DRAFT. Technical Data OPA Ducted Three Phase Packaged Air Conditioners. 47 kw 96 kw

Similar documents
Air Cooled Packaged Units

Ducted Split System Air Conditioners

ISDL SERIES DUCTED SPLIT SYSTEM AIR CONDITIONERS

Air Cooled Packaged Units Technical Data

Ducted Split System Air Conditioners

EC Motor MultiZone Fan Coil Units. IXDL-Y Series l/s

OUTDOOR UNIT CONTROLLER (OUC)

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE.

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C

(click on page links below) XAL-2C Technical Data 1. XAL-4C Technical Data 3

SPLIT DUCTED UNIT SCA300C / SCA300E TECHNICAL SELECTION DATA SPECIFICATION SUMMARY UNIT FEATURES CONTROL OPTIONS UNIT COMPLIANCE

D M S 760 C01 A A 1 1

Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW

Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW

Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW

TRI-CAPACITY PACKAGE UNIT

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS

Landmark Rooftop Packaged Units

ROOF TOP (SERIES SR) 10.8 TO 103 KW 37,000 TO 351,000 Btuh

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS)

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75.

S5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

ACPSE-P Series 50Hz 410A. Rooftop Units Cooling Capacity : 26 to 1388 MBH (8 to 407 kw) Heating Capacity : 28 to 1298 MBH (8 to 380 kw)

RCD Air Cooled Condensing Unit (50/60 Hz)

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM

DC INVERTER DUCTED AIR CONDITIONERS

Q6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

R410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2

AHN 064 to 304 EHN/CHN 064 to 304

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

P6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Electric Cooling Units EER Commercial System Units

Hitachi Inverter Wall Split Air Conditioning

Compresseur scroll. Refrigerant R410A SYSAQUAC. Air Cooled Condensing Units Models 25 to to 136.0kW

Indirect evaporative air conditioning 100% outside air FACTORY INSTALLATION (CW-160)

Air Cooled Water Chillers. CLS 182 to to 150 kw. Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07.

Reversible air-to-water heat pump HEAT PUMP HEATING (30/35 C 40/45 C)

R4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT

From domestic to commercial applications you ll find the detail you need to pinpoint which ActronAir system is most appropriate for your needs.

FDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E

S6BQ Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Split System 2-Stage Air Conditioner. 7 1/2 and 10 Ton rated at 11.2 EER and 12.

R6GP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Gas/Electric Units, with R-410A WARRANTY

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

Ceiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary

Bosch BOVA Split System Heat Pump

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

IDENTIFICATION ACCESSORIES DESCRIPTION

Modular Air Handling. Up to 3,500 Litres / sec. Low profile & Plant room application. Draft. Version. Second Edition A-. AirDesign 2015 AirDesign 2016

R6GN Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Gas/Electric Units with R-410A WARRANTY

GQ6SD Series. Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

R-22, 13 SEER 60 Hertz

AIR HANDLING UNITS. Customisable modular air handling unit, designed and built to suit your project requirements

CWP-CO / CWP-RC / CWP-HP 02 to 35

Operating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

TECHNICAL GUIDE R-410A, 13 SEER LATITUDE SERIES 60 Hertz

Tons BTU/h S.E.E.R* E.E.R** HSPF

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units 11.0 EER

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A

GUIDE SPECIFICATIONS CE Series Two Stage R-410A

R4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT

ULTRA LOW ENERGY. VHR Void Series W/I/s TOTAL SFP Typical. Made in the UK. VHR Void Mounted Heat Recovery Units VHR PERFORMANCE OVERVIEW:

GPC14H. 2- to 5-Ton Packaged Air Conditioner 14 SEER. Cooling Capacity: 24,000-57,500 BTU/H

PCB COMMERCIAL SERIES

GUIDE SPECIFICATIONS. ES Series R-410A

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

1 AIR HANDLING UNIT TYPE AIR ACCESS 75

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons

(click on page links below) General & Performance Data 1. Suggested Spec 3. Accessories 4

HRS. Very high efficiency heat recovery units. from 300 to m³/h >90 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR

