Vol-Con XL (61-086) Voltage/Continuity Tester and Vol-Test (61-085) Voltage Tester Instruction Manual WARNING

Similar documents
MY /2-DIGIT DIGITAL MULTIMETER Users Manual

Users Manual. Accessories Motor and Phase Rotation Indicator ships with the following items: 3 test leads 3 test probes 3 alligator clips 9 V battery

MM300. INSTRUCTION MANUAL Manual-Ranging Digital Multimeter

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS

Mini Multimeter with Non-Contact Voltage Detector (NCV)

Digital Multimeter User's Manual

5.2 PRE-OPERATION PROCEDURE WARRANTY

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

365 Detachable Jaw True-rms Clamp Meter

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Instruction Manual. Model 2831D 4 ½ Digit True RMS Digital Multimeter

362 Clamp Meter. Users Manual

Mini Multimeter with Non-Contact Voltage Detector (NCV)

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER

Table of Contents Title Page No.

Users Manual. Phase Rotation Indicator

Instruction Manual. Model 307A Analog Insulation & Continuity Meter

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

DIGITAL RCD(ELCB) TESTER

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

Safety design conforming to the following provisions

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

True RMS Autoranging Multimeter

373 Clamp Meter. Users Manual

Digital/Analog Megohmmeter Model 1026 USER MANUAL

1.Safe testing IMPORTANT:

Autoranging Industrial Multimeter

Autoranging Multimeter

USER MANUAL. 200A AC Mini Clamp Meter. Model MA130. Please visit for user manual translations

Phase Sequence Tester

302+/303 Clamp Meter. Users Manual

User Guide. Model Insulation Tester / Megohmmeter. Introduction

R&S RT-ZC02 R&S RT-ZC03 AC/DC Current Probe User Manual

OPERATING INSTRUCTION

Calibrator Capabilities Function Range Resolution Measure V dc 28 V 1 mv Measure ma dc Source ma dc

User Guide. Model Insulation Tester / Megohmmeter

Dawson DAN100. Analog Multimeter User s Manual

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

323/324/325 Clamp Meter

Digital/Analog Megohmmeter Model 1026

T2 Tester. Calibration Information. Introduction. Safety Information

362 Clamp Meter. Users Manual

User Guide. Model Insulation Tester / Megohmmeter

i400s Calibration Information Introduction

PRM-2 PHASE SEQUENCE TESTER PRM-3 PHASE SEQUENCE & MOTOR ROTATION TESTER User s Manual

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

Calibration Manual. Detachable Jaw True-rms Clamp Meter

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

Dawson DDM190D. Digital Multimeter User s Manual

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

707Ex. Users Manual. ma Calibrator

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

A.W. SPERRY INSTRUMENTS INC.

INSTRUCTION MANUAL CM69 TRMS AC EARTH LEAKAGE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

ASTROAI USER MANUAL DIGITAL MULTIMETER. NOTE: Fully read and understand this manual before using this instrument.

PY-11 Voltage & Continuity Tester

Users Manual. MegOhmMeter

TIC 300 PRO. Users Manual Mode d emploi Bedienungshandbuch Manual d uso Manual de uso. Non Contact AC Voltage Detector. High Energy Tic Tracer

OPERATING INSTRUCTION

INSP-3 Wiring Inspection Tester

OPERATING INSTRUCTIONS

Item ref: UK & UK MTB01 & MTB02 DIGITAL MULTITESTERS. User Manual

Model Insulation Tester / Megohmmeter. User Manual

BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet

Safety design conforming to the following provisions

POWERED BY KT71 / Portable Appliance Tester. Instruction Manual

INSTRUCTION MANUAL DM5B Fax: (503)

Manual Supplement. For IEC V, CAT I & 600, CAT II Meters only. Serial NO and greater.

IDEAL INDUSTRIES INC. TECHNICAL MANUAL - SUPPLEMENT MODEL

3 PHASE TESTER & MOTOR ROTATION TESTER

PD-20 HIGH VOLTAGE PROBE INSTRUCTION MANUAL

Instruction manual. High voltage insulation resistance tester KEW3121B/3122B

TES-1601 INSTRUCTION MANUAL AUTORANGING INSULATION TESTER SAFETY INFORMATION TES ELECTRICAL ELECTRONIC CORP. Warnings and Safety symbols:

USER MANUAL. Insulation Tester + DMM. Model MG320

Switching DC Power Supply

Visit us at

Rental Industry Safety Tester Safe Check 5s

SLA Battery Capacity Analyzer

OPERATING INSTRUCTION

Instruction Manual IVT-10 / IVT-20 Voltage Tester

51 & 52 Series II. Users Manual. Thermometer. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual

Model ST Instruction Manual. Digital Insulation Tester. reedinstruments. www. com

41210S CIRCUIT BREAKER FINDER WITH GFCI Instrucciones de uso Detector de Interruptores con GFCI 41210S. Operating Instructions

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

HOME CHARGER MODE 2. Series to /32A single phase CONTENTS. Manual IMPORTANT SAFETY INSTRUCTIONS 3 SAFETY INFORMATION 4 INSTALLATION 5

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA.

