Page : 1 / 2 OIL INDIA LIMITED (A Govt. Of India Enterprise) Tel :033 2230 1657, 1658 4, India Exchange Place, Fax :91 33 2230 2596 Kolkata-700001 E-mail :oilcalmn@cal2.vsnl.net.in ANNEXURE-I Item No./ Mat. Code 10 0C000404 Tender No. Tender Date : KID4915P08/07 : 16.04.2007 Material Description Quantity UOM Supply, erection, testing and commissioning of Electrical Panel for capacitor banks for power factor improvement. Technical details of the panel are given in Enclosure - 1. 2 NO Special Notes : (A) General Notes : (i)bidder should have experience of design, fabrication and supplying of Minimum 10 Nos. of similar type of panel. Bidder should furnish the experience and performance certificates from user Industries along with the offer for evaluation of the offer. (ii) Panel shall be procured either from manufacturer or authorized dealer and duly approved dealer ship certificate should be furnished along with offer failing which offer shall be liable for rejection. (iii) Bidder should furnish the details of drawing, catalogue of capacitor, Thyristor, Automatic power factor controller, single line diagram, circuit diagram, GA drawing of the panel for evaluation of the offer of panel. Incomplete offer of the panel shall be liable for rejection. (iv)bidder should quote separately for supply of panel and Erection, testing and commissioning. (v) Bidder shall furnish the list of minimum spare parts required for maintenance of the panel along with the offer. (vi)panel shall be inspected and tested by OIL's Engineer at the premises of supplier before dispatch. (vii) Panel shall be installed and commissioned within 6-8 months from the date of receipt of the order or at the time of annual overhauling of LPG Recovery Plant. (viii) Panel shall be erected by supplier at OIL, Duliajan, Assam at the time of shutdown of the plant during annual maintenance of the plant in the month of October 2007. (ix)the expert Engineer from manufacturer is required for commissioning of the panel at the site. (x) All the tools and tackles required for commissioning of the panel are to be supplied by the supplier. (xi) Panel shall be guaranteed for 18 months from the date of supply or 12 months from the date of commissioning, whichever is earlier and Guarantee Certificate shall be furnished along with supply of materials. (B) Technical Notes : (i) Control circuit wiring shall be done by 2.5 sq.mm single core PVC insulated, sheathed, stranded copper conductor wire of 1.1 KV grade
Page : 2 / 2 ANNEXURE-I Tender No. Tender Date : KID4915P08/07 : 16.04.2007 (ii)2 Nos. of Earth studs shall be provided on both side of the panel for earthing of the panel and 2 Nos. also inside of the panel. (iii) Bottom plate of the panel shall be detachable type for making of suitable hole for cable glanding. Suitable size of brought out terminal shall be provided for incoming and outgoing cable connection. (iv)silicon insulated wire of suitable size shall be used for bus bar connection to the MCCB/ outgoing terminals. (v)control circuit HRC fuses with base shall be provided for indication lamp and voltmeter, ammeter etc. wherever it is required. (vi) Panel shall be painted with powder coated of grey color with thickness of minimum 70 micron after applying of 2 coats of primer. (vii)capacitor unit shall comply with IEEE STD 18-2002 and IEEE STD 1036-1992 ( equivalent to IS: 13340/1998, IEC:60831). (viii) Capacitor unit shall be approved by NABL agency Like CPRI/ERDA and tested or at internationally accredited testing laboratory like KEMA or UL. (ix)applicable standard IS-13410, 13411 for enclosure's cover in case of sheet moulding compound (SMC) use. (x) Thyristor should be turned on when the voltage across is less than 6 volts. Triggering circuit should be immune to EMI and it should not operate due to multiple zero crossing of the input voltage wave from f any. (xi) Panel shall be designed for automatic improvement of the power factor from 0.8 PF to unity power factor with 350 amps load or more at 404V, 50HZ supplied by 1000KVA Transformer of 11KV/400V. The load consists of 80nos. LT motors from 5HP to 150HP and lighting load and also 10KVA and 120KVA UPS for supplying to power for PILC and DCS system.