14 SEER R -410A PACKAGE GAS / ELECTRIC UNIT 2 to 5 TON

PHR5. Product Specifications

Kirby WRC Remote Condenser. With HyBlade EC Fans and AxiTop Diffuser

S3BN Series Split System Air Conditioner 10.3 EER Commercial System 7½ and 10 Ton Capacity R-22 Refrigerant

OmegaAir Series Dedicated Outside Air Systems (DOAS) Engineering Guide

UMXCA/UMXCBA ECVA/ECVBA

DESCRIPTION FEATURES

CHP

R6GI Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

Air-Cooled Liquid Chiller with integrated hydraulic module

13 SEER Light Commercial 3 Phase

Q6SP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

PACKAGE AIR CONDITIONERS

WCA4**4. Product Specifications

V33B High Efficiency 360 Cassette Indoor Models - 60HZ

TECHNICAL SPECIFICATIONS

GPC14H 2- to 5-Ton Packaged Air Conditioner Up to 14 SEER

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

M-SERIES MHP4 MODEL NUMBER GUIDE 3 M HP F P 1 ELECTRIC HEAT PUMP PACKAGED UNITS REVISION CODE

Enhanced Air Conditioning

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology

PHB SERIES 7-1/2 and 10 TON

Q6SD Series 13 SEER, Three Phase, Packaged Heat Pump with R-410A 3-5 Ton Units

Transcription:

DRAFT Ducted Three Phase Packaged Air Conditioners Technical Data 96 Twin System Enables Staging Extra Long Life Epoxy Coated Outdoor Coil OPTION TZT-71 Controller & Digital Scroll Compressor for close temperature control Nominal Cooling Capacity 47 kw 96 kw OCTOBER 211

