CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

Similar documents
CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

VOC Room Sensor in the BAPI-Stat 3 Enclosure with Differential Ground Configuration

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

BAPI-Stat 3 Room Sensor

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

VOC Duct and Rough Service Sensor

DPS/MPS/RAH/RPS/SWP Space Sensor

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

Installation and Maintenance Manual IM

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

GE Measurement & Control

Duct Averaging Transmitters BA/T#-A Temperature Transmitter Installation & Operations

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations

Temperature Transmitters

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14

SE8300 Series Installation Guide 24 Vac Low Voltage

Figure 1: WPR2 Dimensions and Hardware

YCCS TE-6800 Series Temperature Sensors

Digital Room Thermostats with Touch Screen LCD

Section 55 Chapter 6

A419ABG-3C Electronic Temperature Control

MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Combined Ventilation Controller RVWS-T-224HA

Carbon Monoxide Transmitter

OE & OE Digital Room Sensor

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

C7170A,B Encapsulated Temperature Sensor

Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Low Pressure Sensor. Overview. Specifications. Installation and Operation

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

INTECH Micro 2300-RTD6

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

ECONOMIZERS. 1/2012 Supersedes

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Introduction to Carrier sensors... 1 ZS Sensors... 3 Specifications... 5 CO2 sensor installation... 6 Rnet Configuration... 6

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

MS Application. Features. Proportional Valve Actuator General Instructions

SetPoint 150 Controller Installation Manual

ECCII to ECCIII Upgrade Kit

User Manual Solar Charge Controller 3KW

SCC-MPPT Solar Charge Controller

1100 Series Piston Type Differential Pressure Gauges

TM-9100 Series Room Command Module

Table of Contents. Carrier Sensors

SCC-MPPT Solar Charge Controller

Electric Actuator Instructions

System III Wiring Information 54-12

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

Elite Power Solutions Automatic Battery Control (ABC) Operation Manual

SMT-AZC INSTALLATION / OPERATION MANUAL

INSTALLATION INSTRUCTION

Immersion Temperature Sensors

Power Operated Retrofit Kit for Manual Door 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

QUICK START GUIDE VAV CONTROLLERS & WALL SENSORS rue Charles, Suite 100, Mirabel, QC, J7J 1X9

Installation, Operation and Maintenance Manual

Digital Formaldehyde Meter

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

Fuel Level FL1. FL1 - User s manual. Rev Revision#2.0, 28/11/2014 For firmware version 1.2

Solar Charge Controller

READ THIS BEFORE INSTALLING SWITCHGEAR

Description. functions including single duct pressure dependent or pressure independent systems.

EconoMi$er, Power Exhaust, and Sensor Installation Instructions

Therm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1

SEN and SEN Outdoor Air Temperature Sensors

Installation, Operation and Maintenance Manual

Installation and Operation Instructions DLP Series

IMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS

Series 1000 Room Temperature Sensors, 1K Ω Platinum (375α) RTD (MBC/RBC/MEC/UC)

Installation, Operation and Maintenance Manual

Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

Spray Height Controller

SE8300 Series Installation Guide 24 Vac Low Voltage

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

Model 8000XL OPERATOR MANUAL

MAGPOWR Spyder-Plus-S1 Tension Control

User's Guide. CO 2 Meter. Model CO250

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

INSTALLATION INSTRUCTIONS T-59 SPACE TEMPERATURE SENSOR WITH OVERRIDE & SETPOINT ADJUSTMENT

PROVEX Installation Guide. Version 1.0

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

Transcription:

Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to 2,000 ppm with a field selectable output of 0-5 or 0-10 VDC. The non-dispersive infrared (NDIR) technology has been optimized to reduce drift. The sensor is also altitude compensated for longterm accuracy and stability. Changing air pressure, due to altitude or weather patterns, can change the output of most CO 2 sensors by as much as 17%. The BAPI unit has a built-in barometric sensor that continuously compensates the output for accurate readings despite inclement weather or the altitude of the installation. The unit can be ordered as CO 2 alone, or with optional temperature sensing, temperature setpoint, occupant override and humidity sensing. The large format display is easy to read and alternates between the measured values (CO 2, Temperature or Humidity). The display is also field adjustable between F or C and all the displayed values may be turned on or off by an HVAC technician. Optional indication of the CO 2 level as Good, Fair or Poor is available as a three-color LED on the unit or as an arrow on the display. Fig 1: BAPI-Stat 3 Room CO 2 Sensor Specifications Power for 0-5 VDC Outputs: 9-35 VDC @ 150mA max (9-24 VDC recommended) Power for 0-10 VDC Outputs: 15-35 VDC @ 150mA max (15-24 VDC recommended) Sensing Elements: CO2 Single Beam Non-Dispersive Infrared (NDIR) or Dual Channel NDIR for 24/7 Model Humidity Capacitive Polymer ±2% RH Accuracy Temperature Sensor: Thermistor, RTD or Semiconductor Operating Environment: 32-122 F (0-50 C) 0-95%, RH non-condensing Material ABS Plastic, Material Rated UL94V-O CO 2 Detection Range: 0 2000 ppm Start-Up Time: 10 Minutes Response Time: Less Than 2 Minutes (after Start-Up Time) Mounting: 2 x4 J-Box or drywall screws provided Override Output: Contact... SPST, 24V AC/DC, 0.5A max Sensor... Shorts Out direct temperature sensor Setpoint.. Contact in parallel, resistive setpoint only LCD Display: Main Display: 0.76 4-digit Numeric (Numeric Values) Minor Display: 0.34 3-digit Alpha-Numeric (PPM, %RH, F, C) Occ/Un-occ BAPI Man Icon: (Blk=Occupied) Measurement Offsets: (Field Adjustable) ±5 (F or C) in 0.1 increments ±5% RH in 0.1% RH increments CO2 Accuracy: (Automatic Background Calibration model) 400 to 1,250 ppm: ±30ppm or 3% of reading, whichever is greater 1,250 to 2,000 ppm: ±5% of reading + 30ppm CO2 Accuracy: (24/7 model) ±75ppm LED CO 2 Level Indicator: Good, Green < 1,000 PPM Fair, Orange = 1,000 to 1,500 PPM Poor, Red > 1,500 PPM Certifications: RoHS Warranty Period: 2 Years from manufacture date 1 of 6

Mounting Mounting hardware is provided for both junction box and drywall installation (junction box installation shown). Note: Screw the 1/26 Allen lock-down screw into the base to open the case, less chance of losing it this way. Back out the lock-down screw to secure the cover. Junction Box 1. Pull the wire through the wall and out of the junction box, leaving about six inches free. 2. Pull the wire through the hole in the base plate. 3. Secure the plate to the box using the #6-32 x 5/8 inch mounting screws provided. 4. Terminate the unit according to the guidelines in the Termination section. (page 3) 5. Mold the foam on the unit s base to the wire bundle to prevent drafts. (see note below) 6. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. 7. Secure the cover by backing out the lock-down screw using a 1/16 Allen wrench until it is flush with the bottom of the cover. Fig 2: Mounting to a Junction Box Drywall Mounting 1. Place the base plate against the wall where you want to mount the sensor. 2. Using a pencil, mark out the two mounting holes and the area where the wires will come through the wall. 3. Drill two 3/16 holes in the center of each marked mounting hole, DO NOT punch the holes or the drywall anchors will not hold. Insert a drywall anchor into each hole. 4. Drill one 1/2 hole in the middle of the marked wiring area. 5. Pull the wire through the wall and out of the 1/2 hole, leaving about six inches free. 6. Pull the wire through the hole in the base plate. 7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided. 8. Terminate the unit according to the guidelines in the Termination section. (page 3) 9. Mold the foam on the unit s base to the wire bundle to prevent drafts. (see note below) 10. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. 11. Secure the cover by backing out the lock-down screw using a 1/16 Allen wrench until it is flush with the bottom of the cover. NOTE: In any wall-mount application, the wall temperature and the temperature of the air within the wall cavity can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and sensor failure. To prevent these conditions, BAPI recommends sealing the conduit leading to the junction box, filling the junction box with fiberglass insulation or sealing the wall cavity. 2 of 6

