Grounding Of Standby & Emergency Power Systems

Similar documents
DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Technical information No. 01. IT systems. The basis for reliable power supply

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Design considerations for generator set mounted paralleling breakers

Grounding Systems. Resistance. Resistance Grounding Systems Contents

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

EE 741 Over-voltage and Overcurrent. Spring 2014

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

SDC,Inc. SCR-Regenerative Ac Drive

Switchgear and Distribution Systems for Engineers and Technicians

The Case for Hybrid Generator Grounding

Chapter 6 Generator-Voltage System

ECET Distribution System Protection. Overcurrent Protection

TRANSMISSION SYSTEMS

Modular Standardized Electrical and Control Solutions for Fast Track Projects

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series

Service Entrance Methods

Arc-Flash Mitigation Technologies. Dennis Balickie

Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Selective Coordination

TERMS AND DEFINITIONS

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Electromagnetic Industries LLP

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

Recommended Procedures

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

400/230 Volt 60Hz UPS Power

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Overcurrent Protection (2014 NEC) (Homestudy)

UPPCO SERVICE MANUAL

How Protection Relays Solve Electrical Problems

Zone Selective Interlocking

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

Unified requirements for systems with voltages above 1 kv up to 15 kv

Net Metering Interconnection Requirements

Design Standards NEMA

3.2. Current Limiting Fuses. Contents

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Engineering Dependable Protection

Three days training program (Oct 5-7) on. Substation Earthing, Industrial earthing and Neutral earthing. at IEI Mysore, Karnataka India

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

www. ElectricalPartManuals. com Engineering Dependable Protection

mgard-10 microprocessor-based relay

CHAPTER 3. Basic Considerations and Distribution System Layout

ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace

ELECTRICAL POWER and POWER ELECTRONICS

FACT SHEET Standard: Electrical Safety

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

Fuses still the best form of overload protection

UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

AIR COOLED RECTIFIER SPECIFICATION S-50-A

Dual Power. Protection. Protection

Electric Motor Controls BOMA Pre-Quiz

Safe, fast HV circuit breaker testing with DualGround technology

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

GP/GPA GROUND FAULT PROTECTION

Standby Power Systems

The Evolution of Arc Fault Circuit Interruption

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

Air Circuit Breaker Retrofitting

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

Renewable Energy Systems 14

INSTRUCTION BOOK SYSTEM 2001 GROUNDING EQUIPMENT FOR FAULT LOCATION. W/ High Resistance Neutral Grounding. for use on

Guidelines for connection of generators:

Overcurrent Protection According to the 2011 NEC

Transformer Protection

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

DESIGN AND RETROFITTING OF LOW VOLTAGE AIR CIRCUIT BREAKERS.

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Electrical Safety. Introduction

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Review paper on Fault analysis and its Limiting Techniques.

Pretest Module 29 High Voltage Unit 1

Advanced Protective Relay Training

Sources, Effect, and melioration. Power Quality Problems. Asnil Elektro FT UNP

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

A. Submit manufacturer's literature and technical data before starting work.

Application Note CTAN #127

Transcription:

July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due to ground fault can have serious economic or operational consequences. An arcing phase to ground fault can pose a flash hazard to the maintenance worker close to the fault and can totally destroy the equipment. Consequential down time adds to the economic loss. Four typical grounding methods for standby generators and emergency power systems are examined for these factors and the paper concludes that high resistance grounding provides the best power continuity, the best protection against arcing ground fault damage in low voltage distribution systems (up to 1000V) and improves reliability and availability of standby and emergency power systems Standby and emergency systems are often configured to provide 600 V or 480 V, 3-phase 4-wire service and are thus solidly grounded. In solidly grounded systems the ground fault currents are very high and damaging and circuit protective devices have to operate to isolate the faulty circuit and interrupt the supply. This even applies to the emergency or standby system such as a fire pump where the faulted circuit is tripped and the system de-energized, with potentially disastrous consequences if there were no power during an emergency. Benefits Of Proper System Grounding System grounding the intentional connection of the neutral points of transformers, generators and rotating machinery to the earth ground network provides a reference point of zero volts, which offers many advantages over an ungrounded system, including: Reduced magnitude of transient over-voltages Simplified ground fault location Improved system and equipment fault protection Reduced maintenance time and expense Greater safety for personnel Improved lightning protection Reduction in frequency of faults. Solidly Neutral Grounded Systems Offer Partial Protection In a solidly grounded system, the neutral points have been intentionally connected to ground with a conductor having no intentional impedance. This reduces the problem of transient over-voltages found on the ungrounded system and speeds the location of faults. However, solidly grounded systems lack the current-limiting ability of resistance grounding and the extra protection this provides against equipment damage and arcing ground faults. The well-documented destructive nature of arcing ground faults in solidly grounded systems is caused by the energy dissipated in the fault. The faulted circuits need to be tripped and with conventional time-current coordination often it is difficult to selectively trip the circuit with minimum time delay resulting in extensive equipment damage. Advantages Of Resistance Grounded Neutral Systems Resistance grounding is by far the most effective and preferred method. It solves the problem of transient over-voltages and reduces equipment damage. It accomplishes this by allowing the magnitude of the fault current to be predetermined and limited by a simple Ohms law calculation: I = E/R Where: I = Limit of fault current. E = Line-to-neutral voltage of system R = Ohmic value of neutral grounding resistor In addition, limiting fault currents to predetermined maximum values permits the designer to selectively co-ordinate the operation of protective devices that minimizes system disruption and allows quick location of the fault. High resistance grounding can be applied on distribution systems up to 5KV with low resistance grounding recommended at voltages between 15 and 36KV. Utility systems

54 ELECTRICAL LINE July / August 2007 are usually solidly grounded, but on the secondary side of the supply transformer on the customer premises the grounding system is independent and full advantage can be taken of the benefits provided by high resistance grounding. High-resistance grounding of the neutral limits the ground fault current to a very low level (typically under 25 amps). It is used on low-voltage systems of 600 volts or less, under 3000 amps. By limiting the ground fault current, the fault can be tolerated on the system until it can be located, and then isolated or removed at a convenient time. This permits continued production, provided a second ground fault does not occur. High-resistance neutral grounding can be added to existing ungrounded systems without the expense of adding fault clearing relays and breakers. This provides an economical method of upgrading older, ungrounded systems. The resistor must be sized to ensure that the ground fault current is greater than the system s total capacitance-to-ground charging current. If not, then transient over-voltages can occur. By strategic use and location of ground fault sensing relays, troubleshooting can be greatly simplified. High-resistance neutral grounding combined with sensitive ground fault relays and isolating devices, can quickly detect and shut down the faulted circuit. This provides operating personnel with the added safety that s essential in today s operating environments. Another major advantage is the elimination of dangerous and destructive flashovers to ground, which can occur on solidly grounded systems. Grounding Of Standby Generators In 3-Phase 4-Wire Systems In most large commercial buildings and industrial installations, generators are used for standby power or for emergency. So when the distribution includes a distributed neutral then by the electrical Code it must be solidly grounded. There are three ways in which this can be integrated: 1. Each generator neutral is independently grounded and the neutrals are connected together with the normal source neutral that is also grounded and then distributed. 2. Generator neutrals are connected and grounded at one location. Normal supply neutral is also grounded and the common neutral is distributed 3. The generator common neutral is connected to the normal supply neutral and is grounded only at one location. In all of the above the ground fault current has multiple paths through the ground and the neutral conductor to return to the source. Sensing ground fault current becomes very difficult and may cause nuisance tripping, or ground faults may not be sensed at all. Automatic Transfer Switches Automatic transfer switches are used to supply the emergency load. Four wire system necessitates the use of four pole devices with or without an overlapping neutral. The ground fault protection and coordination becomes difficult and complex. Changing the distribution to three wires overcomes this. The Power of ONE Minutes ago, this city lost power. We didn t notice. Finning Power Systems Your ONE Call For: Generator Sets Switchgear Caterpillar Flywheel UPS Preventative Maintenance 1-888-finning finning.ca Circle 38 on Reader Service Card