, 55, 595, 7,,, 96 - DUCTED PACKAGED ROOF TOP CONDITIONER General This OPA Series is a range of reverse cycle (heat pump) packaged roof top air conditioner designed and developed to comply with AS/NZS 33 specified conditions. The system has been tested and proven for cooling operation in outdoor temperatures up to 5 C. Applications These units have been specifically developed for air conditioning of commercial premises, e.g. banks, supermarkets, shopping malls, food outlets, auditoriums and restaurants. Air Flow Selection If the air returning to the indoor coil is regularly expected to be above 5%RH, then the coil face velocity should be limited to be 2.5 m/s or less (refer Air Flow graph; 2.5 m/s is clearly marked). High humidity levels can occur in tropical or subtropical conditions, and/or when heavily moisture laden fresh air is introduced. Consideration must always be given to selecting an air flow and face velocity that avoids water carry-over problems. Applications using full or high proportions of fresh air should be referred to your nearest temperzone sales office to establish the correct selection of units. Features Refrigerant R41A. Each system uses refrigerant R41A which is deemed to have zero ozone depletion potential. Economy. Each OPA unit has two independent refrigeration circuits to provide the flexibility and economy of two stage operation, i.e. utilising one or two circuits as conditions vary, plus the advantage of staggered starting. An economiser option is available to lower operating costs further during the cooling cycle. Efficient. Heat exchange coils incorporate inner grooved (rifled) tube for better heat transfer. The indoor air coil is interlaced for efficient part load performance. Performance. An adjustable pulley on the indoor air fan motor enables fine tuning to match the supply air requirements. The system includes a temperature sensing head pressure control which enables the system to compensate for outdoor ambient temperatures below 2 C on cooling cycle, and above C on heating cycle. / only: Electronic expansion valves (EEV) improve performance across a wide range of operating conditions. Quiet. The unit's generous insulation ensures a quiet unit. Durable. The cabinet and drain tray are constructed from high grade galvanised steel - polyester powder coated (colour Grey) for increased durability. External fasteners are stainless steel. Heat exchange coils comprise aluminium plate fins on mechanically expanded rifled copper tube. The outdoor coil fins are epoxy coated for extra protection in corrosive environments, eg salt laden sea air. Coil protection guards protect against hail damage. Fan motor bearings are sealed for life so as not to incurr regular maintenance. Insulation. Closed cell foam insulation has been used in the indoor air section to ensure no particles are introduced into the air stream. The insulation is foil faced and meets fire test standards AS 3.3 (1989) and BS 476 parts 6 & 7. Self Diagnostics. Each system includes a controller (OUC*) that has a display of LEDs to indicate faults and running conditions. A non-specific fault indicator is included for interface to external systems. * UC on / CONFIGURATIONS Two standard versions are available for each model: 1. Horizontal supply/return air with box mounting channel (OPA RKTBH), 2. Downward supply/return air with box mounting channel (OPA RKTBU). Optional Equipment 1. Filters (rated EU4). 2. Economiser (factory fitted) - includes dampers, weatherhood. 3. Adjustable fresh air damper and weatherhood. 4. TZT-71 thermostat (or TZT- on /). 5. Electronic control systems - available by special arrangement. 6. Digital compressor replaces one of the two compressors for close control applications. SAFETY FEATURES 1. HP and loss of refrigerant protection. 2. Anti-rapid cycle timer and internal overload for compressor protection. 3. Circuit breaker control circuits. 4. Time-and-temperature controlled electronic de-ice prevents icing up of the outdoor coil during heating cycle. 5. Frost protection on cooling cycle. 6. Sensor fault indication. 7. Crankcase heater prevents liquid refrigerant condensing in the compressors during the 'off' cycle. 8. Compressor minimum run time to ensure oil return. 9. Phase rotation protection device. 1. 24V control circuit Compressor Each high efficiency scroll type compressor is hermetically sealed and supported on rubber mounts to minimise vibration. Refrigeration SYSTEM The OPA units are factory charged with HFC-41A (R41A) refrigerant. / only: Electronic expansion valves (EEVs) control the flow of refrigerant. Wiring The electrical supply required (including voltage fluctuation limits) is: 3 phase 342-436 V a.c. 5 Hz with neutral and earth. The units control panel is fully wired ready to accept the main power supply. ECONOMISER OPTION If the outdoor air heat content or temperature is below that of the return air, the fresh air damper opens and the return air damper closes to provide the first stage of cooling. The dampers reverse and the compressor(s) will then operate to provide more cooling if required. A way of exhausting air from the space will be required when operating on % fresh air. The manufacturer operates a quality management system that conforms to AS/NZS ISO 91:28. Also available: OPA 2 3 models (23 38 kw)

