Weather Louvre Test. Report 57668/1. Carried out for Seng Yoon Seng Holdings SDN. BHD. By Andrew Freeth. 14 January 2014

Similar documents
Room, packaged & close control air conditioning United Kingdom

For installation into ductwork

Report. PIBCV Tests. Report 52724/1 Edition 2 February 2010

Louvre systems. Series WL Standard weather louvres. Incorporating. Standard range of single bank louvres as used in countless installations worldwide

McKenzie Martin Louvres & Ventilation Systems Louvres Maximair Louvre Systems Turret Louvres

TABBED ACCESS DOOR RANGE

Pressure relief dampers

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL.

Type WG. External weather louvre made of galvanised steel sections FOR THE MOST DIVERSE APPLICATIONS, AVAILABLE ALSO IN LARGE SIZES

a total louvre design and manufacturing service

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

BL Series Louvres. Factory Assembled Louvre Panels

Louvre systems. Series WL Standard weather louvres. Incorporating. Standard range of single bank louvres as used in countless installations worldwide.

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

The World Leading Air-conditioning Company

Ceiling swirl diffusers

Fan - Powered Terminal Unit Series Flow

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

Shut-off dampers. Type AKK. For contaminated air PD AKK 1

Ventilation grilles for installation into walls, sills or rectangular

Disc valves. Type Z-LVS. For supply air. 03/2017 DE/en PD Z-LVS 1

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular

Ceiling swirl diffusers with perforated face plate

Ventilation grilles for installation into walls, sills or rectangular

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

MT SERIES COUNTER FLOW COOLING TOWER

Ceiling swirl diffusers

The principal activities of UMWD are mainly investment holding and property development.

Room, packaged & close control air conditioning Spain

Splits systems Indonesia

Ceiling swirl diffusers with perforated face plate

CHILLED WATER FAN-COIL UNITS

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES

42CET/ 42CED Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 300 to 1400 cfm Electric heater option

Ceiling swirl diffusers

PERFORMANCE TEST REPORT. Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent

USS - External Louvre. Halton USS. External Louvre

Volume Flow Limiters Type VFL

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178)

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1

Trox-o-mat Automatic Roll Filters F1/1/EN/5

HOTCHKISS AIR ACOUSTICS

Type NAK. Gas-tight shut-off damper with pneumatic actuator

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

AMCA Publication

HIGH SECURITY VENTILATION LOUVRES

CAV controllers Type RN

Incorporating V2.1. Product spec >>> > Series WL - Standard weather louvres

Adjustable Curved Vane Diffusers. Vanes are parallel to the width dimension Vanes are parallel to the height dimension

Highline 260i EC Waterside Fan Coil Unit

Type AK FOR LOW-LEAKAGE SHUT-OFF. Homepage > Products > Control units > Shut-off and restriction > Shut-Off Devices > Type AK

VAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1

Ceiling diffuser 4DE

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

Ventilation grille Model AL

spandek optima LYSAGHT Trapezoidal steel cladding with longer spanning capability Structural Solutions Roofing & Walling Solutions

trimdek optima LYSAGHT Subtle square fluted steel cladding with extra-wide span Structural Solutions roofing & Walling Solutions

ALD. Sound attenuating exterior wall grille QUICK FACTS. Excellent noise attenuation A robust grille that withstands severe climatic conditions

DSA HIGH EFFICIENCY DROPLET SEPARATOR DROPLET SEPARATOR DSA. With heated vanes

CHILLED WATER DUCTED FAN COIL

Type AKK FOR CONTAMINATED AIR. Homepage > Products > Airflow Control - VAV and CAV > Shut-off and restriction > Shut-Off Devices > Type AKK

Heat exchanger. Type WL. For the reheating of airflows in circular ducting PD WL 1. 03/2017 DE/en

Measuring probe For ventilation and air-conditioning Model A2G-FM

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

Ventilation grille Model IB-R

Compact Grille Model KG

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

Incorporating V2.0. Product spec >>> > Series DJ - Drum jet diffusers

ceiling swirl diffuser DQJ

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

AXIAL FANS Catalogue CN0050C01 May 2008

AMD-33 Air Measuring Station with VCD-33 Control Damper

1 AIR HANDLING UNIT TYPE AIR ACCESS 75

Swirl Diffuser DHV Contents Description...3 Models and dimensions...4 Technical data...8

