OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

Similar documents
LCR Series REVERSING ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

LUF Series Unidirectional Electric Actuators

VALVCON. QX-Series ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

UniTorq UTQ Quarter-Turn Actuator Installation and Operation Manual

IMO-517 (7027) ISSUE 3/97 ERA12, 25, 50, 83, 125, 167, 208 AND 250 ELECTRIC ACTUATORS INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC. Installation, Maintenance and Operating Instructions

RP-4000 Reserve Power Control

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC With Iso/Readback Board Installed (Option U )

ADC Series. MODULATING ELECTRIC ACTUATORS With C, CL2 & CL3 Options With N In The Model Number. Installation, Maintenance and Operating Instructions

VALVCON V-Series. ELECTRIC ACTUATORS With Speed Control/Timer Board (Option J ) Installation, Maintenance and Operating Instructions

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

Surepowr Series 100 Installation Manual

HQ Series ¼ Turn Electric Actuator

AF-17 Electronic Positioner Installation, Operation and Maintenance Instructions

SUREPOWR TM SERIES -SURE 49 FIELD INSTALLATION INSTRUCTIONS

Radius, LLC Electric quarter turn actuator EW series Installation, Maintenance and Operating Manual

HQ Series ¼ Turn Electric Actuator

Quarter Master Series 94 Actuator

Type 1051 and 1052 Size 33 Diaphragm Rotary Actuator

Series 72 Electri-SAFE On/Off Operation Including CLC Option Installation, Operation and Maintenance Instructions

Electronic Proportional (EP) Control for Heavy Duty Series 0/1 Piston Pumps Model 33 Model 39 Model 46. Model 54 Model 64 Model 76

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

Surepowr Series Sure 150

VALVCON V-Series. ELECTRIC ACTUATORS 115 VAC AND 230 VAC With Control Board Installed (Option C) Installation, Maintenance and Operating Instructions

ECON ELECTRIC ACTUATOR Fig ELA60 Ex

VALVCON ADC-SERIES ELECTRIC ACTUATOR WITH OPTIONAL BATTERY BACK-UP POWER

Electric Modulating Actuator Installation, Operation & Maintenance Manual

R81EAA-2 Economizer Circuit Board

Installation, Maintenance and Operation Manual

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Eaton Electronic Proportional (EP) Control for Medium Duty Piston Pumps

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

V Series. 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS With Isolated Control/Position Feedback Board Installed (Option U )

V Series 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

M100F Incremental Motor Actuator R81F Interface Board

VALVCON I-SERIES I6600 OPTION DN DEVICENET PROTOCOL

Electronic Proportional (EP) Control for Medium Duty Piston Pumps

Quarter Master Chief Series 92 Actuator

AE Installation Operation & Maintenance Instructions

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Direct-Coupled ControlSet Actuators (120/180/320 in-lbs.) Installation Guide 2-7/16"

Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

VG7000 Valve Linkage for M100 Series Motor Actuators

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

ELECTRIC ACTUATORS 115 VAC AND 230 VAC

Thermal Shut-Off I. OVERVIEW OF THERMAL SHUT-OFF VALVES

Installation, Operation and Maintenance Manual

DeZURIK DR 40B ROTARY DIAPHRAGM ACTUATOR

Installation Instructions

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Milwaukee's Electric Actuator Installation, Operation & Maintenance Manual

Electronic Proportional (EP) Control for Heavy Duty Series 2 Piston Pumps Model 33

12 Series Linear Electric Actuator Installation, Operation & Maintenance Manual

PEAKTRONICS DMC-101 ADDITIONAL FEATURES. DC Motor Controller, 5A DMC-101

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

Electric Actuator Installation, Operation & Maintenance Manual

ATP-2040 Electric Damper Actuator/Transmitter

VALVCON. V-Series. STANDARD ELECTRIC ACTUATORS With Speed Control/Timer Board (Option J ) Installation, Maintenance and Operating Instructions

LF Series At A Glance

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

M9216 Series Electric Spring Return Actuators

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

V Series. 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS With Control Board Installed (Option C) Installation, Maintenance and Operating Instructions

Part Number Mini Linear Lift Assembly Installation & Operator s Instruction Manual

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

Installation Instructions

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

715B CONTROL SERIES. Instruction Manual Line Voltage DC Brushless Motor Control CONTROLS. Phone (317) Fax (317)

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator


TIMING BELT REPLACEMENT. Tools Required. J A (KM-421-A) Timing Belt Adjuster J Angle Meter KM-470-B Angular Torque Gage

NOAH ACTUATOR NA-SERIES MANUAL EMICO EUNHA MACHINERY INDUSTRIAL CO.,LTD.