AMB V Insulation Resistance Tester. Users Manual. For detailed specifications and ordering info go to

KMP7010. Ground Resistance Tester. Users Manual

1 INTRODUCTION SPECIFICATIONS Electrical Data General Data... 3

80 Series V Digital Multimeter Safety Information

MODEL No: TA SAFETY INSTRUCTIONS 2. FEATURES. fig.1. Original Language Version

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com INSTRUCTION MANUAL PSMR1

PL900 ILLUMINATOR. Fiber-Lite. Operation Manual. Setup. Fiber Optic Connection A PRODUCT OF DOLAN-JENNER INDUSTRIES. Voltage Selection:

Transcription:

Vol-Con XL (61-086) Voltage/Continuity Tester and Vol-Test (61-085) Voltage Tester Instruction Manual WARNING #61-085 #61-086 Read First: Safety Information This tester complies with UL3111-1, Cat III-600 overvoltage protection, Pollution Degree 2. Use the tester only as specified in this manual; otherwise, the protection provided by the tester may be impaired. In this manual, a Warning identifies conditions and actions that pose hazards to the user. A Caution identifies conditions and actions that may damage the meter or the equipment under test. Warning To avoid possible electric shock or personal injury, follow these guidelines: Do not use tester if it is damaged. Visually inspect tester to ensure case is not cracked and battery cap is in place. Inspect and replace leads if insulation is damaged, metal is exposed, or probes are cracked. Pay particular attention to the insulation surrounding the connectors. Do not use tester if it operates abnormally as protection maybe impaired. Do not use during electrical storms or in wet weather. Do not use around explosive gas, dust, or vapor. Do not apply more than the rated voltage to the tester. Voltage is not to exceed 600V. Always operate this solenoid-type tester within the specified duty cycle on the front of the tester. Duty cycle ratio is: 1:15 ON:OFF time. Maximum ON time is 15 seconds. Do not use without batteries and cap properly installed. Remove test leads prior to removing battery cap. Caution To protect yourself, think "Safety First": Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution. Never ground yourself when taking electrical measurements. Use appropriate personal protective equipment such as safety glasses, face shields, insulating gloves, insulating boots, and/or insulating mats. Use the 3-Step Testing Method. Before each use: Perform a continuity test by touching the probe tips together, an audible sound should be heard and the continuity LED should light. This test verifies the functionality of the batteries and test leads (61-086 only).

Verify tester operation by measuring a known voltage. Apply tester to circuit under test. And, then test on the known live voltage again to ensure proper operation. Connect the black common lead to ground before applying the red test lead to voltage. Disconnect the red test lead from the voltage first. Always work with a partner. When using the probes, keep fingers as far behind the probe tips as possible. Features: Vibration Mode w/indicator movement Audible and LED Indication of Voltage Levels (61-085 has LED indication only). Auto-Switching Voltage/Continuity Technology (61-086 only) Independent solenoid and electronic circuitry design provides back-up voltage indication for added safety. Low Impedance Measuring Device Replaceable Test Leads Shielded probe tips Ultrasonically welded and o-ring sealed for added durability Accessories: TL-82 Resistor-fused test leads C-90 Soft-sided carrying case load or circuit. The tester indicates both the voltage type and the voltage level. (See Tester Operation table) To Measure DC Voltage: Connect the tester in parallel with the load or circuit. The tester indicates the voltage type, polarity, and the voltage level. (See Tester Operation table) To Test for Continuity: (61-086 only) De-Energize circuit before performing continuity test. Note, if voltage is present in the circuit, the tester automatically switches to voltage indication mode. Test for continuity by connecting the tester to the circuit. If circuit has 500kΩ or less resistance, an audible indication is heard and the Continuity LED lights. (See Tester Operation table) Reversing prods on the circuit under test verifies continuity versus low voltage +DC. To Measure AC Voltage: Connect the tester in parallel with the