Mixed Flow Roof Fans (RMH)

2/18/EN/2. Air Handling Lights. Type LR. Recommended for use in rooms with ceiling heights of approx m

AIR HANDLING UNIT. MODEL: PM0809 to PM CFM to CFM

Airscrew 200+ Vmax Vaneaxial Fans

Air Distribution SWIRL DIFFUSERS DW SERIES SERIES

400ºC/2h centrifugal roof fans with horizontal or vertical air outlet CHT 200 4T BS. Installed capacity

Swirl Diffuser Model DQF

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options.

EVALUATION REPORT 347

TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS

SETTLEMENT AGREEMENT BETWEEN D.J. DESIGN SUPPLIERS SDN. BHD., SOLID PROMENADE SDN. BHD. AND IKHMAS JAYA SDN. BHD., A WHOLLY OWNED SUBSIDIARY OF IJGB

Louvre systems. Series WLSS / WLG Stainless / galvanised steel weather louvres. Incorporating

BC 08. Sand Trap Louvers STL-AB-11A LISTED

Incorporating V2.1. Product spec >>> > Series ECG - Egg crate grilles

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

Transcription:

Weather Louvre Test Report 57668/1 Carried out for Seng Yoon Seng Holdings SDN. BHD By Andrew Freeth 14 January 2014

Weather Louvre Test Carried out for: Seng Yoon Seng Holdings SDN. BHD No. 46, Jalan Industri PBP 3 Taman Industri Pusat Bandar Puchong 47100 Puchong Selangor Darul Ehsan Malaysia Contract: Report 57668/1 Date: 14 January 2014 Issued by: BSRIA Limited Old Bracknell Lane West, Bracknell, Berkshire RG12 7AH UK Telephone: +44 (0)1344 465600 Fax: +44 (0)1344 465626 E: bsria@bsria.co.uk W: www.bsria.co.uk Compiled by: Name: Andrew Freeth Title: Senior Test Engineer Approved by: Name: Mark Roper Title: Principal Test Engineer This report must not be reproduced except in full without the written approval of an executive director of BSRIA. It is only intended to be used within the context described in the text. BSRIA Page 3 of 10 Report 57668/1

CONTENTS 1 INTRODUCTION... 5 1.1 Test item information...5 2 TEST METHOD... 7 2.1 Water penetration...7 2.2 Pressure drop...7 2.3 Test equipment used...7 3 RESULTS... 8 APPENDICES APPENDIX: A MANUFACTURER S DRAWING... 10 FIGURES Figure 1 Test item 57668A1 (front)... 6 Figure 2 Test item 57668A1 (rear)... 6 BSRIA Page 4 of 10 Report 57668/1

INTRODUCTION 1 INTRODUCTION This report concerns tests conducted on a louvre to determine the Rainwater Penetration and the Pressure Drop versus Airflow Curve, with the associated Coefficient of Entry using the test methods contained within EN 13030 : 2001. The work was commissioned by Seng Yoon Seng Holdings SDN. BHD. and was carried out at BSRIA on 29 November to 3 December 2013. Items received for test Test Item LV3575 BSRIA ID 57668A1 1.1 TEST ITEM INFORMATION Contract 57668 Date 28-11-13 Manufacturer Louvre Model Material Painted Blade Height Blade Width Blade Depth Frame Depth Seng Yoon Seng Holdings SDN. BHD LV3575 Galvanised Steel No 948 mm 950 mm 98mm 100 mm No. of Blades 9 Blade Pitch Blade Angle 107 mm (average) 45 approx. No. of Banks 1 Guard Type Guard Spacing Side Channels Water Drip Tray Blade Orientation None N/A None No Horizontal Note: Nominal pitch is 110mm but was reduced slightly for test sample purposes. BSRIA Page 5 of 10 Report 57668/1

INTRODUCTION Figure 1 Test item 57668A1 (front) Figure 2 Test item 57668A1 (rear) BSRIA Page 6 of 10 Report 57668/1