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

DeZURIK TEN-POSITION LEVER MANUAL ACTUATOR

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

Tooling Assistance Center

Series 10 Actuator. Installation, Operation and Maintenance Manual

Y20EBA Linkage Kit, M100 to Barber-Colman 1/2 to 1-1/4 Inch Valves

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

FSAF24(-S) US, FSAF120(-S) US

ELECTRONIC CONTROL ACTUATOR

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

SmartX MF and MS

INSTRUCTION MANUAL. A battery protector for vehicles with equipment that Is operated with the engine not running. MODEL# INPUT: 12 Volts D.C.

JAMESBURY ELECTRIC ACTUATORS VALVCON ADC-SERIES WITH OPTIONAL BATTERY BACK-UP POWER

Electric Actuator Installation, Operation & Maintenance Manual

LF Series Spring Return Direct Coupled Actuator

Installation, Operating & Maintenance Instructions

Electro-Mechanical Swing Operator. Table of Contents

BLDC SPEED CONTROL INSTRUCTION MANUAL Low voltage Brushless DC control

Versatile and Powerful

Kit INSTALLATION GUIDE. 5 psi Low Pressure Sensor (Single Gauge)

Installation, Operation and Maintenance Manual

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) EN44 and EN88 Non-Spring Return Electronic Actuators

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

ELECTRICAL. Contents - Wiring Diagrams

Transcription:

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1 This instruction manual contains important information regarding the installation, operation, and troubleshooting of Valvcon's Electric Q 6.0.1 Actuator. Please read these instructions carefully and save them for future reference. Description The Q 6.0.1 is a 600 inch pound, 12 VDC electric actuator with 100% duty cycle. With Valvcon's unique modular design, all the actuator accessories simply plug into the terminal board. Installation is simplified and reliability is improved. The Q 6.0.1 is controlled by two 12 VDC internal relays. This Instruction Manual pertains only to the Q 6.0.1 actuators. PARTS LIST 1 - Cover 2 - Cover Screws 3 - Q 6.0.1 Terminal Board 4 - Q 6.0.1 Board Bracket 5 - Cams (2) 6 - Limit Switches (4) 7 - Override Shaft 8 - Motor 9 - Base plate 10 - Base Plate Screws 11 - Cam/Output Shaft 12 - Snap Ring 13 - Bull Gear 14 - Pinion Gear 15 - Output Coupling 16 - Base Figure 1 Parts Identification PAGE 1

Caution Dangerous voltages are present inside the actuator cover unless the power supply to the actuator has been shut off or disconnected. Use extreme caution whenever working on the actuator with the cover removed. NOTE: THE ACTUATOR IS DESIGNED FOR HAZARDOUS LOCATIONS. AFTER IT IS FIELD INSTALLED, THE ACTUATOR MUST NOT BE OPERATED WITH THE COVER OFF OR WITH LESS THEN ALL EIGHT COVER BOLTS SECURELY FASTENED. Tools Required 1/16 inch hex wrench (limit switches) 3/16 inch Hex wrench (cover screws) Temperature Limits Low ambient temperatures - The minimum recommended ambient temperature without a heater is approximately 30 F (varies with frequency of use). With an optional heater and thermostat installed, the recommended minimum ambient temperature is -40 F. High ambient temperatures - The maximum recommended ambient temperature is 150 F with the actuator shaded from direct sunlight. High media temperatures - With media temperatures up to 200 F, additional precautions are not usually necessary. For media temperatures between 200 F and 300 F, a shielding plate (about one inch larger than the actuator in each dimension) should be placed between the actuator and the mounting bracket. In addition, the actuator should be mounted at the 3 o'clock or 9 o'clock position relative to the pipe. For media temperatures above 300 F, a valve with an extended shaft mounting arrangement should be used. Actuator Mounting Verify that the output torque of the actuator is appropriate for the torque requirements of the valve. The Q6.0.1 actuator is furnished with a female drive output. 0.75" square. Two I.S.O. bolt patterns (ISO 5211) are provided for ease of actuator mounting. (fig. 2 ). It is mandatory that the actuator be firmly secured to a sturdy mounting bracket. A minimum of four bolts with lock-washers should be used to secure the actuator to the bracket. No flexibility in the bracket is allowed, and backlash, or "play", in the coupling should be minimized. The actuator output shaft must be in line (centered) with the valve shaft to avoid side-loading the shaft. Figure 2 on the following page provide dimensions for sizing and mounting purposes. PAGE 2

Figure 2 Actuator mounting Wiring: The identification label on each actuator specifies the voltage and current requirements for the actuator, and a wiring diagram is provided on the terminal board of each actuator. For convenience, Figure 3 shows the standard power and control wiring connections for the actuator. For clockwise (CW) and counter-clockwise (CCW) control, switch the power negative to terminal 5 for CW or to terminal 4 for CCW operation. Open and closed limit indication is provided at terminals 9 through 12 (A dry contact closure occurs between terminals 12 and 11 at the full CCW position. A dry contract closure between terminals 10 and 9 occurs at the full CW position.). If power is properly connected the power indicator light above terminal 1 and 2 will be on. Figure 3 Actuator wiring PAGE 3