Enclosure -1 Supply, Erection, Testing and Commissioning of Thyristorized Switched Capacitor (TCS) panel with Detuned Series Reactor Technical specifications of capacitor panel are as follows: Thyristorized Zero Crossing Switched Capacitor (TSC) system with Detuned Series Reactor panel is to be designed, fabricated out of 2.5mm CRCA sheets modular compartmentalized, free standing, floor mounting, front doors hinged for indoor use, removable bottom gland plates for incoming cables, dust and vermin proof with TPN Aluminium bus bars of suitable rating with internal wiring, ferrules, name plates, painting etc. It consists of the following: S.No. Particulars Specifications TSC Panel / Auto detuned harmonic filter (capacitor) panel 1 Rating of TSC panel - 200KVAR(Approximately) 2 Rated voltage of the panel - 415±10%(3Phase 4 wire system) 3 Frequency-50± 5% 4 No. of phases-3 5 Series Reactor- 7% 6 Operating temperature - 4 to 50 0 C 7 Maximum Temperature rise over ambient- 20 0 C 8 Relative Humidity-90% 9 No. of switching steps- 5No.s 10 Configuration - 10+20+20+50++100 =200KVAR 11 Insulation strength - 2.5KV 12 Automatic power factor controller -6 Stage THD measurements with supply voltage, current and capacitor current. TSC must have following features: (i)should not be on Zero crossover switching but it should be zero differential voltage technique only. (ii) Should have voltage spike protection features. (iii)should have spike current protection. (iv) Controlling through high speed processor,self monitoring and built in with diagnosis tools.
(v)various possibilities for bank selection,including user defined bank values in KVAR. (vi) Protection against Over / under voltage Over/ under capacitor Amp/ THD Over/ under Frequency (vii)compensation on fundamental waveform KVAR calculations with effects of supply frequency and voltage (viii) Operating voltage for 415V line to line config: 250V to 500V (ix) Measurement Accuracy: Class-1 (x) Operating temperature 0 to 55 0C (xi) Storage temperature -10 to +75 0C (xii) Display of electrical parameters like voltage, current, frequency, THD (current & voltage), KW, KVAR, KVA, PF (Lead/Lag) temperature, No. of steps switching, various faults etc. (xiii)capable of giving correction every cycle of mains wave form. (xiv)capable of showing harmonics (xv) Corrected PF is to be maintained in between 0.8 to 0.99 and if actual requirement is within range, Make- ABB/ BELUK/Nokian or similar type 13 Auto / Manual operation Auto / manual operation facility is to be provided through controller. 14 Capacitor & Reactor (i) Capacitors - MPP dry type, heavy duty capacitor with internal Fuse in each element only Make- ABB / FRAKO/ GE Power/Nokian (ii) capacitor voltage -525V (iii)series Reactor - 7 % Detuned Make- Reputed 15 Enclosure details (i) Materials - CRCA (ii) Thickness of sheet steel- Frame- 2.5mm, doors -2mm Partitions -2.00mm (iii)dimensions - Height -1.8 mts, depth -1.0, Length- 1.5mtrs (iv) Protection class - IP-42 (v) Application- Indoor (vi) Cable entry- Bottom (vii)type of cooling- Forced Air (viii)cable Termination to be done by party (ix) Name plate- Anodized AL engraved for each stage, indications at proper locations. (x) Painting - Siemens Gray, powder coated (RAL7032) Bus bar & insulators details: S.No. Particulars Specifications 1 Main bus bar materials- Copper 2 Main bus cross section- 30x10mm Cu 3 Earthing bus -25x6mm Cu 4 Bus bar support- SMC/DMC
Switchgear details: S. No. Particulars Specifications 1 Incoming MCCB - 400Amps with Electronics Thermal and short circuit protection with earth modules Make -Merlin Gerin/ABB/ MDS Legrand/ Siemens 2 Digital voltmeter with selector switch, size 96x96mm - 1No., Make- Conzev/ AEI 3 Suitable Current transformer with Digital ammeter with selector switch, size 96x96mm - 1set, Make Conzerv/ AEI 4 R,Y, B,ON,OFF, TRIP Indication LED lamp with name plate- 6Nos.,Make- Technic/Siemens/ABB 5 Over voltage and under voltage protection relay with timer - Should be built in controller 6 Out going Feeders - MCCB of the following ratings, Make- Merlin Gerin /ABB LTD/ MDS Legrand/ Siemens 32Amps-10KVAR, 63Amps-20KVAR, 125Amps-50KVAR, 250Amps-100KVAR with Electronics Thermal and short circuit and earth fault protection of 50KA 7 Thyristor - Semikron/ Mitsubishi/IRF/EUPEC/Paragon 8 Protection for Thyristor - Spike current protection, over current protection, short circuit monitoring, over temperature cutoff 9 Reset for Thyristor protection/ contactor - Auto start after normalizing the fault for spike, over current and over temperature faults 10 Controller / Firing card for Thyristor - As required with reputed make