Neon Bulb Indicator Applications: Locating Blown Fuses With power off: Place tester across the suspected fuse to perform continuity check. If continuity LED turns On, the fuse is good. If the continuity LED does not turn On, the fuse is defective. (61-086 only) Left LED Right LED 61-086 61-086 only LED Right Neon Bulb Left LED Indicator Continuity Off On Off No movement. Open Circuit No Voltage Off Off Off No movement. 6-65 AC Off On On No movement. 6-90 DC Off On if black On if red No movement. prod is prod is on negative, on negative, 65-110 AC On On On Little or no movement. 90-110 DC On On if black On if red Little or no prod is prod is movement. on negative, on negative 110-600 AC On On On Scale indicates relative magnitude. 110-600 DC On On if black On if red Scale indicates prod is prod is relative voltage. on negative, on negative, With power on: Place tester across the source side of one fuse and the load side of an adjoining fuse. If no voltage is indicated, the fuse next to the load side prod is blown. If voltage is indicated, the fuse next to the load side prod is OK. Repeat the same test with the prods on the opposite side of the same two fuses to check the other fuse. On a three phase circuit, repeat the same test as above. An indication of no voltage or lower than normal line voltage indicates the blown fuse. Finding Grounded Side of Line (neutral) Hold one test prod to the ground and touch the other test prod to each of the line terminals until one is found that does not give a voltage indication. The continuity LED should be On. This is the grounded side of the line. Tester Operation Table

Testing for Grounded Side of Motor or Appliance With power to motor or appliance Off, touch one test prod to the frame and the other prod to each of the terminal connections. The terminal which turns the continuity LED On is the grounded side. With power to motor or appliance On, place tester across the frame and to each of the terminal connections. The terminal which does not give a voltage indication, but does give a continuity indication, is the grounded side. Testing for 25 to 60 Cycle Frequency Place tester between each side of AC line. A low frequency hum and slow vibrations indicate 25 cycle current. 60 cycle current is indicated by a higher frequency hum and more rapid vibrations. Checking Continuity of Cords, Motors, Appliances, etc. (61-086 only) Remove power source and place tester across circuit to be tested. Continuity LED turns On and an audible beep is heard if resistance is less than 500K ohms. Locating Excessive Leakage to Ground Place tester across the neutral terminal and the ground, only the continuity light should turn On, indicating neutral and ground are connected. If the DC light also turns On, there is 6VAC or greater between neutral and ground indicating a high resistance leakage to ground. High resistance leakage is qualified since a low resistance (high current) leak to ground would open a circuit breaker or blow a fuse. Battery Replacement: (61-086 only) Replace batteries when touching the leads together no longer lights the continuity LED or produces an audible sound. Remove test leads from tester. Loosen the encapsulated screw from the bottom of the case. Remove battery cap. Replace the batteries with (4) new 1.5V button-type batteries (IDEAL# 61-201, IEC #LR44, or NEOA# 1166A). Replace battery cap and re-tighten the encapsulated screw. Test Lead Replacement: Replace leads only with IDEAL test leads below. # TL-80 Standard Test Leads with Shielded Probe Tips # TL-82 Resistor-fused Test Leads with Shielded Probe Tips. Each probe tip contains a special, currentlimiting resistor which acts like a fuse to limit short-circuit current and pre-

vents dangerous arcing during a shorted condition. The resistors are rated to 140Ω +/- 10%. Fusing current is 1A at 125V. Fusing time is 30-60ms at 125V, without causing dangerous conditions during opening of the fuse element. Leads need to be replaced when fuse has opened. Note that TL-80 and TL-82 test leads can only be specifically used with the 61-085 and 61-086 testers. Maintenance: Clean the case with a damp cloth and mild detergent. Do not use abrasives or solvents. Service, and Replacement Parts: For replacement parts or to inquire about service information contact IDEAL INDUSTRIES, INC. Attn: Repair Dept. 1000 Park Avenue Sycamore, IL 60178 Technical Support: 1-877-901-2005 or visit our website www.testersandmeters.com. Specifications: VAC Ranges: 120V, 240V, 480V, 600V AC. VAC Accuracy: Relative indication only VDC Ranges: 120V, 240V, 600V DC VDC Accuracy: Relative indication only Continuity (61-086 only): Continuous LED and audible indication at less than 500kΩ resistance. Response time of 100ms. Operating Frequency: 25-60 Hz Input Impedance: Low Operating Environment: 32 F to 122 F (<70% humidity) Storage Temp.: -4 F to 140 F (<80% humidity) Altitude: 2000m Indoor Use Battery: (4) 1.5V (IDEAL# 61-201, IEC #LR44, or NEOA# 1166A). Battery Life: 200 hours typical. Accessories included: Test Leads, (4) 1.5V "LR44" batteries, operating instructions Dimensions: 6.0" (H), 2.3" (W), 1.2" (D) Weight: 8.0 oz Safety: EN61010, CAT III 600V, CE, UL, (3111) cul Double Insulation Warranty Statement: This tester is warranted to the original purchaser against defects in material and workmanship for five years after purchase. During this warranty period, IDEAL INDUS- TRIES, INC. will, at it s option, replace or repair the defective unit, subject to verification of the defect or malfunction.