TORQUE LIMIT The Q6.0.1 actuator has a linear response of current draw to torque output. At 600 inch pounds, the current draw is 1.3 amps. A current monitoring circuit disables the actuator motor if a preset current limit is exceeded. The torque-out level is factory set at 1.5 amp and should not need to be adjusted. There is a 2 sec delay in the torque circuit to allow the start up current of the motor to be ignored. If a torque out condition occurs a 12 volt positive signal appears at terminal 3. The actuator remains locked out until the control signal at terminal 4 or 5 is removed. The actuator's current draw can be measured while the actuator is running. Take a voltage measurement at test point A (see figure 5), current in amps corresponds to a reading in volts, i.e. 1 volt = 1 amp,.7 volts =.7 amps. MANUAL CONTROL Two push buttons operate the actuator CW/CCW for initial set up. The WHITE button drives the actuator CCW. The BLACK button drives the actuator CW. THE ACTUATOR IS DESIGNED FOR HAZARDOUS LOCATIONS AND MUST NOT BE OPERATED WITH THE COVER OFF OR WITH LESS THEN ALL EIGHT COVER BOLTS SECURELY FASTENED AFTER IT IS FIELD INSTALLED. SPEED CONTROL The motor speed can be set by adjusting the voltage supplied to the actuator motor. The Control range is from approximately 6 to 10 volts with corresponding speed of 60 to 20 sec. The motor volts should be measured at test point V (+ and -) with the actuator loaded by the valve's running torque. To change the motor speed adjust the control potentiometer labeled "Speed." The factory setting is 20 seconds. FEEDBACK POTENTIOMETER The Feedback Potentiometer is a 0 to 1000 ohm potentiometer to provide the status of the actuator's position. The feedback pot is connected to plug S4. Figure 3 shows the wiring for a Feedback Pot installed into connector S4. Manual Override NOTE: THE MANUAL OVERRIDE TURNS THE OPPOSITE DIRECTION AS THE OUTPUT DRIVE. TURN THE OVERRIDE CW TO DRIVE THE VALVE IN THE CCW DIRECTION. To use the manual override function, push the override shaft down to disengage the motor from the gear train. While holding the shaft down, turn the shaft with a wrench to obtain the desired position. Be careful not to drive the actuator past the limit switch settings; it is possible to damage installed options such as a feedback potentiometer. The manual override shaft must be returned to its fully upward position before operating the actuator. PAGE 4

Limit Switches Two limit switches operated by cams on the output shaft determine the exact positions where the actuator will stop at the end of each cycle. Limit switch #2 determines the full CW position. Limit switch #3 determines the full CCW position. Figure 4 Limit Switches and Cam Configuration PAGE 5

Adjustment of Limit Switches If adjustment of the clockwise or counter-clockwise position is required, proceed as follows: A. Remove Actuator Cover 1. Remove the actuator cover by removing the screws securing the cover to the base. B. Adjust the CW limit switch cam 1. Using the manual override, rotate the actuator until you can access the set screw on the lower cam from the side of the actuator opposite the limit switch wires. 2. Using a 1/16 inch hex wrench, loosen the set screw in the lower cam. 3. Using the manual override, rotate the actuator to the full CW position. 4. Rotate the cam clockwise toward the limit switch arm until you hear both limit switch #1 and #2 "click" closed. NOTE: The indication limit switch "clicks" closed one degree ahead of the motor switch. Make sure both switches click closed. 5. Re-tighten the set screw on the limit switch cam. C. Adjust the CCW limit switch cam 1. Using the manual override, rotate the actuator until you can access the set screw on the upper cam from the side of the actuator opposite the limit switch wires. 2. Using a 1/16 inch hex wrench, loosen the set screw in the upper cam. 3. Using the manual override, rotate the actuator to the full CCW position. 4. Rotate the cam counterclockwise toward the limit switch arm until both limit switch #3 and #4 "click" closed. NOTE: The indication limit switch "clicks" closed one degree ahead of the motor switch. Make sure both switches click closed. 5. Re-tighten the set screw on the limit switch cam. Troubleshooting If the actuator fails to operate: Check that proper voltages are present at the actuator's terminal connections. Check all the plug-in connections to be sure they are properly installed (see Figure 5). Motor to connector S3 Bottom limit switch to connector S5 Second limit switch to connector S2 Third limit switch to connector S1 Fourth limit switch to connect S6 If the actuator is stalling: Check that the limit switches are properly set. Check that the actuator has enough torque for the application. PAGE 6

Figure 5 Terminal Board VALVCON Corporation P.O. Box 901, Milford, NH 03055 TELEPHONE: (603) 249-9020 - FAX: (603) 249-9140 528 ROUTE 13 SOUTH, MILFORD, NH 03055 1997 VALVCON CORPORATION PAGE 7