PERFORMANCE DATA OPA 55 OPA INDOOR FAN SPEED l/s 2 2 37 4 42 52 INDOOR COIL E.A.T. D.B. C W.B. C Cooling Capacity (kw) Total = Total Capacity (kw) Sens. = Sensible Capacity (kw) E.A.T. = Entering Air Temperature = Nominal Capacity (kw) Note: Capacities are gross and do not include allowance for fan motor heat loss. For fan motor heat loss refer to Air Handling graphs. COIL ENTERING TEMPERATURE C D.B. 23 27 31 35 39 43 Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. 45.8 36.2 45.2 36.2 43.9 35.5 41.9 34.3 39.1 32.4 35.7 29.9 48.2 35.4 47.6 35.4 46.3 34.8 44.3 33.7 41.5 32. 38.1 29.7 5.7 4.5 5.1 4.6 48.8 4. 46.7 38.8 44. 36.9 4.5 34.4 53.1 48. 52.5 48. 51.2 47.4 49.1 46.1 46.4 44. 42.9 41.2 55.1 43.5 54.3 43.5 52.8 42.7 5.3 41.2 47. 39. 42.9 36. 58. 42.5 57.3 42.5 55.7 41.8 53.2 4.5 49.9 38.4 45.7 35.7 6.9 48.7 6.2 48.7 58.6 48. 56.1 46.6 52.8 44.4 48.7 41.4 63.8 57.7 63.1 57.7 61.5 57. 59.1 55.4 55.8 52.9 51.6 5.1 68.3 53.9 67.4 53.9 65.4 53. 62.4 51.1 58.3 48.4 53.1 44.6 71.9 52.7 71. 52.7 69. 51.9 66. 5.2 61.9 47.7 56.8 44.2 75.5 6.4 74.6 6.4 72.7 59.6 69.6 57.8 65.5 55.1 6.4 51.3.1 71.5.2 71.6 76.3 7.7 73.3 68.7 69.2 65.6. 61.5.2 61. 76.2 61. 74. 59.9 7.6 57.9 66. 54.7 6.1 5.5.3 59.6.3 59.6.1 58.7 74.7 56.8 7.1 53.9.2 5..4 68.4.4 68.4.2 67.4.7 65.4 74.1 62.3 68.3 58.1 89.5.9 88.5. 86.3..9.7.2 74.3 72.4 69.5.7 62.8.3 62.5. 61.6 75.6 6.6 73.2 59.7 7.4 58.2 86.8 63.9.1 62.5.7 61.6.3 6.6. 59.7 75.6 58.6 92.6 72.8 89.8 72.1 87.5 7.7.1 7.6.7 69.6.8 68.7 97.9.6 95.1.6 92.7.7 9.3.2 87.5.3.6.3 93.3 7.8 9.6 7.5 87.9 69.5.3 68.4.6 67.3.4 65.7 97.9 72.1 96. 7.5 93.3 69.5 9.6 68.4 87.9 67.3.3 66.1 14.5.1 11.3.3 98.7.8 96..7 93.3.6 9.1.5 11.4 93.2 17.2 92. 14.5 91. 11.9 9.4 98.7 89.4 95.4 88.3 Indoor Air Flow Correction Factors @ nominal conditions Indoor Air Flow (%) Total Capacity Sensible Capacity -2%.95.89-1%.975.95 Rated 1. 1. +1% 1. 1.5

PERFORMANCE DATA OPA 595 OPA INDOOR ENTERING TEMP. C D.B. 2 2 2 2 2 2 heating capacity (kw) G = Gross Heating Capacity kw, based on nominal air flow. N = Net Heating Capacity kw allowing for average defrost. = Nominal Capacity (kw) outdoor coil ENTERING TEMPERATURE (e.a.t.) c d.b. 5 3 1 1 3 5 7 9 G n G n G n G n G n G n G n G n 29.7.5 32.2 27.2 34.4 27.5 36.6 28.2 38.8 28.5 41.7 33.3 44.4 44.4 46.6 46.6 29.2.1 31.6 26.6 33.7 26.9 35.9 27.6 38.1 28. 4.9 3.7 43.5 43.5 45.7 45.7 28.1 24.1 3.4.7 32.5 26. 34.6 26.6 36.7 26.9 39.4 29.5 41.9 41.9 44. 44. 34.3 29.5 37.1 31.3 39.6 31.7 42.2 32.5 44.8 32.9 48.1 38.4 51.1 51.1 53.7 53.7 33.6 28.9 36.4 3.7 38.9 31.1 41.4 31.9 43.9 32.3 47.1 35.4 5.1 5.1 52.7 52.7 32.4 27.8 35. 29.6 37.4 29.9 39.8 3.7 42.3 31.1 45.4 34. 48.3 48.3 5.7 5.7 46.1 41.4 49.8 44.8 53.3 47.4 56.7 48.7 6.1 51.4.6 61.4 68.7 68.7 72.2 72.2 45.1 4.6 48.9 44. 52.2 46.5 55.6 47.8 59. 5.4 63.3 6.2 67.4 67.4 7.8 7.8 43.5 39.1 47. 42.3 5.3 44.8 53.5 46. 56.8 48.5 61. 57.3.9.9 68.1 68.1 48.3 43.4 52.3 47.1 55.9 49.7 59.5 51.2 63.1 54. 67.8.4 72.1 72.1 75.7 75.7 47.4 42.6 51.3 46.1 54.8 48.8 58.3 5.2 61.9 52.9 66.5 63.1 7.7 7.7 74.2 74.2 45.6 41.1 49.4 44.4 52.8 47. 56.2 48.3 59.6 5.9. 6.2 68.1 68.1 71.5 71.5 57.1 49.9 61.7 53.1 66. 54.5 7.3 55.5 74.5 56.3.1 62.2.2 66.4 89.4 89.4 55.9 49. 6.5 52.1.7 53.4 68.9 54.4 73.1 55.2.5 57.3 83.5 65.1 87.7 87.7 53.9 47.1 58.3 5.1 62.3 51.4 66.3 52.4 7.4 53.1 75.6 55.2.4 62.7.4.4 61.5 53.8 66.6 57.2 71.1 58.7 75.7 59.8.3 6.6 86.3 67. 91.8 71.6 96.4 96.4 6.3 52.8 65.3 56.1 69.8 57.5 74.3 58.7.8 59.5.6 61.8 9. 7.2 94.5 94.5 58.1 5.8 62.8 54. 67.2 55.4 71.5 56.5 75.8 57.3.5 59.5 86.7 67.6 91. 91.

