIL test, but failed at 50 kv, 19 minutes into the 5-hour AC withstand test. The failure was located at a certain distance away from the cable semi-conductive edge, within the length of the void-filling mastic. Sample 6 failed the initial PD test (15.9 kv inception and 14.6 kv extinction voltage). It also failed PD testing after the HOT BIL (16.6 kv inception and 15.5 kv extinction voltage) and ultimately failed 95 minutes into the 5-hour AC withstand test at 56 kv. Failure location was in the vicinity of the cable semi-conductive step down layer. 7

Research samples *The pictures below show a failed cable after termination removal, typical of Samples 2, 3, 5 and 6. Sample 2 Sample 3 Sample 5 Sample 6 8

Discussion The results of this study demonstrate the following three key benefits to choosing 3M Cold Shrink Terminations with high dielectric constant (Hi-K) capacitive stress control: 1.0 High withstand capabilities and greater reliability 2.0 A more uniform distribution of electrical field This can be easily demonstrated by gradually raising the voltage on two types of terminations one with geometric and one with Hi-K capacitive stress control until leakage currents become visible. At a certain voltage, the geometric stress cone will develop intense stresses, followed by surface discharges, while the Hi-K capacitive stress control termination remains free of visible discharges.2 20% 40% 60% 80% 100% A uniform electric field distribution lowers surface stress and improves track resistance. The plots in Figure 4 below, drawn to scale, illustrate how the equipotential lines are more agglomerated (closer together) over a shorter distance for a geometric stress cone, compared to a Hi-K capacitive stress cone, where the equipotential lines are spread more uniformly and over a longer termination surface distance.2 Geometric Equipotential lines are closer 20% 40% 60% 50% 70% 30% 80% 90% 10% High Dielectric Constant Equipotential lines are further apart 20% 10% 30% 40% 50% 60% 70% 80% 90% Figure 4 9

3.0 Shorter overall Hi-K termination A shorter termination improves safety and overall reliability because it lowers the risk of cable preparation errors associated with longer insulation interfaces. It can also be an installation benefit in tight spaces, such as inside switchgear. Table 2 shows the approximate lengths of an installed 15 kv tape stress cone termination, 3M QT-III Silicone Rubber Hi-K Indoor and Outdoor Terminations and a competitive stress cone silicone termination. As shown, the 3M Cold Shrink Hi-K Capacitive Terminations are the shortest. Table 2: approximate lengths of installed 15 kv terminations Termination type 3M 15 kv tape stress cone Picture Installed length * 50.8 cm (20 in) 3M 15 kv outdoor QT III Hi-K termination 25.4 cm (10 in) 3M 15 kv indoor QT III Hi-K termination 25.4 cm (10 in) Competitive 15 kv cold shrink stress cone termination 33.02 cm (13 in) *Installed lengths are approximate because for cold shrink terminations the actual installed length depends on the cable insulation diameter. 10

Conclusion Testing shows that the 3M Cold Shrink Terminations with Hi-K capacitive stress control meet and exceed the requirement of the IEEE 48 standard. The tested competitive cold shrink geometric stress control terminations rated for 25/28 kv voltage levels do not meet the requirements of the standard, although the 15 kv terminations comply with the standard requirements. 3M Cold Shrink QT-III Termination s Hi-K capacitive stress control termination design enables uniform distribution of the electric field resulting in lower surface stress and improved track resistance. In closing, 3M Cold Shrink QT-III Termination s Hi-K capacitive stress control tested is a more reliable technology for medium voltage cable terminations. For more information about 3M electrical products and solutions contact us at 3Menergysolutions@mmm.com. 11

3M Science. Applied to Life.TM Customized Solutions Technical Expertise Electrical Markets Division Building Customer Value Customer Experience Reliable Products and Total Cost of Ownership References Bill Taylor, PCIC-2007-27 Paper, An overview of cold applied technology for medium voltage cable accessories H.C Hervig, P.N. Nelson, IEEE Transaction on Power Apparatus and Systems, Vol. PAS-103, No. 11, November 1984, High dielectric constant materials for primary voltage cable terminations 3 R. A. Wandmacher, J.D. Heyer, John Morris, IEEE T&D Conference Los Angeles, September 1996, New Silicone Cold Shrink Termination 1 2 Important Notice The technical information, guidance, and other statements contained in this document or otherwise provided by 3M are based upon records, tests, or experience that 3M believes to be reliable, but the accuracy, completeness, and representative nature of such information is not guaranteed. Such information is intended for people with knowledge and technical skills sufficient to assess and apply their own informed judgment to the information. No license under any 3M or third party intellectual property rights is granted or implied with this information. 3M Electrical Markets 3M Canada P.O. Box 5757 London, ON N6A 4T1 1-800-364-3577 3M.ca/Electrical 3M and 3M Science. Applied to Life. are trademarks of 3M. Used under license in Canada. 2018, 3M. All rights reserved. 1806-12295 E BA-18-26732