TEST METHOD 2 TEST METHOD A schematic representation of the rig used during testing The test comprises of two parts: 2.1 WATER PENETRATION The weather louvre is subjected to fan driven wind at a speed of 13 m/s and water sprayed as rainfall at a rate of 75 l/h. In addition to the simulated wind and rain, air is drawn through the louvre at various set velocities (0, 0.5, 1.0, 1.5, 2.0, 2.5, 3.0 and 3.5 m/s). Each test is preceded by a suitable pre-test soak which is typically around 30 minutes. Each test is run until the results become stable, and in any case, for a minimum of 30 minutes. The penetrated water is collected in the collection duct and is measured and recorded against time elapsed. A range of measurements are taken to give the characteristic curve for the test louvre. 2.2 PRESSURE DROP For this test, the Aerodynamic Measuring Section (AMS) is separated from the main rig. The louvre is then mounted in the upstream opening of the AMS. Pressure tappings in the plenum walls of the AMS allow measurement of the static pressure within the plenum during testing. The airflow volume is calculated from the differential pressure at the measuring cones. The plenum has a set of settling screens within to produce even flow through the cones and therefore give accurate reading of the total volume. By adjusting the fan speed, the total airflow through the system varies and therefore changes the pressure on the louvre under test. A range of measurements are taken to give the characteristic curve for the test louvre. 2.3 TEST EQUIPMENT USED Test equipment BSRIA ID Calibration Expiry Date Water supply measurement 352 12-1-14 Rain measuring system 353 11-1-14 Airflow cones 364 15-1-14 Micromanometer 502 14-2-14 Scales (water) 1364 8-2-14 BSRIA Page 7 of 10 Report 57668/1

RESULTS 3 RESULTS 3.1 RAINWATER PENETRATION MANUFACTURER Seng Yoon Seng Date 29/11/2013 MODEL LV3575 Contract 57668 louvre height 948 mm Simulated rainfall 75 mm/hr louvre width 950 mm Wind speed 13.0 m/s louvre area 0.901 m 2 VENTILATION RATE WATER FLOW RATES Volume Velocity Supply Penetrated Effectiveness Class m 3 /s m/s l/h l/h 0.00 0.00 93.0 3.7 94.6% C 0.45 0.50 93.0 7.4 89.0% C 0.90 1.00 93.0 7.9 88.3% C 1.35 1.50 93.0 10.1 85.1% C 1.80 2.00 93.0 12.6 81.3% C 2.25 2.50 93.0 17.0 74.8% D 2.70 3.00 93.0 25.3 62.6% D 3.15 3.50 93.0 34.9 48.3% D Effectiveness of Louvre with Simulated Wind and Rain 100 100% 80 80% water flow rates l/h 60 40 20 60% 40% 20% louvre effectiveness % 0 0% 0.00 1.00 2.00 3.00 4.00 face velocity m/s Supply l/h qso Penetrated l/h corrected Effectiveness BSRIA Page 8 of 10 Report 57668/1

RESULTS COEFFICIENT OF ENTRY MANUFACTURER Seng Yoon Seng Date 29/11/2013 MODEL LV3575 Contract 57668 air temperature 17.3 C louvre height 948 mm barometer 1016 mbar louvre width 950 mm air density 1.214 kg/m 3 louvre area 0.901 m 2 louvre face velocity air flow rate louvre pd test theoretical coefficient Pascals m/s m 3 /s m 3 /s C e 304.0 4.35 3.916 20.159 0.194 288.0 4.23 3.806 19.621 0.194 275.0 4.13 3.722 19.173 0.194 224.0 3.73 3.363 17.304 0.194 158.0 3.16 2.847 14.533 0.196 91.0 2.39 2.153 11.029 0.195 63.0 1.99 1.793 9.177 0.195 37.2 1.53 1.381 7.052 0.196 24.2 1.23 1.109 5.688 0.195 13.4 0.92 0.827 4.232 0.195 mean C e 0.195 Class 4 Resistance to Airflow ( C e ) 350 300 Louvre Pd ( Pa ) 250 200 150 100 50 0 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 Airflow ( m 3 /s ) BSRIA Page 9 of 10 Report 57668/1

APPENDIX: A MANUFACTURER S DRAWING APPENDIX: A MANUFACTURER S DRAWING Note: Nominal pitch is 110mm but was reduced slightly for test sample purposes. BSRIA Page 10 of 10 Report 57668/1