PERFORMANCE DATA HANDLING Note: Airflows are for a dry coil. Reduce airflow by 5% in high moisture removal conditions. In a free blow or low resistance application, beware of exceeding indoor fan motor's full load amp limit (refer back page). As filters are optional, the fan air flows given are for units installed without filters. OPA 55 4 3 2 67 RPM 65 RPM 73 RPM 3 kw MOTOR LIMIT 2 22 24 26 2 3 FLOW (l/s) 2. m/s Face Velocity 4 3 2 67 RPM 73 RPM 3 kw MOTOR LIMIT 9 RPM 22 24 26 2 3 32 FLOW (l/s) 2.3 m/s Face Velocity OPA 5.5 kw MOTOR LIMIT 4 RPM 3 RPM 7 RPM 2 2 3 3 4 4 5 FLOW (l/s) 2.5 m/s Face Velocity 5.5 kw MOTOR LIMIT 4 RPM 3 RPM 7 RPM 2 2 3 3 4 4 5 FLOW (l/s) 2.5 m/s Face Velocity 4 75 RPM 3 6 RPM 6 RPM 2 5.5 kw MOTOR LIMIT 3 3 4 4 5 FLOW (l/s) 2.5 m/s Face Velocity RPM 6 4 2 9 RPM RPM 7.5 kw MOTOR LIMIT 3 3 4 4 5 FLOW (l/s) 2.5 m/s Face Velocity

PERFORMANCE DATA Model : OPA 55 OPA 899 Std Motor Size kw 5.5 (x2) 5.5 (x2) 5.5 7.5 Max. D.O.L. Motor kw 7.5 (x2) 7.5 (x2) 7.5 7.5 Max. Fan Speed RPM 95 Std Pulley Range RPM 97 97 6 75 97 Factory Setting RPM 5 5 6 5 Optional Filters - Pressure Drop Based on Koch Multi-Pleat HC filter. Max. final pressure drop Pa. PRESSURE DROP (Pa) 75 5 INITIAL (Clean Filter) 1.5 2. 2.5 3. FILTER FACE VELOCITY (m/s) SOUND LEVELS RADIATED OPA 55 OPA FAN SPEED SWL db(a) 1 Sound Power Levels (SWL) Measured in decibels re 1 picowatt. 83 OCTAVE BAND FREQUENCY Hz 1 k SOUND POWER LEVELS (SWL) db 76 74 75 2 k 69 67 73 76 4 k 61 69 61 66 71 FAN SPEED SPL @ 3 m db(a) 1 Sound Pressure Levels (SPL) Measured in decibels re 2 µpa. OCTAVE BAND FREQUENCY Hz 1 k SOUND PRESSURE LEVELS (SPL) db 2 k 4 k OPA 55 OPA 62 66 66 66 67 68 69 68 69 73 62 67 63 66 6 62 63 58 63 59 62 61 62 54 61 51 57 58 57 47 53 45 5 53 49 SUPPLY OUTLET INDOOR FAN SPEED OPA 44 83 RPM OPA 55 83 RPM 75 RPM OPA RPM 75 RPM RPM RPM RPM SWL db(a) 88 86 9 86 92 1 87 88 9 Sound Power Levels (SWL) Test Conditions: BS 8 PT2 19. Installation Type A (free inlet and outlet). Direct method of measurement (reverberant room). Measured in decibels re 1 picowatt. 83 89 91 OCTAVE BAND FREQUENCY Hz 1 k SOUND POWER LEVELS (SWL) db 88 88 86 9 87 2 k 76 76 4 k 73 72 74