Termination BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device s wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such as motors, contactors and relays. BAPI s tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your BAPI representative. BAPI recommends against wiring the sensor with power applied as accidental arcing may damage the product and void the warranty. Fig 3: Circuit Board Optional Test and Balance Switch Terminal OVR SET EXT TP+ & TP- CO 2 / VOC RH GND PWR Function Override Output (Dry Contact Switch). When Override switch is pushed this terminal is connected to the GND terminal. Setpoint output. Referenced to GND terminal. External occupied LCD indicator is activated by logic LOW or ground at this terminal, referenced to the GND terminal. Temperature Sensor Output (Resistive Output). When a jumper is on J16, TP- is connected to the GND terminal. When the jumper is off of J16, the temperature sensor is floating. (Semiconductor TP+ = +, TP- = -) Voltage output CO2 Signal (0 to 2,000 ppm) referenced to the GND terminal. Voltage output Humidity Signal referenced to the GND terminal. To controller Ground [GND or Common] Power, referenced to GND 9 to 35 VDC @ 150 ma Max (9 to 24VDC recommended) for 0 to 5 VDC Outputs 15 to 35 VDC @ 150mA Max (15 to 24VDC recommended) for 0 to 10 VDC Outputs Note: Unit is not ready for operation until the ten-minute start-up time has elapsed. Sensor Type Low Temp High Temp 1000 RTD 1.02K (41.2 F) 1.15K (101.5 F) 3000 Thermistor 7.87K (39.8 F) 1.50K (106.8 F) 10K-2 Thermistor 30.1K (34.9 F) 4.75K (109.1 F) 10K-3 Thermistor 26.7K (35.9 F) 5.11K (108.4 F) 10K-3(11K) Thermistor 7.32K (43.7 F) 3.65K (105.2 F) Fig 4: Test and Balance Switch Operation 3 of 6

26141_ins_room_CO2 Optional Communications Jack Wiring Table 1: C35 Wiring Ground Tip Ring Wire Color Black White Red C35 Communication Jack (Male jack shown for clarity) C11 C35 Table 2: C11 Wiring Comm Jack Pin Wire Color 1 Not Connected 2 Black 3 Red 4 Yellow 5 Green 6 Not Connected User Operation C11 Communication Jack Fig 5: Communication Jacks BAPI Man Icon Minor Display 0.34 3-digit Alpha-Numeric Main Display 0.76 4-digit Numeric Fig 6: Optional Display The display indicates CO 2 in PPM, air temperature in degrees Fahrenheit or Celsius, relative humidity in %RH, temperature setpoint in degrees Fahrenheit or Celsius and override using the BAPI Man icon. The three triangle icons are used with the ARW option to show CO 2 levels and their meaning. The main display indicates the numeric value of the quantity being displayed. The minor display indicates the engineering units of the value, such as PPM, F, C or %RH. CO 2 Concentration Indicator: A three color LED will light green, yellow or red to indicate CO 2 concentrations. Temperature Setpoint Slide-Pot: Moving the slide pot enough to change the setpoint by one degree will display the setpoint on the main LCD display if equipped with display. The setpoint display will hold for five seconds after moving the slide pot. Override Button: When the override button is pressed on display units, the BAPI Man icon will display. A dry resistance of less than 1 ohm appears from the override output (OVR) to the Ground terminal (GND). Latching the Icon to show that the system is in override requires that a dry contact on your controller be used to connect terminal EXT to ground. Table 3: CO₂ Level Indication LED Color CO₂ ppm Air Quality Green <1,000 Good Yellow 1,000 to 1,500 Fair Red >1,500 Poor 4 of 6