ASCO: your partner in power. the expertise to meet all your power challenges: issues like high summer demand for electricity and risks to the environment. By using high-technology R EMIS ASCO recently put a solution like this to work for Toronto Hydro, to meet consumersõ needs during summer afternoons when electricity demand and costs are at their peak. By fueling an ASCO power switch with used cooking il T t H d h t ti f and a switch that could work for you, too. Network Power Circle 39 on Reader Service Card

56 ELECTRICAL LINE July / August 2007 Connecting standby or emergency supply in a 3 phase 3-wire systems only requires 3 pole transfer switches, whereas four-wire distribution systems with the sources independently grounded require four pole transfer switches. In multiple source distribution schemes where single grounding location of the neutral is used, the application of ground fault protection becomes very complex and very expensive. False tripping can occur if circulating load neutral currents and the returning ground fault current are not properly sensed. Solidly Grounded Systems To High Resistance Grounding In most large commercial and industrial distribution systems at 600V the single-phase 347V load is very limited (mostly the high voltage lighting). The load is essentially 3 phase motors and transformers and therefore conversion of 3 phase 4 wire to 3 phase 3 wire is entirely practical and feasible. If the neutral is not distributed it can be impedance grounded. Only 3 pole transfer switches are used. Small lighting transformers are used for the 347/600 V or 120/208 V distribution to service single phase loads. Figure 1 shows a typical arrangement. The generator bus is grounded through an artificial neutral and the normal supply transformer neutral is grounded through high resistance. A 3-pole automatic transfer switch feeds the essential load. Only alarm and indication of ground fault is required and no tripping occurs in the main and standby switchboards. Fire pumps are usually 3 wire loads and conversion to 3-wire distribution becomes an easy retrofit for existing installations. This concept is being retrofitted in a high-rise office tower in downtown Toronto. The two 1750KVA generators will be converted to high resistance grounding. A ground alarm relay will alarm to the building management system on the occurrence of a ground fault The maintenance electrician will then be able to find the faulty circuit by tracing a pulsing ground current using a hand held multimeter while the system remains energized and working. The rest of the supply distribution will remain unaffected and is 3-phase 4- wire solidly grounded. Summary Ungrounded delta systems have many operating disadvantages including high transient over-voltages and difficulty in locating faults. Solidly grounded neutral systems provide greater safety for personnel, limit the system potential to ground, and speed the detection and location of the ground fault. However, the system must be shut down after the first ground fault. Applying coordinated ground fault protection is very difficult and almost impossible with multiple sources and standby generators. Low-resistance grounded neutral Standby Generator Figure 1 Essential Load 3Φ / 3W ATS systems only limit the magnitude of the ground fault current so that serious damage does not occur. The system must still be shut down after the first ground fault. This level of resistance grounding is generally used on medium and high-voltage systems. If the power system is changed to resistance grounding then the ground fault current can be reduced to 10A or less which has significant impact on reducing the fire risk and equipment damage. In addition it ensures that standby power and emergency power systems continue to operate and do not suffer tripout of a faulted feeder. Andrew Cochran is President of I-Gard Corporation in Mississauga, Ontario. Circle 40 on Reader Service Card R 3Φ / 3W 4 Wire Loads Normal Load Motor, Drive & Control Power Quality Power Distribution Power Quality Diagnosis Engineering Installation Beaver provides a complete package of for many types of Power Quality problems. Power Factor Correction Harmonic Filtering Surge Suppression UPS Systems Power Quality Monitoring Systems Now stocking GE UPS Systems Beaver Electrical Machinery Ltd. Burnaby T. (604) 431-5000 F. (604) 431-5066 Prince George (Field) T. (250) 563-1443 F. (250) 563-1215 Prince George (Shop) T. (250) 563-9256 F. (250) 563-6585 Nanoose Bay T. (250) 468-9796 F. (250) 468-9794 Campbell River T. (250) 286-1128 F. (250) 286-1728 24HR SERVICE Circle 41 on Reader Service Card