DIMENSIONS (mm) Fig. 1 Horizontal Supply & Return Air OPA SRKTBH MIN. CLEARANCE B W PANEL Z MIN. CLEARANCE FLOW V MIN. CLEARANCE Y 3 MIN. CLEARANCE A U X OPTIONAL RETURN 6 SUPPLY Not to Scale A B C D E F G H J K L M N 22 195 1635 532 443 195 5 955 497 135 1 18 21 OPA 55 22 195 175 535 483 19 59 955 497 135 1 18 21 2 2 186 4 558 235 6 12 596 13 13 2 266 2 2 186 4 558 235 6 12 596 13 13 2 266 Note: The, 96 models have four outdoor air fans. MIN. CLEARANCE FOR FILTER FILTER F E J K OPA 55 OPTIONAL POINT Loads (kg) U V W X Y Z 13 12 11 134 147 9 16 136 111 132 148 1 172 172 1 27 27 221 183 183 195 22 219 235 PROJECTION C D H L L MOUNTING CENTRES DRAIN 1" BSP FEMALE G M MOUNTING CENTRES N MIN. BENEATH Fig. 2 Downward Supply Air & Return Air OPA SRKTBU FLOW R S T R S T U V W X Y Z 93 12 475 6 435 2 1 483 U OPA 55 93 12 475 68 435 2 1 483 OPA 65 93 12 21 475 56 47 2 35 45 V 1165 16 22 575 545 567 235 4 475 1165 16 22 575 545 567 235 4 475 W FLOW Z Y X Note: The, 96 models have four outdoor air fans. Refer to Fig.1 for overall dimensions. 6 SUPPLY & RETURN NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation. Certified data is available on request.

DIMENSIONS (mm) Fig. 3 Horizontal Supply & Return Air RKTB1, OPA RKTB1 MIN. CLEARANCE 224 U PANEL Z MIN. CLEARANCE FLOW V Y FLOW MIN. CLEARANCE MIN. CLEARANCE PANEL W X OPTIONAL 6 RETURN SUPPLY MIN. CLEARANCE FOR FILTER 19 FILTER 56 6 Not to Scale PROJECTION POINT Loads (kg) U V W X Y Z 243 189 135 249 222 195 Opposite Hand version also available, ie RKTB1 or OPA RKTB1 Note : A 2 m clearance is required above the exhaust air fans OPTIONAL 195 483 12 1355 1355 MOUNTING CENTRES 299 O/A DRAIN 1" BSP FEMALE 6 21 MOUNTING CENTRES 4 27 Fig. 4 Downward Supply Air & Return Air OPA SRKTB23 1165 13 575 76 NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation. Certified data is available on request. Opposite Hand version also available, ie RKTB32 or OPA RKTB32 475 1 57 43 6 SUPPLY & RETURN