Optional Technician Adjustments BAPI s CO 2 room sensor comes calibrated and ready to operate. In some installations the sensor may not match local instrumentation. The technician adjustment procedure allows F or C display units, temperature or humidity offsets or display information to be changed at any time. Removing Ground from Temperature Sensor Some installations may experience erratic temperature readings. A possible remedy may be to float the temperature sensor as shown in figures 7 and 8. Run wires directly from TP+ and TP- to the controller s analog input. The VOC/CO 2 and RH jumpers are omitted for clarity. F or C Display Units Figure 9 and figure 10 show the jumper positions for displayed values of Celsius or Fahrenheit degrees. The jumpers on pins PRG and BNK are omitted for clarity. Parameter Offsets & Display Information Fig 7: Temp. Sensor Grounded Fig 8: Temp. Sensor Floating Figure 11 and figure 12 show how to place the unit into field setup mode. Take the jumper from the BNK terminals and place it on the PRG terminals. The F/C jumper is omitted for clarity. The major display should read P1 and the minor display should read DSP. Use the UP/DN buttons (See Figure 13) to select the desired page. Press and release the ENT button to select the desired page. Use the UP/DN buttons to adjust the desired value Press and release the ENT button to save the change and return to the page display. Adjust another page or place the jumper into normal operation. Parameter Display Options P1 DSP Temperature Offset Table 4: Parameter Offsets & Display Information Display Adjustment Main Minor P2 TMP %RH Offset P3 %RH CO 2 Offset P4 CO2 Altitude P5 ALT Item Display Action 1 Temperature Only 2 % RH Only 3 CO 2 Only 4 Temperature and %RH (10 second rotation) 5 Temperature and CO 2 (10 second rotation) 6 %RH and CO 2 (10 second rotation) 7 Temperature, %RH and CO 2 (10 second rotation) 8 Setpoint Display Only ±5 in 0.1 increments ±5% RH in 0.1% RH increments ±100 ppm in 1 ppm increments Effective Pressure Altitude (display only, no adjustment) Fig 9: F Fig 10: C Fig 11: Normal Operation Fig 12: Programming Setup Fig 13: Calibration Buttons 5 of 6

Output Selection The CO 2 outputs may be field configured for 0 to 5 VDC or 0 to 10 VDC outputs at any time. Set the jumpers on J16 as shown in figures 14 and 15. The humidity outputs may be field configured for 0 to 5 VDC or 0 to 10 VDC outputs at any time. Set the jumpers on J16 as shown in figures 16 and 17. Note: The sensor may be ordered with optional humidity outputs of 1 to 5 VDC or 2 to 10 VDC, figures 16 and 17 describe those options. Note: The jumpers on pins not being described are omitted for clarity on the figures at right. Diagnostics Possible Problems: General troubleshooting Incorrect CO 2 Incorrect Humidity Incorrect Temperature Fig 14: CO 2 Output 0 to 5 VDC Fig 15: CO 2 Output 0 to 10 VDC Fig 16: RH Output 0 to 5 or 1 to 5 VDC Fig 17: RH Output 0 to 10 or 2 to 10 VDC Possible Solutions: Determine that the input is set up correctly in the controller's and building automation software. Check wiring at the sensor and controller for proper connections. Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip the interconnecting wire and reapply the connection. In extreme cases, replace the controller, interconnecting wire and/or sensor. Label the terminals that the interconnecting wires are connected to at the sensor end and the controller end. Disconnect the interconnecting wires from the controller and the sensor. With the interconnecting wires separated at both ends measure the resistance from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms, open or OL depending on the meter you have. Short the interconnecting wires together at one end. Go to the other end and measure the resistance from wire-to-wire with a multimeter. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or less). If either test fails, replace the wire. Check power supply/controller voltage supply Disconnect sensor and check power wires for proper voltage (see specifications below) Wait 15 minutes after a power interruption. Check all software parameters Determine if the sensor is exposed to an external environment different from the room (conduit draft) Check all software parameters If available, check the sensor against a calibrated instrument such as a hygrometer Determine if the sensor is exposed to an external environment different from the room (conduit draft) Determine that the temperature sensor's wires are connected to the correct controller input terminals and are not loose. Check the wires at the sensor and controller for proper connections. Measure the physical temperature at the temperature sensor's location using an accurate temperature standard. Output to Controller Disconnect the temperature sensor's wire (Terminals TP+ & TP-) and measure the temperature sensor's resistance across the sensor output pins with an ohmmeter. Put the ohmmeters black lead on Terminal TP- and the red lead on Terminal TP+. Compare the temperature sensor's resistance to the appropriate temperature sensor table on the BAPI web site (See below). If the measured resistance is different from the temperature table by more than 5% call BAPI technical support. Don't forget to reconnect the wires. How to Find Temperature Sensor Resistance Find BAPI's web site at www.bapihvac.com; click on the link labeled SENSOR SPECS on the lower left of the screen and then click on the sensor type you have. Make sure that the sensor leads are not touching one another. Determine if the sensor is exposed to an external environment different from the room (conduit or wall cavity draft) 6 of 6