DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

Similar documents
Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break

ABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount

Low voltage bushings for pad-mounted distribution transformers Technical information guide

Effective March 2015 Supersedes S August 2012

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

CSP Circuit Breaker Three Phase

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

A 1.2 kv class externally removable secondary bushing

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

RBA Catalog Numbers and Information

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

PROTECTION AND CONTROL

Product Specifications for Phase Over Phase GOABS(r)

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

Power Fuses. > Power Fuses > BPA & HPA kv AMPs

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

Type ICX Interchangeable Cutout kv Outdoor Distribution Cutout Product Bulletin 1VAG DB

GROUP D. Switch & Protective device.

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

S&C Manual PME Pad-Mounted Gear

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

Medium Voltage Metal-Enclosed Switches

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

3.5. Current Limiting Fuses. Contents. CLPT and NCLPT Type Fuses. CLPT and NCLPT Type Fuses

INSTRUCTION MANUAL #103

Type ICX Outdoor open type cutout

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Molded Current-Limiting Fuse

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

Pretest Module 29 High Voltage Unit 1

3.2. Current Limiting Fuses. Contents

Technical Specification For Outdoor Substation Harmonic Filter Banks

K-Limiter high ampere Companion II fuse

Figure 1. Two and Three-phase MagneX.

34-SDMS-01 SPECIFICATIONS FOR

25 kv Apparatus Bushings

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

3.6. Current Limiting Fuses. Contents. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

ZX-Family Gas-insulated medium voltage switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

C1000 Series Automatic Cap Bank

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

NH fuse-links am 690VAC top indicator/live tags size 4, 4a

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Boric Acid Fuse Links

Product Specifications for Aluminum Vertical Break Switches

Medium Voltage Metal-Enclosed Switches

Technical Specification for Pole Mounted Capacitor Rack

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

CMU medium voltage power fuses

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Publication No.: PSG

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

EE 741 Over-voltage and Overcurrent. Spring 2014

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

SPECIFICATION BULLETIN

Transcription:

DO-III DO-III Fuse Holder TPL 44-835, May 2000, Page 1 of 4 General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder ABB Inc.

General Description The ABB DO-III fuse holder is a draw out load break expulsion fuse holder designed for use with pad-mounted transformers filled with transformer oil or other approved fluid. It is designed to protect the distribution system in the event of an internal transformer fault, secondary fault, or severe overload when used with properly coordinated series fuses. Following industry safety practices, the DO-III fuse holder can be used to break load. BIL 60 Hz, 1 minute Withstand kv L-G Features & Advantages Ratings 150 kv 50 kv Interrupting Rating Applications Available Current Symmetrical (Amperes) 2.4 4,500 8.3 3,500 15.5 2,500 23.0 1,000 rms Load Make/Break Ratings at 80% Power Factor kv kv Current L-G L-L (Amperes) 5.8 10 160 8.9 15. 5 150 15.4 26. 7 80 19.9 34. 5 50 Maximum Transformer Wall Thickness 0.25 inches (6.4 mm) Ordering Information Complete Fuse Holder Assembly with Mounting Hardware 1 C10775G01 Vent Hole Only 1 C10775G02 Check Valve Only 1 C10775G03 Vent Hole & Check Valve Options with Silver Plated Contacts for High Current Applications 1 C10775G04 Vent Hole Only - Cartridge not included 1 C10775G06 Vent Hole Only 1 C10775G07 Check Valve Only 1 C10775G08 Asssembly Includes : Check Valve Only - Cartridge not included Spare Parts 1C10775G05 Mounting Nut & Gasket 1C10765G01 Puller Assembly, Fuse Cartridge & End Plug 1C10765G02 Puller Assembly Only 1B11142G01 Fuse Cartridge, & End Plug 3A33981H01 End Plug Only 1C10765G03 Puller Assembly, Silver Plated Fuse Cartridge, & End Plug 1B11120G02 End Plug & Silver Plated Cartridge Oil Containment The DO-III fuse holder s housing has been redesigned to improve safety and minimize environmental concerns. It features a vent hole located within the gas space of pad mounted transformers. This vent hole reduces the risk of oil spillage resulting from line personnel inadvertently removing the puller assembly without first venting the transformer. The redesigned housing also incorporates an optional check valve as another method to reduce the risk of injury or cleanup caused by excessive oil spillage. There are two methods for applying the check valve. First, it can be used in conjunction with the vent hole to limit the amount of spillage produced if the oil level rises above the vent hole. Secondly, the check valve can serve as the sole protection by sealing the vent hole. In this configuration the amount of oil released is dependent on the speed at which the puller assembly is withdrawn. As shown in Figure 1, the check valve actuates as the puller assembly is withdrawn and seals the transformer. Interchangeable The DO-III fuse holder is generally interchangeable with competitive designs. The housing, fuse cartridge, and puller are individually interchangeable with competitive counterparts. Tapered Flange The DO-III fuse holder s newly designed housing incorporates a 7 tapered flange. The tapered gasket seat holds the tank gasket in place during installation and retains the gasket in service. High Impact Strength Operating Handle The operating handle is constructed of a special impact resistant, glass reinforced polymer to prevent breakage during hot stick operations and accidental dropping on hard surfaces. Page 2 of 4

Figure 1: Fuse cartridge withdrawn closing check valve. Positive Latching Handle The handle is designed with sufficient clearance between the handle clamp and the lip of the outer tube in order to provide smoother operation and to ensure positive latching for greater safety. Hot Oil Resistant Housing The DO-III fuse holder s outer tube is constructed of a high temperature, high dielectric strength, arc resistant, glass reinforced, polyester material. This material has proven itself over many years of use in these types of distribution transformer applications. Large Contact Surface The DO-III fuse holder has a large contact surface area to minimize heating of the contacts and provide positive contact alignment. Installation The DO-III fuse holder is inserted through the transformer tank wall as shown in 44-885 page 11. The mounting nut should be tightened between 100 and 120 in-lbs (11.3 to 13.6 N-m). The assembly must be used in series with a current limiting fuse or isolation link (not supplied by ABB). Connect the high voltage bushing lead to either the isolation link or the current limiting fuse, and attach the link or fuse to the lower contact in accordance with supplier s recommendations. Next, connect the transformer s primary winding to the upper contact. Refer to Figure 2 for illustration of proper connections. Remove puller assembly and install fuse element in accordance with supplier s recommendations. Design Tests The ABB Type DO-III fuse holder successfully passed a battery of tests (See TD 44-815 Rev 2 for test details) including: Dielectric tests Load switching tests Fault interruption tests Mechanical strength tests Seal integrity tests Contact temperature rise tests Production Tests In addition to the design testing, the following routine production tests are done on an audit basis to ensure compliance to requirements: Dimension check on critical dimensions. Insertion force test to verify contact pressure. Visual inspection to verify molding and assembly process. Page 3 of 4

Figure 2: Illustration of DO-III fuse holder connections ABB Inc. Power Technology Products Division USA 1128 Highway 412 S. Alamo, TN 38001-3813 U.S.A. (800) 955-8399 (901) 696-5561 (901) 696-5269 Fax TPL 44-835 May 2000 Page 4 of 4