Fig. 5 Economiser Option OPA 55 P Q 735 35 735 35 MOTORISED FRESH DAMPER P Dimensions (mm) OPA 975 37 975 37 875 31 875 31 INDOOR SECTION ECONOMISER Q FRESH INTAKE mm MINIMUM SUPPLY RETURN ROOF MOTORISED RETURN DAMPER Fig. 6 Fresh Air Damper Option OPA 55 R S 435 5 435 5 ADJUSTABLE FRESH DAMPER R OPA 26 835 26 835 43 FRESH 43 FRESH INTAKE S Nomenclature O P A 4 6 5 R K T B G e.g. Series Size Type D H O - Outdoor P - Packaged A - Air Cooled Divide by 1 to get approx. nominal Capacity in kilowatts R - Reverse cycle K - Refrigerant R41A T - Three phase power supply B - Twin compressor system (twin circuit) G - Digital compressor system (single) D - TZT-71 Room Temp. Controller H - Horizontal discharge supply air fan U - Downward discharge supply air fan O P A 7 R K T B 1 e.g. Series Size Type Configuration O - Outdoor P - Packaged A - Air Cooled Divide by 1 to get approx. nominal Capacity in kilowatts R - Reverse cycle K - Refrigerant R41A T - Three phase power supply B - Twin compressor system G - Digital compressor system (one of two) 1 - Std Horiz. S/A, Horiz. R/A 1 - Opp Hd Bott. S/A, Vert. R/A 23 - Std Bott. S/A, Bott. R/A 32 - Opp Bott. S/A, Bott. R/A

SPECIFICATIONS Model opa 465 OPA 55 OPA Nominal Cooling Capacity * 1 kw 46.7 56.1 69.6.7.1 96. Net Cooling Capacity kw 44.6 53.9 66.2 74.2.1 87.9 Heating Capacity * 2 kw 43.5 49.5 67.4 7.7 83.5 9. E.E.R. (Cooling) 2.96 3.5 3.17 2.99 3.4 2. Air Flow * 3 l/s 2 2 37 4 42 52 Power Source * 4 3 p h a s e 3 4 2-4 3 6 V a. c. 5 H z Indoor Fan Full Load Amps A/ph. 6.5 6.5 11 11 1.3 13.8 Running Amps (Total System) A/ph. 32 / 27 / 27 39 / 3 / 29 42 / 36 / 37 5 / 4 / 4 51 / 46 / 46 68 / 59 / 59 Recom'd External Protection A/ph. 5 12 12 Finish G r e y p o l y e s t e r p o w d e r c o a t Net Weight kg 95 1 1234 1234 1162 1233 Shipping Weight kg 96 13 13 12 13 Notes: * 1 Nominal Cooling Capacity at AS/NZS 33 conditions: Indoor Entering Air Temperature 27 C D.B., 19 C W.B.; Outdoor Entering Air Temperature 35 C D.B. Net Cooling Capacity at AS/NZS 33 includes an allowance for indoor fan motor heat loss. * 2 Heating Capacity at AS/NZS 33 conditions: Indoor Entering Air Temperature 21 C D.B.; Outdoor Entering Air Temperature 7 C D.B., 6 C W.B. * 3 Supply air flow at Nominal Cooling Capacity conditions stated above. * 4 Power source includes voltage limits. NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation. Certified data is available on request. Available from 1/11 Pamphlet No. 37 temperzone limited 211 temperzone limited Head Office, Auckland : 38 Tidal Rd, Mangere, N.Z. Private Bag 9333, Otahuhu, NEW ZEALAND. Email sales@temperzone.co.nz Website: www.temperzone.biz temperzone australia pty ltd Head Office, Sydney : 14 Carnagie Place PO Box 48, Delivery Centre, Blacktown, NSW 2148, AUSTRALIA. Email sales@temperzone.com.au AUCKLAND SYDNEY Ph. -9-2 5 Ph. (2) 82-57 Fax -9-275 5637 Fax (2) 82-5711 WELLINGTON ADELAIDE Ph. -4-569 3262 Ph. (8) 8376-5 Fax -4-566 6249 Fax (8) 8376-1449 CHRISTCHURCH SINGAPORE Ph. -3-3 3216 Ph. SNG 6733 4292 Fax -3-3 5956 Fax SNG 6235 71 MELBOURNE Ph. (3) 8769-76 Fax (3) 8769-761 BRISBANE Ph. (7) 338-8333 Fax (7) 338-833 NEWCASTLE Ph. (2) 4962-15 Fax (2) 4961-511 PERTH Ph. (8) 9314-34 Fax (8) 9314-35 TOWNSVILLE Ph. (7) 43-9566 Fax (7) 43-9166 HOBART Ph. (3) 6272-66 Fax (3) 6272-56 Manx Press